SERVICE Manual
For more information, Please access to our service web site (http://itself.sec.samsung.co.kr)
● Connect only the indoor units fit on R410A refrigerant. Check whether the indoor units can be connected with the
product’s catalogue.
(When incorrect indoor units are connected,they cannot operate normally.)
If you don’t follow the safety precautions, you may get the risk of serious wound or death.
● The installation must be done by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard.
– Installation by an unqualified person may cause a water leakage, electric shock or fire and so on.
● The electric work must be done by service agent or similarly qualified persons according to national wiring regulations and use
only rated cable.
– If the capacity of the power cable is insufficient or electric work is not properly completed, electric shock or fire may occur.
● Install the outdoor unit correctly according to the installation manual.
– An incorrect installation may cause a water leakage, electric shock or fire and so on.
● Manufacturer is not responsible for accidents due to incorrect installation.
● When you install the air conditioner in a small room, you consider a proper ventilation to prevent a leakage level within the
maximum permissible limit.
– In that case, you may die from suffocation by some possibility.
● Use only rated parts and tools.
– If you don’t use the rated parts and tools, it can cause trouble with the air conditioner and bring about injury.
● Install the outdoor unit on a hard and even place that can support its weight.
– If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
● Fix the outdoor unit securely to prepare against strong wind or earthquake.
– If the outdoor unit is not properly fixed, it turns over and accidents may occur.
● Install the cables with supplied cables firmly.Fix them securely so that external force is not exerted to the terminal board.
– If the connection or fixing is incomplete, it can cause trouble with a heat generation, electric shock or fire and so on.
● Arrange the cables between the indoor and outdoor unit after connecting.Attach the cover securely so that the electrical
component box cover does not get loosen.
– If the cover is attached incompletely, it can cause trouble with a heat generation, electric shock or fire of the terminal board.
● Install separate MCCB and ELB when installing the power cable.
– If you do not install the MCCB and ELB, electric shock or fire may occur.
● The unit must be plugged into an independent circuit if applicable or connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be incorporated in the fixed wiring with a contact opening of >3mm.
● If any gas or impurities except R410A refrigerant come into the refrigerant pipe, serious problem may occur and it may cause
injury.
● Make sure there is no leakage after installation.
– Toxic gas may generate when refrigerant gas contacts with fire.
● Leak test must be done using only Nitrogen(NO2)gas.
If you don’t follow the safety precautions, you may get the risk of injury or loss of property.
The compact design that requires less space reduces the installation
space and all the corners become comfortable with the ceiling airflow type
that cool air blows from the ceiling.
Cabinet
3. Convenient Installation
• Compact Design
This can be installed easily in a limited space due to compact
design that requires less space.
Height : A
(Unit : m)
Type A H
1 way cassette 180 195
2 way cassette 230 255
Over 1/100
Flexible Hose
Ceiling
With the ceiling installation type which winds come from 4 directions,
the space is cool equally and the nobility of the air conditioner is more
upgraded.
Antibacterial cooler
Turbo fan
Easy installation/
maintenance of front box
Antibacterial &
purifying long-life air filter
Washable front grill
255
Height(5.6kw~7.1kw:230mm)
315
Height(11.2kw~14.0kw:288mm)
Below 550mm
is more convenient.
Over 1/100
Flexible Hose
Ceiling
• Stylish design
The trendy and noble design blends with any interior design;
so, installation itself is beautiful. With the compact size, you can
install it in a narrow space.
Cabinet
2. Features
• Ideal for Small Space
The Mini 4 way cassette’s body is so slim; only 260mm in <Samsung>
260mm
575mm
9/12/18/21k
<Company A>
575mm
286mm
575mm
9/12/18/21k
260
• Free installation
Not restricted by room structure and the location of lighting fixtures. Possible to attach a drain pump which is an option.
• Duct type(Built-in)
350mm
• Duct type(Slim)
Cross Fan
Since Samsung's Bio Cross Fan has been molded
with an antibacterial formula, it can suppress proliferation
of molds and bacteria, preventing the causes of foul
odors. This extends the durability of the unit.
Silver-Nano EvaporatorTM
• The new H-Fin technology enhances the power of
removing bacteria.
• The heat exchanging function is upgraded.
• It provides pure and fresh air, similar to an air purifier.
• Samsung applied the chrome-free evaporator to all
products in 2005.
• According to EU environmental and health regula-
tions, all appliances and products must be void of
harmful materials such as chrome beginning in 2006.
Deodorizing filter
Activated carbon is incorporated in the filter,
efficiently absorbing cigarette smoke, pet odors,
and other unpleasant smells, replacing them with
clean, refreshing air.
Catechin filter
Catechin, extracted from green tea, is contained in the
filter and deactivates captured bacteria and unpleasant
odors.
Silver-Nano filterTM
The unit's outermost filter, which is uniquely treated
with an antibacterial agent, catches very small dust
particles in the air.
✳ This is an image diagram. Some parts may not be shown in actual size.
Cross Fan
Silver-Nano
EvaporatorTM
Deodorizing filter
Anti-allergy filter
Silver-Nano e-filterTM
4. Digital i
The Digital i not only displays the current temperature
but also the power and current operation mode.
2. Features
• Convertible Installation
The Ceiling type can be installed on the ceiling or floor. In the case that your ceiling is very shallow or has complex fixtures. it is
surface mounted. If you want to install it on floor level, the unit can be used in this configuration also.
Cross fan
Heat exchanger
5way display
4 Directions of piping
Outdoor Type
Outdoor Type
Outdoor Type
Outdoor Type
Outdoor Type
Outdoor Type
Outdoor Type
Outdoor Type
2-2-3 Accessory
Classification Model Relevant Product Group Description Option class
MXJ-YA1509A
MXJ-YA2212A
MXJ-YA2512A Including Liquid pipe, Gas pipe,
Refnet Joint Outdoor Unit Requisite
MXJ-YA2815A Insulating materials
MXJ-YA3119A
MXJ-YA3819A
MXJ-HA2512A
Including Liquid pipe, Gas pipe,
Refnet header MXJ-HA3115A Outdoor Unit Option
Insulating materials
MXJ-HA3819A
Outdoor unit
connection MXJ-T3819A Outdoor unit Liquid pipe, Gas pipe Option
pipe
Duct type
MDP-E075SEE
(Slim)
Duct type
MDP-075SA
(Low pressure)
Drain Pump 750mm drain up Option
Duct type
MDP-075SB
(High pressure)
Duct type
MDP-H075SA
(Built-in)
Accessory (cont.)
Classification Model Relevant Product Group Description Option class
Duct type
MF-E0BF
(Slim 1)
Duct type
MF-E0BA
(Slim 2)
Duct type
MF-E0BD
(Slim 3)
Duct type
MF-H0BE1
(High pressure)
Omni System,
Korea Micronics, LS
Edition Electric industrial systems The high-tech digital system displays
MCM-B102C(485) co., possible to
Power Division accumulated amount of used power to Option
✳ For China communicate to
System China standard divide power rate by each indoor unit
protocol electronic
wattmeter
MR-AC10 :
Wireless (Cooling) Cassette type,
Remote Individual control Option
MR-AH10 : Duct type
Control
(Cooling/Heating)
Wireless
Remote
MRK-A00(C, U) Duct type Wireless Remote Control Receiver Option
Control
Receiver Kit
Wireless
Remote
Control MRW-10A(C, U) Duct type Wire length 10m Option
Receiver Kit
Wire
MWR-TH01S :
(Cooling/
Wired Remote Cooling & Heating) Cassette type Includes group/individual control,
Option
Control MWR-TH01 : Duct type 7day scheduling
(Cooling/
Cooling & Heating)
Accessory (cont.)
Classification Model Relevant Product Group Description Option class
Green Red
Indoor temperature sensor error • Indoor temperature sensor • Check the indoor
(Open/Short) connector breakaway temperature sensor
• Short of temperature connector
sensor wire • Check the temperature
sensor wire
Indoor heat exchanger sensor error • Indoor pipe temperature • Check the temperature
Indoor heat exchanger OUT sensor error sensor connector sensor connector
Indoor emission temperature sensor error breakaway breakaway
(Open/Short) : Heater using models
Mixed operation error Operate cooling & heating • Change the operation
operation simultaneously mode
Indoor fan motor error: maintains for Not drive the indoor fan • Check the connector
over 15 seconds below 450RPM motor breakaway
• Check the fan motor lock
Outdoor temperature sensor error Outdoor unit operation • Manage after checking
COND sensor error error the error on the outdoor
DISCHARGE sensor error PCB display window
1. Detect the indoor unit when there is Outdoor unit operation • Manage after checking
no communication between the indoor error the error on the outdoor
unit and outdoor unit for 2 minutes. PCB display window
(When communication error is for
over 2 minutes)
2. The indoor unit receives the
communication error signal from the
outdoor unit
3. The outdoor unit tracking 3 minutes
error
4. When the outdoor unit transmits a
communication error which is caused
by difference between the number of
the installation unit and the number of
communication unit after completion
of tracking. (When communication
error is for over 2 minutes)
: On : Flickering : Off
Green Red
Self diagnosis error display • Indoor unit EEV defect • Check electronic valve
(Include the indoor unit that is not • Indoor unit EVAP IN/OUT operation
detected) sensor breakaway • Check the sensor
11. EEV close status defect breakaway
12. EEV open status defect
13. EVAP OUT sensor breakaway
14. EVAP IN sensor breakaway
15. COND MID sensor breakaway Outdoor unit operation error Manage after checking the
16. Refrigerant complete leakage 2nd error on the outdoor PCB
detection display window
17. COND high temperature 2nd detection
18. DISCHARGE high temperature 2nd
detection
19. Low pressure switch 2nd detection
COMP DOWN
10. Reverse phase detection error
11. Freezing 6th detection compressor
stop
12. Compression sensor self diagnosis
(G8, G9)
13. Compressor down error by
compression ratio control
Peripheral control device option setting Setting error of the indoor Readjust the indoor PCB
error unit option device option S/W
EEPROM error Incorrectly input the indoor Input the indoor unit option
unit option code code
EEPROM option error Not input the indoor unit Input the indoor unit option
option code code
: On : Flickering : Off
- When stopping the operation during an error is displayed, all lamps are off.
- When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation.
- Refer to the “10. Troubleshooting” for detail contents related to the error mode.
Indoor temperature sensor error • Indoor temperature sensor • Check the indoor
(Open/Short) connector breakaway temperature sensor
• Short of temperature connector
sensor wire • Check the temperature
sensor wire
Indoor heat exchanger sensor error • Indoor pipe temperature • Check the temperature
Indoor heat exchanger OUT sensor error sensor connector sensor connector
Indoor emission temperature sensor error breakaway breakaway
(Open/Short) : Heater using models
Indoor fan motor error: maintains for Not drive the indoor fan • Check the connector
over 15 seconds below 450RPM motor breakaway
• Check the fan motor lock
Outdoor temperature sensor error Outdoor unit operation • Manage after checking
COND sensor error error the error on the outdoor
DISCHARGE sensor error PCB display window
1. Detect the indoor unit when there is Outdoor unit operation • Manage after checking
no communication between the indoor error the error on the outdoor
unit and outdoor unit for 2 minutes. PCB display window
(When communication error is for
over 2 minutes)
2. The indoor unit receives the
communication error signal from the
outdoor unit
3. The outdoor unit tracking 3 minutes
error
4. When the outdoor unit transmits a
communication error which is caused
by difference between the number of
the installation unit and the number of
communication unit after completion
of tracking. (When communication
error is for over 2 minutes)
: On : Flickering : Off
Self diagnosis error display • Indoor unit EEV defect • Check electronic valve
(Include the indoor unit that is not • Indoor unit EVAP IN/OUT operation
detected) sensor breakaway • Check the sensor
11. EEV close status defect breakaway
12. EEV open status defect
13. EVAP OUT sensor breakaway
14. EVAP IN sensor breakaway
15. COND MID sensor breakaway Outdoor unit operation error Manage after checking the
16. Refrigerant complete leakage 2nd error on the outdoor PCB
detection display window
17. COND high temperature 2nd detection
18. DISCHARGE high temperature 2nd
detection
19. Low pressure switch 2nd detection
COMP DOWN
10. Reverse phase detection error
11. Freezing 6th detection compressor
stop
12. Compression sensor self diagnosis
(G8, G9)
13. Compressor down error by
compression ratio control
Peripheral control device option setting Setting error of the indoor Readjust the indoor PCB
error unit option device option S/W
EEPROM error Incorrectly input the indoor Input the indoor unit option
unit option code code
EEPROM option error Not input the indoor unit Input the indoor unit option
option code code
: On : Flickering : Off
- When stopping the operation during an error is displayed, all lamps are off.
- When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation.
- Refer to the “10. Troubleshooting” for detail contents related to the error mode.
Indoor temperature sensor error • Indoor temperature sensor • Check the indoor
(Open/Short) connector breakaway temperature sensor
• Short of temperature connector
sensor wire • Check the temperature
sensor wire
Indoor heat exchanger sensor error • Indoor pipe temperature • Check the temperature
Indoor heat exchanger OUT sensor error sensor connector sensor connector
Indoor emission temperature sensor error breakaway breakaway
(Open/Short) : Heater using models
Mixed operation error Operate cooling & heating • Change the operation
operation simultaneously mode
Outdoor temperature sensor error Outdoor unit operation • Manage after checking
COND sensor error error the error on the outdoor
DISCHARGE sensor error PCB display window
1. Detect the indoor unit when there is Outdoor unit operation • Manage after checking
no communication between the indoor error the error on the outdoor
unit and outdoor unit for 2 minutes. PCB display window
(When communication error is for
over 2 minutes)
2. The indoor unit receives the
communication error signal from the
outdoor unit
3. The outdoor unit tracking 3 minutes
error
4. When the outdoor unit transmits a
communication error which is caused
by difference between the number of
the installation unit and the number of
communication unit after completion
of tracking. (When communication
error is for over 2 minutes)
: On : Flickering : Off
Self diagnosis error display • Indoor unit EEV defect • Check electronic valve
(Include the indoor unit that is not • Indoor unit EVAP IN/OUT operation
detected) sensor breakaway • Check the sensor
11. EEV close status defect breakaway
12. EEV open status defect
13. EVAP OUT sensor breakaway
14. EVAP IN sensor breakaway
15. COND MID sensor breakaway Outdoor unit operation error Manage after checking the
16. Refrigerant complete leakage 2nd error on the outdoor PCB
detection display window
17. COND high temperature 2nd detection
18. DISCHARGE high temperature 2nd
detection
19. Low pressure switch 2nd detection
COMP DOWN
10. Reverse phase detection error
11. Freezing 6th detection compressor
stop
12. Compression sensor self diagnosis
(G8, G9)
13. Compressor down error by
compression ratio control
Peripheral control device option setting Setting error of the indoor Readjust the indoor PCB
error unit option device option S/W
EEPROM error Incorrectly input the indoor Input the indoor unit option
unit option code code
EEPROM option error Not input the indoor unit Input the indoor unit option
option code code
: On : Flickering : Off
- When stopping the operation during an error is displayed, all lamps are off.
- When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation.
- Refer to the “10. Troubleshooting” for detail contents related to the error mode.
Power reset
Error of heat exchanger sensor in indoor unit Displayed on appropriate indoor unit
Error of heat exchanger OUT sensor in indoor unit which is operating
Error of outlet temperature sensor in indoor unit
(OPEN/SHORT): For heat pump models only
: On : Flickering : Off
EEPROM error
: On : Flickering : Off
- If you turn off the air conditioner when the LED is flickering, the LED is also turned off.
- If you re-operate the air conditioner, it operates normally at first, then detects an error again.
✳ Step 1
✳ Method)
✳ !Remove the battery of remote
controller.
✳ @Push the temperature adjustment
button simultaneously.
✳ #Insert the battery.
✳ Result)
✳ When the display of remote
✳ controller is indicated as shown
✳ in the right, then go to the step 2.
✳ Step 2
✳ Method)
✳ If the first digit of remote
controller shows "0", go to the
step 3.
• If it shows 1, press the operation
selection button one time to change
it into 0 and then go to step 3.
✳ Step 3
✳ Method)
✳ Input the second digit of option code
by pressing the temperature
adjustment button (up).
example) 021E31142285
✳ Result)
✳ If 2 is displayed, go to the step 4
(whenever pressing the button, 1~9,
A,B,C,D,E,F are lit in order.)
✳ Step 4
✳ Method)
✳ Input the third digit of option code
by pressing the temperature
adjustment button (down).
example) 021E31142285
✳ Result)
✳ If 1 is displayed, go to the step 5.
✳ Step 5
✳ Method)
✳ Input the fourth digit of option code
by pressing the fan speed
adjustment button.
example) 021E31142285
✳ Result)
✳ If E displays, go to step 6.
✳ Step 6
✳ Method)
✳ Input the fifth digit of option code by
pressing the On timer button.
example) 021E31142285
✳ Result)
✳ If 3 displays, go to step 7.
SEG 5
✳ Step 7
✳ Method)
✳ Input the sixth digit by pressing the
Off timer button.
example) 021E31142285
✳ Result)
✳ If 1 displays, go to step 8.
✳ Step 8
✳ Method)
✳ After completion up to step 7,
pressing mode button.
✳ !1~7 steps are saved internally.
✳ @ If the first number is 1 at the time,
it is correct. So go to step 9.
✳ • If wanting to see the screen
of 2~7 steps, press the mode
button to make the first digit 0.
✳ Step 9
✳ Method)
✳ Input the eighth digit by pressing
the temperature adjustment
button (up).
example) 021E31142285
✳ Result)
✳ If 4 displays, go to step 10.
✳ Step 10
✳ Method)
✳ Input the ninth digit by pressing the
temperature adjustment
button (down).
example) 021E31142285
✳ Result)
✳ If 2 displays, go to step 11.
✳ Step 11
✳ Method)
✳ Input the tenth digit by pressing fan
speed adjustment button.
example) 021E31142285
✳ Result)
✳ If 2 displays, go to step 12.
✳ Step 12
✳ Method)
✳ Input the 11st digit by pressing the
On timer button.
example) 021E31142285
✳ Result)
✳ If 8 displays, go to step 13.
✳ Step 13
✳ Method)
✳ Input the 12th digit by pressing the
Off timer button.
example) 021E31142285
✳ Result)
✳ If 5 displays, go to step 14.
✳ Step 14 ■ Error
✳ Method) ■ ! If the On/Off, Timer and Fan
✳ Turn the remote controller toward indicator is flickering, the wrong
the indoor unit and press the On/Off option code is input. Put off the
button, and if the "Ting" or "Tiriring" power of indoor unit and turn it
sounds, the input of option is com- on again and then input the option
pleted. code again.
✳ • If error displays, solve the If the same error occurs, it is the
problem with reference to the EEPROM is defective or not
right side. inserted. Replace the PCB.
■ @ If all of On/Off, Timer, Fan and Filter
Sign indicator are flickering along
with the "Tiriring" sound, there is
option code already input which are
different from the current ones.
Check the option code and press the
button again if correct. Option code
✳ Step 15 will be input. (Check the option code
✳ Method) correctly. At the time, if the same
✳ If the steps 1 to 14 are completed, error continues to occur, the option
remove the battery and insert it again code is out of input range.
to return to the original Check the option code again and
display of remote controller. repeat the step 1~14.
(Operation mode/SET TEMP.
/fan speed displays.)
rear side
Type Model SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
AVXC1H022E✳ 0 0 5 6 0 0 1 1 6 0 c 8
1 way
cassette type AVXC1H028E✳ 0 0 5 6 0 0 1 4 6 2 1 d
AVXC1H036E✳ 0 0 5 6 0 0 1 6 6 3 4 0
2 way AVXC2H056E✳ 0 2 5 6 0 0 1 9 4 3 6 1
cassette type AVXC2H071E✳ 0 2 5 6 0 0 1 d 4 3 8 2
AVXC4H056E✳ 0 4 5 2 0 0 1 9 4 0 0 0
AVXC4H071E✳ 0 4 5 2 0 0 1 c 4 0 0 0
4 way
cassette type AVXC4H112E✳ 0 4 5 A 0 0 1 0 4 0 0 0
AVXC4H128E✳ 0 4 5 A 0 0 1 2 4 0 0 0
AVXC4H140E✳ 0 4 5 A 0 0 1 3 4 0 0 0
AVXCMH028E✳ 0 4 5 2 2 4 1 4 4 0 b 3
Mini 4 way AVXCMH036E✳ 0 4 5 2 2 4 1 6 4 0 b 3
cassette type AVXCMH056E✳ 0 4 5 2 2 4 1 9 4 0 b 3
AVXCMH060E✳ 0 4 5 2 2 4 1 b 4 0 F 7
AVXDDH045E✳ 0 1 5 2 0 0 1 8 4 0 0 0
Duct type
AVXDDH056E✳ 0 1 5 2 0 0 1 9 4 0 0 0
(Low
silhouette) AVXDDH071E✳ 0 1 5 2 0 0 1 c 4 0 0 0
AVXDDH090E✳ 0 1 5 2 0 0 1 E 4 0 0 0
Duct type AVXDHH112E✳ 0 1 5 A 0 0 1 0 4 0 0 0
(High AVXDHH128E✳ 0 1 5 A 0 0 1 2 4 0 0 0
pressure)
AVXDHH140E✳ 0 1 5 A 0 0 1 3 4 0 0 0
AVXDLH071E✳ 0 1 5 2 0 0 1 c 4 0 0 0
Duct type AVXDLH090E✳ 0 1 5 2 0 0 1 E 4 0 0 0
(Low AVXDLH112E✳ 0 1 5 A 0 0 1 0 4 0 0 0
pressure)
AVXDLH128E✳ 0 1 5 A 0 0 1 2 4 0 0 0
AVXDLH140E✳ 0 1 5 A 0 0 1 3 4 0 0 0
AVXDBH022E✳ 0 1 5 2 0 0 1 1 4 0 0 0
AVXDBH028E✳ 0 1 5 2 0 0 1 4 4 0 0 0
Duct type
(Built-in) AVXDBH036E✳ 0 1 5 2 0 0 1 6 4 0 0 0
AVXDBH056E✳ 0 1 5 2 0 0 1 9 4 0 0 0
AVXDBH071E✳ 0 1 5 2 0 0 1 c 4 0 0 0
AVXDSH022E✳ 0 1 5 2 0 1 1 2 0 0 E A
AVXDSH028E✳ 0 1 5 2 0 1 1 2 0 2 2 c
AVXDSH036E✳ 0 1 5 2 0 1 1 2 0 3 A 0
Duct type
(Slim) AVXDSH040E✳ 0 1 5 2 2 3 1 7 0 1 3 5
AVXDSH045E✳ 0 1 5 2 2 3 1 7 0 1 3 5
AVXDSH056E✳ 0 1 5 2 2 3 1 9 0 1 b A
AVXDSH071E✳ 0 1 5 2 2 3 1 c 0 3 9 E
AVXWPH022E✳ 0 d 7 6 0 0 1 2 2 2 3 F
Wall- AVXWPH028E✳ 0 d 6 6 0 0 1 3 2 3 5 1
mounted AVXWPH036E✳ 0 d 7 6 0 4 1 5 2 3 6 2
type AVXWPH045E✳ 0 d 5 6 0 8 1 7 2 3 5 1
(Premium)
AVXWPH056E✳ 0 d 5 6 0 8 1 A 2 3 5 1
AVXWPH071E✳ 0 d 5 6 0 8 1 c 2 3 7 1
AVXWHH028E✳ 0 E 8 6 0 0 1 3 2 2 2 8
Wall- AVXWHH036E✳ 0 E 7 6 0 0 1 5 2 2 6 E
mounted
type AVXWHH045E✳ 0 E 5 6 0 4 1 7 2 2 1 d
(Prestige) AVXWHH056E✳ 0 E 5 6 0 4 1 A 2 2 3 F
AVXWHH071E✳ 0 E 5 6 0 4 1 c 2 2 3 F
AVXTFH056E✳ 0 3 5 2 0 0 1 9 4 0 0 0
Ceiling type
AVXTFH071E✳ 0 3 5 2 0 0 1 d 4 0 0 0
3) Filter Separation
(1) Pull back the hook at the Panel Grill
and remove the Filter.
1 Front Grille 1) Push the tap on the Front Grille to open it.
&
Filter-Air
3) Filter Disassembly
(1) Draw the Dust-Collecting Filter
forward.
4) Loosen 4 bolts.
Take
Take
Take
Take
Take
Take out
out
Takeout
out
out
out the
the
outthe
the
the
the washer
washer
thewasher
washer
washer
washer
washer
1 Front Grille 1) Push the tap on the Front Grille to open it.
– Dust-Collecting
Filter
3) Filter Disassembly
(1) Draw the Dust-Collecting Filter
forward.
Take
Take
Take
Take
Take
Take out
out
Takeout
out
out
out the
the
outthe
the
the
the washer
washer
thewasher
washer
washer
washer
washer
Bracket
3 Tray Drain 1) Pull Tray Drain out from the Back Body.
4-2-1 4/5/6HP
4-2-2 8/10HP
4-2-3 12/14HP
24
25 5
6
3 2 15
23
7
16
22
18
9 8 17
10 19
14-2
14-1
11
20
14
14-3
12
21
13
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXC1H022E✳ AVXC1H028E✳ AVXC1H036E✳
5
2
9 8
10
11
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AGKH118IK✳
1-8 1-6
1-2 1-7
3 3-2
1-4
2 1-5
1-1 1
1-3
3-1
5
4
5-2 11
12 8
5-1
9
10
11
7
8 6
12
14
9
21
13
20
23
25
15
19
18 22
17
24
16
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXC2H056E✳ AVXC2H071E✳
6 12
10
20 8
11
14
9
19 13
16
15
18
17
2
3
4
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AGGH103IK✳
1
2
5
6 4
7 3
10
8 11
9
12
13
14
24 15
18 17
19 24
16 22
21 27
28
20
29
26
30
31
25 32
33
34
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXC4H056E✳ AVXC4H071E✳
1
2
5
6 4
7 3
10
8 11
9
12
13
14
15
24 16
19 18
20 25
17 23
22 28
29
21 30
27
31
32
26 33
34
35
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXC4H112E✳ AVXCH4H128E✳ AVXC4H140E✳
28 16
28
15 18
28 30
13
12
11 14+31
17 10
28
1
7
18 27
2
26 30 29
4
3 9
24
29
51 5
6 8
29
28
19 20
28 25
28
23
21
22
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AGCH095IKE
31
7 1
2 8 3 5
6 4
9
10
11
16 15
18
12
14 21
17 16
13
20
19
23
22
24 25
32
26
27 33
28
29
30
■ Parts List
Q'TY
No. Code No. Description Specification AVXCMH028E✳ SA/SNA
AVXCMH056E✳ AVXCMH060E✳
AVXCMH036E✳
1 DB63-01367A COVER CONTROL ABS(V0),T2.0 1 1 1 SNA
2 DB93-04122A ASS'Y PCB MAIN MINI 4WAY CASSETTE 1 1 1 SNA
3 DB65-00029M TERMINAL BLOCK 4P 1(L),2(N),Vc,Vc 1 1 1 SA
4 DB65-00182A TERMINAL BLOCK 2P F1,F2 1 1 1 SA
5 DB65-00029Z TERMINAL BLOCK 4P V1,V2,F3,F4 1 1 1 SA
6 2301-001378 C-FILM,LEAD-OTHER 450VAC,3.5uF 1 1 1 SA
7 DB61-02499A BRACKET EARTH WIRE SGCC-M,T1.0 1 1 1 SA
8 DB32-00067D THERMISTOR WIRE IN 103AT,-20~100˚C 1 1 1 SA
9 DB61-02486A PCB BASE CONTROL ABS(V0),T2.0 1 1 1 SNA
10 DB94-00826A ASS'Y DRAIN PAN MINI 4WAY CASSETTE 1 1 1 SA
11 DB94-00812A ASS'Y FAN TURBO SAN+GF20% 1 1 1 SA
12 DB90-02221A ASS'Y CABI SIDE A MINI 4WAY CASSETTE 1 1 1 SA
13 DB90-02220A ASS'Y CABI SIDE B MINI 4WAY CASSETTE 1 1 1 SA
14 DB94-00847A ASS'Y PARTITION MINI 4WAY CASSETTE 1 1 1 SA
15 DB95-00131D ASS'Y SENSOR FLOAT 250mm,MINI 4WAY CASSETTE 1 1 1 SA
16 DB73-00307A RUBBER WIRE HOLE NBR 45˚ 2 2 2 SNA
17 DB90-02225A ASS'Y COVER PIPE MINI 4WAY CASSETTE 1 1 1 SA
18 DB61-02527A HOLDER EVAP STS304,T0.7 4 4 4 SA
19 DB94-00846A ASS'Y DRAIN HOSE MINI 4WAY CASSETTE 1 1 1 SA
20 DB90-01010A ASS'Y COVER DRAIN CH040EZM,NEW 4WAY CASSETTE 1 1 1 SNA
21 DB61-02490A GUIDE EVAP STS304,T0.7 1 1 1 SA
22 DB96-06279A ASS'Y EVAP UNIT MINI 4WAY CASSETTE 1 - - SNA
DB96-05354D ASS'Y EVAP UNIT MINI 4WAY CASSETTE - 1 1 SNA
23 DB31-00303A PUMP DRAIN FUJIKOKI,220V 50Hz,60Hz 1 1 1 SA
24 DB73-00022C RUBBER PUMP EPDM+BUTYL,40~45˚ 4 4 4 SNA
25 DB61-02492A BRACKET PUMP SGCC-M,T1.5 1 1 1 SA
26 DB90-02223A ASS'Y BASE CUSHION MINI 4WAY CASSETTE 1 1 1 SA
27 DB31-00305A MOTOR FAN ASS035WTVA,4WAYMINI-PJT,50Hz 1 1 1 SA
28 DB61-02495A BRACKET MOTOR IN SGCC-M,T1.2 1 1 1 SA
29 DB63-01407A GROMMET MOTOR NR,35˚ 3 3 3 SA
30 DB90-02222A ASS'Y CABI BASE MINI 4WAY CASSETTE 1 1 1 SA
31 DB63-01372A GUARD SAFETY HSWR,T2.5 1 1 1 SA
32 DB32-00066E THERMISTOR EVAP IN 300mm,MINI 4WAY CASSETTE 1 1 1 SA
33 DB97-04440A ASS'Y DRAIN HOSE INSTALL MINI 4WAY CASSETTE 1 1 1 SNA
30 19
5 2 28 33 15 27
4
18
24
23
31
3
12
17 13
1
14
10
20
11
16 22
26 21
25
7 29 8 6 32
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
MGMH067IM
1
2
5
5-3 5-4
5-6
5-1
5-2
5-5
19
8
20
19-2
17 9
19-3
19-1
19-4
19-5 7
18
13 6
12
4
10
11
21
14
15
16
3
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXDDH056E✳ AVXDDH071E✳
6 10
10-6
10-1
10-2 10-5
5
10-4
3
10-3
10-7
10-8
7
7-1
7-2
9
8-1 8-5
8-6
2
8-7
■ Parts List
Q'TY
No. Code No. Description Specification AVXDHH128E✳ SA/SNA
AVXDHH112E✳
AVXDHH140E✳
1 DB98-06745B ASS'Y CABI TOP DUCT TYPE 1 1 SNA
2 DB98-06744B ASS'Y CABI BASE PART DUCT TYPE 1 1 SNA
3 DB94-00599A ASS'Y DRAIN PAN DUCT TYPE 1 1 SA
4 DB96-05143B ASS'Y EVAP DUCT TYPE 1 1 SA
5 DB32-00016B THERMISTOR-ASS'Y DUCT TYPE 1 1 SA
6 DB98-05296D ASS'Y-CABI SIDE LF PART DUCT TYPE 1 1 SNA
7 DB98-05298D ASS'Y-CABI SIDE RH PART DUCT TYPE 1 1 SNA
7-1 DB64-01147A CABI SIDE RH DUCT TYPE 1 1 SA
7-2 DB63-01023A COVER CABI SIDE DUCT TYPE 1 1 SA
8 DB93-01037K ASS'Y CONTROL IN 220~240V,50Hz - 1 SA
DB93-01037J ASS'Y CONTROL IN 220~240V,50Hz 1 - SA
8-1 DB61-00451A CASE-CONTROL SGCC-M,T0.8 1 1 SNA
8-2 DB26-10065B TRANS-POWER 230V,50Hz 1 1 SA
8-3 DB65-00004H TERMINAL BLOCK-6P 6p 1 1 SA
8-4 DB65-00004C TERMINAL BLOCK-4P 4p 1 1 SA
8-5 DB93-03260A ASS'Y PCB MAIN DUCT,PCB 1 1 SA
8-6 DB61-40291B HOLDER-WIRE PP,BLK 2 2 SNA
8-7 DB63-00186A COVER-CONTROL SGCC-M,T0.8 1 1 SNA
9 DB90-01513A ASS'Y-BRACKET OUTLET DUCT TYPE 2 2 SA
10 DB94-00586G ASS'Y BLOWER DUCT TYPE - 1 SNA
DB94-00586P ASS'Y BLOWER DUCT TYPE 1 - SNA
10-1 DB31-00079E MOTOR FAN OSME-1604SAC(S324) - 1 SA
DB31-00079C MOTOR FAN OSME-1604SAC(S322) 1 - SA
10-2 DB67-00117A BLOWER LF SGCC-M 1 1 SA
10-3 DB67-00117B BLOWER-RH SGCC-M 1 1 SA
10-4 DB90-00313A ASS'Y-HOUSING DUCT TYPE 2 2 SNA
10-5 DB72-00710A BAND MOTOR SGCC-M,T1.6 4 4 SNA
10-6 DB61-00540B BRACKET-MOTOR GUIDE SGCC-M,T1.6 1 1 SNA
10-7 DB64-01148A PANEL-DUCT SGCC-M 1 1 SA
10-8 DB61-01880A BASE MOTOR SGCC-M,T2.3 1 1 SNA
■ Parts List
Q'TY
No. Code No. Description Specification AVXDLH071E✳ SA/SNA
AVXDLH090E✳
■ Parts List
Q'TY
No. Code No. Description Specification AVXDLH128E✳ SA/SNA
AVXDLH112E✳
AVXDLH140E✳
4
6
7
11 8
9
12
30-1 30-3 30-2
30
5 13
10 30-4
25 30-5
16 14 31 30-6,7
32 30-8
17 20-1 15 33 30-9
29
34
18 19 20
26
28
27
21
23 24
22
■ Options
Q'TY
No. Code No. Description Specification Remark
MDP-075SB MDP-07SBU
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXDBH022E✳ AVXDBH028E✳ AVXDBH036E✳
3 11
4
35
7 13
6
8
9 12
5
10 14
15 30-3 30-2
17 16 30-1
20-1 30
18 30-4
20 30-5
19 25 30-6,7
31
34 30-9 30-8
32
33
26 29
21 28
27
23
22 24
■ Options
Q'TY
No. Code No. Description Specification Remark
MDP-075SB MDP-075SBU
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXDBH056E✳ AVXDBH071E✳
1
8
20
2
17
18
19
16
21
13 15
12
11
24 23
25
14 4
3 5
9 22
10 8
7
23-4 23-5
23-1
23-6
23-7
23-3
23-2
23-8
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXDSH022E✳ AVXDSH028E✳ AVXDSH036E✳
28
27
8
26
22
21
1 25
20
23 18
24
19
17
16
3
32
4
11
5
31 8
12
13
14
30
15
10
6
29 30-1
30-6
30-2
33
30-3
7
30-4
30-5
34
■ Parts List
Q'TY
12
7-1
14
15
7-3
15-1
15-6
15-2
7-2 15-4
8
15-3
15-5
3
3-2 10
9
3-1
11
1-2
1 16
13
1-1-2
1-1-3 1-1
1-1-1
1-3 1-1-4
1-1-5 2
1-1-6
1-4
4 5
■ Parts List
Q'TY
No. Code No. Description Specification AVXWPH022E✳ SA/SNA Remark
AVXWPH036E✳
AVXWPH028E✳
1 DB92-00561F ASS'Y PANEL FRONT TOTAL ASS'Y - 1 SA
DB92-00558F ASS'Y PANEL FRONT TOTAL ASS'Y 1 - SA
1-1 DB92-00560A ASS'Y PANEL FRONT SUB-P ASS'Y - 1 SC
DB92-00557A ASS'Y PANEL FRONT SUB-P ASS'Y 1 - SA
1-1-1 DB92-00559A ASS'Y PANEL FRONT SUB ASS'Y - 1 SA
DB92-00556A ASS'Y PANEL FRONT SUB ASS'Y 1 - SC
1-1-2 DB31-00166B MOTOR STEP - 1 1 SA
1-1-3 DB61-01114A HOLDER MOTOR DC HIPS - 1 SA
DB61-01123A HOLDER MOTOR DC HIPS 1 - SC
1-1-4 DB61-01115A HINGE GRILLE HIPS - 1 SC
DB61-01132A HINGE GRILLE HIPS 1 - SC
1-1-5 DB61-01116A GUIDE LINK HIPS - 1 SC
DB61-01133A GUIDE LINK HIPS 1 - SC
1-1-6 DB66-00364A LINK MOTOR ABS - 1 SA
DB66-00365A LINK MOTOR ABS 1 - SA
1-2 DB64-00640A GRILLE UP ABS - 1 SA
DB64-00655A GRILLE UP ABS 1 - SA
1-3 DB63-00585E FILTER-PRE LF PP - 1 SA
DB63-00590F FILTER-PRE LF PP 1 - SA
1-4 DB63-00586E FILTER-PRE RH PP - 1 SA
DB63-00591F FILTER-PRE RH PP 1 - SA
2 DB92-00540A ASS'Y GRILLE LOW ASS'Y - 1 SA
DB92-00538A ASS'Y GRILLE LOW ASS'Y 1 - SA
3 DB96-03801B ASS'Y EVAPORATOR TOTAL ASS'Y - 1 SA
DB96-03796B ASS'Y EVAPORATOR TOTAL ASS'Y 1 - SA
3-1 DB96-03800A ASS'Y EVAPORATOR ASS'Y - 1 SNA
DB96-03797B ASS'Y EVAPORATOR ASS'Y 1 - SNA
3-2 DB67-00051A SPACER-EVAP LOW PVC 1 - SNA
4 DB95-00367E ASS'Y FILTER BIO ASS'Y 1 1 SC
5 DB63-00581A COVER TERMINAL HIPS - 1 SA
DB63-00588A COVER TERMINAL HIPS 1 - SNA
6 DB93-03016N ASS'Y REMOCON ASS'Y 1 1 SA
7 DB94-00488A ASS'Y BACK BODY-SUB ASS'Y - 1 SA
DB94-00486A ASS'Y BACK BODY-SUB ASS'Y 1 - SA
7-1 DB61-01098A BACK BODY HIPS - 1 SNA
DB61-01119A BACK BODY HIPS 1 - SNA
7-2 DB63-00580A COVER-IONIZER HIPS 1 1 SA
7-3 DB94-00258A ASS'Y BEARING ASS'Y 1 1 SA
8 DB94-00040R ASS'Y CROSS FAN ASS'Y - 1 SC
DB94-00040F ASS'Y CROSS FAN ASS'Y 1 - SA
■ Parts List(cont.)
Q'TY
No. Code No. Description Specification AVXWPH022E✳ SA/SNA Remark
AVXWPH036E✳
AVXWPH028E✳
9 DB31-00152B MOTOR-FAN IN - - 1 SA
DB31-00152A MOTOR-FAN IN - 1 - SA
10 DB61-01099A HOLDER-MOTOR PP - 1 SA
DB61-01120A HOLDER-MOTOR PP 1 - SC
DB61-01126A BLADE-V PP 3 - SC
■ AVXWPH045E✳ /AVXWPH056E✳/AVXWPH071E✳
7-4
11
7-7 12
7-8
12-4
12-6
7-1
12-1
12-3
7-6
7-2
12-2
7-5 12-5
7-3
3
8
13
1
10
1-2
1-1-2
1-1
1-1-3
1-1-1
1-3
1-1-4
1-1-5
2
1-1-6
1-4
5
4
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXWPH045E✳ AVXWPH056E✳ AVXWPH071E✳
17
14
6
14-1
15
11
14-2
7
12 14-3
14-4
16 14-5 22
3
18 14-6
22-1
3-1
9 13 19
9-2 3-2
3-4
10
20
9-3
22-2
3-3
9-1
1
5 23
1-1
4
2-5
8 2-4
1-2
2-1
2-5-1
2-2 2-6
2-3
21
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXWHH028E✳ AVXWHH036E✳
■ Parts List(cont.)
Q'TY
No. Code No. Description Specification SA/SNA
AVXWHH028E✳ AVXWHH036E✳
■ AVXWHH045E✳ /AVXWHH056E✳/AVXWHH071E✳
17
14
6
14-1 15
11
14-2
12 14-3 7
14-4
14-5
21
16 3
18 14-6
21-1
9 3-1
13
24 3-2
3-4
10 19
21-2
23 3-3
1
5 22
1-1
4
2-5
2-4
8
2-1
2-5-1
1-2
2
2-2 2-6
2-3
20
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXWHH045E✳ AVXWHH056E✳ AVXWHH071E✳
■ Parts List(cont.)
Q'TY
No. Code No. Description Specification SA/SNA
AVXWHH045E✳ AVXWHH056E✳ AVXWHH071E✳
24
30 26
39 29
38
41
28
4
5
27
2
17
40
42
18 1
19 8 9 10
20
22 1112
35
23 32 31 6
16 3
13 34 43
21 7 25
46
36
37
45-7
33
45-6
15 45-3
45-4
45-5
45
45-2
45-8 45-1
14
44
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
AVXTFH056E✳ AVXTFH071E✳
■ Parts List(cont.)
Q'TY
No. Code No. Description Specification Remark
AVXTFH056E✳ AVXTFH071E✳
5-2-1 4/5/6HP
12
1
32
27 28
21 13-1
2
7
6
13
10
13-2
8 22
18
11
19 33
15
17
30
3 16
9 14
24
4 5
31 20-1
25
26 20-2
29
20
23
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
RVXMHF040E✳ RVXMHF050E✳
■ Parts List
Q'TY
No. Code No. Description Specification SA/SNA
RVXMHF050G✳ RVXMHF060G✳
5-2-2 8/10HP
3
20
4 44
26
5
19 43
12
6 8
42
9
28
10
7
42 31
29
34 18
30
32 37
39
36 40
25 35
21 27
22 23
24
13
41
45
33
14 46
15
16
17
8/10HP (cont.)
48-1
48-2
47-3
48-3
48-4
48-11
47-4 48-12
48-5
48-8
48-13
48-7
47-2
■ Parts List
■ Parts List(cont.)
5-2-3 12/14HP
20
26
43
12
44
8
19 6
42
28 7
9
25
11
31
18
29 34 37
21
30 32
22 39
10 40 35
13 36
23
24
14
38
27
33 46 41
15
45
16
17
12/14HP (cont.)
48-1
48-2
47-3
48-3
48-4
48-12
47-4 48-13
48-11
48-5
48-6
48-9
48-14
48-10 47-5
47-1
48-7
48-8
47-2
■ Parts List
■ Parts List(cont.)
Wall-mounted type(Premium)(cont.)
■ MAIN PCB : DB93-02779D(cont.)
6-2-1 RVXMFH040E✳
■ MAIN PCB : DB93-03828A
6-2-2 RVXMFH050E✳
■ MAIN PCB : DB93-03828B
RVXMFH050E✳(cont.)
■ MAIN PCB : DB93-03828B(cont.)
6-2-3 RVXMFH050G✳
■ MAIN PCB : DB93-03828C
6-2-4 RVXMFH060G✳
■ MAIN PCB : DB93-03828D
RVXVHT140G✳ /RVXFHT140G✳(cont.)
■ MAIN PCB : DB93-02756G(cont.)
■ CT PCB B : DB93-03531B
■ CT PCB C : DB93-03531C
7-2-4 8/10HP
7-2-5 12/14HP
■ RVXMHF✳✳✳✳✳
■ RVXVHT100G✳
Ambient
Sensor
Main EEV
4Way
Liquid EEV
Valve
High Liquid
Pressure Tube
Sensor Valve
Sub-Cooler
Hot Gas Valve Pressure Switch
Oil Seperator
Discharge
Sensor
Double tube sensor
PWM
Accumulator
■ RVXVHT140G✳
4Way
Liquid EEV
Valve
High Liquid
Pressure Tube
Sensor Valve
Sub-Cooler
Hot Gas Valve Pressure Switch
Oil Seperator
Discharge
Sensor
Discharge Double tube sensor
Sensor
PWM
Accumulator
■ RVXMHF✳✳✳✳✳
■ RVXVHT100G✳
Ambient
Sensor
Main EEV
4Way
Liquid EEV
Valve
High Liquid
Pressure Tube
Sensor Valve
Sub-Cooler
Hot Gas Valve Pressure Switch
Oil Seperator
Discharge
Sensor
Double tube sensor
PWM
Accumulator
■ RVXVHT140G✳
4Way
Liquid EEV
Valve
High Liquid
Pressure Tube
Sensor Valve
Sub-Cooler
Hot Gas Valve Pressure Switch
Oil Seperator
Discharge
Sensor
Discharge Double tube sensor
Sensor
PWM
Accumulator
12. Fixed
Fixing capability compressor which ON/OFF by the load.
22. Sub-cooler
Do the heat exchange of the overcooling liquid of the condenser outlet with the refrigerant of the compressor inhalation side
during cooling operation.
! @ # $ % ^ & * ( )
A
2
4
5
7 6
No. SW Function
SW01 SW02
Centralized
control
address set
(00~FF)
SW03 SW04
K12 Preparation
! @ # $ % ^ & +
A
=
*
‘ Q
(
B
‘
)
1
0
2
9
8 7 6 5 4 3
& CN61 BLACK SUB PCB CONNECTER 0 CN78 BLUE FAN MOTOR 2
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K12 Preparation
! @5 # 4 $ 2 ) % ^
&
B (
3 1
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K3 RPM up normal up
K12 Preparation
! 0 % ^ & *
A B
(
)
@
1
# 2
3
$ 4
9 8 7 6 5
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K3 RPM up normal up
K12 Preparation
5 4
! @ # $ % ^ & *
(
)
9 B
7 6 3 2 1
EXTERNAL OPTION
% CN83 RED EXTERNAL CONTROL 5 CN76 YELLOW
PCB CONNECTER
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K3 RPM up normal up
K12 Preparation
5 4
! @ # $ % ^ & *
(
)
9 B
7 6 3 2 1
EXTERNAL OPTION
% CN83 RED EXTERNAL CONTROL 5 CN76 YELLOW
PCB CONNECTER
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K3 RPM up normal up
K12 Preparation
5 4
! @ # $ % ^ & * 9
7 6 0 3 2 1
EXTERNAL OPTION
% CN83 RED EXTERNAL CONTROL 5 CN76 YELLOW
PCB CONNECTER
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K3 RPM up normal up
K12 Preparation
! @ #
&
(
5
4 3 2 1 $
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
■ MAIN PCB
! @ # $
&
4 3 2 1
■ SUB PCB
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K12 Preparation
! @ # $ 8 9 % ^&
A B
7 6 5 4 3 2 1 ) (
No. SW Function
Main address
set
(00 ~99)
SW01 SW02
Centralized control
address set
(00 ~FF)
SW03 SW04
K3 RPM up normal up
K12 Preparation
*! @ # $ % &
( ) 1 2 3 4 5 6 7 8 9 0^
3 2 1 ) ( * & ^ % $ # @
! @# $ % ^ &
9
8
0
*
7 (
)
6
3 2 1 5 4
@ # $
& ^
! CN71 BLUE 220V POWER INPUT % CN72 WHITE DC310V FAN INPUT
# GT2 SILVER 220V TRANS INPUT & CN73 WHITE FAN IN/OUT SIGNAL
$ CN70 BLACK 220V POWER OUTPUT * CN99 WHITE DC SIGNAL TO MAIN PCB
10-3-4 CT PCB
11-1-1 Features
■ The performance of the Digital Scroll compressor
• There will be running cost savings due to the high efficiency of the compressor.
• The wide capacity range will be able to control the room temperature and humidity very precisely for customer’s comfort.
• The whole system is very reliable; the compressor is extremely reliable and the electronics is simple and the oil return very well
for system operation.
• No electromagnetic interference issue.
PWM valve(Actuator)
Rotational
Scroll
Pump
signal signal
2s 8s
5s 5s
Floating Seal
Fixed Scroll
Orbiting Scroll
Controller Signal
Orbiting Scroll
Note : • The Digital Scroll operates in 2 states: loaded state and unloaded state. There is an external solenoid valve in the Digital
Scroll. When a 220V signal is given to the solenoid valve, the top scroll moves up by about 1 mm.
The movement of the top scroll creates a gap between the 2 scroll elements and there is no axial sealing between the
scrolls. As a result, even though the motor is running, the compressor is unable to compress any refrigerant.
The capacity in the loaded state is 100% and during the unloaded state is 0%. Capacity from the compressor is a time
average of the loaded state and the unloaded state. For example, in a cycle time of 20 seconds, if the scrolls are loaded
for 10 seconds and unloaded for 10 seconds, the time-averaged capacity is 50%.
The PWM receives the On/Off signal and controls the loading/unloading status. When the PWM valve is turned off, the fixed scroll
is pushed down to the orbiting scroll (Loading). When the PWM valve is turned on, the fixed scroll is separated from the orbiting
scroll (Unloading). This process is repeatedly done to make the outdoor unit controlling automatically depending on the number of
operating indoor unit(s) and their weighting factors.
100
90
80
70
60
50
40
30
20
10
0
0 2500 5000 7500 10000 12500
Total capacity of operating indoor unit(s)
■ Fast Cooling
EEV distributes the optimized refrigerant to each
indoor units with the least energy generated from the
Digital Scroll compressor loading/unloading function. Room Temperature(°C)
100
The indoor units senses not only the temperature Samsung mini-DVM
90 Samsung’s other energy-saving air conditioner
difference between inlet and outlet of evaporator but 80 Samsung energy-saving A’s air conditioner
■ Space saving
With the compact size of the outdoor unit, you can use
enough living space at home. The outdoor unit is
available for 4.0~6.0HP with the same size.
The indoor unit with slim and compact design also
contributes to save your space. Additionally, it is suit-
able for installing in the narrow area such as the
kitchen.
Common air conditioners Samsung mini-DVM
Multiple outdoor units Only one outdoor unit
1,128
+
638
320 375
880 932
■ Easy Installation
The refrigerant piping length between the outdoor and Refrigerant branch
11-1-2 Installation
■ Specification of the refrigerant pipe
ø19.05(6HP)
ø9.52 100 30(25)
ø15.88(4~5HP)
Note : • The value in brackets indicates the length when the outdoor unit is lower than the indoor unit.
■ Selecting the refrigerant pipe and the allowable length of the pipe
The refrigerant pipe should be short as much as possible and minimize the maximum allowable difference of height.
Outdoor unit
✳ A, B, C, D, E : Y-joint (When selecting the Y-joint B : Total capacity of the indoor unit 2, 3, 4, 5, 6)
Outdoor unit
EEV kit
✳ A, B, C : Y-joint (When selecting the Y-joint B:Total capacity of the indoor unit 2,3,4,5,6)
● Selecting the size of the refrigerant pipe after the first Y-joint
Note : • When installing pipe between the Y-joint,the minimum size of the liquid pipe is ø9.52(3/8”)and the minimum size of the gas
pipe is ø15.88(5/8”).
Note : • When total pipe length is more than 40m, the diameter of pipe from the outdoor unit to the first Y-joint has to step up.
11-2-1 Features
■ DVM Plus2 New
Outdoor unit
Combinations
Compressor 2 2 3 3 4 4 4
Outdoor unit
Combinations
Compressor 5 5 6 6 6 7 7
Outdoor unit
Combinations
Compressor 8 8 9 9 9 10 10
1.60m2
26% Reduced
28.0HP 1.84m2
2.48m2
DVM Plus 2
DVM Plus
42% Reduced
1.6m2
DVM Plus
0.92m2
DVM Plus II
Easy to lift
Cooling Heating
43°C 21°C
-15°C
Advanced
-5°C -20°C
DVM Plus DVM Plus 2 DVM Plus DVM Plus 2
Outdoor temperature
5. Long Piping
Long piping allows flexible and convenient installation of DVM Plus 2.
5m
ing
al pip m
Actu 17 0
h
lengt
15m
50m
45m
5m
difference
of height
30.0HP
8. Back up Function
If a compressor breaks down, it alerts the problem to the main system. After the compressor has stopped, the other compressors
inside the same outdoor unit or different unit continue operating with balance. Therefore it is reducing inconvenience while repairs
are made.
Broken
Running
Trouble
Off On On On On On On
Alarm
Service call
Stop
Back up
Running
Off Off On On On On On
11-2-2 Technology
■ DVM(Digital Variable Multi)'s is the practical proposal for your space!
1. The Performance of the Digital Scroll Compressor
Rotational
Scroll Pump
Signal
2s 8s
8 sec non compression
2 sec compression
100% Capacity
Signal
5s 5s
5 sec non compression
5 sec compression
0% Capacity
2-compressor system(10.0HP)
Unit : kcal/h
100
Running ratio of compressor(%)
90 High capacity
PWM valve Fixed scroll Operation
80
70
Digital Scroll
Loading Off Loading Compression 60
50
40
Unloading On Unloading No Compression Low capacity
30
Fixed scroll
20
Digital Scroll
10
0
0 5,000 10,000 15,000 20,000 25,000
Total capacity of operating indoor unit(s)
ΔQ=3
1
❶ ❷
0.5
ΔQ=3 ΔQ=2
❶ Falling room temperature
0
ΔQ=2 ❷ Rising room temperature
-0.5 ❸ Open electronic expansion valve
❸ ❹ Closed electronic expansion valve
-1
❹ ΔQ=0
The graph shows that the unloaded power consumption is 10% of full load power in case of 6 seconds loaded and 6 seconds
unloaded. In each cycle of modulation, the discharge pressure builds up during the loaded cycle, then the discharge pressure
decreases during the unloaded cycle. Similarly, the suction pressure decreases during the loaded cycle and it increases during
the unloaded cycle. The transition time to build up the pressure is a fraction of a second. The average value is around 0.4 sec-
ond.
4,000
2,000
0
0 20 40 60 80 100 Time 0 20 40 60 80 100 Time
100% Loading
On Off On
• Turn on the air conditioner • Room is colder than desired. • Room is warmer
• Set temperature at 22°C • Start/Stops consumes energy. than desired.
Reliability of the compressor is very important in multi evaporator systems, where only one compressor is air-conditioning the
whole area. The DSC compressor has passed high compression tests, high load tests, start/stop tests and many other extreme
tests, to deliver class leading reliability.
The solenoid valve of the Digital Scroll has a life of 40 million cycles equivalent to 30 years normal usage.
Room 1
Sum of individual
Room 2 system capacity in
5.0HP
Room 3
Multi Replace by
evaporator 3.0~4.0HP
system multi system
Compressor output
Heating Cooling
-20 -10 0 10 20 30 40
Ambient temperature(°C)
5. Energy Saving
Main operating range of commercial A/C is 50%~75% which affects the total system efficiency.
• In case of U.S.A., DOE(Department of Energy) investigated operating range of chillers in 29 cities during 25 Years. Based on
this data, weighting of part load point in efficiency calculation for chillers are established.
Weighting of
75%~50%
part load becomes
increased.
1%
100%
17%
42%
75%
39%
45%
50%
33%
• COP efficiency is 40% higher than other systems for DVM 10.0HP.
• It was measured in Samsung multi calorimeter by KSC 9306 at the same condition.
• Test Condition : Indoor DB 27.0/WB 19.0, Outdoor DB 35.0/WB 24.0, Operated by remote controllers
3.0
DSC
2.0
COP(W/W)
COP(W/W)
7~18%
1.0 Inverter
0
0 10,000 20,000 30,000 Compressor load
capacity(W) Peak
100 4.00
80 3.50
Pressure drop(Pa)
60 3.00
40 2.50
20 2.00
W-slit(FP1.3)
W-slit(FP1.5)
0 1.50
W-slit(FP1.7)
0.5 1 1.5 2 2.5 3
Slit(FP1.3) Air velocity(in)
Slit(FP1.5)
120
124.7%
107.7% 110
Pressure drop(Pa)
111% 104.9%
100
90
80
Pressure drop 70
W-slit(FP1.3) W-slit(FP1.5)
Capacity
1. Cost Saving
The graph shows that the unloaded power consumption is 10% of full load power in case of 6 seconds loaded and 6 seconds
unloaded. In each cycle of modulation, the discharge pressure builds up during the loaded cycle, then the discharge pressure
decreases during the unloaded cycle. Similarly, the suction pressure decreases during the loaded cycle and it increases during
the unloaded cycle. The transition time to build up the pressure is a fraction of a second. The average value is around 0.4 sec-
ond.
en ind
piping
eight
(Max.
50m(H
170m
For high story building applications, 100~170meter-long pipes and 40~50meter-high elevation system must provide reliable
capacity and oil management to prolong system life.
10m
Indoor chamber
Normal Scroll
10 12 14 16 18 20 22 24 26 28 30 35 40 50min
4. Space Saving
Compared to the conventional system, DVM system saves much more space because one single outdoor unit manages many
indoor units, resulting in maximizing your space.
11-2-3 Installation
■ Locating the Units
1. Outdoor unit combination Remarks - RVXVHT✳✳ : Digital variable outdoor unit
• Install the indoor unit only for R410A. Remarks - RVXFHT✳✳ : Fixed outdoor unit
3 phase
4 wires
380 -
415V~ Digital Fixed Fixed
ELB
220V
Outdoor
communication cable Earth
Indoor Wired remote
communication cable control
3 phase 1 phase
4 wires 220V
380 -
415V~ Digital Fixed Fixed
ELB ELB
220V
Earth Outdoor
communication cable Earth
Wired remote
Indoor control
communication cable
• Connect the communication cable between indoor and outdoor units to the digital outdoor unit.(RVXVHT✳✳)
• If the communication cable between indoor and outdoor units is not connected to the digital outdoor unit,
communication error may occur.
Manifold gauge • Use manifold gauge only for R410A to prevent the inflow of foreign substances.
• Use vacuum pump with check valve to prevent pump oil from flowing backward while the
Vacuum pump vacuum pump is stopped.
• Use the vacuum pump that the vacuum induction is available up to 100.7kPa(5Torr,755mmHg).
Flare nut • Use only flare nut supplied with the product.
Outdoor unit Normal installation Total length is more than 90m Oil balancing
capacity (HP) Liquid side Gas side Liquid side Gas side pipe
8 9.52 19.05 12.70 22.23
10 9.52 22.23 12.70 25.40
12, 14 12.70 25.40 15.88 28.58
6.35
16, 18, 20, 22, 24 15.88 28.58 19.05 31.75
26, 28, 30, 32, 34 19.05 31.75 22.23 38.10
36, 38, 40, 42, 44, 46, 48 19.05 38.10 22.23 44.50
• The total length includes elbows and joints over an allowable equivalent length. Should size up one grade of pipe between the
outdoor unit and the first Y-joint.
• Use the copper pipe of semi-hard(1/2H)when installing the pipe of ø19.05. If you use Soft(O)pipe,the internal pressure is too
low to cause personal injury.
Outdoor unit
Y-joint
Outdoor unit
Y-joint
Outdoor unit
Y-joint
Branch joint
Outdoor unit
Y-joint
Branch joint
Allowable Length of the Refrigerant Pipe and the Installation Examples (cont.)
Outdoor unit
Branch joint
Outdoor unit
Branch joint
- The connected pipe should be connected from the side of the air conditioner.
Allowable Length of the Refrigerant Pipe and the Installation Examples (cont.)
Using only Y-joint Using Y-joint and branch joint Using only branch joint
The distance between the outdoor unit and the furthest indoor unit ≤ 170m
Actual
Ex)Indoor unit 8 :
length Ex)Indoor unit 6:a+b+h ≤ 170m Ex)Indoor unit 8:a+i ≤ 170m
a+b+c+d+e+f+g+p ≤ 170m
Maximum Outdoor unit~
Indoor unit Equivalent The distance between the outdoor and the furthest indoor unit ≤ 190m
allowable length (The equivalent length of Y-joint :0.5m,The equivalent length of branch joint :1m)
length of
pipe Total The total distance from the outdoor unit to all indoor units ≤ 300m
length
Outdoor unit~ Actual The distance between the outdoor joint and the outdoor unit ≤ 10m,
Outdoor unit
(16HP ≤ ) length Equivalent length ≤ 13m
Outdoor unit~
Height H3:Difference of height among the outdoor units → ≤ 5m
Outdoor unit
The distance between the first Y-joint and the indoor unit ≤ 45m
Maximum allowable length Actual Ex)Indoor unit 8 : b+c+d+e+f+g+p ≤ 45m/ r≤10m(Equivalent length≤13m)
after the first branch pipe length Indoor unit 6 : b+h ≤ 45m/Indoor unit 8 : i ≤ 45m s≤10m(Equivalent length≤13m)
t≤10m(Equivalent length≤13m)
The distance between the EEV kit and indoor unit ≤ 20m
A◗ A◗
Installing pipes between more than Between Y-joints
1 outdoor unit and first Y-joint - Select it depending on attached
- Select the size depending on the indoor units.
outdoor unit capacity.
Outdoor unit total Liquid side Gas side Indoor unit total Liquid side Gas side
capacity (HP) (mm) (mm) capacity (kW) (mm) (mm)
8 ø9.52 ø19.05 X < 22.4 ø9.52 ø15.88
10 ø9.52 ø22.23 22.4 ≤ X < 33.0 ø9.52 ø22.23
12,14 ø12.70 ø25.40 33.0 ≤ X < 47.0 ø12.70 ø25.40
16,18,20,22,24 ø15.88 ø28.58 47.0 ≤ X < 71.0 ø15.88 ø28.58
26,28,30,32,34 ø19.05 ø31.75 71.0 ≤ X < 104.0 ø19.05 ø31.75
36,38,40,42, 104.0 ≤ X ø19.05 ø 38.10
ø19.05 ø38.10
44,46,48
B◗ C◗ D◗
Among the outdoor units Outdoor unit connection Oil balancing pipe
- Depend on the total capacity of - Depend on the outdoor unit - Applicable only 16HP or more
attached outdoor units.
Outdoor unit Liquid side Gas side Outdoor unit Liquid side Gas side Outdoor unit
All diameters (mm)
capacity (HP) (mm) (mm) capacity (HP) (mm) (mm) capacity (HP)
X < 26 ø15.88 ø28.58 8 ø9.52 ø19.05
26 ≤ X < 36 ø19.05 ø31.75 10 ø9.52 ø22.23 X ≥ 16 ø6.35
36 ≤ X ø19.05 ø38.10 12,14 ø12.70 ø25.40
A B
C
Liquid side pipe ø22.23 Liquid side pipe ø19.05 Liquid side pipe ø15.88
A= + + +
Total pipe length(m)X 0.35 Total pipe length(m)X 0.27 Total pipe length(m)X 0.18
Liquid side pipe ø12.70 Liquid side pipe ø9.52 Liquid side pipe ø6.35
+ +
Total pipe length(m)X 0.125 Total pipe length(m)X 0.06 Total pipe length(m)X 0.02
HP Factory charged (kg) Liquid side pipe (mm) Basic charging for pipes (kg)
8/10 6.3 ø6.35 0.02
12/14 7.5 ø9.52 0.06
ø12.70 0.125
ø15.88 0.18
ø19.05 0.27
ø22.23 0.35
Power on
Yes
No
Tracking completed?
No
Is 3 phase power OK?
No
Is preheating of CCH completed?
Preheating CCH
Yes
(For 2.5 hours)
Normal operation
1. When the power is on, the MICOM of outdoor unit check the
indoor units, transmitters installed in the same system,
which is called as Tracking.
1) The left side display shows the address of indoor unit with which the outdoor
unit is trying to communicate.
(0-1-2- . . . -d-E-F)
2) The right side display shows the address of indoor unit responding to the
communication.
3) The right side display displays together when the related indoor unit
address displays at the left side. Left Right
(For example, if there is 4 sets of indoor units having the address of Display of outdoor unit
0, 1, 2, 3 at the outdoor unit, and when the left side display trying to
communicate to 0 -1-2- ... d-E-F, the right side displays 0-1-2-3 only
when the left side is 0-1-2-3.)
2. To check the numbers of indoor unit connected with outdoor unit by use of indoor unit
numbers setting switch.
■ Heat pump
Display
Reset key
K3
Installed indoor
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
units numbers
3. If the numbers of indoor units checked through installed indoor unit number setting switch
do not match with those during tracking, the display shows E201 alternately.
12-1-2 Reverse Phase/Missing Phase Detection (outdoor unit using 3 phase power)-
indicated if abnormal
1. If the power is on, check the power to be used for 3 phase power compressor.
If there is any change of order for 3 phase L1(R)-L2(S)-L3-(T) (reverse phase) or the phase power
(missing phase) which means the power is not on, E425 are indicated alternately and the air conditioner is kept to
stop.
Display
Reset key
5) If there is abnormal condition even after one more check, check the cable color for 3 phase power. If there is no abnormal
as a result of check, replace the PCB.
! communication part
@ indoor power
! @ # $ # power
$ power(Compressor)
single phase
clamp AC230V supply
line
communication line indoor power supply line 3 phase power supply line
! communication part
OF1 OF2 R S T N @ power
# power(Compressor)
! @ #
2. If it is the condition for compressor operation as the result of check, the flickering of Ch disappears and the indoor
unit address trying to communicate with outdoor unit displays and the responding address on the right part.
3. If it is not the condition for the compressor operation at the moment, Ch is kept flickering on the display part and
CCH (crank case heater) heats the compressor for 2 and half hours.
The compressor cannot be operated for the time, but can be operated if Ch disappears due to the sufficient heating
for 2 and half hours.
4. The check of operation ability by the temperature is performed only once at the initial stage.
However, in case that the product is installed and operated for the first time, the power shall be put 6 hours before.
Power reset
Error of heat exchanger sensor in indoor unit Displayed on appropriate indoor unit
Error of heat exchanger OUT sensor in indoor unit which is operating
Error of outlet temperature sensor in indoor unit
(OPEN/SHORT): For heat pump models only
: On : Flickering : Off
EEPROM error
On Blink Off
✳ When stopping the operation during an error is displayed, all lamps are off.
✳ When restarting after stopping an operation, redisplay the error status by deciding the error again on normal operation.
E P U A
Display method of an error that is occurred at Error No. → Indoor unit address → E471 → A002 → E471 → A002
indoor unit Error No., repeat display
Display method of an error that is occurred at Error No. → Outdoor unit address →
E471 → U200 → E471 → U200
outdoor unit or other error display method Error No., repeat display
✳ In case several errors are displayed simultaneously, only the most high priority number of an error among errors in the below table is displayed.
(The upper location at the below table has more high priority.)
✳ In case same error occurs at several indoor units, only the smallest indoor unit address is displayed.
Forbid an operation during heat mode with refrigerant charging operation when outdoor
temperature is over 15°C
Communication error between main of outdoor unit and sub MICOM or between units
Loading failure
CT_over current
CT_low current
: An error occurs and starting is prohibited right before starting the heat mode of
the outdoor unit by the remote control on signal of the indoor unit or when outdoor
temperature is over 30°C.
Judgment method
: An error occurs and starting is prohibited right before starting the heat mode with
refrigerant charging operation by the K1 switch of outdoor PCB or when outdoor
temperature is over 15°C.
1. Check Method
The above error code is not for the products' error. Because this specification is to protect the products by restricting the
temperature ranges, use it by referring the temperature range of use condition in the manual.
If the above error code is occurred despite the condition does not correspond to the above judgment method, read the value
of the outdoor inlet air temperature sensor by use of the view mode or S-net, and then if the value is different from the actual
outdoor temperature, replace the temperature sensor.
Before the pump down start for 3 consecutive seconds, when the low pressure sensor value
(high pressure sensor does not come under) among Main Units is below 3.1kg/cm2G during
Judgment method
cooling operation and below 2.6kg/ cm2G during heating operation, start is prohibited.
(Impossible to restart and error display on the indoor unit).
1. Check Method
1) Measure the pressure using the Manifold Gauge when the system is stopped.
2) Read the low pressure sensor value using the View Mode or S-net.
3) If the value of no. 1 and no. 2 is similar, refrigerant is leaked out almost; therefore, release remaining refrigerant, vacuum
again, and recharge it.
4) If the value of no. 1 and no. 2 is different by much, check and replace it because the contact badness of low pressure
sensor connector part or defect of the sensor itself.
• Above error can be occurred because pressure is low on the low pressure side according to the refrigerant is
only gathered at the outdoor heat exchanger after pump-down. In this case, after correctly connecting the
pipe to the indoor unit and open the service valve, refrigerant circulates to the low pressure side; thus, the
error is disappeared.
■ : Oil Valve(Equal Oil Valve) 1 Self Diagnosis(Open or Close Error, Sensor Breakaway or Defect)
Oil valve (equal oil valve) temperature sensor breakaway / oil valve (equal oil valve) 1 defect /
Causes
coil defect or terminal contact badness
1. Check Method
Yes
Is the oil valve 1 temperature Insert the sensor correctly.
sensor separated?
No
No
Is the temperature measuring value proper? Replace the temperature sensor
(Using S-net and View Mode)
Yes
No
Is the oil service valve opened? Open the oil service valve.
Yes
Yes
No
Is the resistance value of the coil proper? Replace the coil.
Yes
Judgment method Detect when the high pressure sensor value is over 41kg/cm2
<Cooling operation>
Outdoor unit fan motor error (lock, defect) / Motor Driver defect or Wire short / Contamination of
the outdoor unit heat exchanger / SSR defect for Fan control / Service Valve closeness /
Causes Excess amount of refrigerant
<Heating operation>
Indoor unit fan motor error (lock, defect) /Fan Motor Capacitor defect or Wire short / Service
Valve closeness / Excess amount of refrigerant
1. Check Method
No
Is the service valve opened all? Open the service valve.
Yes
Yes
Yes
No
Yes
Detect when the low pressure sensor value is under 2.6kg/cm2 during cooling operation and
Judgment method
when the value is under 1.4kg/cm2 during heating operation.
1. Check Method
Test operation
Connect the S-net and Manifold
Gauge (Requisite)
No
Is the service valve opened all? Open the service valve.
Yes
Yes
Yes
No
No
When the temperature of indoor unit heat exchanger during cooling operation maintains for
Judgment method
over 5 minutes below -4°C
1. Check Method
Yes Yes
Operate when every room is cool. After checking the connection wire
of the fan motor, replace the motor.
No
Is high/low pressure normal? Check the amount of refrigerant.
Yes
Completion
Judgment method Sump temperature maintains for over 5 minutes over 95°C
1. Check Method
No
Is the Loading or Unloading of the Digital Check the PWM Valve.
compressor operated normally?
Yes
Yes
Yes
Judgment method Detect when the compressor emission temperature sensor value is over 135°C
Insufficient refrigerant / Indoor and outdoor EV clogging / Service valve clogging / Emission tem-
Causes perature sensor defect / Pipe and filter clogging / Liquid EEV break / Liquid Tube Valve break /
Compressor Discharge Check Valve leakage of the outdoor unit on the stop side
1. Check Method
Yes
Test operation
Connect the S-net and Manifold
Gauge(Requisite)
No
Is the service valve opened all? Open the service valve.
Yes
No
Are the indoor unit and outdoor unit Check the relevant EEV.
EEV operated normally?
Yes
Yes
Is there any clogged part in a piping Check the pipe.
(Filter, etc.)?
No
No
Causes Outdoor unit COND OUT sensor breakaway / sensor defect / corresponding path is blocked
1. Judgment Method
1) Not detect during cooling operation
2) Heating operation (The below conditions should be satisfied for over 20 minutes.)
2. Check Method
Yes
Yes
Yes
Completion
Suppose the Suction temperature right before Comp start that has high priority of start = Tsuc,
Judgment method ini and the Suction temperature of current Comp = Tsuc, real. When | Tsuc, real - Tsuc, ini | <
2°C condition maintains for 30 minutes, the error is judged.
1. Check Method
Yes
Yes
Completion
When the CT sensor value of the relevant compressor is maintained for over 5 seconds at over
Judgment method
20A, the error is displayed.
1. Check Method
No
Is the CT sensor connector resistance normal? Replace the CT sensor.
Yes
Yes
Test operation
Connect the separate
ampere-meter. (Optional)
Yes
No
When the ratio of (High pressure + 1) / (Low pressure + 1) is over 8.5 and it maintains for over
Judgment method
10 minutes.
Causes Indoor & Outdoor EEV break and pipe clogging / High & Low sensor defect
1. Check Method
Test operation
Connect the S-net and Manifold
Gauge (Requisite)
No
Is the service valve opened all? Open the service valve.
Yes
Yes
No
Are the indoor unit and outdoor unit EEV Check the relevant EEV.
operated normally?
Yes
No
No
■ ( for 1st Detection) Detection of Floating Switch of Indoor Unit Drain Pump
Rise of the water level of the drain plate according to the indoor unit drain pump break or detec-
Causes
tion sensor defect
1. Check Method
Yes
Replace the indoor unit PCB.
Reset the indoor unit power
and check whether the drain Normally operated.
pump is operated normally or not.
It causes by plot switch defect ;
thus, replace it and reset the indoor
unit power.
No
Is the drain pump operated?
Yes
Is the terminal voltage No
of the drain pump PCB approximately
AC 220V?
No
Is the water level of the drain plate lowered?
Yes
Replace the indoor unit
Yes Replace the drain pump.
PCB.
1. Judgment Method
1) Cooling operation (The below conditions should be satisfied for over 20 minutes.)
2. Check Method
1) Check whether the EEV wire is connected to the indoor unit PCB correctly.
2) Check whether the EEV coil is inserted into the body correctly.
3) Check with the naked eye whether rust is generated on the outside of the EEV coil, the resistance between each
terminal of coils, and the open and short on the coil inside.
4) After pressing the outdoor unit Reset Key (K3), check that same error is occurred.
- In case close error, do not operate the indoor unit that the error is occurred.
- In case open error, do not operate the indoor unit that the error is occurred.
5) If no error is checked for the above check points, replace the relevant indoor unit EEV.
- The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus,
before replacing it, must check the above points.
Causes Indoor unit EV moving defect (refrigerant is leaked to the stopped indoor unit)
1. Judgment Method
Detect only during cooling operation (Not detect during heating operation)
When the inlet or outlet temperature of the indoor heat exchanger on the stop side during cooling operation maintains for
over 20 minutes at below 0˚C.
2. Check Method
1) Check whether the EEV wire is connected to the indoor unit PCB correctly.
2) Check whether the EEV coil is inserted into the body correctly.
3) Check with the naked eye whether rust is generated on the outside of the EEV coil, the resistance between each
terminal of coils, and the open and short on the coil inside.
4) After pressing the outdoor unit Reset Key (K3), check that same error is occurred.
- In case close error, do not operate the indoor unit that the error is occurred.
- In case open error, do not operate the indoor unit that the error is occurred.
5) If no error is checked for the above check points, replace the relevant indoor unit EEV.
- The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus, before replacing it,
must check the above points.
Outdoor unit display ↔ A*** (*** : Indoor unit address which an error is occurred)
1. Judgment Method
1) Cooling operation
2) Heating operation
2. Check Method
After checking whether the indoor heat exchanger EVAP IN sensor is separated or not, adjust after assembly.
Outdoor unit display ↔ A*** (*** : Indoor unit address which an error is occurred)
1. Judgment Method
1) Cooling operation
2) Heating operation
2. Check Method
After checking whether the indoor heat exchanger EVAP OUT sensor is separated or not, adjust after assembly.
1. Judgment Method
Suppose the Suction temperature right before Comp start = Tsump, ini and the Suction temperature of current
Comp = Tsump, real. When the difference of the absolute value between Tsump, ini and Tsump, real is less than 2°C,
in other words, |Tsump, real - Tsump, ini | < 2°C, maintains for 60 minutes after compressor is started, the error is judged.
After 60 minutes after compressor is started, do not perform the detection of the Sump temperature sensor breakaway.
2. Check Method
After checking whether the relevant compressor sensor is broken away by the error code or not, assemble and adjust.
✳ Must organize because the location of the compressor Discharge temperature sensor is different by the error code.
1. Check Method
After checking whether the relevant compressor sensor is broken away by the error code or not, assemble and adjust.
Yes
Is the emission
No
temperature sensor resistance value proper? Sensor defect : Replace the sensor
(Refer to )
Yes
Yes
Complete
When the CT sensor value of the relevant compressor is maintained for over 10 minutes at over
Judgment method
4A, the error is displayed.
1. Check Method
Yes
Yes
Test operation
Connect the separate
ampere-meter. (Optional)
Yes
No
If compression is achieved
smoothly during the relevant
Is the CT value measured below Yes compressor operation, there is
4A during operation? no error. If compression is not
achieved, the compressor is
broken.
No
Judgment method When the temperature of the outdoor Fan Motor operated is overheated at over 110°C
1. Check Method
1) The system is programmed that operating after cooling the motor by lowering the number of rotation of the motor in
case of the overload and error action as for the motor protecting action. If the motor is operated, there is no error.
2) Check whether there is rotation of the outdoor Fan Motor and whether there is a lock.
3) Possible to operate after removing the cause of the lock in case of the lock.
When the difference between the number of rotation of the outdoor Fan Motor under an
Judgment method
operation and an ordered value is over 100rpm
1. Check Method
1) The system is programmed that operating by attempting to restart several times to operate the motor if an error signal
is generated on the starting defect. If the motor is operated, there is no error.
2) Check whether the outdoor unit Fan Motor is rotated and locked or not.
3) Check the motor and the signal terminal connection status.
4) If the motor is not operated, the motor defect is judged.
Judgment method When the temperature of IPM during the operation of the outdoor Fan Motor is over 150°C
1. Check Method
1) Check whether the outdoor unit Fan Motor is rotated and locked or not.
2) When the above error is occurred in case there is no lock, check whether the motor is restarted after cooling the motor
in case of the overload and error action as for protecting the inside circuit of the motor.
3) When is occurred after , the defect by the break of the inside circuit of the motor is judged.
When the current value of the outdoor Fan Motor on operation maintains over 1 minute at
Judgment method
over 7A
1. Check Method
1) Check whether the outdoor unit Fan Motor is rotated and locked or not.
2) When the above error is occurred in case there is no lock, the signal by overload and error action is judged.
The signal is to display the motor load status and it is not an error.
3) Need to check whether there is an error of Fan load status or not.
Judgment method When the rotation direction of the outdoor unit Fan Motor is rotated reversely before starting
Causes Wind that let the Fan operate reversely is generated, ex) Typhoon
1. Judgment Method
Check whether there is reverse rotation (CCW) before ordering of starting the outdoor unit Fan.
2. Check Method
1) This signal is for motor protection in order not to start under reverse rotation condition by checking the moving status
when the power of the outdoor unit fan motor is not turned on.
2) Check there is outside wind which can rotate the fan by force in the place where the outdoor unit is installed.
Outdoor unit display ↔ A*** (***: Indoor unit address which an error is occurred)
Causes Open/Short defect of the no. *** indoor unit room temperature sensor
Temperature Resistance
Detach the indoor room temperature sensor (°C) (Kߟ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Outdoor unit display ↔ A*** (***: Indoor unit address which an error is occurred)
Causes Open/Short error of the no. *** indoor unit EVAP IN sensor
Temperature Resistance
Detach the indoor EVAP IN (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Outdoor unit display ↔ A*** (***: Indoor unit address which an error is occurred)
Causes Open/Short error of the no. *** indoor unit EVAP OUT sensor
Temperature Resistance
Detach the indoor EVAP OUT (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Outdoor unit display ↔ A*** (***: Indoor unit address which an error is occurred)
1. Judgment Method
Occur when a feedback of RPM value is not returned from PID control style fan motor to MICOM.
2. Check Method
1) Check the HALL IC connector which gives feedback of RPM valve.
2) In case the fan motor starting Capacitor is PCB separate type, check the connection terminal.
3) Check the fan motor starting status.
4) If no error is checked for the above check points, replace the PCB.
■ Communication Error between Indoor Unit and Outdoor Unit during Tracking
Judgment method Communication error between the indoor unit and outdoor unit
Causes Setup error of the setting switch for setting the number of indoor unit’s to be installed.
Is the voltage
between both wires No
square wave over
DC ±0.7V? If there is no defect in address,
replace the indoor unit PCB after checking the
communication wire.
Yes
■ Communication Error between Indoor Unit and Outdoor Unit after Completion of Tracking
In case there is no communication between indoor unit and outdoor unit for 2 minutes during
Judgment method
the operation (When not being received in every room)
Causes Communication error between the indoor unit and outdoor unit.
Yes
Good Bad
0.7V
0.7V
Temperature Resistance
Detach the outdoor temperature sensor (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Yes
Temperature Resistance
Detach outdoor constant speed compressor
discharge temperature sensor connector from
(°C) (KΩ)
PCB and measure the resistance value between 130 8.9
the both terminals.
120 11.2
100 18.5
80 32
Yes 60 59
25 200
20 242
10 362
0 553
Is the resistance value far from the No
temperature table? -10 ( )
Temperature Resistance
Detach outdoor oil temperature sensor (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 130 8.9
120 11.2
100 18.5
80 32
Yes 60 59
25 200
20 242
10 362
Is the resistance value far 0 553
from the No
-10
temperature table?
Temperature Resistance
Detach outdoor COND OUT sensor (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value far -10 43.0
from the No
temperature table?
Temperature Resistance
Detach the dual-pipe temperature sensor (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value far -10 43.0
from the No
temperature table?
In case the order of phases is reversed or one or every phase voltage is not entered compare to
Judgment method the 3 phase defect circuit wave. (If the phase voltage is returned to normal, error is
automatically released.)
Causes 3 phase power L1(R), L2(S), L3(T) open error or not input 3 phase power
1. Check point
1) Check the power of the 3 phase detection part on the outdoor unit PCB.
2) The color of the power cable on 1(R), L2(S), and L3(T) of the 3 phase detection connector is red, white, and black.
(Make sure not to change the color and order.)
Yes
Yes
The reverse problem of inlet 3 phase
lines is solved, thus it operates normally.
Replace the PCB because it is a defect of
3 phase detection circuit.
■ EEPROM Error
■ Communication Error between the Outdoor Unit Main and Sub MICOM or Communication
Error between the Outdoor Units
Outdoor unit display ↔ U*** (***: Outdoor unit address which an error is occurred.)
No
Is the power supply normal? Check the power.
12V, 5V
Yes
Yes
No
Check the outdoor unit setting Change the setting.
option K13, K14
Yes
Mismatching of the indoor unit numbers set with those communicated after completion of tracking
In removing frost
Recovery of oil
Stop operation the unit when the crank case heater is being heated
Outdoor unit display ↔ A*** (***: Indoor unit address which an error is occurred)
Causes Open/Short defect of the no. *** indoor unit room temperature sensor
Temperature Resistance
Detach the indoor room temperature sensor (°C) (Kߟ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Outdoor unit display ↔ A*** (***: Indoor unit address which an error is occurred)
Causes Open/Short error of the no. *** indoor unit EVAP IN sensor
Temperature Resistance
Detach the indoor EVAP IN (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Outdoor unit display ↔ A*** (***: Indoor unit address which an error is occurred)
Causes Open/Short error of the no. *** indoor unit EVAP OUT sensor
Temperature Resistance
Detach the indoor EVAP OUT (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Outdoor unit display ↔ A*** (*** : Indoor unit address which an error is occurred)
1. Judgment Method
1) Cooling operation
2) Heating operation
2. Check Method
After checking whether the indoor heat exchanger EVAP IN sensor is separated or not, adjust after assembly.
Outdoor unit display ↔ A*** (*** : Indoor unit address which an error is occurred)
1. Judgment Method
1) Cooling operation
2) Heating operation
2. Check Method
After checking whether the indoor heat exchanger EVAP OUT sensor is separated or not, adjust after assembly.
Causes Indoor unit EV moving defect (refrigerant is leaked to the stopped indoor unit)
1. Judgment Method
Detect only during cooling operation (Not detect during heating operation)
When the inlet or outlet temperature of the indoor heat exchanger on the stop side during cooling operation maintains for
over 20 minutes at below 0˚C.
2. Check Method
1) Check whether the EEV wire is connected to the indoor unit PCB correctly.
2) Check whether the EEV coil is inserted into the body correctly.
3) Check with the naked eye whether rust is generated on the outside of the EEV coil, the resistance between each
terminal of coils, and the open and short on the coil inside.
4) After pressing the outdoor unit Reset Key (K3), check that same error is occurred.
- In case close error, do not operate the indoor unit that the error is occurred.
- In case open error, do not operate the indoor unit that the error is occurred.
5) If no error is checked for the above check points, replace the relevant indoor unit EEV.
- The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus, before replacing it,
must check the above points.
1. Judgment Method
1) Cooling operation (The below conditions should be satisfied for over 20 minutes.)
2. Check Method
1) Check whether the EEV wire is connected to the indoor unit PCB correctly.
2) Check whether the EEV coil is inserted into the body correctly.
3) Check with the naked eye whether rust is generated on the outside of the EEV coil, the resistance between each
terminal of coils, and the open and short on the coil inside.
4) After pressing the outdoor unit Reset Key (K3), check that same error is occurred.
- In case close error, do not operate the indoor unit that the error is occurred.
- In case open error, do not operate the indoor unit that the error is occurred.
5) If no error is checked for the above check points, replace the relevant indoor unit EEV.
- The replacement of EEV is inconvenient because it collects all refrigerant of the system; thus,
before replacing it, must check the above points.
■ ( for 1st Detection) Detection of Floating Switch of Indoor Unit Drain Pump
Rise of the water level of the drain plate according to the indoor unit drain pump break or detec-
Causes
tion sensor defect
1. Check Method
Yes
Replace the indoor unit PCB.
Reset the indoor unit power
and check whether the drain Normally operated.
pump is operated normally or not.
It causes by plot switch defect ;
thus, replace it and reset the indoor
unit power.
No
Is the drain pump operated?
Yes
Is the terminal voltage No
of the drain pump PCB approximately
AC 220V?
No
Is the water level of the drain plate lowered?
Yes
Replace the indoor unit
Yes Replace the drain pump.
PCB.
■ : Communication Error between Indoor Unit and Outdoor Unit during Tracking
Judgment method Communication error between the indoor unit and outdoor unit
Causes Setup error of the setting switch for setting the number of indoor unit’s to be installed.
Is the voltage
between both wires No
square wave over
DC ±0.7V? If there is no defect in address,
replace the indoor unit PCB after checking the
communication wire.
Yes
■ : Communication Error between Indoor Unit and Outdoor Unit after Completion of
In case there is no communication between indoor unit and outdoor unit for 2 minutes during
Judgment method
the operation (When not being received in every room)
Causes Communication error between the indoor unit and outdoor unit.
Yes
Good Bad
0.7V
0.7V
Temperature Resistance
Detach the outdoor temperature sensor (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value -10 43.0
far from the No
temperature table?
Temperature Resistance
Detach outdoor COND OUT sensor (°C) (KΩ)
connector from PCB and measure the resistance
value between the both terminals. 70 2.2
60 3.0
50 4.2
40 5.8
Yes 30 8.3
20 12.1
10 18.0
0 27.3
Is the resistance value far -10 43.0
from the No
temperature table?
■ : The error of outdoor unit COND MID temperature sensor (open / short)
Judgment method - When opening or shorting of outdoor heat exchanger temperature sensor
Temperature Resistance
(˚C) (kΩ)
Detach the outdoor heat exchanger 70 2.2
temperature sensor connecter from PCB,
and measure the resistance value 60 3.0
between the both terminals. 50 4.2
40 5.8
30 8.3
20 12.1
Yes
10 18.0
0 27.3
-10 43.0
Is the resistance
Yes
value far from the temperature
table?
Causes Outdoor unit COND OUT sensor breakaway / sensor defect / corresponding path is blocked
1. Judgment Method
1) Not detect during cooling operation
2) Heating operation (The below conditions should be satisfied for over 20 minutes.)
2. Check Method
Yes
Yes
Yes
Completion
1. Judge method
2) Cond Out Sensor is detected in the condition that it is under heating test operation and the capacity of compressor is
the maximum ste (20 step).
2. Check method
Check if the corresponding outdoor unit COND OUT sensor is separated according to the error code, assemble and
adjust it.
Yes
1. Judgment Method
If digital compressor discharge temperature is Tdisc, d
Fixed compressor discharge temperature are Tdisc, f1/tdisc, f2/Tdisc, f3,
I Tdisc, d - Tdisc, f1 I > In case of 40˚C, E262 error
I Tdisc, d - Tdisc, f1 I > In case of 40˚C, E263 error
I Tdisc, d - Tdisc, f1 I > In case of 40˚C, E264 error
2. Check method
Check if the corresponding compressor sensor is separated according to the error code, assemble and adjust it.
✳Display method of the order and number of compressor (In case of 4 compressors)
@ #
! $
Front
Digital compressor
Judgment method - When the temperature of indoor unit heat exchanger on cooling operation maintains
over 5 minutes below -4˚C
Error reset(KEY3)
Operate a corresponding
indoor unit.
Yes Yes
Restart after PCB
exchange.
Yes
After checking the quantity of
It is completed to check the system. refrigerant, if needed recharge
the refrigerant.
- If the outdoor temperature is below -5˚C at the right before of compressor start,
- prohibit cooling operation. ➞
Judgment method
- If the outdoor temperature is over 30˚C at the right before of compressor start,
- prohibit heating operation ➞
■ Check method
■ The above error code is not the products error, but specification to protect the products by restricting the use temperature
ranges. Use it by reference to the temperature range of use condition in manual.
If the above error code is occurred despite of condition being not included above judge method, read the value of outdoor
inlet air temperature by use of view mode or S-net. And then if it is different with the actual outdoor temperature, replace the
temperature sensor.
1. Judge method
1) Cooling operation
2) Heating operation
Yes
Error reset(KEY 3)
No
Yes
• The replacement of PWM valve due to the loading failure is the difficult work to abolish the refrigerant in the
system and recharging it, and there is little possibility to appear actually.
So, check the above check items carefully.
• The restart after OLP trip is possible only when the inside temperature of compressor is down lower than 60˚C,
and therefore it takes about 2~3 hours.
• If waiting at the state that the power is on during the temperature failing down.
CCH(Crank case heater) operates to delay the time to restart. Accordingly, separate the connecter to the CCH
to block the power and reconnect the connecter after the completion of final check.
1. Check method
This is the special operation mode to recollect oil discharged from the compressor, and it is entered for 3 minutes in 7
hours interval.
It returns to the normal operation after oil collection operation for 3 minutes automatically.
Extra...
1. Display interface
2. Sensor Input(room, eva in/out)
3. Program download interface
FAN Starting Capacitor 4. External PBA interface
FUSE 5. EEV DRIVE
6. BUZZER DRIVE
1. Noise Filter
FUSE
1. Main/Rmc Address
MPU 2. Operation Condition
Extra...
1. Display interface
2. Sensor Input(room, eva in/out)
3. EEV DRIVE
Program
Download
interface
MPU
Setting Part
Fan Motor Drive 1. Main/Rmc Address
(TAP TYPE) 2. Operation Condition
Communication Part
1. Wired Remocon
2. Outdoor Unit
FUSE BUZZER
DRIVE
Power Generation Part
1. Rectifier
1. Power Input 2. Linear Regulator
2. Noise Filter
External Control
Signal/
Indoor Louver External Status
EEV Control Output
Drain Pump,
Ventilator Address, Option Setting Switch Floating Switch
Sensor
Indoor FAN(SSR Control) (Room, Eva.
-in,out temp)
485
Display Communication
Extra...
1. Display interface
2. Sensor Input(room, eva in/out)
3. EEV DRIVE
Program
Download Communication
interface 1. Wired
Remocon
2. Outdoor Unit
Fan Motor Driver MPU
Setting Part
(TAP TYPE)
1. Main/Rmc Address
2. Operation Condition
Power Generation
1. Rectifier
1. Noise Filter FUSE 2. Linear Regulator
Extra...
1. Display interface
2. Sensor Input(room, eva in/out)
3. EEV DRIVE
Communication
Part
1. Wired
Program
Remocon
Download
2. Outdoor Unit
Setting Part MPU interface
1. Main/Rmc Address
2. Operation Condition
F Power Generation
U 1. Rectifier
Fan Motor S 2. Linear Regulator
1. Power Input E
Driver
2. Noise Filter
(SSR TYPE)
FUSE
Setting Part
1. Main/Rmc Address
1. Power Input 2. Operation Condition
2. Noise Filter
3. Fan Motor Driver
Power Generation Part (SSR TYPE)
1. Rectifier
2. Linear Regulator
Communication
1. Wired Remocon
2. Outdoor Unit
BUZZER
DRIVE
MPU
1. Sensor Input(room, eva in/out)
1. Program download interface 2. Display interface
2. EEV DRIVE 3. AUTO GRILLE
3. LOUVER
Communication
Part
Wired Remocon
MPU Outdoor Unit
1. Program download
interface
2. EEV Display interface
Download
Centralized Control
*Wired remote controller
*Transmitter
*Centralized Controller
Interface with
Power Input DC LINK Main PBA
Surge Protector Noise Filter
Charging Part AC
Power
Rectifier
Linear Current Transducer
Regulator AC Power Rect.
For main PBA For main PBA
Model Code
model name
! @ # $ % ^ &
& Version
A~Z(Export)
Model Code
model name
! @ # $ % ^ &
The number of
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
indoor unit installation
Example) If 3 indoor units are installed, adjust the arrow of switch to "3".
Note : • The display method of English characters and figures on PCB display part
0 1 2 3 4 5 6 7 8 9 A B C D E F G H
I J K L M N O P Q R S T U V W X Y Z
Check Mode
G2 b c e d G2 b c e d
K1 K2 K3 K4
g a f G1 g a f G1
SEG1 SEG2 SEG3 SEG4
Reset View Mode Reset View Mode
3. Key function
Function K1 K2 K3 K4
Enter times (SEG 3, 4 display) (SEG 3, 4 display) (SEG 3, 4 display) (SEG 3, 4 display)
Heating refrigerant Cooling refrigerant
1 time Reset Data display
supplement( ) supplement( )
Refrigerant collection
3 time Completion ( ) - -
Pump down
4 time - Completion - -
4. Display Mode
4. When K4 is input, every temperature and cycle data are displayed.
4. Refer to the following table for the number of times that the key is pressed.
The number
Contents Display Remark Example
of times
SEG 1 : 1Flickers
1 HP of indoor unit - 5HP → 0.5
SEG 3, 4 : Data display
SEG 1 : 4 Flickers
4 The temperature of outdoor - 101 → Display 1, 0, 1
SEG 2, 3, 4 : Data display
SEG 1 : 6 Flickers
6 Cond Out Temperature - 101 → Display 1, 0, 1
SEG 2, 3, 4 : Data display
SEG 1 : 7 Flickers
7 Cond Mid Temperature - 101 → Display 1, 0, 1
SEG 2, 3, 4 : Data display
SEG 1 : 8 Flickers
Fan 1 : Low, Fan 2 : High
8 Outdoor unit FAN mode SEG 2, 3, 4 : Fan 1, -
→ Low, High
Fan 2 display mode
SW02 SW03
Electronic
Outdoor component
unit box
4. The outdoor unit starts a tracking to check the connected indoor unit and option at power ON.
● The left of outdoor unit PCB check display part checks the
responded indoor unit by communication to 0~F address,
and displays the responded address to the right of PCB
check display part.
● Check if the indoor unit address at installation and the indoor
unit address responded is same.
● Check if the number of indoor unit installed and the number
of outdoor unit PCB setup is same.
● If the number of indoor unit set on outdoor unit PCB and
responded by communication is same after tracking, go
Left Right
ahead the next step.
PCB display part
● If CH is displayed on the part of outdoor unit PCB check
display after completion of tracking, the compressor is not
preheated. Turn the power On to heat the compressor,
and wait until the CH is disappeared.
● The communication between the indoor unit and the outdoor unit is performed if the compressor is preheated. And the
connected indoor unit address is displayed at the right of the outdoor unit PCB check display part.
• E201 is displayed on the part of outdoor unit PCB check display if the tracking is failed.
• Perform the re-tracking by pressing KEY 3 after checking address of indoor and outdoor unit.
• Check the input value after 30 minutes after running the compressor because the high/low is changed
continually at the initial operation.
• Don't perform the system operation more than 1 hour to check system pressure.
(COM1/COM2)
Port Power
Power
Outdoor Communication wire
connecter
Display Key
K1 K2 K3 K4
■ PUMP DOWN
This is an operation mode to collect the refrigerant in the indoor unit to the outdoor unit.
Use the K2 Key.
2) If pumping down the remained refrigerant after putting some of refrigerant of the system into a empty and rechargeable
refrigerant case, you can perform the pumpdown smoothly.
• If putting refrigerant into a refrigerant case, must use a rechargeable case for exclusive use.
If remodeling the normal refrigerant case illegally, may get damaged by an accident such as explosion.
2. In case of single installation of outdoor unit (If the installed indoor unit is 1 unit)
Display
3 times :
3) If the compressor is operated, observe the low pressure by using the view
mode of K4 button. (If the first number of LED is '3,' below three numbers
are low pressure value. Displayed down to one decimal point)
e.g.) ➔ : means low pressure value, : means the low pressure
is 12.2kg/cm2,g
4) If the low pressure goes down to below 2kg/cm2,g, lock the SVC valve on the gas side immediately and end the pumpdown
operation. (For ending of the pumpdown operation, press the K2 button two times or press the K3 button once to reset.)
2) Press the K2 button of the outdoor PCB 3 times. At this time, K7A is
displayed on the PCB LED.
• If the compressor on the Main Unit is operated after pressing the button,
wait approximately 20~30 minutes.
Display
3 times :
4) Lock the valves on the liquid side of the Main Unit and observe the low pressure same as the single outdoor unit case.
5) If the low pressure is lowered, lock the valves on the gas side of the Main Unit and end the pumpdown operation mode.
■ PUMP OUT
This is the operation mode to collect the refrigerant in the outdoor unit to the pipe or to the indoor unit.
Use the K1 Key.
2) Close the high pressure valve of the outdoor unit to PUMP OUT.
Display Key
K1 K2 K3 K4
1. This is an operation mode to recollect compressor oil that moved to pipe or indoor unit after mixing with refrigerant during
operation.
1. This is an operation mode to recover compressor oil that moved to pipe or indoor unit after mixing with refrigerant during opera-
tion.
1. Purpose :
According to the valves such as EEV, Solenoid Valve, and Check Valve, the vacuum and the emission of refrigerant may not be
succeeded smoothly. Therefore, insert a separate operation mode for the vacuum or the complete emission of refrigerant.
4. Operation Method :
All the EEV of the outdoor unit on the vacuum mode is opened to the maximum degree of openness and all the Solenoid Valve is
waited on the open state.
Breakdown
1. Same as above illustration, prevent spreading of the contaminant from the breakdown compressor by equipping the Filter Drier
to the liquid pipe side of each outdoor unit after replacing the compressor.
2. Applied Filter
2. Because DVM plus 2 is the air-conditioning and heating product, must use the Bi-Directional Filter Drier.
Use the Filter Drier specified on the below according to the outdoor unit's capacity.
Outdoor unit Liquid Pipe Diameter Samsung SVC Material Code Manufacturer (ALCO) Model Name
8 HP / 10 HP 3/8" DB97-01222A BFK-083
12 HP / 14 HP 1/2" DB97-01222B BFK-164
• Must use the Bi-Directional Filter Drier that are stated on the above Table.
• The installation location of the Filter Drier is the liquid pipe in front of the outdoor unit as stated the above
illustration. (Do not install on the gas side's pipe)
• If opening and leaving the Seal Cap on the both side of the Filter Drier for a while, the efficiency of moisture
absorption by the Drier is decreased. So, open the Seal Cap right before the installation.
• If the foreign substance is accumulated on the Filter excessively, clogging may be generated; so, must be
careful. (Need to replace when the temperature difference between before and after of Filter Drier is over 1˚C)
3.2 Mpa (gauge pressure) 4.15 Mpa (gauge pressure) 2.75Mpa (gauge pressure)
Design pressure
= 32.6 kgf/cm2 = 42.3 kgf/cm2 = 28.0 kgf/cm2
Ozone destruction
0 0 0.05
factor (ODP)
✳ 1. Non-azeotropic mixture refrigerant: mixture of two or more refrigerants having different boiling points.
✳ 2. Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar boiling points.
✳ 3. The design pressure is different at each product. Please refer to the installation manual for each product.
(Reference) 1 Mpa 10.19716 kgf/cm2
• It depends on the total length of the liquid side pipe after the first Y-Joint.
Liquid side pipe ø22.23 Liquid side pipe ø19.05 Liquid side pipe ø15.88
A= + + +
Total pipe length(m)x0.35 Total pipe length(m)x0.27 Total pipe length(m)x0.18
Liquid side pipe ø12.70 Liquid side pipe ø9.52 Liquid side pipe ø6.35
+ +
Total pipe length(m)x0.0125 Total pipe length(m)x0.06 Total pipe length(m)x0.02
• R410A is used with a polyester oil but a • The degree of vacuum is 5torr(-5 torr from
Vacuum vacuum pump uses a conventional mineral atmospheric pressure).
pump oil. • Need a check valve to prevent reverse oil flow
if using a conventional vacuum pump.
• Coat the connection with refrigerant oil • All refrigerants are available as using a
film.If not,leakage is possible because of synthetic oil
Refrigerant the pressure of R410A. • High rust resistance
oil • Coat after flare work on pipe connection. • Long stability over long period time
• Since R410A don't have chlorine, the tester • R410A, R407C(E), R404A, R507A, R134a,
must can detect Hydrogen. R12, R22, R502, R500 are detected.
Gas leak • Available in the range of 0 to 40˚C.
tester
A When it is hot outside, its cooling capacity decreases due to the increase of the ambient temperature.
When the dust filter gets blocked or warm outside air gets in, the cooling capacity will decrease. So,
make sure to clean the dust filter frequently, prevent heat loss by closing the doors and insulate the
cooling area by using curtains, blinds, shades or window tinting.
Q The cooling is good generally. But, it gets weak when it is considerably hot.
A It occurs when the outdoor unit is exposed to direct sun light and heat-up air is not ventilated well.
So, set up a sunblind over the outdoor unit and keep stuff away from the unit to increase the ventila-
tion. When the cooling capacity decreases during a heat wave, clean the heat exchanger of the out-
door unit or spray some cold water to the heat exchanger to increase the cooling capability.
Cooling
Q The cooling is weak. Does it need refrigerant charging?
A It is not correct charging refrigerant regularly. Except that you have moved in several times or the
connection pipes are broken, the refrigerant does not run low. So, when refrigerant is additionally
charged, it could be costly and cause a product's failure. When the refrigerant leaks, all of it will
escape in a short time resulting in cooling failure and no water coming out of the drain hose. So, if
water comes out from the drain hose, it indicates the normal operation of the product and it does not
need refrigerant charging.
Q It fails to do cooling.
A When the air conditioner is set to Ventilation or the desired temperature is set higher than the current
temperature, it fails to do cooling. In this case, select Cooling or set the desired temperature lower.
A Place the drain hose properly. When it is not placed properly, the drain water would flow back flooding
the floor. So, straighten out the drain hose for the water to be drained well.
Q Water drips at the drain connection (service valve) of the outdoor unit.
A When a glass bottle is taken out of the refrigerator, moisture gets condensed on its surface due to the
temperature differences. The same principle applies to the air conditioner. When cold refrigerant goes
through the copper tube, moisture gets condensed on the surface of the tube and the connection
Leakage areas. To prevent the water condensation, the pipes are insulated. But, the connection areas of the
outdoor unit are not insulated for the purpose of maintenance or repair, and water gets condensed due
to the temperature differences and drips down. Generally, it evaporates right away. But, when it drips
much during muggy days, put a water pan on the floor.
A It occurs when the drain pump is plugged out or it is out of order. Check the power of the drain pump
and the position of the drain hose, and when the pump is faulty, contact the drain pump manufacturer.
Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump
problems.
Q Whenever the air conditioner is turned on, it irritates my eyes and gives me a headache.
A There are no components in the air conditioner irritating the eyes and sending out chemical smells.
Smells But, when the air conditioner is turned on, other smell sources are sucked into the air conditioner and
get out of it. So, find and root out the smell sources. Generally, it occurs at a interior renovated place,
a pharmacy, a gasoline handling place, a tire shop, a second-hand book shop or an electronic
component handling place; when its chemical or musty smells are sucked in and sent out, it can be
misled that the air conditioner generates them. So, find and root out the problem or refresh the room
frequently.
A There are no components in the air conditioner sending out chemical smells. But, when the air condi-
tioner is turned on, other smell sources are sucked into the air conditioner and get out of it. So, find
and root out the smell sources. Generally, when the drain hose is taken out to the washing room or
there are sources of smells such as a diaper bin, a shoe shelf or a socks bin, bad smells generate.
Also, it occurs where glass cleaners or air fresheners are used; when they are sucked in interacting
with dusts and moistures inside, bad smells generate. These kinds of organic materials noxious to
human bodies. So, we recommend against the use of them.
A When the room is papered recently, its paste smells would be sucked inside. Also, when the air condi-
tioner is installed in the study room of young boys loving sweat-generating activities such as the bas-
Smells ketball, excessive sweats evaporate and get sucked into the air conditioner resulting in bad smells. So,
find and root out the problem or refresh the room frequently.
A It is due to the improper keeping of the product after its use. When keeping the product, dry up the
inside with the operation of Ventilation to prevent must. When the product is kept without drying up the
inside with Ventilation, mold would grow inside resulting in must. So, open the windows and switch on
the Ventilation function to get rid of the saturated smell inside.
Q Whenever the air conditioner is turned on, it sends out bad smells such as stale smells.
A It occurs generally when there are pet animals in the house. Their smells stay at the same place.
But, when the air conditioner is turned on, the air gets circulated resulting in the circulation of the
smells. So, find and root out the problem or refresh the room frequently.
A When the air filter is filthy, it could send out bad smells. So, clean the filter and ventilate the room with
the windows open while operating the Ventilation function.
Q It won't start.
A There is a power failure or it is plugged out. Also, check if the power distribution panel is switched off.
A When the hot air does not escape properly, it goes off during operation. It occurs when it does not
ventilate properly because the outdoor unit is covered, the back of the outdoor unit is blocked by a
cardboard or a plywood panel, and the front of the outdoor unit is blocked by the closed window or
Operation
other obstacles. Clear the above obstacles from the outdoor unit.
Q It generally works properly. But, when it's considerably hot, it goes off during operation.
A It occurs when the outdoor unit is exposed to direct sunlight and the hot air does not escape properly.
Set up a sun blind over the outdoor unit and clear the neighboring obstacles from the outdoor unit to
provide good ventilation. When it goes off frequently during a heat wave, it would prevent the turn-off and
increase the cooling capacity cleaning the outdoor unit or spraying some water to the heat exchanger.
A When the batteries run out or the transmitter or receiver of the remote controller is blocked by obsta-
Operation cles, change the batteries or keep the obstacles away from the controlling area. Also, the remote con-
troller may not work under intensive light from a 3-wave length lamp or a neon sign due to the EMI.
In this case, take the remote controller closer to the receiver.
A When relocating or re-installing the air conditioner, make sure to contact Samsung Electronics Service
Center or Authorized Service Agent and have them to do the job.(If not, it could cause personal injury
or product damage.)
The cost for the relocation/re-installation of the air conditioner is subject to the customer's expense.
There is a cost table. But, our service engineer needs to visit to total up the cost correctly.
When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service
Agent in advance to streamline the process.
Q What can be done to install the outdoor unit facing the road because it is a commercial building?
A The following is an excerpt from Building Code going into effect from JUNE 1st 2005. "The exhaust
pipe of a cooling or ventilation facility installed in a building adjacent to the streets of commercial or
residential areas shall be installed higher than 2m to prevent the exhaust air from blowing directly to
passers-by and the current facilities shall be corrected by MAY 31st 2005." So, please install it higher
than 2m or not to blow the hot exhausting air directly to passers-by.
Q What about installing a windscreen during installation not to blow hot air directly to passers-by?
A When the hot air from the front of the outdoor unit is blocked, the product's performance will be
affected and it will fail to operate properly. So, keep it at least 300mm away from its surrounding walls
and give it good ventilation.
This Service Manual is a property of Samsung Electronics Co., Ltd. © Samsung Electronics Co., Ltd. Jun. 2006.
Any unauthorized use of Manual can be punished under applicable Printed in Korea.
International and/or domestic law. Code No. DB98-25391A(1)