multi-line 2 PPU/GPU/GPC – version 2


4189340268B

D1: Controller for


• Constant voltage control (stand-alone)
• Constant reactive power (parallel w. mains)
DEIF A/S

• Constant power factor (parallel w. mains)


• Reactive load sharing (island w. other gens.)

D2: Controller for


• Constant voltage (synchronising / stand-alone)

DEIF A/S Tel.: +45 9614 9614


Frisenborgvej 33, DK-7800 Skive Fax: +45 9614 9615
Denmark E-mail: deif@deif.com
DESCRIPTION OF OPTION D1 AND D2
multi-line 2 4189340268B

INDEX:

1 Warnings and legal information..........................................................................................................................................3


2 Function descriptions..........................................................................................................................................................3
2.1 Controllers..............................................................................................................................................................................3
2.2 multi-line 2 GPC/PPU option D1 ............................................................................................................................................3
2.2.1 Binary input selection of control mode ...................................................................................................................................3
2.2.2 Binary input selection of external set-point ............................................................................................................................4
2.2.3 Voltage control .......................................................................................................................................................................4
2.2.4 var controller ..........................................................................................................................................................................4
2.2.5 Power factor (PF) controller ...................................................................................................................................................4
2.2.6 Relay control ..........................................................................................................................................................................4
2.2.7 Synchronising window, enabling and disabling of synchronising...........................................................................................5
2.2.8 Governor/AVR regulation failure ............................................................................................................................................5
2.3 multi-line 2 GPU option D2 + G2............................................................................................................................................6
2.3.1 Voltage control .......................................................................................................................................................................6
2.3.2 Synchronising window, enabling and disabling of synchronising...........................................................................................6
2.3.3 Governor/AVR regulation failure ............................................................................................................................................6

This manual is valid for standard multi-line 2 PPU/GPU/GPC units with firmware version 2.00.0 or later.

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 2 of 6
DESCRIPTION OF OPTION D1 AND D2
multi-line 2 4189340268B

1 Warnings and legal information


This manual gives guidelines to the use and installation of the DEIF multi-line 2 units. It is, however, not a complete installation
instruction. Therefore, even if terminal numbers may be shown in the drawings, the drawings are to be used as guidance only.

Installing and operating the multi-line 2 units implies work with dangerous currents and voltages, and therefore only
qualified personnel should do it.

During the installation care must be taken to protect the terminals against static discharges. Once the units are installed and
connected, these precautions are no longer necessary.

DEIF takes no responsibility for operation or installation of the generator set. If there is any doubt about how to install or
operate the system on which the multi-line 2 unit is measuring, the company responsible for the installation or the operation
must be contacted.

2 Function descriptions

2.1 Controllers
The working way of the PI controller outputs is described in the Designers Reference Handbook of multi-line 2.

The outputs can be relay or analogue 20…0…20 mA.

2.2 multi-line 2 GPC/PPU option D1

2.2.1 Binary input selection of control mode


The binary inputs called mode 4 and 5 (terminals 51 and 52, common terminal 56) can be used to select the control method as
follows:

Input Mode 4 Mode 5


Mode (terminal 51) (terminal 52)
Fixed voltage (stand-alone generator) OFF OFF
Fixed var (fixed reactive power) ON OFF
Fixed PF (fixed power factor) OFF ON
var sharing (island plant reactive power sharing) ON ON

The set-point for voltage/reactive power/power factor is normally set internally, voltage as the nominal setting, var and power factor
set in specific settings.

Voltage.

No. Setting Min. setting Max. setting Factory setting


4010 Nominal settings Selection display - - -
4014 Nominal settings Generator voltage 100 V 25000 V 440 V

Reactive power/power factor.

No. Setting Min. setting Max. setting Factory setting


4040 Controller Selection display - - -
4042 Controller var 0.0% 100.0% 30.0%
4043 Controller Power factor (inductive) 0.60 1.00 0.90

NOTE:
The 0…100% var relates to the nominal power (Pnom, setting 4012) of the generator, just to have a figure to relate to.

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 3 of 6
DESCRIPTION OF OPTION D1 AND D2
multi-line 2 4189340268B

2.2.2 Binary input selection of external set-point


The binary input called mode 6 (terminals 53 and 56) can be used to activate the use of an analogue input as reference.

The set-point input is terminal 42(+) and 41(-), and the signal level is +/-10 VDC.

Mode Mode 6 (terminal 51) ON


Fixed voltage (stand-alone generator) +/-10 VDC input ~ nominal voltage +/-10%
Fixed var (fixed reactive power) 0…10 VDC input ~ 0…100% reactive power *
Fixed PF (fixed power factor) 0…10 VDC input ~ 1…0.6 inductive PF
var sharing (island plant reactive power sharing) +/-10 VDC input ~ nominal voltage +/-10%

* NOTE:
The 0…100% relates to the nominal power (Pnom, setting 4012) of the generator, just to have a figure to relate to.

2.2.3 Voltage control


Voltage deadband % setting is only relevant for voltage control relay outputs and relates to nominal generator voltage. If analogue
output is used, the deadband setting is ignored.

No. Setting Min. setting Max. setting Factory setting


2190 Voltage control Selection display - - -
2191 Voltage control Deadband 0.0% 10.0% 0.2%
2192 Voltage control U KP 0 1000 250
2193 Voltage control U KI 0 1000 160

2.2.4 var controller


var deadband % setting is only relevant for voltage control relay outputs and relates to nominal generator power value, i.e. it is
assumed that the generator var value is the same as the kW value. This is not correct, but the assumption is made for control
purposes only. If analogue output is used, the deadband setting is ignored.

No. Setting Min. setting Max. setting Factory setting


2200 var control Selection display - - -
2201 var control Deadband 0.0% 10.0% 0.2%
2202 var control Q KP 0 1000 250
2203 var control Q KI 0 1000 160

2.2.5 Power factor (PF) controller


PF control is being carried out using the var control settings.

2.2.6 Relay control


This setting is used to tune in the GOV/AVR ON time when relay outputs are being used for control. The total relay ON time will
depend on the deviation from the set-point. tN is the minimum time the relay can be activated. This is further described under PI
controller in the Designers Reference Handbook.

No. Setting Min. setting Max. setting Factory setting


2250 Relay control Selection display - - -
2253 Relay control AVR ON time tN 10 ms 3000 ms 100 ms
2254 Relay control AVR per. time tP 50 ms 15000 ms 500 ms

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 4 of 6
DESCRIPTION OF OPTION D1 AND D2
multi-line 2 4189340268B

2.2.7 Synchronising window, enabling and disabling of synchronising

No. Setting Min. setting Max. setting Factory setting


2050 Sync. window Selection display - - -
2051 Sync. window Set-point +/- 2.0% 20.0% 15.0%
2052 Sync. window Delay 0.1 s 2.0 s 0.5 s
2053 Sync. window Output A R0 (none) R15 (relay 15) R0 (none)
2054 Sync. window Output B R0 (none) R15 (relay 15) R0 (none)
2055 Sync. window Enable OFF ON OFF

The function deactivates the synchronisation if the voltage level on the busbar is out of range according to the nominal generator
voltage. The purpose of the delay function is that a short intermittent voltage dive does not block the synchronising.

Even though the maximum output setting is R15, the setting is limited by the options selected. An alarm will be displayed if a wrong
relay is chosen.

This function is mainly used with a relay configured as a limit contact. This is done in the system setup channels 4600 to 4730.

2.2.8 Governor/AVR regulation failure


These alarm functions are activated when the “Start sync./control” input (terminal 25) is ON. The alarms are activated if the difference
between the measured value and the set-point is out of the alarm deadband.

No. Setting Min. setting Max. setting Factory setting


2180 Governor reg. failure Selection display - - -
2181 Governor reg. failure Deadband 1.0% 100.0% 30.0%
2182 Governor reg. failure Timer 10.0 s 360.0 s 60.0 s
2183 Governor reg. failure Output A R0 (none) R4 (relay 4) R2 (relay 2)
2184 Governor reg. failure Output B R0 (none) R4 (relay 4) R2 (relay 2)

No. Setting Min. setting Max. setting Factory setting


2230 AVR reg. failure Selection display - - -
2231 AVR reg. failure Deadband 1.0% 100.0% 30.0%
2232 AVR reg. failure Timer 10.0 s 360.0 s 60.0 s
2233 AVR reg. failure Output A R0 (none) R4 (relay 4) R2 (relay 2)
2234 AVR reg. failure Output B R0 (none) R4 (relay 4) R2 (relay 2)

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 5 of 6
DESCRIPTION OF OPTION D1 AND D2
multi-line 2 4189340268B

2.3 multi-line 2 GPU option D2 + G2


To enable the option D2 (fixed voltage/voltage synchronisation), the option G2 (synchronising) must also be chosen.

2.3.1 Voltage control


Voltage deadband % setting is only relevant for voltage control relay outputs and relates to nominal generator voltage. If analogue
output is used, the deadband setting is ignored.

No. Setting Min. setting Max. setting Factory setting


2190 Voltage control Selection display - - -
2191 Voltage control Deadband 0.0% 10.0% 0.2%
2192 Voltage control U KP 0 1000 250
2193 Voltage control U KI 0 1000 160

2.3.2 Synchronising window, enabling and disabling of synchronising

No. Setting Min. setting Max. setting Factory setting


2050 Sync. window Selection display - - -
2051 Sync. window Set-point +/- 2.0% 20.0% 15.0%
2052 Sync. window Delay 0.1 s 2.0 s 0.5 s
2053 Sync. window Output A R0 (none) R15 (relay 15) R0 (none)
2054 Sync. window Output B R0 (none) R15 (relay 15) R0 (none)
2055 Sync. window Enable OFF ON OFF

The function deactivates the synchronisation if the voltage level on the busbar is out of range according to the nominal generator
voltage. The purpose of the delay function is that a short intermittent voltage dive does not block the synchronising.

Even though the maximum output setting is R15, the setting is limited by the options selected. If e.g. the option D1 is selected, it is not
possible to use the AVR relays 10 and 11. An alarm will be displayed if a wrong relay is chosen.

This function is mainly used with a relay configured as a limit contact. This is done in the system setup channels 4600 to 4730.

2.3.3 Governor/AVR regulation failure


These alarm functions are activated when the “Start sync./control” input (terminal 25) is ON. The alarms are activated if the difference
between the measured value and the set-point is out of the alarm deadband.

No. Setting Min. setting Max. setting Factory setting


2180 Governor reg. failure Selection display - - -
2181 Governor reg. failure Deadband 1.0% 100.0% 30.0%
2182 Governor reg. failure Timer 10.0 s 360.0 s 60.0 s
2183 Governor reg. failure Output A R0 (none) R4 (relay 4) R2 (relay 2)
2184 Governor reg. failure Output B R0 (none) R4 (relay 4) R2 (relay 2)

No. Setting Min. setting Max. setting Factory setting


2230 AVR reg. failure Selection display - - -
2231 AVR reg. failure Deadband 1.0% 100.0% 30.0%
2232 AVR reg. failure Timer 10.0 s 360.0 s 60.0 s
2233 AVR reg. failure Output A R0 (none) R4 (relay 4) R2 (relay 2)
2234 AVR reg. failure Output B R0 (none) R4 (relay 4) R2 (relay 2)

Errors and changes excepted

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 6 of 6