Document SINCOR C.A.

: CA02-10-31-P-CN-001
Document OTEPI S.A.:
TEMPORARY FACILITIES
ELECTRICAL
PANELBOARD SHEET

Prepared by: Alberto Henriquez Rev : Preliminar


Checked by: J. Alberto Alves Date: 03 Feb 99
Panelboard: DPGR FEEDER CONNECTED LOAD (kVA): 23.54
Type: NLAB424AB100 Phases: 3-1/C #2/0 AWG VOLTAGE Lighting demand (100%): 3.34
Nº de Circuits: 24 Neutral:1-1/C #2/0 AWG (V) Outlet demand (70%): 3.64
Installation: EMBEDDED Ground: 1-1/C #6 AWG 208 Hydrop. demand (50%): 7.50
Bus capacity (A): 225 Conduit: 2" CURRENT
Short-circuit capacity (kA rms): 10 See DWG. No.: (A) SPARE (20%): 2.90
Main breaker (A): 100 48.28 MAX. LOAD (kVA): 17.37
R S T
LOADS LOADS
VA Description # Cable Prot. Nº Nº Prot. # Cable Description VA
2000 GENERATOR AREA LIGHTING # 12 AWG 20A 1 2 20A # 12 AWG RECEPTACLES 120V. 1000
1112 SWITHGEAR AREA LIGHTING # 12 AWG 20A 3 4 20A # 10 AWG RECEPTACLES 2100
25 EMERGENCY LIGHTING # 12 AWG 20A 5 6 20A # 10 AWG 208V, 2 PHASES 2100
SPARE 20A 7 8 20A # 8 AWG BOMBA DE 2500
SPARE 20A 9 10 20A # 8 AWG COMBUSTIBLE 2500
200 FIRE PANEL # 12 AWG 20A 11 12 20A # 8 AWG B-D-01 A 2500
SPARE 20A 13 14 20A # 8 AWG BOMBA DE 2500
SPARE 20A 15 16 20A # 8 AWG COMBUSTIBLE 2500
SPARE 20A 17 18 20A # 8 AWG B-D-01 B 2500
SPACE 19 20 SPACE
SPACE 21 22 SPACE
SPACE 23 24 SPACE
Phase R: 8.00 kVA Lighting load (kVA): 3.34
Phase S: 8.21 kVA Neutral Outlet load (kVA): 5.20
Phase T: 7.33 kVA Ground Pumps (kVA): 15.00
Connected load (kVA): 23.54

Notes:
- Branch circuit breakers are Westinghouse type HQP or similar.
- Main breaker are Westinghouse type FDB or similar.
- A permanent circuit directory shall be provided on each panelboard.

Arch: 551511949.xls ; hoja: DPGR


Arch: 551511949.xls ; hoja: DPGR