You are on page 1of 1

SES-12

SPECIFICATIONS:
1. AVR Type SES 12
2. Make SANELEC
3. INPUT
3.1 SENSING Let us know existing Sensing P.T. specification.
3.2 Burdon Less than 2 VA
3.3 Frequency 50/60 c/s
3.4 Power Input Please let us know the existing P. T. specification.
3.5 DROOP 5 Amps (derived though Line CT) form 'W Phase.
3.6 Accessory Input ± 4.5 V DC.
4. OUTPUT
DC Volts Max 200V DC for 240V AC input
DC Amps. 15 Amps DC (Maximum)
(Limited by fuse rating for particular applications)
5. VOLTAGE REGULATION ± 0.5% at sensing input terminals of AVR.
6. VOLTAGE DRIFT Less than ±1% for 40°C changes in ambient.
7. Under Speed Protection Settable between 40Hz slope 3.0 P.U.
8. Build up (at power input Terminals) 1.5 V (typical)
2.5 V Guaranteed
9. Voltage Variation ± 20% (typ.) with voltage trimmer.
10. Droop 10% (Max) for 5 A
11. Response AVR Response time about 70 m. sec. closed loop voltage
recovery at m/c terminals between 0.5 to 2.0 sec depending
on size of ACG. (This is machine design dependent)
12. Accessory Input ± 4.5V will change terminal voltage by ± 15% (approx).
13. Excitation Current Limit Inverse Time - Delayed; Settable by over
(As given at the time of ordering). Excitation Pot. Range 2./0 to 15.0 Amps
(Which allowed by fuse rating for particular application).
14. Temperature operation -20°C to +60°C
15. Size Overall : 330 x 200 x 120(mm)
Mounting : 313 x 148 (4 holes of 5.5 dial)
Weight : 4.8 KGs