Release date:03/2022
990-5756D-001
06ME0092@00B0140
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
This manual contains general information, safety instructions, and guidance. Updates
may be published from time to time and are available upon request. This manual is
not a substitute for the user conducting a detailed operational and site-specific
development plan.
This product is for industrial use only. It should only be used for the functions for
which it has been designed as set out in this manual. User must evaluate and take
adequate precautions to address risks associated with use of this product in
environments and/or processes not specifically addressed in this manual (e.g. heavy
industry, medical, marine environments, railway, etc.).
All work must be carried out in a way that does not give rise to danger and using
appropriate personal protective equipment (PPE).
Schneider Electric shall not be responsible for any works carried out by anyone other
than Schneider Electric; or for integration or use of the product with other products
(including spare parts and software) that are neither approved nor provided by
Schneider Electric for such purposes; or for any non-Schneider Electric software,
firmware, information or memory data contained in, stored on, or integrated with this
product.
To the maximum extent permitted by applicable law, neither Schneider Electric nor
any of its affiliates shall be liable for any claims, costs, losses, damages, death or
injuries arising out of the improper use of this product or any failure to comply with
any of the above requirements.Schneider Electric’s quality management system is
ISO 9001 certified and the products are marked
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units
Table of Contents
General Information ....................................................................................7
Translation Reference.................................................................................7
Abbreviations .............................................................................................7
Cross-Reference Symbol Used in This Manual .............................................7
Unit Overview ..............................................................................................8
Model Nomenclature...................................................................................8
Overview ...................................................................................................9
General Description ..............................................................................9
Standard Features ..............................................................................10
Optional Features ...............................................................................12
Accessories........................................................................................13
Compliance..............................................................................................15
Certifications ......................................................................................15
Pressurized Equipment .......................................................................16
Safety Valve .......................................................................................17
Canalization for Safety Valves Drainage ...............................................17
Environmental Considerations .............................................................18
Equipment Disposal ............................................................................19
Refrigerant Information........................................................................19
Airflow Configurations ...............................................................................21
Upflow ...............................................................................................21
Downflow ...........................................................................................21
Under Floor ........................................................................................22
Equipment Guidelines...............................................................................23
Working Conditions and Environmental Limits.......................................23
Voltage, Frequency, and THD Limits.....................................................24
Operating Descriptions .............................................................................25
Air-Cooled Direct Expansion Units .......................................................25
Water-Cooled Direct Expansion Units...................................................25
Indirect Free Cooling Units ..................................................................25
Performance Specifications.......................................................................26
Air–Cooled Units.................................................................................26
Water–Cooled Units ............................................................................33
Indirect Free Cooling Units ..................................................................37
General Specifications ..............................................................................41
LDAV, LDWV Models ..........................................................................41
LDEV Models .....................................................................................43
IDAV, IDWV Models ............................................................................44
IDEV Models ......................................................................................47
LUAV Models......................................................................................48
IUAV, IUWV Models ............................................................................51
IUEV Models ......................................................................................53
IXAV, IXWV Models ............................................................................55
IXEV Models ......................................................................................56
Sound Data..............................................................................................58
Electrical Specifications ............................................................................66
LDAV, LDWV, LDEV Models ................................................................66
IDAV, IDWV, IDEV Models ...................................................................70
990-5756D-001 / 06ME0092@00B0140 3
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units
LUAV Models......................................................................................75
IUAV, IUWV, IUEV Models ...................................................................78
IXAV, IXWV, IXEV Models....................................................................83
Component Identification .........................................................................86
External Components ...............................................................................86
Downflow Units...................................................................................86
Upflow Units .......................................................................................87
Under Floor Units................................................................................88
Dimensions and Weights...........................................................................89
Downflow Units...................................................................................89
Upflow Units .......................................................................................91
Under Floor Units................................................................................93
Service Clearance ..............................................................................94
Connection Access—Bottom .....................................................................94
Floor Cutout .............................................................................................95
Suction Motorized Damper ........................................................................98
Floor Stand ..............................................................................................99
Base Frame ........................................................................................... 100
Plenum .................................................................................................. 101
Piping Sizing-Air-Cooled Units................................................................. 103
Discharge Line Sizing........................................................................ 103
Connecting the Refrigeration Circuit to the Condenser ......................... 104
Outdoor Heat Exchanger Data ............................................................. 105
General Information ................................................................................ 105
Airflow Configurations ....................................................................... 106
Dimensional Data ................................................................................... 107
Air-Cooled Condenser Performance Data................................................. 109
Air-Cooled Condenser Sound Data .......................................................... 110
Recommended Condensers .................................................................... 111
Low Temperature Kit ............................................................................... 112
Main Components ................................................................................... 113
Self-Supporting Frame ............................................................................ 113
Brazed Plate Water-Cooled Condenser .................................................... 113
Fixed-Speed Scroll Compressors............................................................. 113
Variable-Speed (Inverter-Driven) Scroll Compressors................................ 115
Fans ...................................................................................................... 116
Electrical Panel ...................................................................................... 117
Hydraulic Circuit-Indirect Free Cooling Units............................................. 118
Intelligent Dehumidification Logic............................................................. 121
Discharge Temperature Control and Moisture Control................................ 121
Humidifier .............................................................................................. 122
Supply Water.................................................................................... 123
Microprocessor Controller ....................................................................... 124
Microprocessor Overview ................................................................. 124
Display Interface ............................................................................... 125
BMS Compatibility ............................................................................ 126
Accessories ............................................................................................. 127
Options for Downflow, Under Floor, Upflow Units ...................................... 127
Sensors ........................................................................................... 131
Condensing Control Options.................................................................... 132
4 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units
990-5756D-001 / 06ME0092@00B0140 5
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
General Information Cooling Units
General Information
Translation Reference
The original version of this manual has been written in the English language.
Manuals written in other languages have been translated from the original English
version.
Abbreviations
The following are abbreviations and terms used in this manual:
• EXV or EEV—Electronic expansion valve
• I*AV—Air-cooled units with variable-speed compressors
• I*WV—Water-cooled units with variable-speed compressors
• I*EV—Indirect free cooling units with variable-speed compressors
• LDAV, LUAV—Air-cooled units with fixed-speed compressors
• LDWV —Water-cooled units with fixed-speed compressors
• LDEV—Indirect free cooling units with fixed-speed compressors
• DX—Direct Expansion
• *U = Upflow; D = Downflow; X = Under floor
990-5756D-001 / 06ME0092@00B0140 7
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Unit Overview
Model Nomenclature
Indoor Cooling Units
I D A V 20 2 2 A
Identifying prefix
L = Fixed-Speed Compressors
I = Variable-Speed Compressors
Airflow Pattern
D = Downflow
U = Upflow
X = Underfloor
Heat Rejection Type
A = Air-Cooled
W= Water-Cooled
E = Indirect Free Cooling
Fan Type
V = Radial Fans with Backward-Curved Blades with
Electronic Commutation
Nominal Cooling Capacity
Fan Type
AC = Axial Fans with asyncronous Motor
EC = Axial Fans with electronically commutated Motor
LT = Axial Fans with asyncronous Motor suitable for
Low temperature applications
Power Supply Voltage
0000769540_A
8 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Overview
General Description
Uniflair™ Room Cooling units are precision air conditioners designed to
specifically meet the air conditioning needs of Data Centers and Internet
providers, data-processing centers, and any technological environment
characterized by high levels of heat value to dissipate. To ensure proper operation
of the equipment in such installations, it is essential to keep the temperature and
humidity conditions constant throughout the year; that is why the Room Cooling
units control the ambient conditions, not just cooling. The air-conditioning systems
intended for the purposes of “comfort” are designed specifically to ensure the well-
being of the people in the room and are generally incapable of ensuring that the
ambient conditions required by technologically sophisticated equipment can be
kept constant, especially in the presence of much higher specific heat loads. In
precision air conditioning applications, there are five main objectives to pursue:
• Air temperature control (±1.0°C (±1.8°F))
• Air humidity control (±7/8%)
• High airflow rate
• Year-round operation (24 hours a day, 365 days a year)
• Energy efficiency
In the air-conditioning of large technical rooms used for telephone and Internet
applications, the density of the heat load (per unit of surface area) is very high,
even as much as 6–10 times the density of the heat load in comparable areas
used as commercial offices, for instance. Standard air-conditioning equipments
used for ensuring comfort are unable to cope with such densities and types of heat
load, especially concerning the total absence of any latent load characteristic of
technological applications.
990-5756D-001 / 06ME0092@00B0140 9
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Standard Features
Compact design The Uniflair™ Room Cooling direct expansion units deliver a high capacity of
cooling in a compact overall footprint. Since the system requires only front
service access, the units can be placed side by side and valuable floor space is
not wasted.
External panels The external panels are coated with RAL9003 epoxy-polyester paint, which
provides long-term durability of the original features. The panels are internally
insulated with a heat and soundproofing layer made of melamine (or bare fiber
glass, on request) covered by a protective film. The external coated panels are
fully compliant with UNI EN ISO 12944 - 1/2/3/4/5/6 and tested for installation in
atmospheric environments belonging to a corrosivity category classified at least
as C2, according to EN ISO 12944 - 2.
Electronic expansion valve The EEV provides accurate control of the refrigerant superheat in order to
(EEV) ensure an increase in efficiency at low external temperatures because it
enables the unit to operate at much lower condensing pressures than it would
be possible with a traditional mechanical valve.
Electronically commutated The Uniflair™ Room Cooling units come standard with highly efficient and
fans reliable EC fans. EC fans are quiet, require minimal maintenance, and produce
very low noise vibration. EC fans have the latest generation impellers made
from high-tech compound material with optimized flow control and high
efficiency GreenTechTM EC motors. The directly coupled EC motor is three-
phase with an external rotor with IP54 protection grade. The fan impeller is
statically and dynamically balanced with lifelong-lubricated bearings. Each fan
is easier to service with a quick-removal kit.
Full front service access The Uniflair™ Room Cooling units are designed for all maintenance work to be
accessible through the front of the unit ((850-mm (33.5-in.) service clearance
recommended).
10 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Hydrophilic coated coil The copper and aluminium coil has a large surface and it is designed for
pressure drop minimization. Hydrophilic coating on the coil allows condensate
water to flow more efficiently to the drain installed below the evaporating coil
and provides anti-microbial and corrosion protection.
Brazed plate water-cooled The water cooled and indirect free cooling units are equipped with an internal
condenser brazed plate heat exchanger that has the function of a condenser. The brazed
plate heat exchanger is made of stainless steel.
Internal panels The Uniflair™ Room Cooling units are equipped with internal panels for
isolation of the compartments with hazardous rotating fans. Internal panels also
ensure noise reduction and allow for servicing the components with doors open
while the unit is still in operation.
EU4 filters High efficiency, EU4, pleated air filters are contained in a metal frame and
equipped with a dirty filter differential pressure switch and a low airflow
differential pressure switch.
Main power disconnect A non-fused main power switch disconnects all high voltage power to the unit if
necessary. The disconnect switch is accessible from the exterior of the unit.
R410A refrigerant R410A refrigerant does not harm the ozone layer and has a very low
contribution to the global warming impact.
Fixed-speed scroll All LD*V and LU*V models are equipped with fixed-speed scroll compressors.
compressor They have a high-level of energy efficiency and low noise levels and include
built-in thermal protection.
Variable-speed scroll All ID*V, IU*V and IX*V models with two refrigerant circuits are equipped with
compressor one fixed-speed scroll compressor and one variable-speed scroll compressor.
Each compressor operates on a separate, independent refrigerant circuit.
I**V1511A and I**V1911A models are equipped with a variable-speed
compressor operating on the single refrigerant circuit.
Electrical panel The electrical panel is located in a compartment separated from the airflow and
complies with the directive 2014/35/EU and related standards.
Packaging Indoor units are delivered with standard packaging composed by wooden pallet,
protecting polystyrene elements and plastic film.
User display The standard arrangement of the touch-screen display interface, RS 485 serial
card, and USB connection allows for direct connection to BMSs based on serial
lines. The USB port provides access to quick downloads of the unit settings and
parameters. The seven-inch, touch-screen display interface is accessible by the
user. It provides clear information on the unit status and any current alarms.
Unit controller The controller contains the regulation software and is installed in the electrical
panel. The control system uses sophisticated algorithms to control the outlet
water temperature within a minimal range and to monitor and protect the
various unit components.
990-5756D-001 / 06ME0092@00B0140 11
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Supply air temperature Two supply air temperature sensors are provided as standard components. The
sensor control of supply air temperature is available only in units with variable speed
compressors. It is not available in units with on/off compressors.
Remote air-cooled Air-cooled condensers are suitable for outdoor installation in a vertical position
condenser with AC or EC with horizontal air flow or in a horizontal position with vertical air flow if the
fans appropriate brackets are used. The external condenser can be equipped with
AC axial fans or electronically commutated (EC) axial fans.
Special surface treatments on the finned coil are available on request and
increase the resistance to more aggressive weather conditions.
Remote dry cooler Remote dry coolers are suitable for outdoor installation in a vertical position with
horizontal air flow or in a horizontal position with vertical air flow if the
appropriate brackets are used. The external dry cooler is equipped with axial
fans with AC motor.
Hydraulic circuit coating The hydraulic circuit is entirely coated with flexible insulation having an
elastomeric structure of the type closed cells, CFC HCFC and PVC free. Main
characteristics:
• Fiber free – powder free
• Values of ODP =0 and GWP < 150
Optional Features
• Unit version options
◦ Cooling only: cooling units operate by controlling the air temperature set
point (return or supply). The unit is equipped with one return temperature
sensor and two supply air temperature sensors located in the air discharge
section
◦ Cooling and humidification: cooling and humidification units operate by
controlling the air temperature set point (return or supply) and the relative
humidity set point. The unit is equipped with one return air temperature
and humidity sensor and two supply air temperature sensors. The
humidification cycle is activated if the relative humidity value of the return
air overcomes the minimum threshold. The unit is equipped with an
immersed electrode humidifier for humidification purposes
◦ Cooling and dehumidification: cooling units operate by controlling the air
temperature set point (return or supply) and the maximum humidity value.
The unit is equipped with one return air temperature and humidity sensor
and two supply air temperature sensors. The de-humidification cycle is
activated if the relative humidity value of the return air overcomes the
maximum threshold
• Condensing control options (water-cooled units only)
◦ Pressostatic valve
◦ Condensing pressure regulation valve
• Power supply options
◦ Single power supply with ultracapacitor
◦ Double power supply with ultracapacitor and automatic changeover
12 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Accessories
• Plenums
◦ Suction/discharge
◦ Suction/discharge soundproofed
◦ Direct free-cooling plenum with room air suction from the front and fresh
air suction from the back
◦ Direct free-cooling plenum with room air suction from the front and fresh
air suction from the top
• Base frames
◦ Height adjustable base frame
◦ Height adjustable base frame with air deflector
◦ Adjustable legs
• Floor stands
◦ Floor stand (suggested for installation of upflow cooling units with frontal
suction or downflow units with frontal discharge with no raised floor to
create the required space for piping connections)
◦ Floor stand with motorized damper
990-5756D-001 / 06ME0092@00B0140 13
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
• External sensors
◦ Room temperature/humidity sensor
• Safety sensors
◦ Smoke sensor
◦ Fire sensor
◦ 24-VAC relay for remote fire/smoke alarm
• Water leak detection
◦ Spot leak detector
◦ Tape leak detector
14 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Compliance
These units are intended for installation in a non-public location with restricted
access, and with installation, use, and maintenance performed by qualified
personnel.
Moreover, these units underwent the risk analysis in compliance with Machinery
Directive. The technical solutions implemented during the design phase are
described in the unit technical documentation. The appliance was built to operate
safely in the areas of application for which it was designed, provided its
installation, commissioning and maintenance are performed in compliance with
the instructions provided in this manual and on the labels affixed to the unit.
In compliance with ATEX Directive, these units must not be used in potentially
explosive atmospheres. In any case, always abide strictly by the applicable laws in
force in the place of installation of the system.
Certifications
The cooling units are in conformity with the following directives:
990-5756D-001 / 06ME0092@00B0140 15
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Pressurized Equipment
This appliance is subject to Pressure Equipment Directive concerning pressurized
equipment. Any and all work performed on the pressure circuit must be expressly
authorized by Schneider Electric and personnel must be approved by Schneider
Electric. If maintenance is needed (intended as servicing work and/or components
replacement), any of the following components or specific information must be
16 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Safety Valve
WARNING
QUALIFIED AND CERTIFIED PERSONNEL ONLY
Charging and maintaining the refrigeration circuit must only be performed by
qualified and certified personnel.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
HIGH PRESSURE REFRIGERANT
This unit contains pressurized coolant gas and water circuit; all work on
pressurized circuits must be performed by qualified and certified personnel.
Failure to follow these instructions can result in injury or equipment
damage.
990-5756D-001 / 06ME0092@00B0140 17
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
NOTICE
QUALIFIED AND CERTIFIED PERSONNEL ONLY
• The laying of the lines and the refrigerant connections must be performed by
qualified and certified personnel.
• All lines must be properly supported, insulated, and isolated to avoid
premature joint failures due to system vibrations.
Failure to follow these instructions can result in equipment damage.
Environmental Considerations
Wind
The equipment is not intended for installation in areas of high wind. Consult the
sales representative for information on any applicable options for installation in
areas of high wind.
Earthquakes
The equipment is not intended for installation in areas at risk of seismic activity.
Consult the sales representative for information on any applicable options for
installation in areas at risk of seismic activity.
ATEX
The equipment is not intended for use in potentially explosive atmospheres and
does not comply with Directive 2014/34 / EU (ATEX).
Dust
The equipment is not intended for use in dusty environments and in environments
with conductive dust.
Corrosion
The equipment is not intended for use in a potentially corrosive environment.
18 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Equipment Disposal
Waste Electrical and Electronic Equipment (WEEE) Disposal
Oil Disposal
Refrigerant oil is harmful to the environment, therefore it must be properly recycled
or disposed of, according to 2008/98/EC (Water Framework Directive).
• Collect the oil from the unit by draining it until it is no longer flowing. Be aware
that oil recovered from an air-conditioning equipment may contain halogens.
• Measure and record the quantity of recovered waste oil, then pour it into a
suitable 208 liters container. Do not fill containers over 90% of their capacity
and leave the remaining 10% for expansion.
NOTE: Do not mix refrigerant oil with waste oils.
• If the appliance is being dismantled, store waste oil containers in a diked area
or in a containment vessel, until the dismantling procedure is completed.
• Once the waste oil collection has been completed, contact a licensed waste
oil company for pick up.
Refrigerant Information
Environmental Impacts
Synthetic refrigerants contribute to global warming increase. The refrigerants
listed below feature low global warming potential (GWP). This is possible due to
their thermodynamic properties.
990-5756D-001 / 06ME0092@00B0140 19
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Safety Classes
Each refrigerant is assigned to one of three classes (1, 2, or 3) and one optional
subclass (2L), based on lower flammability limit testing, heat of combustion, and
the optional burning velocity measurement.
• Safety class A1: Refrigerants belonging to this class do not feature any
propagation of flame at 60°C air temperature and atmospheric pressure.
• Safety class A2: Refrigerants belonging to this class are slightly flammable
and feature a low flammability limit higher than 0.10 kg/m3 at 60°C air
temperature and atmospheric pressure, and a combustion heat lower than
19.000 kJ/kg.
• Safety class A2L: Refrigerants belonging to this class are slightly flammable
and feature a low flammability limit higher than 0.10 kg/m3 at 60°C air
temperature and atmospheric pressure, and a combustion heat lower than
19.000 kJ/kg and a maximum burning velocity of 10 cm/s.
• Safety class A3: Refrigerants belonging to this class are extremely flammable
and feature a low flammability limit lower than 0.10 kg/m3 at 60°C air
temperature and atmospheric pressure. Even those refrigerants featuring a
combustion heat of 19.000 kJ/kg belong to this flammability class.
R410A Refrigerant
R410A consists of an equicomponent mix of R32 and R125 refrigerants, although
due to the lack of chlorine it allows for environmentally friendly, efficient and
reliable operation in air conditioning system.
20 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Airflow Configurations
Upflow
Upflow units are designed to distribute air through a supply plenum,
pre-engineered duct system, or drop ceiling. Return air can enter the unit via the
front, rear, or bottom of the unit based on configuration. A floor stand is required to
allow access for power, water, and refrigerant connections on non-raised floor
installations.
na4934b
FRONT RETURN BOTTOM RETURN FRONT RETURN WITH
WITH TOP SUPPLY WITH TOP SUPPLY FRONT SUPPLY
(PLENUM AND GRILLE)
Downflow
Downflow units are designed to distribute air through a void under a raised access
floor or a front supply floor stand when a raised floor is not available. Return air
enters the top of the unit directly from the environment or through a duct system.
na4933d
990-5756D-001 / 06ME0092@00B0140 21
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Under Floor
Under floor units uniformly distribute large volumes of air into the environment by
means of a void under a raised access floor. The air enters the unit directly from
the environment or through a ventilated or false ceiling.
NOTE: Image is an example only: the unit in use may differ.
na5294a
TOP RETURN WITH TOP RETURN WITH TOP RETURN WITH
FRONT SUPPLY FRONT AND SIDE SUPPLY OPEN SUPPLY
22 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Equipment Guidelines
Working Conditions and Environmental Limits
Limit Working Conditions
Power supply 400 V/ 3Ph+N / 50 Hz – TN
Main nominal power supply tolerance* – R0 400 V ±10%
Acceptable Frequency Range* 50 Hz ±0.5%**
50 Hz ±1%***
Limits of THD values* +12%****
Refrigerant type R410A
Room conditions (temperature/humidity) Temperature: 18°C to 40°C (64.4°F to 104°F)
Relative humidity: 30% to 70% and humidity ratio: 5
to 12 gr/kg
External condenser conditions (temperature) –20°C to 50.0°C (5.0°F to 122.0°F)
Low ambient temperature version: –40.0°C to 40.0°C
(-40°F to 104°F)
Maximum inlet dew point 15°C (59°F)
Maximum installation altitude 3000 m (9842.5 ft)
Chilled-Water Circuit
Maximum glycol percentage 50%
Storage Conditions
Temperature –20 to 50°C (–4 to 122°F)
Humidity Relative humidity: <85%RH
*Data refers to IEC/EN 60204–1 prescription standards.
**Nominal frequency continuosly
***For limited periods
****Best practices indicate 5% of the pick as an admitted value for THD. THD values higher than 12% generate
unpredictable unit operation and failures.
990-5756D-001 / 06ME0092@00B0140 23
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
24 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Operating Descriptions
Air-Cooled Direct Expansion Units
Air-cooled Direct Expansion units extract heat from the room and transfer it to the
outside using air-cooled refrigerant heat exchangers (condensers). The indoor
unit and external condenser form an autonomous sealed circuit once installed.
Each refrigeration circuit must be connected to its remote air-cooled condenser
with two copper pipes, one for the gas discharge and one for the liquid return.
990-5756D-001 / 06ME0092@00B0140 25
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Performance Specifications
Air–Cooled Units
Downflow Models with Fixed–Speed Compressors–LDAV Models
Gross Cooling Capacity—Condensing Temperature 45°C
Compressor Power
Consumption – kW 11.00 15.20 17.20 17.10 19.50 30.40
Compressor Power
Consumption – kW 11.00 15.10 17.20 17.10 19.50 30.40
Compressor Power
Consumption – kW 10.90 15.10 17.10 17.00 19.40 30.30
Compressor Power
Consumption – kW 10.90 15.00 17.00 16.80 19.30 30.30
Compressor Power
Consumption – kW 10.60 14.80 16.70 16.30 18.90 30.00
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
26 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Compressor Power
Consumption – kW 11.00 15.20 17.20 17.10 19.50 30.40
Compressor Power
Consumption – kW 11.00 15.10 17.20 17.10 19.50 30.40
Compressor Power
Consumption – kW 10.90 15.10 17.10 17.00 19.40 30.30
Compressor Power
Consumption – kW 10.90 15.00 17.00 16.80 19.30 30.30
Compressor Power
Consumption – kW 10.60 14.80 16.70 16.30 18.90 30.00
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
990-5756D-001 / 06ME0092@00B0140 27
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Compressor Power
Consumption – kW 12.8 17.4 14.5 14.5
Compressor Power
Consumption – kW 12.8 17.4 14.5 14.4
Compressor Power
Consumption – kW 12.8 17.4 14.4 14.3
Compressor Power
Consumption – kW 12.8 17.5 14.3 14.2
Compressor Power
Consumption – kW 12.7 17.5 14.1 13.9
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
Compressor Power
Consumption – kW 20.7 22.0 31.8
28 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Compressor Power
Consumption – kW 20.6 22.0 31.8
Compressor Power
Consumption – kW 20.6 21.9 31.7
Compressor Power
Consumption – kW 20.6 21.8 31.7
Compressor Power
Consumption – kW 20.3 21.5 31.4
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
990-5756D-001 / 06ME0092@00B0140 29
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Compressor Power
Consumption – kW 12.8 17.4 14.5 14.5
Compressor Power
Consumption – kW 12.8 17.4 14.5 14.4
Compressor Power
12.8 17,4 14.4 14.3
Consumption – kW
Compressor Power
Consumption – kW 12.8 17.5 14.3 14.2
Compressor Power
Consumption – kW 12.7 17.5 14.1 13.9
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
Compressor Power
Consumption – kW 20.7 22 31.8
30 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Compressor Power
Consumption – kW 20.6 22.0 31.8
Compressor Power
Consumption – kW 20.6 21.9 31.7
Compressor Power
Consumption – kW 20.6 21.8 31.7
Compressor Power
Consumption – kW 20.3 21.5 31.4
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
990-5756D-001 / 06ME0092@00B0140 31
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Compressor Power
Consumption – kW 20.7 22.0 31.7
Compressor Power
Consumption – kW 20.6 22 31.6
Compressor Power
Consumption – kW 20.6 22.0 31.6
Compressor Power
Consumption – kW 20.6 21.8 31.5
Compressor Power
Consumption – kW 20.3 21.6 31.2
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
32 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Water–Cooled Units
Downflow Models with Fixed–Speed Compressors–LDWV Models
Gross Cooling Capacity—Inlet/Outlet Water Temperatures 30/35°C, 0% Glycol
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
NOTE: Contact the local sales representative for special conditions.
990-5756D-001 / 06ME0092@00B0140 33
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Compressor Power
Consumption – kW 12.0 12.8 12.8 19.6 20.8 29.3
Compressor Power
Consumption – kW 12.0 12.8 12.7 19.6 20.8 29.3
Compressor Power
Consumption – kW 12.0 12.8 12.6 19.6 20.7 29.3
Compressor Power
Consumption – kW 12.0 12.7 12.5 19.5 20.7 29.3
Compressor Power
Consumption – kW 12.1 12.4 12.3 19.3 20.6 29.3
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
NOTE: Contact the local sales representative for special conditions.
34 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Compressor Power
Consumption – kW 12.0 12.8 12.8 19.6 20.8 29.3
Compressor Power
Consumption – kW 12.0 12.8 12.7 19.6 20.8 29.3
Compressor Power
Consumption – kW 12.0 12.8 12.6 19.6 20.7 29.3
Compressor Power
Consumption – kW 12.0 12.7 12.5 19.5 20.7 29.3
Compressor Power
Consumption – kW 12.1 12.4 12.3 19.3 20.6 29.3
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
NOTE: Contact the local sales representative for special conditions.
990-5756D-001 / 06ME0092@00B0140 35
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Compressor Power
Consumption – kW 19.6 20.8 29.3
Compressor Power
Consumption – kW 19.6 20.8 29.3
Compressor Power
Consumption – kW 19.5 20.7 29.3
Compressor Power
Consumption – kW 19.5 20.7 29.3
Compressor Power
Consumption – kW 19.3 20.8 29.2
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
NOTE: Contact the local sales representative for special conditions.
36 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
NOTE: Note: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan
speed.
NOTE: Contact the local sales representative for special conditions.
990-5756D-001 / 06ME0092@00B0140 37
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
NOTE: Contact the local sales representative for special conditions.
38 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
NOTE: Contact the local sales representative for special conditions.
990-5756D-001 / 06ME0092@00B0140 39
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
NOTE: All values are accurate to +/– 8% on cooling capacity and +/– 5% on power consumption and based on nominal fan speed.
NOTE: Contact the local sales representative for special conditions.
40 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
General Specifications
LDAV, LDWV Models
LDAV2422A LDAV2522A
Unit Data LDAV1511A LDAV1911A
LDWV2442A LDWV2522A
Supply Voltage – V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50
Quantity 2 2 2 2*
Nominal Water Flow – C Version 500 l/h 500 l/h 500 l/h 500 l/h
Nominal Water Flow – D Version 500 l/h 500 l/h 500 l/h 500 l/h
Evaporator Coil
Compressors
Quantity 1 1 2 2
Physical Data
Filters (EU4)
Quantity 2 2 3 4
990-5756D-001 / 06ME0092@00B0140 41
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
LDAV2422A LDAV2522A
Unit Data LDAV1511A LDAV1911A
LDWV2442A LDWV2522A
Hot Gas Line – mm (ODS) 22 22 22 22
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS 3/4 GAS
* If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
**Includes plenum
***Per element
LDAV2722A LDAV3822A
Unit Data
LDWV2722A LDWV3822A
Supply Voltage – V/Ph/Hz 400/3/50 400/3/50
Quantity 2* 3
Compressors
Quantity 2 2
Physical Data
42 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
LDAV2722A LDAV3822A
Unit Data
LDWV2722A LDWV3822A
Height** – mm 2150 2150
Filters (EU4)
Quantity 4 4
Water Inlet
Water Outlet
Condensate
Drain Line w/ Humidifier – mm (OD hose) 20 20
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS
* If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
**Includes plenum
***Per element
LDEV Models
Unit Data LDEV2422A LDEV2722A
Supply Voltage – V/Ph/Hz 400/3/50 400/3/50
Quantity 2* 3
990-5756D-001 / 06ME0092@00B0140 43
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Compressors
Quantity 2 2
Physical Data
Filters (EU4)
Quantity 3 4
Water Connections
Water Inlet G2 – UNI ISO 228/1
Water Outlet G2 – UNI ISO 228/1
Condensate
Drain Line w/ Humidifier – mm (OD hose) 20 20
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS
* If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
**Includes plenum
***Per element
44 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Quantity 2 2 2 2
Quantity – – 1 1
Quantity 1 1 1 1
Physical Data
Filters (EU4)
Quantity 2 2 2 3
990-5756D-001 / 06ME0092@00B0140 45
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS 3/4 GAS
* If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
**Includes plenum
***Per element
Quantity 2 2* 3
Quantity 1 1 1
Quantity 1 1 1
Physical Data
46 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Quantity 3 4 4
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS
* If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
**Includes plenum
***Per element
IDEV Models
Unit Data IDEV1511A IDEV2022A IDEV2922A
Supply Voltage – V/Ph/Hz 400/3/50 400/3/50 400/3/50
Quantity 2 2* 3
990-5756D-001 / 06ME0092@00B0140 47
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Quantity – 1 1
Quantity 1 1 1
Physical Data
Filters (EU4)
Quantity 2 3 4
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS
*If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
**Includes plenum
***Per element
LUAV Models
Unit Data LUAV1511A LUAV1911A LUAV2422A LUAV2522A
Supply Voltage – V/Ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50
48 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Quantity 2 2 2 2*
Nominal Water Flow – C Version 500 l/h 500 l/h 500 l/h 500 l/h
Nominal Water Flow – D Version 500 l/h 500 l/h 500 l/h 500 l/h
Evaporator Coil
Compressors
Quantity 1 1 2 2
Physical Data
Filters (EU4)
Quantity 2 2 3 4
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS 3/4 GAS
* If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
***Per element
990-5756D-001 / 06ME0092@00B0140 49
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Quantity 2* 3
Compressors
Quantity 2 2
Physical Data
Filters (EU4)
Quantity 4 4
50 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS
* If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans instead of two fans.
***Per element
Quantity 2 2 2 2
Quantity – – 1 1
Quantity 1 1 1 1
Physical Data
990-5756D-001 / 06ME0092@00B0140 51
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Filters (EU4)
Quantity 2 2 2 3
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS 3/4 GAS
* Per element
**If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans.
Quantity 2 ** 3
52 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Quantity 1 1 1
Quantity 1 1 1
Physical Data
Filters (EU4)
Quantity 3 4 4
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS
* Per element
**If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans.
IUEV Models
Unit Data IUEV1511A IUEV2022A IUEV2922A
Supply Voltage – V/Ph/Hz 400/3/50 400/3/50 400/3/50
990-5756D-001 / 06ME0092@00B0140 53
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Quantity 2 2* 3
Quantity – 1 1
Quantity 1 1 1
Physical Data
Filters (EU4)
Quantity 2 3 4
Water Connections
Water Inlet G1 1/2 – UNI ISO 228/1 G2 – UNI ISO 228/1
Humidifier
54 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
*If the unit is equipped with high-efficiency air filters (EU6 or EU7), the unit is equipped with three fans.
**Per element
Quantity 2 2 3
Quantity 1 1 1
Quantity 1 1 1
Physical Data
Filters (EU4)
990-5756D-001 / 06ME0092@00B0140 55
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS
*Includes plenum
**Per element
IXEV Models
Unit Data IXEV2311A IXEV2622A IXEV4022A
Supply Voltage – V/Ph/Hz 400/3/50 400/3/50 400/3/50
Quantity 2 2 2
56 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Quantity – 1 1
Quantity 1 1 1
Physical Data
Filters (EU4)
Quantity 2 3 4
Water Connections
Water Inlet G2 – UNI ISO 228/1
Water Outlet G2 – UNI ISO 228/1
Condensate
Drain Line w/ Humidifier – mm (OD hose) 20 20 20
Humidifier
Supply Line – in. 3/4 GAS 3/4 GAS 3/4 GAS
*Includes plenum
**Per element
990-5756D-001 / 06ME0092@00B0140 57
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Sound Data
Sound Pressure Measurement Positioning
1 m (3.28 ft)
na3883a
2 m (6.56 ft)
LDAV1511A 16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
LDAV1911A 16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
LDAV2422A
20,000 49.4 59.5 58.3 53.8 57.6 57.7 50.2 46.6 62.4
LDWV2422A
LDAV2522A
24,300 52.6 61.9 61.3 58.1 60.2 63.0 55.5 48.4 66.7
LDWV2522A
LDAV2722A
26,000 53.7 63.8 62.1 60.2 61.6 65.1 58.9 50.6 68.8
LDWV2722A
LDAV3822A
27,000 50.7 59.0 58.4 54.7 58.6 58.2 50.7 48.1 63.1
LDWV3822A
58 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Hz Linear Frequency – dB
Airflow – dB (A)
Model
m3/h
63 125 250 500 1000 2000 4000 8000
LDAV1511A 16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63.0
LDAV1911A 16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63.0
LDAV2422A
20,000 49.7 59.2 58.1 55.1 58.4 58.8 51.9 48.8 63.4
LDWV2422A
LDAV2522A
24,300 52.0 62.2 60.5 58.6 60.5 62.7 56.6 49.8 66.8
LDWV2522A
LDAV2722A
26,000 53 67.5 61.9 60.3 61.6 64.5 59.8 51.8 68.7
LDWV2722A
LDAV3822A
27,000 52.7 59.9 60.6 56.7 59.7 59.8 53.0 50.9 64.7
LDWV3822A
LDEV Models
Hz Linear Frequency – dB
Airflow – dB (A)
Model
m3/h
63 125 250 500 1000 2000 4000 8000
LDEV2422A 20,000 <40 46.5 52.8 53.7 60.7 62.0 54.3 48.6 65.5
LDEV2722A 26,000 <40 45.4 52.3 54.0 61.1 61.9 54.2 49.5 65.6
Hz Linear Frequency – dB
Airflow – dB (A)
Model
m3/h
63 125 250 500 1000 2000 4000 8000
LDEV2422A 20,000 <40 46.1 52.5 54.9 61.4 63.0 55.9 50.7 66.4
LDEV2722A 26,000 <40 46.3 54.5 56.0 62.2 63.5 56.5 52.3 67.2
990-5756D-001 / 06ME0092@00B0140 59
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
IDAV1911A 16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
IDAV1922A
16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
IDWV1922A
IDAV2022A
17,000 49.7 55.0 55.9 52.3 56.4 55.1 46.9 43.4 60.4
IDWV2022A
IDAV2422A
20,000 50.9 61.0 59.8 55.3 59.1 59.2 51.7 48.1 63.9
IDWV2422A
IDAV2922A
26,000 55.2 65.3 63.6 61.7 63.1 66.6 60.4 52.1 70.3
IDWV2922A
IDAV3822A
27,000 52.2 60.5 59.9 56.2 60.1 59.7 52.2 49.6 64.6
IDWV3822A
Hz Linear Frequency – dB
Airflow – dB (A)
Model
m3/h
63 125 250 500 1000 2000 4000 8000
IDAV1511A
16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63.0
IDWV1511A
IDAV1911A 16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63.0
IDAV1922A
16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63.0
IDWV1922A
IDAV2022A
17,000 50.1 57.0 56.9 53.4 57.4 56.5 48.8 46.2 61.6
IDWV2022A
IDAV2422A
20,000 51.2 60.7 59.6 56.6 59.9 60.3 53.4 50.3 64.9
IDWV2422A
IDAV2922A
26,000 54.5 69.0 63.4 61.8 63.1 66.0 61.3 53.3 70.2
IDWV2922A
IDAV3822A
27,000 54.2 61.4 62.1 58.2 61.2 61.3 54.5 52.4 66.2
IDWV3822A
60 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
IDEV Models
Airflow – Hz Linear Frequency – dB dB (A)
Model m3/h
63 125 250 500 1000 2000 4000 8000
IDEV1511A 16,800 <40 42.8 50.3 52.2 59.5 59.7 51.7 47.0 63.6
IDEV2022A 17,000 <40 40.5 48.9 50.7 58.0 57.9 49.5 43.9 61.9
IDEV2922A 26,000 <40 45.4 52.3 54.0 61.1 61.9 54.2 49.5 65.6
IDEV1511A 16,800 <40 44.7 52.5 53.7 60.4 61.1 53.8 49.6 65
IDEV2022A 17,000 <40 42.2 49.6 51.5 58.7 59.0 51.1 46.4 62.9
IDEV2922A 26,000 <40 46.0 54.2 55.7 61.9 63.2 56.2 52.0 66.9
LUAV Models
Hz Linear Frequency – dB
Airflow – dB (A)
Model
m3/h
63 125 250 500 1000 2000 4000 8000
LUAV1511A 16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
LUAV1911A 16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
LUAV2422A 20,000 49.4 59.5 58.3 53.8 57.6 57.7 50.2 46.6 62.4
LUAV2522A 24 300 52.6 61.9 61.3 58.1 60.2 63.0 55.5 48.4 66.7
LUAV2722A 26,000 53.7 63.8 62.1 60.2 61.6 65.1 58.9 50.6 68.8
LUAV3822A 27,000 50.7 59.0 58.4 54.7 58.6 58.2 50.7 48.1 63.1
Hz Linear Frequency – dB
Airflow – dB (A)
Model
m3/h
63 125 250 500 1000 2000 4000 8000
LUAV1511A 16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63.0
LUAV1911A 16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63.0
LUAV2422A 20,000 49.7 59.2 58.1 55.1 58.4 58.8 51.9 48.8 63.4
LUAV2522A 24,300 52.0 62.2 60.5 58.6 60.5 62.7 56.6 49.8 66.8
LUAV2722A 26,000 53 67.5 61.9 60.3 61.6 64.5 59.8 51.8 68.7
LUAV3822A 27,000 52.7 59.9 60.6 56.7 59.7 59.8 53.0 50.9 64.7
990-5756D-001 / 06ME0092@00B0140 61
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
IUAV1911A 16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
IUAV1922A
16,800 50.0 56.6 56.6 53.1 57.2 56.2 48.4 45.8 61.3
IUWV1922A
IUAV2022A
17,000 49.7 55 55.9 52.3 56.4 55.1 46.9 43.4 60.4
IUWV2022A
IUAV2422A
20,000 50.9 61 59.8 55.3 59.1 59.2 51.7 48.1 63.9
IUWV2422A
IUAV2922A
26,000 55.2 65.3 63.6 61.7 63.1 66.6 60.4 52.1 70.3
IUWV2922A
IUAV3822A
27,000 52.2 60.5 59.9 56.2 60.1 59.7 52.2 49.6 64.6
IUWV3822A
Hz Linear Frequency – dB
Model Airflow – m3/h dB (A)
63 125 250 500 1000 2000 4000 8000
IUAV1511A
16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63
IUWV1511A
IUAV1911A 16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63
IUAV1922A
16,800 52.0 58.8 59.1 54.9 58.4 57.9 50.8 48.7 63
IUWV1922A
IUAV2022A
17,000 50.1 57.0 56.9 53.4 57.4 56.5 48.8 46.2 61.6
IUWV2022A
IUAV2422A
20,000 51.2 60.7 59.6 56.6 59.9 60.3 53.4 50.3 64.9
IUWV2422A
IUAV2922A
26,000 54.5 69.0 63.4 61.8 63.1 66.0 61.3 53.3 70.2
IUWV2922A
IUAV3822A
27,000 54.2 61.4 62.1 58.2 61.2 61.3 54.5 52.4 66.2
IUWV3822A
62 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
IUAV1911A 16,800 54.0 60.6 60.6 57.1 61.2 60.2 52.4 49.8 65.3
IUAV1922A
16,800 54.0 60.6 60.6 57.1 61.2 60.2 52.4 49.8 65.3
IUWV1922A
IUAV2022A
17,000 53.7 59.0 59.9 56.3 60.4 59.1 50.9 47.4 64.4
IUWV2022A
IUAV2422A
20,000 54.9 65.0 63.8 59.3 63.1 63.2 55.7 52.1 67.9
IUWV2422A
IUAV2922A
26,000 59.2 69.3 67.6 65.7 67.1 70.6 64.4 56.1 74.3
IUWV2922A
IUAV3822A
27,000 56.2 64.5 63.9 60.2 64.1 63.7 56.2 53.6 68.6
IUWV3822A
Hz Linear Frequency – dB
Airflow – m3/ dB (A)
Model
h
63 125 250 500 1000 2000 4000 8000
IUAV1511A
16,800 56.0 62.8 63.1 58.9 62.4 61.9 54.8 52.7 67.0
IUWV1511A
IUAV1911A 16,800 56.0 62.8 63.1 58.9 62.4 61.9 54.8 52.7 67.0
IUAV1922A
16,800 56.0 62.8 63.1 58.9 62.4 61.9 54.8 52.7 67.0
IUWV1922A
IUAV2022A
17,000 54.1 61.0 60.9 57.4 61.4 60.5 52.8 50.2 65.6
IUWV2022A
IUAV2422A
20,000 55.2 64.7 63.6 60.6 63.9 64.3 57.4 54.3 68.9
IUWV2422A
IUAV2922A
26,000 58.5 73.0 67.4 65.8 67.1 70.0 65.3 57.3 74.2
IUWV2922A
IUAV3822A
27,000 58.2 65.4 66.1 62.2 65.2 65.3 58.5 56.4 70.2
IUWV3822A
990-5756D-001 / 06ME0092@00B0140 63
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
IUEV1511A 16,800 <40 42.8 50.3 52.2 59.5 59.7 51.7 47 63.6
IUEV2022A 17,000 <40 40.5 48.9 50.7 58.0 57.9 49.5 43.9 61.9
IUEV2922A 26,000 <40 45.4 52.3 54.0 61.1 61.9 54.2 49.5 65.6
Hz Linear Frequency – dB
Airflow – m3/ dB (A)
Model
h
63 125 250 500 1000 2000 4000 8000
IUEV1511A 16,800 <40 44.7 52.5 53.7 60.4 61.1 53.8 49.6 65
IUEV2022A 17,000 <40 42.2 49.6 51.5 58.7 59.0 51.1 46.4 62.9
IUEV2922A 26,000 <40 46.0 54.2 55.7 61.9 63.2 56.2 52.0 66.9
IUEV1511A 16,800 <40 46.8 54.3 56.2 63.5 63.7 55.7 51.0 67.6
IUEV2022A 17,000 <40 44.5 52.9 54.7 62.0 61.9 53.5 47.9 65.9
IUEV2922A 26,000 <40 49.4 56.3 58.0 65.1 65.9 58.2 53.5 69.6
Hz Linear Frequency – dB
Airflow – m3/ dB (A)
Model
h
63 125 250 500 1000 2000 4000 8000
IUEV1511A 16,800 <40 48.7 56.5 57.7 64.4 65.1 57.8 53.6 69.0
IUEV2022A 17,000 <40 46.2 53.6 55.5 62.7 63.0 55.1 50.4 66.9
IUEV2922A 26,000 <40 50.0 58.2 59.7 65.9 67.2 60.2 56.0 70.9
64 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Hz Linear Frequency – dB
Model Airflow – m3/h dB (A)
63 125 250 500 1000 2000 4000 8000
IXAV2322A
18,800 52.2 61.0 60.3 56.9 60.3 60.4 53.3 50.9 65.2
IXWV2322A
IXAV2622A
23,400 53.6 65.9 62.0 61.1 62.7 64.2 59.0 53.5 68.7
IXWV2622A
IXAV4022A
30,000 54.1 63.7 62.4 59.7 62.8 63.2 56.4 53.5 67.9
IXWV4022A
IXEV Models
Hz Linear Frequency – dB
Model Airflow – m3/h dB (A)
63 125 250 500 1000 2000 4000 8000
IXEV2311A 18,800 <40 44.5 51.3 52.5 59.6 60.4 52.3 46.8 64.1
IXEV2622A 23,400 <40 47.7 54.2 56.7 62.3 65.3 58.4 50.2 68.3
IXEV4022A 30,000 <40 46.1 52.5 53.3 60.3 61.6 53.8 47.9 65.1
Hz Linear Frequency – dB
Model Airflow – m3/h dB (A)
63 125 250 500 1000 2000 4000 8000
IXEV2311A 18,800 <40 45.0 51.8 53.8 60.4 61.7 54.4 49.9 65.3
IXEV2622A 23,400 <40 49.7 53.3 57.8 62.6 65.3 59.9 52.3 68.6
IXEV4022A 30,000 <40 45.9 52.1 54.8 61.1 62.7 55.7 50.7 66.2
990-5756D-001 / 06ME0092@00B0140 65
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Electrical Specifications
LDAV, LDWV, LDEV Models
Unit
Version C D T
Reheat Option None None Standard Electric Reheat**
SC-
Model V*** CR* kW OA FLA LRA kW OA FLA LRA kW OA FLA LRA
(kA)
LDAV1511A 400 15 18.80 33.0 39.3 201.2 24.56 41.3 47.6 209.5 18.80 33.0 39.3 201.2
LDAV1911A 400 15 23.96 40.2 47.2 219.2 29.73 48.5 55.5 227.5 23.96 40.2 47.2 219.2
LDAV2422A
LDWV2422A 400 15 24.46 43.1 56.7 180 30.23 51.4 65.0 188 24.46 43.1 56.7 180
LDEV2422A
LDAV2522A
400 15 24.8 43.6 56.7 180 30.57 52.0 65.0 188 24.80 43.6 56.7 180
LDWV2522A
LDAV2722A
LDWV2722A 400 15 28.74 49.5 62.3 193 34.51 57.8 70.6 202 28.74 49.5 62.3 193
LDEV2722A
LDAV3822A
400 15 41.54 69.9 93.7 268 47.31 78.2 102.0 276 41.54 69.9 93.7 268
LDWV3822A
*According to CEI EN 60947-2
**Standard heaters
***Voltage
66 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Version T + Dehumidification H
Reheat Option Standard Electric Reheat** Standard Electric Reheat**
Volt- SCCR*
Model age (kA) kW OA FLA LRA kW OA FLA LRA
LDAV1511A 400 15 18.80 33.0 39.3 201.2 27.80 46.0 52.3 214.2
LDAV1911A 400 15 32.96 53.2 60.2 232.2 32.96 53.2 60.2 232.2
LDAV2422A
LDWV2422A 400 15 24.46 43.1 56.7 180 30.23 51.4 65.0 188
LDEV2422A
LDAV2522A
400 15 32.16 50.6 58.5 180 30.57 52.0 65.0 188
LDWV2522A
LDAV2722A
LDWV2722A 400 15 34.60 54.2 62.3 193 34.51 57.8 70.6 202
LDEV2722A
LDAV3822A
400 15 41.54 69.9 93.7 268 47.31 78.2 102.0 276
LDWV3822A
*According to CEI EN 60947-2
**Standard heaters
LDAV2422A
LDEV2422A
LDAV2522A
400 24,300 1.76* 3.52** 2.7 4.2
LDWV2522A
LDAV2722A
LDEV2722A
LDAV3822A
400 27,000 1.50* 4.50** 2.3 4.2
LDWV3822A
kW: Absorbed power
990-5756D-001 / 06ME0092@00B0140 67
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Electric heaters
Heater Type Standard
Version T H
Model kW OA kW OA
LDAV1511A 9 13 9 13
LDAV1911A 9 13 9 13
LDAV2422A
LDEV2422A
LDAV2522A
18.00 26.0 18.00 26.0
LDWV2522A
LDAV2722A
LDEV2722A
LDAV3822A
18.00 26.0 18.00 26.0
LDWV3822A
kW: Absorbed power
68 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Humidifier
Unit Version Version H Version D
Model Voltage kW OA kW OA
LDEV2422A
LDAV2522A
400 5.77 8.3 5.77 8.3
LDWV2522A
LDAV2722A
LDEV2722A
LDAV3822A
400 5.77 8.3 5.77 8.3
LDWV3822A
kW: Absorbed power
Fixed-speed compressors
LDEV2422A
LDAV2522A
400 10.64 19.1 24.2 147
LDWV2522A
LDAV2722A
LDEV2722A
LDAV3822A
400 18.76 31.78 38.76 215
LDWV3822A
kW: Absorbed power
990-5756D-001 / 06ME0092@00B0140 69
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
SC-
Model V*** CR* kW OA FLA LRA kW OA FLA LRA kW OA FLA LRA
(kA)
IDAV1511A
IDWV1511A 400 15 18.03 28.9 35.9 35.9 23.80 37.3 44.2 44.2 18.03 28.9 35.9 35.9
IDEV1511A
IDAV1911A 400 15 25.65 40.7 44.4 44.4 31.42 49.1 52.7 52.7 25.65 40.7 44.4 44.4
IDAV1922A
400 15 19.70 31.2 42.0 147.3 25.47 39.5 50.3 155.6 19.70 31.2 42.0 147.3
IDWV1922A
IDAV2022A
IDWV2022A 400 15 19.08 30.3 42.0 147.3 24.85 38.6 50.3 155.6 19.08 30.3 42.0 147.3
IDEV2022A
IDAV2422A
400 15 25.29 42.9 60.1 182.9 31.06 51.3 68.4 191.2 25.29 42.9 60.1 182.9
IDWV2422A
IDAV2922A
IDWV2922A 400 15 31.79 52.6 62.9 193.9 37.56 60.9 71.2 202.2 31.79 52.6 62.9 193.9
IDEV2922A
IDAV3822A
400 15 43.42 71.5 89.4 263.8 49.19 79.8 97.7 272.1 43.42 71.5 89.4 263.8
IDWV3822A
*According to CEI EN 60947-2 SCCR: Short circuit current rating
70 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Version T + Dehumidification H
Reheat Option Standard Electric Reheat** Standard Electric Reheat**
Volt- SCCR*
Model age (kA) kW OA FLA LRA kW OA FLA LRA
IDAV1511A
IDWV1511A 400 15 27.03 41.9 48.9 48.9 27.03 41.9 48.9 48.9
IDEV1511A
IDAV1911A 400 15 34.65 53.7 57.4 57.4 34.65 53.7 57.4 57.4
IDAV1922A
400 15 kA 20.91 33.0 42.0 147.3 25.47 39.5 50.3 155.6
IDWV1922A
IDAV2022A
IDWV2022A 400 15 kA 20.29 32.1 42.0 147.3 24.85 38.6 50.3 155.6
IDEV2022A
IDAV2422A
400 15 kA 25.29 42.9 60.1 182.9 31.06 51.3 68.4 191.2
IDWV2422A
IDAV2922A
IDWV2922A 400 15 kA 37.65 57.3 62.9 193.9 37.56 60.9 71.2 202.2
IDEV2922A
IDAV3822A
400 15 kA 43.42 71.5 89.4 263.9 49.19 79.8 97.7 272.1
IDWV3822A
*According to CEI EN 60947-2
**Standard heaters
990-5756D-001 / 06ME0092@00B0140 71
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
IDAV1511A
IDEV1511A
IDAV1922A
400 16,800 1.29 2.0 4.4
IDWV1922A
IDAV2022A
IDEV2022A
IDAV2422A
400 20,000 1.62 2.5 4.4
IDWV2422A
IDAV2922A
IDEV2922A
IDAV3822A
400 27,000 1.53 2.4 4.4
IDWV3822A
kW: Absorbed power
Electric heaters
Heater Type Standard
Version T H
Model kW OA kW OA
IDAV1511A
IDEV1511A
IDAV1911A 9.00 13.0 9.00 13.0
IDAV1922A
9.00 13.0 9.00 13.0
IDWV1922A
IDAV2022A
IDEV2022A
IDAV2422A
9.00 13.0 9.00 13.0
IDWV2422A
IDAV2922A
IDEV2922A
IDAV3822A
18.00 26.0 18.00 26.0
IDWV3822A
kW: Absorbed power
72 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Humidifier
Unit Version Version H Version D
Model Voltage kW OA kW OA
IDAV1511A
IDEV1511A
IDAV1911A 400 5.77 8.3 5.77 8.3
IDAV1922A
400 5.77 8.3 5.77 8.3
IDWV1922A
IDAV2022A
IDEV2022A
IDAV2422A
400 5.77 8.3 5.77 8.3
IDWV2422A
IDAV2922A
IDEV2922A
IDAV3822A
400 5.77 8.3 5.77 8.3
IDWV3822A
kW: Absorbed power
Fixed-speed compressors
IDAV1511A
IDWV1511A – – – – –
IDEV1511A
IDAV1911A – – – – –
IDAV1922A
400 9.33 15.9 19.7 125
IDWV1922A
IDAV2022A
IDEV2022A
IDAV2422A
400 10.64 19.1 24.2 147
IDWV2422A
IDAV2922A
IDEV2922A
IDAV3822A
400 18.52 31.5 40.6 215
IDWV3822A
kW: Absorbed power
990-5756D-001 / 06ME0092@00B0140 73
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Variable-speed compressors
IDAV1511A
IDEV1511A
IDAV1911A 400 20.45 32.3 35.96 –
IDAV1922A
400 7.79 11.2 13.5 –
IDWV1922A
IDAV2022A
IDEV2022A
IDAV2422A
400 11.41 18.8 27.1 –
IDWV2422A
IDAV2922A
IDEV2922A
IDAV3822A
400 20.31 32.8 35.6 –
IDWV3822A
kW: Absorbed power
74 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
LUAV Models
Unit
Version C D T
Reheat Option None None Standard Electric Reheat**
SC-
Model V*** CR* kW OA FLA LRA kW OA FLA LRA kW OA FLA LRA
(kA)
LUAV1511A 400 15 18.80 33.0 39.3 201.2 24.56 41.3 47.6 209.5 18.8 33.0 39.3 201.2
LUAV1911A 400 15 23.96 40.2 47.2 219.2 29.73 48.5 55.5 227.5 23.96 40.2 47.2 219.2
LUAV2422A 400 15 24.46 43.1 56.7 180 30.23 51.4 65.0 188 24.46 43.1 56.7 180
LUAV2522A 400 15 24.8 43.6 56.7 180 30.57 52.0 65.0 188 24.8 43.6 56.7 180
LUAV2722A 400 15 28.74 49.5 62.3 193 34.51 57.8 70.6 202 28.74 49.5 62.3 193
LUAV3822A 400 15 41.54 69.9 93.7 268 47.31 78.2 102 276 41.54 69.9 93.7 268
*According to CEI EN 60947-2
**Standard heaters
***Voltage
Version T + Dehumidification H
Reheat Option Standard Electric Reheat** Standard Electric Reheat**
Volt- SCCR*
Model age (kA) kW OA FLA LRA kW OA FLA LRA
LUAV1511A 400 15 18.8 33.0 39.3 201.2 27.80 46.0 52.3 214.2
LUAV1911A 400 15 32.96 53.2 60.2 232.2 32.96 53.2 60.2 232.2
LUAV2422A 400 15 24.46 43.1 56.7 180 30.23 51.4 65.0 188
LUAV2522A 400 15 32.16 50.6 58.5 180 30.57 52.0 65.0 188
LUAV2722A 400 15 34.60 54.2 62.3 193 34.51 57.8 70.6 202
LUAV3822A 400 15 41.54 69.9 93.7 268 47.31 78.2 102.0 276
*According to CEI EN 60947-2
**Standard heaters
990-5756D-001 / 06ME0092@00B0140 75
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Electric heaters
Heater Type Standard
Version T H
Model kW OA kW OA
LUAV1511A 9.00 13.0 9.00 13.0
LUAV1911A 9.00 13.0 9.00 13.0
LUAV2422A 9.00 13.0 9.00 13.0
LUAV2522A 18.00 26.0 18.00 26.0
LUAV2722A 18.00 26.0 18.00 26.0
LUAV3822A 18.00 26.0 18.00 26.0
kW: Absorbed power
Humidifier
Unit Version Version H Version D
Model Voltage kW OA kW OA
76 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Fixed-speed compressors
990-5756D-001 / 06ME0092@00B0140 77
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
SC-
Model V*** CR* kW OA FLA LRA kW OA FLA LRA kW OA FLA LRA
(kA)
IUAV1511A
IUWV1511A 400 15 18.03 28.9 35.9 35.9 23.80 37.3 44.2 44.2 18.03 28.9 35.9 35.9
IUEV1511A
IUAV1911A 400 15 25.65 40.7 44.4 44.4 31.42 49.1 52.7 52.7 25.65 40.7 44.4 44.4
IUAV1922A
400 15 19.70 31.2 42.0 147.3 25.47 39.5 50.3 155.6 19.70 31.2 42.0 147.3
IUWV1922A
IUAV2022A
IUWV2022A 400 15 19.08 30.3 42.0 147.3 24.85 38.6 50.3 155.6 19.08 30.3 42.0 147.3
IUEV2022A
IUAV2422A
400 15 25.29 42.9 60.1 182.9 31.06 51.3 68.4 191.2 25.29 42.9 60.1 182.9
IUWV2422A
IUAV2922A
IUWV2922A 400 15 31.79 52.6 62.9 193.9 37.56 60.9 71.2 202.2 31.79 52.6 62.9 193.9
IUEV2922A
IUAV3822A
400 15 43.42 71.5 89.4 263.8 49.19 79.8 97.7 272.1 43.42 71.5 89.4 263.8
IUWV3822A
*According to CEI EN 60947-2 SCCR: Short circuit current rating
Version T + Dehumidification H
Reheat Option Standard Electric Reheat** Standard Electric Reheat**
IUAV1511A
IUWV1511A 400 15 kA 27.03 41.9 48.9 48.9 27.03 41.9 48.9 48.9
IUEV1511A
IUAV1911A 400 15 34.65 53.7 57.4 57.4 34.65 53.7 57.4 57.4
IUAV1922A
400 15 kA 20.91 33.0 42.0 147.3 25.47 39.5 50.3 155.6
IUWV1922A
IUAV2022A
IUWV2022A 400 15 kA 20.29 32.1 42.0 147.3 24.85 38.6 50.3 155.6
IUEV2022A
IUAV2422A
400 15 kA 25.29 42.9 60.1 182.9 31.06 51.3 68.4 191.2
IUWV2422A
IUAV2922A
IUWV2922A 400 15 kA 37.65 57.3 62.9 193.9 37.56 60.9 71.2 202.2
IUEV2922A
78 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Version T + Dehumidification H
Reheat Option Standard Electric Reheat** Standard Electric Reheat**
IUAV3822A
400 15 kA 43.42 71.5 89.4 263.9 49.19 79.8 97.7 272.1
IUWV3822A
*According to CEI EN 60947-2
**Standard heaters
IUAV1511A
IUEV1511A
IUAV1922A
400 16,800 1.29 2.0 4.4
IUWV1922A
IUAV2022A
IUEV2022A
IUAV2422A
400 20 000 1.62 2.5 4.4
IUWV2422A
IUAV2922A
IUEV2922A
IUAV3822A
400 27,000 1.53 2.4 4.4
IUWV3822A
kW: Absorbed power
990-5756D-001 / 06ME0092@00B0140 79
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Electric heaters
Heater Type Standard
Version T H
Model kW OA kW OA
IUAV1511A
IUEV1511A
IUAV1911A 9.00 13.0 9.00 13.0
IUAV1922A
9.00 13.0 9.00 13.0
IUWV1922A
IUAV2022A
IUEV2022A
IUAV2422A
9.00 13.0 9.00 13.0
IUWV2422A
IUAV2922A
IUEV2922A
IUAV3822A
18.00 26.0 18.00 26.0
IUWV3822A
kW: Absorbed power
Humidifier
Unit Version Version H Version D
Model Voltage kW OA kW OA
IUAV1511A
IUEV1511A
IUAV1911A 400 5.77 8.3 5.77 8.3
IUAV1922A
400 5.77 8.3 5.77 8.3
IUWV1922A
IUAV2022A
IUEV2022A
IUAV2422A
400 5.77 8.3 5.77 8.3
IUWV2422A
IUAV2922A
IUEV2922A
IUAV3822A
400 5.77 8.3 5.77 8.3
IUWV3822A
kW: Absorbed power
80 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Fixed-speed compressors
IUAV1511A
IUWV1511A – – – – –
IUEV1511A
IUAV1911A – – – – –
IUAV1922A
400 9.33 15.9 19.7 125
IUWV1922A
IUAV2022A
IUEV2022A
IUAV2422A
400 10.64 19.1 24.2 147
IUWV2422A
IUAV2922A
IUEV2922A
IUAV3822A
400 18.52 31.5 40.6 215
IUWV3822A
kW: Absorbed power
990-5756D-001 / 06ME0092@00B0140 81
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
Variable-speed compressors
IUAV1511A
IUEV1511A
IUAV1911A 400 20.45 32.3 35.96 –
IUAV1922A
400 7.79 11.2 13.5 –
IUWV1922A
IUAV2022A
IUEV2022A
IUAV2422A
400 11.41 18.8 27.1 –
IUWV2422A
IUAV2922A
IUEV2922A
IUAV3822A
400 20.31 32.8 35.6 –
IUWV3822A
kW: Absorbed power
82 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
SC-
Model V*** CR* kW OA FLA LRA kW OA FLA LRA kW OA FLA LRA
(kA)
IXEV2311A 400 15 18.03 28.9 35.9 35.9 23.8 37.3 44.2 44.2 18.03 28.9 35.9 35.9
IXAV2322A
400 15 24.91 42.4 60.1 182.9 30.68 50.7 68.4 191.2 24.91 42.4 60.1 182.9
IXWV2322A
IXAV2622A
IXWV2622A 400 15 29.03 48.5 62.9 193.9 34.80 56.8 71.2 202.2 29.03 48.5 62.9 193.9
IXEV2622A
IXAV4022A
IXWV4022A 400 15 43.51 71.6 89.4 263.8 49.28 79.9 97.7 272.1 43.51 71.6 89.4 263.8
IXEV4022A
*According to CEI EN 60947-2
**Standard heaters
***Voltage
Version T + Dehumidification H
Reheat Option Standard Electric Reheat** Standard Electric Reheat**
Volt- SCCR*
Model age (kA) kW OA FLA LRA kW OA FLA LRA
IXEV2311A 400 15 27.03 41.9 48.9 48.9 27.03 41.9 48.9 48.9
IXAV2322A
400 15 24.91 42.4 60.1 182.9 30.68 50.7 68.4 191.2
IXWV2322A
IXAV2622A
IXWV2622A 400 15 29.03 48.5 62.9 193.9 34.80 56.8 71.2 202.2
IXEV2622A
IXAV4022A
IXWV4022A 400 15 43.51 71.6 89.4 263.8 49.28 79.9 97.7 272.1
IXEV4022A
*According to CEI EN 60947-2
**Standard heaters
990-5756D-001 / 06ME0092@00B0140 83
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Unit Overview
IXAV2322A
400 18,800 1.43 2.2 4.4
IXWV2322A
IXAV2622A
IXEV2622A
IXAV4022A
IXEV4022A
kW: Absorbed power
Electric heaters
Heater Type Standard
Version T H
Model kW OA kW OA
IXEV2311A 9.0 13.0 9.0 13.0
IXAV2322A
9.0 13.0 9 13.0
IXWV2322A
IXAV2622A
IXEV2622A
IXAV4022A
IXEV4022A
kW: Absorbed power
Humidifier
Unit Version Version H Version D
Model Voltage kW OA kW OA
IXEV2622A
IXAV4022A
IXEV4022A
kW: Absorbed power
84 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Unit Overview Cooling Units
Fixed-speed compressors
IXEV2311A – – – – –
IXAV2322A
400 10.64 19.1 24.2 147
IXWV2322A
IXAV2622A
IXEV2622A
IXAV4022A
IXEV4022A
kW: Absorbed power
IXAV2322A
400 11.41 18.8 27.1 –
IXWV2322A
IXAV2622A
IXEV2622A
IXAV4022A
IXEV4022A
kW: Absorbed power
990-5756D-001 / 06ME0092@00B0140 85
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
Component Identification
External Components
Downflow Units
0000174037_A
Item Description
Plenum (optional)
Filter plenum
Touch-screen display interface
Main disconnect switch
External panels
Base frame (optional)
Air deflector (optional)
86 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Component Identification Cooling Units
Upflow Units
na6348a
Item Description
Motorized damper (optional)
Touch-screen display interface
Main disconnect switch
External panels
Floor stand (optional)
990-5756D-001 / 06ME0092@00B0140 87
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
na6361a
Item Description
Motorized damper (optional)
Filter plenum
Touch-screen display interface
Main disconnect switch
External panels
Fan module
Adjustable leg kit (optional)
88 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Component Identification Cooling Units
C
B
A
na5941a
Dimensions mm (in)
Heat Rejection Model Net Weight kg*
A B C
LDAV1511A 2150 1777 900 600
LDAV1911A 2150 1777 900 640
LDAV2422A 2150 2082 900 755
LDAV2522A 2150 2650 900 870
LDAV2722A 2150 2650 900 880
LDAV3822A 2150 2650 900 1005
Air-Cooled IDAV1511A 2150 1777 900 695
IDAV1911A 2150 1777 900 615
IDAV1922A 2150 1777 900 740
IDAV2022A 2150 2082 900 715
IDAV2422A 2150 2082 900 770
IDAV2922A 2150 2650 900 870
IDAV3822A 2150 2650 900 985
LDWV2422A 2150 2082 900 795
LDWV2522A 2150 2650 900 905
LDWV2722A 2150 2650 900 910
LDWV3822A 2150 2650 900 1035
IDWV1511A 2150 1777 900 710
Water-Cooled
IDWV1922A 2150 1777 900 750
IDWV2022A 2150 2082 900 725
IDWV2422A 2150 2082 900 795
IDWV2922A 2150 2650 900 905
IDWV3822A 2150 2650 900 1005
Indirect Free
Cooling LDEV2422A 2150 2082 900 850
990-5756D-001 / 06ME0092@00B0140 89
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
Dimensions mm (in)
Heat Rejection Model Net Weight kg*
A B C
LDEV2722A 2150 2650 900 950
IDEV1511A 2150 1777 900 740
IDEV2022A 2150 2082 900 775
IDEV2922A 2150 2650 900 945
LDAV1511A OD M 22 OD M 22 –
LDAV1911A OD M 22 OD M 28 –
LDAV2422A OD M 20 OD M 22 –
LDAV2522A OD M 20 OD M 22 –
LDAV2722A OD M 20 OD M 22 –
LDAV3822A OD M 22 OD M 28 –
Air-Cooled IDAV1511A OD M 22 OD M 22 –
IDAV1911A OD M 22 OD M 28 –
IDAV1922A OD M 22 OD M 22 –
IDAV2022A OD M 16 OD M 22 –
IDAV2422A OD M 20 OD M 22 –
IDAV2922A OD M 20 OD M 22 –
IDAV3822A OD M 22 OD M 28 –
LDWV2422A – – 2” G
LDWV2522A – – 2” G
LDWV2722A – – 2” G
LDWV3822A – – 2” G
IDWV1511A – – 1 1/2 ” G
Water-Cooled
IDWV1922A – – 1 1/2 ” G
IDWV2022A – – 1 1/2 ” G
IDWV2422A – – 2” G
IDWV2922A – – 2” G
IDWV3822A – – 2” G
LDEV2422A – – 2” G
LDEV2722A – – 2” G
Indirect Free Cooling IDEV1511A – – 1 1/2 ” G
IDEV2022A – – 1 1/2 ” G
IDEV2922A – – 2” G
Key: L1/ L2 = Refrigerant liquid connection 1/2; G1/ G2 = Refrigerant gas connection 1/2; ICW/ UCW = Water inlet/ outlet
90 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Component Identification Cooling Units
Upflow Units
C
B
A
na5902a
Dimensions mm
Heat Rejection Model Net Weight kg*
A B C
IUAV1511A 1950 1777 900 600
IUAV1911A 1950 1777 900 640
IUAV1922A 1950 1777 900 665
IUAV2022A 1950 2082 900 710
IUAV2422A 1950 2082 900 760
IUAV2922A 1950 2650 900 835
Air-Cooled IUAV3822A 1950 2650 900 955
LUAV1511A 1950 1777 900 600
LUAV1911A 1950 1777 900 665
LUAV2422A 1950 2082 900 740
LUAV2522A 1950 2650 900 855
LUAV2722A 1950 2650 900 860
LUAV3822A 1950 2650 900 1010
IUWV1511A 1950 1777 900 615
IUWV1922A 1950 1777 900 675
IUWV2022A 1950 2082 900 715
Water-Cooled
IUWV2422A 1950 2082 900 780
IUWV2922A 1950 2650 900 785
IUWV3822A 1950 2650 900 865
IUEV1511A 1950 1777 900 650
Indirect Free
Cooling IUEV2022A 1950 2082 900 765
IUEV2922A 1950 2650 900 825
990-5756D-001 / 06ME0092@00B0140 91
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
IUAV1511A OD M 22 OD M 22 –
IUAV1911A OD M 22 OD M 28 –
IUAV1922A OD M 22 OD M 22 –
IUAV2022A OD M 16 OD M 22 –
IUAV2422A OD M 20 OD M 22 –
IUAV2922A OD M 22 OD M 28 –
Air-Cooled IUAV3822A OD M 22 OD M 28 –
LUAV1511A OD M 22 OD M 22 –
LUAV1911A OD M 22 OD M 28 –
LUAV2422A OD M 20 OD M 22 –
LUAV2522A OD M 22 OD M 28 –
LUAV2722A OD M 22 OD M 28 –
LUAV3822A OD M 22 OD M 28 –
IUWV1511A – – 1” 1/2 G
IUWV1922A – – 1” 1/2 G
IUWV2022A – – 1” 1/2 G
Water-Cooled
IUWV2422A – – 2” G
IUWV2922A – – 2” G
IUWV3822A – – 2” G
LDEV2422A – – 2” G
LDEV2722A – – 2” G
Indirect Free Cooling IDEV1511A – – 1” 1/2 G
IDEV2022A – – 1” 1/2 G
IDEV2922A – – 2” G
Key: L1/ L2 = Refrigerant liquid connection 1/2; G1/ G2 = Refrigerant gas connection 1/2; ICW/ UCW = Water inlet/ outlet
92 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Component Identification Cooling Units
B
na6343a
* Net weight refers to the basic unit and includes the plenum.
990-5756D-001 / 06ME0092@00B0140 93
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
Key: L1/ L2 = Refrigerant liquid connection 1/2; G1/ G2 = Refrigerant gas connection 1/2; ICW/ UCW = Water inlet/ outlet
Service Clearance
To service the cooling unit, 850 mm of clearance on the front side is required.
5 in.)
m (33.
850 m
na5896d
Connection Access—Bottom
See the Installation drawing supplied with the unit for more information on the connection access.
94 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Component Identification Cooling Units
Floor Cutout
Downflow Units
A section of floor under the cooling unit is required to be removed for installation
on a raised floor.
B
na5580a
990-5756D-001 / 06ME0092@00B0140 95
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
Upflow Units
A section of floor under the cooling unit is required to be removed for installation
on a raised floor.
B
na5580a
96 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Component Identification Cooling Units
B
na5580a
990-5756D-001 / 06ME0092@00B0140 97
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
Dimensions – mm
Damper Weight – kg
A B C
200 1777 897 45.0
C B 200 2083 897 50.0
na6738a
C
B
na6739a
98 990-5756D-001 / 06ME0092@00B0140
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Component Identification Cooling Units
Floor Stand
See Accessories, page 127 for more information.
Dimensions – mm Weight – kg
Floor Stand
A B C
200 1763 890 28.0
C 200 2070 890 31.0
B
200 2638 890 37.0
na6381a
C B
500 2070 890 90.0
500 2638 890 110.0
na6382a
990-5756D-001 / 06ME0092@00B0140 99
Uniflair™ DX Air Cooled, Water Cooled and Indirect Free
Cooling Units Component Identification
Base Frame
See Accessories, page 127 for more information.
Dimensions – mm
Base Frame Weight –kg
A B C
600-650 1775 920 23.6
C B 600-650 2070 920 26.0
Plenum
See Accessories, page 127 for more information.
Dimensions – mm
Plenum Weight –kg
A B C
700 1777 900 33
C 700 2082 900 37
B
700 2650 900 43
0000905836_A
A
0000905835_A
Dimensions – mm
Plenum Weight –kg
A B C
700 1777 900 120
C 700 2082 900 125
B
700 2650 900 140
na6380a
WARNING
BURN RISK
Discharge lines must be insulated where contact could be made to avoid a
contact burn.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
The discharge line must be sized in such a way that it ensures the flow of oil at all
operating levels. Particular attention should be paid to operation at partial load on
units equipped with variable-speed compressors to provide oil return in all
conditions. Even if it is recommended to minimize load losses, using an oversized
discharge line to reduce the refrigerant speed would cause a decrease in the oil
flow. When the unit uses variable-speed drive compressors for the cooling circuit,
the discharge line must convey the oil at all operating levels.
The pressure drops along the discharge line cause an increase in the condensing
temperature and a decrease in the cooling capacity of the cooling unit. Note that
each percentage point of decrease in the cooling capacity corresponds to a
decrease of 1 °C of the maximum operating temperature. The systems are
normally sized in such a way that the loss of load from the discharge line does not
cause a decrease in the efficiency of the cooling unit of more than –3%. The
responsibility of installing the refrigerant line between the condenser and the
external unit lies with the installer. Units can operate with a maximum equivalent
length up to 100 meters (including a maximum height difference of 30 meters)
considering the consequent penalization in performance.
NOTE: When the distance of 50 meters equivalent length is exceeded, it is
required to contact Schneider Electric Customer Support.
The oil type is specific for each compressor. See the documentation
of the compressor.
To define the optimal refrigerant lines, please refer to UNICALC
Piping Size Tool.
NOTE: It is recommended to install the Check and Bypass Valve Kit and the
Low Temperature Kit according to the following table, where:
• L = refrigerant line length
• T = ambient temperature
L
T 0 < L < 20 m L > 20 m
T > —20 °C NO Kit Check and Bypass Valve Kit
—40 °C < T < –20 °C Low Temperature Kit Low Temperature Kit
1/100
1/100
MAXIMUM
10 M
1/100
MAXIMUM
MAXIMUM 30 M
5M
MAXIMUM
5M
0000679936_A
It is required to install a syphon or oil trap every time the piping changes from a
horizontal to a vertical position.
It is also required to install a syphon or oil trap every 5 meters on the vertical
piping section.
0000525018_A
The external condensers can be equipped with AC axial fans or electronically
commutated (EC) axial fans. Both fans are statically and dynamically balanced on
two levels and include protection grade IP54 class “F.” Safety protection grilles on
the fans comply with safety standards and regulations. AC and EC remote air-
cooled condensers are designed to operate in a wide range of external
temperatures ( -25°C ÷ 50°C). In case of lower external temperatures ( down to
-40°C), the OCC range offer a specific version OCCxxxxLT. Remote air-cooled
condensers for Low temperature applications are available only in single circuit
version and with AC fan. In case of Low Temperature applications the external
condenser is always powered by the indoor unit.
The condensing coil is constructed of copper tubes mechanically expanded onto
aluminum fins. The internal surface of the tubes is made in such a way as to
increase turbulence of the refrigerant and increase the exchange capacity
equivalent to that of the air supply produced. The large frontal area and upward
arrangement of the fans provide efficient air distribution.
The electrical connections of the condensers consist of a general main switch with
protection grade IP54 located on the fan side of the unit, a pressure transducer,
and a pre-wired speed regulator.
The fan speed pressure switch regulator on the low temperature units provide
control of the exchange capacity of the condenser by means of an electronic
device sensitive to the supplied gas pressure. The regulator varies the speed of
the fan motor to maintain constant condensation pressure.
In the remote condensers for low temperature applications (LT), the fan speed
regulator is installed inside the in-room unit. The indoor units manage the fan
speed regulator and the parameter of the remote condensers exclusively through
ModBus command. The remote condensers with 230V/1ph+N/50Hz power supply
are equipped with single phase fan speed regulator. In case of double refrigerant
circuit remote condenser, this type of regulator is able to control independently two
ventilation sections through ModBus signal.
The remote condensers with power supply 400V/3ph/60Hz are equipped with one
three phase fan speed regulator. In case of double refrigerant circuit, the remote
condenser is equipped with two speed regulators to manage independently two
ventilation sections.
Except for the OCC Low temperature version (LT) that are always powered by the
indoor units, in case of AC and EC condensers are selected, the indoor unit is
provided with set-up for power condenser only if it is configured with double power
supply. In this case the cooling unit can power one single refrigerant circuit
condenser single phase type (230V/1ph/50Hz).
Airflow Configurations
Horizontal Air Discharge
Units installed with a horizontal discharge must be protected from wind that can
interfere with the operation of the fan. This configuration is characterized by the
best protection from snow and objects falling from above, as well as for ease of
maintenance.
na5722b
Dimensional Data
Condenser—horizontal configuration
B
0000689611_A
C
D
A E
NOTE: Image is an example only: your model may differ. Refer to the
installation drawing for more detailed information on the unit dimensions.
Condenser—vertical configuration
A B
C
0000689610_A
D E
NOTE: Image is an example only: your model may differ. Refer to the
installation drawing for more detailed information on the unit dimensions.
Access clearance
For proper operation and servicing, the following access clearance is required:
>1m
na5725a
Air-Cooled Condenser Performance Data
Cooling Fan Sound
Voltage – V/ Fan Current – Air flow – m3/
Condenser with AC Fans Capacity – Absorbed Pressure @
ph/Hz A h
kW Power – kW 10 m – dB(A)
1m
(3 ft)
na5911a
10 m (33 ft)
OCC1701 17,227 45
OCC2401 15,216 45
OCC2601 22,275 47
OCC3101 23,372 47
OCC3301 32,700 51
OCC3901 29,525 51
OCC3502 34,453 48
OCC4202 32,625 48
OCC4702 30,431 48
OCC6202 46,744 50
OCC6702 65,400 54
OCC7702 59,050 54
OCC1701 17,227 45
OCC2101 16,313 45
OCC2401 15,216 45
OCC3101 23,372 47
OCC3301 32,700 51
OCC3901 29,525 51
OCC3502 34,453 48
OCC4202 32,625 48
OCC4702 30,431 48
OCC6202 46,744 50
OCC6702 65,400 54
OCC7702 59,050 54
Recommended Condensers
Condenser Refrigerant Connections
OCC2601
OCC1701 OCC3101
OCC2101 OCC3301
OCC2401 OCC3901
Condenser Model
OCC3502 OCC5302
OCC4202 OCC6202
OCC4702 OCC6702
OCC7702
Ø Inlet Gas – mm 28 35
Ø Outlet Liquid – mm 18 22
na6413a
Main Components
Self-Supporting Frame
The structure of the unit is characterized by a metal framework and internal parts
made from of zinc-plated sheet steel. These profiles are connected together by
structural rivets designed to ensure sturdy assembly and to withstand severe
transport and handling conditions. The units are also equipped with internal
panels to isolate compartments affected by the produced airflow. These panels
are made of zinc-plated sheet fitted with captive screws and are used to ensure:
• Reduction in the noise transmitted through the paneling
• Air tightness even without external panels so that the units can also operate
with the doors open during servicing
• Inspection of internal elements without interfering with the operation of the
unit and while the unit is in operation
The external panels are coated with RAL9003 epoxy-polyester paint which
provides long term durability of the original features. The front panels are attached
to the framework by means of rapid coupling fasteners. The standard panels are
internally lined with heat- and sound-proofing insulating material made of
melamine covered by a protective film. Melamine is an exceptionally high-quality
product, coupled with high fire-resistance (class B1 according to DIN 4102, BS
476 part 7, V0 according to UL94, ASTM E84, class M1 according to NFP92–501)
and excellent sound-insulation properties.
10%
8%
6%
4%
2%
na6376a
0%
15 17 19 21 23 25 27 29 31 33 35
Outdoor Ambient Temperature (°C)
Extending Operating
Model IDV Non-Return Valve Map
LD*V2722A
Integrated in the
LD*V3822A Yes compressor Yes
* may be A (air-cooled), W (water-cooled), or E (indirect free cooling) if the heat rejection version is
available for that model.
Extending Operating
Model IDV Non-Return Valve Map
LUAV2722A
Integrated in the
LUAV3822A Yes compressor Yes
100%
95%
90%
0 10 20 30 40 50 60 70 80 90 100
SPEED (RPS)
Variable-speed compressors in I**V units provide a soft start that reduces in-rush
current, decreasing the impact on the power grid and allowing savings in energy
consumption during the year.
The VFD has built-in harmonic filters to provide easy installation and comply with
most industry standards (EMC).
Variable-speed compressors installed in the 1922A and 2022A models include
intermediate discharge valves (IDVs), which result in better energy efficiency at
partial load and at low-pressure ratios.
Fans
The units are equipped with single-inlet centrifugal fans with electronically
commutated (EC), backward curved fan blades made from a composite material.
ROTOR
HALL-IC
STATOR
STATOR WINDING
PERMANENT MAGNET
SOUTH POLE
PERMANENT MAGNET
na5574a
NORTH POLE
Electrical Panel
The electrical panel is located in a compartment separated from the airflow and is
in compliance with the directive 2014/35/EU and related standards. The following
are the main features:
• Three-phase power supply 400 V/3 Ph+N/50 Hz for all units with a single
power supply
• Three-phase power supply 400 V/3 Ph+N/50 Hz for all units with double
power supplies
• Low-voltage secondary circuit 24 Vac with isolation transformer
• Metal isolation screen for protection from live components
• General isolator with mechanical interlock
• Thermo-magnetic circuit-breakers for protection
• Terminal board for no-voltage signal and control contacts
All of the units undergo a safety test cycle to check the continuity of the protection
circuit, the insulation resistance, and a voltage test (dielectric strength).
Mechanical Mode
In mechanical mode, the refrigerant undergoes the vapor compression cycle as it
evaporates to a low pressure in the DX evaporator in order to cool air from the IT
environment. The refrigerant is then compressed by the scroll compressor and
then condensed to a liquid in a plate heat exchanger (condenser).
A water/glycol mixture conveys heat from the refrigerant via the condenser to the
dry cooler.
In this mode, flow control device (B) is 100% open to direct the water/glycol
mixture from the dry cooler to the condenser. Flow control device (A) is 0% open
(closed) and flow control device (C) is closed so that the water/glycol mixture
bypasses the chilled-water coil and is introduced directly into the condenser.
The pressure drop of the system in mechanical mode is the sum of the pressure
drop across flow control device (B) and the condenser.
Item Description
Chilled-water coil
Direct-expansion (DX)
evaporator
Compressor
Condenser
Dry cooler
na6740a
Hybrid Mode
In hybrid mode, flow control device (B) is 0% open (closed) and flow control device
(A) is 100% open so that the water/glycol mixture is directed through the chilled-
water coil and introduced to the heat exchanger (condenser).
The water/glycol mixture conveys heat from the refrigerant via the condenser to
the dry cooler.
Flow control device (C) remains closed. The pressure drop of the system during
hybrid mode is the pressure drop across the chilled-water coil and the condenser.
Flow control devices (A) and (C) are configured as “full port, which allows
negligible pressure drops.
Item Description
Chilled-water coil
Direct-expansion (DX)
evaporator
Compressor
Condenser
Dry cooler
na6741a
Free-Cooling Mode
During free-cooling mode, the external air temperature is low enough to cool the
IT air to the set point temperature without the need of the evaporation cycle.
All flow control devices, (A), (B), and (C), may be used to control the water/glycol
mixture flow from the dry cooler to the chilled-water coil. In the dry cooler, the heat
is dissipated and the water/glycol mixture is cooled by the external air. In the
chilled-water coil, the heat is absorbed and the water/glycol mixture is heated by
the air in the IT space.
During free cooling mode, flow control devices (A) and (B) are modulated in order
to allow the water/glycol mixture flowing from the dry cooler to the chilled-water
coil or to flow control device (B).
Flow control device (C) is open in order to allow the water/glycol mixture (as the
combination of part of the flow coming from the dry cooler and part coming from
the chilled-water coil) to bypass the condenser and to go directly in the dry cooler.
Flow control devices (A) and (B) are modulated according to the room load, i.e.
the air temperature in the IT space.
Item Description
Chilled-water coil
Direct-expansion (DX)
evaporator
Compressor
Condenser
Dry cooler
0.96
.028 28 0.45
32.0
30
0.94
90 .026 26
30.0
30
W
ET
BU 0.50
LB .024 24 28.0 13
TE 0
80 M
PE
RA
T
HUMIDITY RATIO (or Specific Humidity) GRAMS OF MOISTURE PER KILOGRAM OF DRY AIR
UR .022 22 26.0
0.92
E 0.55
-°
C
AIR
70 24.0
RY
.020 20 25 12
0
D
OF
0.60
RA
25
OG
KIL
0.65
0.90
20.0
ER
JP
11
.016 16 0
-K
0.70
AL
20
TH
0.75
.014 14
EN
16.0
20
0.80
0.88
40 10
.012 12 0
0.85 14.0
%
90
0.90
15
%
25
%
.010 10 0.95 12.0
80
30
0.86
15 1.00
V
10.0
OLU
.008 8
20
%
10
ME -
60
8.0
0.84
10
CUB
% %
10 50 15 .006 6
IC
5
%
METE
40 ITY 6.0 80
0 5 MID
0.82
E HU
TIV
R PE
.004 4
-1 3 0% R ELA 0
0 8% 4.0
R KG
0.80
20% 6% -5
-2
MIDITY 2
DRY
-5 .002
0.78
0 HU 4% 2.0
LATIVE -10
-10 10% RE
0.76
AIR
-15 2% 70
0.74
.000
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55
na5587a
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com DRY BULB TEMPERATURE - °C
-2 -1 0 10 20 30 40 50 60
0 0
Humidifier
NOTICE
STATEMENT OF HAZARD
• Do not treat with softeners. This can cause corrosion of the electrodes or the
formation of foam, leading to potential operation problems or failure.
• Avoid using well water, industrial water, or water drawn from cooling circuits.
In general, avoid using water potentially contaminated with chemicals.
• Avoid adding disinfectants or corrosion inhibitors to the water. These
substances are potentially irritant.
Failure to follow these instructions can result in equipment damage.
Supply Water
The following table provides values related to the feed water for medium-high level
of conductivity of a humidifier with immersed electrodes.
Limits
Description Units Minimum Maximum
Temperature °C (°F) 1°C (33.8) 40°C (104°C)
Pressure MPa (bar/ 0.1 (1/14.5) 0.8 (8/116)
psi)
Hydrogen ion activity pH — 7 8.5
Specific conductivity at 20°C σ R, 20°C µS/cm 350 1250
Total dissolved solids TDS mg/l * *
Residual fixed at 180°C R180 mg/l * *
Total hardness TH mg/l 100** 400
Temporary hardness mg/l 60*** 300
Iron + manganese mg/l Fe + 0 0.2
Mn
Chlorides ppm Cl 0 30
Silica mg/l 0 20
Residual chloride mg/l 0 0.2
Calcium sulphate mg/l 0 100
Metallic impurities mg/l 0 0
Solvents, soaps, and lubricants mg/l 0 0
* Values dependent on the specific conductivity; in general: TDS @ 0.93 x s20; R180 @ 0.65 x s20
*** Not lower than 300% of the chloride content in mg/l di Cl-
The following table provides values related to the feed water for medium-low level
of conductivity of a humidifier with immersed electrodes.
Limits
Description Units Minimum Maximum
Hydrogen ion activity pH — 7 8.5
Specific conductivity at 20°C σ R, 20°C µS/cm 125 350
Total dissolved solids TDS mg/l * *
Residual fixed at 180°C R180 mg/l * *
Total hardness TH mg/l 50** 250
Temporary hardness mg/l 30*** 150
Iron + manganese mg/l Fe + 0 0.2
Mn
Chlorides ppm Cl 0 20
Silica mg/l 0 20
Residual chloride mg/l 0 0.2
Calcium sulphate mg/l 0 60
Metallic impurities mg/l 0 0
Solvents, soaps, and lubricants mg/l 0 0
* Values dependent on the specific conductivity; in general: TDS @ 0.93 x s20; R180 @ 0.65 x s20
*** Not lower than 300% of the chloride content in mg/l di Cl-
Microprocessor Controller
Microprocessor Overview
The microprocessor control of the unit automatically manages unit operation and
has the following main components:
• Seven-inch, touch-screen, LCD display interface, externally mounted and
viewed from the front of the unit.
• Integrated microprocessor control board to which the probes are connected
as well as all of the analogical and digital inputs necessary for the unit control
(J5 controller).
The display interface is equipped with a seven-inch, touch-screen display. By
means of the display interface, it is possible to set operating parameters, monitor
the trends of the main working parameters, and read any alarm messages.
The J5 controller physically separates the internal I/O and external I/O. This
separation is achieved by placing the external I/O on the upper level of connectors
closest to the top of the assembly and internal I/O on the lower level of connectors
closest to the bottom of the assembly. The external connections on the upper level
are sometimes referred to as the “field interface” and offer a wide variety of
accessibility options such as external CAN and group CAN, isolated 2-wire and 4-
wire RS485 ports, NetBotz™ universal sensor ports, alarm/shutdown contacts,
USB ports (Host, Device), Ethernet, HDMI display interface, Modbus, and remote
shutdown input.
The control system enables the following functions:
• Temperature and humidity control based on a set point which can be
configured using the display interface
◦ Return temperature
◦ Supply temperature
◦ Remote temperature
◦ Reheat temperature
◦ Humidity (relative or absolute)
◦ Dehumidification (relative or absolute)
• Complete alarm detection system
• Alarm event history storage of up to 1500 events
• Alarm signal contacts that can be configured on the Web interface
• Automatic restart when power returns after a loss of power
• Remote switching on/off of the unit
• Configuration changes are protected on the display interface separately for
user settings and service settings
• Compatibility with EcoStruxure™ IT Software - cloud-based Datacenter
Management
• Operating hour counters and cycle counters for all main components
• Color touch screen display with graphic interface describing overall state of
the unit
• Provisions for runtime balancing based on run hour differences, a fixed delta
time, or a specific time and day of the week
• Units in standby able to automatically assist active units in the group when
demand is needed
• Service function allowing full manual control of the unit while providing
automatic protection of components
• Optionally select to deactivate heaters, humidifier, compressors, and/or
evaporator fans on loss of primary power in order to reduce the load on
emergency backup systems.
Display Interface
Display
Reset 10/100
Micro
SD
Service
Port
USB
Console
na4820a
BMS Compatibility
Uniflair Room Cooling units can be connected to a network managed by a
supervision system. They are compatible with the most common external BMS
(Building Management Systems).
Accessories
Options for Downflow, Under Floor, Upflow Units
NOTE: Plenums can be provided with:
• external panels lined with insulation made of melamine covered by a
protective film 15 mm (0.59 in.) thick with a density of 10 kg/m3(0.62 lb/
ft3). They are fully compliant with UNI EN ISO 12944 - 1/2/3/4/5/6
• external double-walled panels classified A1–DIN. These panels are
double-skinned and coated with RAL9003 epoxy-polyester paint. The
internal panel is hot-zinc plated with insulation 15 mm (0.59 in.) thick
NOTE:
Floor stands can be provided with external panels lined with insulation made
of melamine covered by a protective film 15 mm (0.59 in.) thick with a density
of 10 kg/m3(0.62 lb/ ft3). They are fully compliant with UNI EN ISO 12944 - 1/2/
3/4/5/6.
See Suction Motorized Damper, page 98 and the following pages for
the dimensions of optional components.
Plenums
Floor Stands
Base Frames
Base Frame
Upflow Units
The following accessories are available for upfow Uniflair Room Cooling units.
Plenums
Floor Stands
Base Frames
Base Frame
Sensors
Water Detection Sensors
Uniflair Room Cooling units can be equipped with either rope water leak detection
sensors or spot water leak detection sensors to detect water leaks in the IT space.
Both types of sensors can be configured to stop unit operation upon the detection
of water.
Smoke/Fire Sensors
The smoke and fire sensors are field
installed on the side of the electrical
panel and wired to digital inputs inside
the electrical panel. If smoke or fire are
detected in the data center, the cooling
unit is shut down and audible and
visual alarms are produced via the
display interface.
na7397a
The 24-V relay for external smoke/fire
sensors is available for data centers
that already have smoke and fire
sensors available. The relay is field
installed inside the electrical panel. If
smoke or fire are detected in the data
center, the cooling unit is shut down
na7398a
and audible and visual alarms are
produced via the display interface.
Pressostatic Valve
A 2-way modulating ball valve varies the water flow through the brazed plate heat
exchanger to control the condensing temperature and let the compressor operate
within its own operating envelope with the highest efficiency. The 0...10-V signal
valve is controlled by the main unit controller according to the high pressure
reading.
The valve and the related piping and connections are shipped loose inside the unit
and are installed on the water outlet inside the fan module (under floor and
downflow units) or close to the unit (upflow units). The power and signal
connections are made through the dedicated cables connected to the electrical
panel.
MAXIMUM
FAN SPEED
MINIMUM
MINIMUM MAXIMUM
na6414a
COOLING CAPACITY
SE C OND A RY LIN E
na5583a
Energy Meter
The energy meter is an optional component in the electrical panel, used to
monitor:
• the unit energy consumption
• the voltage between phases
• the current of each phase
• the cosphi power factor
• the power on each phase
• the energy consumption in kWh and kVAR/h
The calculation varies from country to country depending on the mix of renewable
and traditional energy sources. The installation country can be selected from a list
or entered manually if it is not available. The value of the coefficient is then able to
be automatically configured (source: International Energy Agency).
na4413a
The system also manages the constant pressure underneath the floor during
ordinary and extraordinary maintenance of the floor and also when new servers
are installed, adapting the flow when the following events occur:
• New equipment is added
• The floor panels are opened during maintenance/installation of new
equipment (without creating hot spots in another point of the same room)
• Partition walls underneath the floor break or are damaged
The system is able to manage all of the information read by different units and
define combined regulation strategies by means of a local area network (LAN)
connection and is able to define the nominal pressure value requested via the
microprocessor control settings. The system can read the average pressure value
of a specific area (one for each unit) with its management logic. The system may
have a single point of reference in the room or may be managed according to
various areas. In the second case, it is possible to control all units based on the
average pressure read by all of the units with the exception of the areas in which
the pressure differs too much from the average value. In this case, the units within
this area manage the airflow independently in such a way that this specific single
area also returns to a nominal value.
The system manages the increase in room dimensions over time, automatically
changing the cooling capacity and the airflow depending on the number of units,
grilles, and air distribution systems added. This enables the fans absorption to be
reduced: when the room is not complete, the airflow needed is lower than the
nominal value. When a unit is in standby, it is recommended to keep it switched on
in order to optimize the energy efficiency, especially at partial loads.
Group Control
Overview
The following group activities are available when units are grouped together on a
network and are managed by the group controller:
• Redundancy designates a set of standby units, one of which will be placed
into operation in the event of failure of the active unit.
• Runtime balancing changes roles of active and standby units to maintain an
even runtime of unit components across the cooling group.
• Assist activates a standby unit when the active unit is unable to meet the
cooling demand. This is supported for both temperature and humidity.
Group Controller
The group controller is selected by the group members when the group is created.
The selected group controller remains the group controller until the unit is no
longer on the network or the group is connected to another network and the group
controller loses an arbitration.
Group Data
Group data are data shared among the group. When entered on any display
interface of a unit in the group, the data is broadcast to the entire group. The group
controller ensures that a new member of the group has data consistent with the
other group members.
Redundancy
A unit in the group has one of the possible states:
• Active: The unit is providing environmental control.
• Standby: The unit is not currently providing environmental control but is
ready to become active if an active unit fails or requires assistance.
• Assist: The unit is providing environmental control in response to a request
for assistance. When assistance is no longer required, the unit returns to the
standby state.
Operation
The number of active units in the group is determined by the Number of Units in
Group minus the Number of Standby Units in Group. By default, the group
controller will select which units are primary units and which units are standby
units. The group controller will designate the unit with the least system runtime as
an active unit. A unit can be forced to be an active unit by selecting Primary Only
as the Preferred Role.
The group controller maintains the active number of units in the group. If there are
no standby units available to replace an active unit, a No Standby Units
Available alarm is activated.
Events that activate a standby unit are configured via the Web interface; the active
unit will switch over to a standby unit if one is available. When the issue with the
active unit has been resolved and the alarm is cleared by user acknowledgment,
the previously active unit will come back online, and the group controller will return
the currently active unit to standby mode.
Runtime Balancing
Runtime balancing maintains even runtimes on units within a group. Runtime
balancing can be turned off via the Run Time Balancing setting.
An active unit will switch roles with a standby unit when the system runtime
exceeds the set threshold. The threshold is set in one of the following ways:
• Differential: The roles are switched when the system runtime of the active
unit exceeds the system runtime of the standby unit. This difference in
runtime is set in the Runtime Balancing Difference setting.
• Time relative: The roles are switched after the Relative Switchover Time: it
is the time passed since the previous switchover.
• Scheduled: The roles are switched on the day and time entered in the Day of
Week Switchover Time setting.
When the switchover occurs, the group controller selects a standby unit with the
least amount of system runtime. The group controller will also maintain both units
running until the Switchover Handoff Time expires.
Assist
The assist mode activates a standby unit to assist the active unit when the active
unit cannot maintain the relevant set point alone. Assisting is provided for cooling,
humidification, and dehumidification.
Only one standby unit is allocated to assist at a time. When selecting a unit as the
assisting unit, the group controller will attempt to select a unit that supports both
the temperature and humidity control assist. If a unit with both is not available, the
group controller will select a unit with the desired assist function enabled.
Cooling assist: The group controller will assign a standby unit to assist when the
air temperature process variable exceeds the set point plus the Cooling Assist
Threshold. The unit will be returned to standby mode when it no longer has a
demand.
Humidification assist: The group controller will assign a standby unit to assist
when the humidity is below the set point minus the Humidify Assist Threshold.
The unit will be returned to standby mode when it no longer has a demand.
Dehumidification assist: The group controller will assign a standby unit to assist
when the humidity is above the set point plus the Dehumidify Assist Threshold.
First Aid
IMPORTANT: The following measures can be carried out by trained and
qualified personnel only.
6. If needed, take a pain reliever making sure to carefully read the related
information leaflet
In case of severe burn, contact the emergency aid or go to the nearest hospital.