multi-line 2 – version 2
4189340269A

E1: Analogue controller outputs


DEIF A/S

DEIF A/S Tel.: +45 9614 9614


Frisenborgvej 33, DK-7800 Skive Fax: +45 9614 9615
Denmark E-mail: deif@deif.com
DESCRIPTION OF OPTION E1
multi-line 2 4189340269A

INDEX:

1 Warnings and legal information ......................................................................................................................................... 3


2 Terminal description: GPU, GPC, PPU .............................................................................................................................. 3
2.1 Slot #4, analogue output........................................................................................................................................................ 3
3 Functional description ........................................................................................................................................................ 3
3.1 Slot #4, analogue controller output........................................................................................................................................ 3
3.2 Controller functionality ........................................................................................................................................................... 4
3.2.1 Analogue output offset........................................................................................................................................................... 4
4 General data......................................................................................................................................................................... 4
4.1 Technical specifications ........................................................................................................................................................ 4

This manual is valid for standard multi-line 2 PPU/GPU/GPC units with firmware version 2.00.0 or later.

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 2 of 4
DESCRIPTION OF OPTION E1
multi-line 2 4189340269A

1 Warnings and legal information


This manual gives guidelines for the use and installation of the DEIF multi-line 2 units. It is, however, not a complete installation
instruction. Therefore, even if terminal numbers may be shown in the drawings, these are to be used as guidance only.

Installing and operating the multi-line 2 units implies work with dangerous currents and voltages, and therefore only
qualified personnel should do it.

During the installation care must be taken to protect the terminals against static discharges. Once the units are installed and
connected, these precautions are no longer necessary.

DEIF takes no responsibility for operation or installation of the generator set. If there is any doubt about how to install or
operate the system on which the multi-line 2 unit is measuring, the company responsible for the installation or the operation
must be contacted.

2 Terminal description: GPU, GPC, PPU

2.1 Slot #4, analogue output


Slot #4 is used for either transducer outputs or governor/AVR outputs.

The analogue outputs are active outputs, i.e. they use the internal power supply. The outputs are galvanically separated from each
other and the rest of the unit.

Term. Function Description


65 Not used
66 +/-20 mA out Speed governor set-point output
67 0
68 Not used
69 Not used
1
70 +/-20 mA out AVR voltage set-point output
71 0
72 Not used
1
NOTE :
Voltage control set-point to AVR is an option (option D).

If a combination of analogue signals and relay signals is needed, option EF4 is to be used instead of option E1.

3 Functional description

3.1 Slot #4, analogue controller output


The current outputs can, if needed, be converted to voltage using a resistor across the terminals (250 Ω will convert the +/-20 mA into
+/-5 VDC). Refer to the document “Interfacing DEIF equipment to governors and AVRs” for information about interfacing.

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 3 of 4
DESCRIPTION OF OPTION E1
multi-line 2 4189340269A

3.2 Controller functionality


The controller functionality of the multi-line 2 is described in the basic handbook of the GPC/GPU/PPU.

3.2.1 Analogue output offset


In addition to the controller parameters described in the basic handbook this additional setting can be used. The purpose of this
setting is to give the analogue output an offset value.

100% = -20 mA
100% = 20 mA

No. Setting Min. setting Max. setting Factory setting


2160 Analogue offset Selection display - - -
2161 Analogue offset Offset -100% 100% 0%

4 General data

4.1 Technical specifications


Accuracy: Class 1.0 according to IEC 688

Operating temperature: -25…70°C

Galvanic separation: Between AC voltage, AC current and other I/O’s: 3250 VAC – 50 Hz – 1 min. Between analogue outputs:
500 VDC – 1 min.

Climate: HSE, to DIN 40040


2 2
Connections: 4 mm multi stranded for AC currents, all others 2.5 mm multi stranded

Protection: Case: IP40


Terminals: IP20
Operator panel: IP52 (IP54 when mounted with gasket)
To IEC 529 and EN 60529

Errors and changes excepted

DEIF A/S • Tel.: +45 9614 9614 • Fax: +45 9614 9615 • E-mail: deif@deif.com Page 4 of 4