Data Sheet for Design and Manufacture of Liquid-Immersed Power Transformers
of 500 kVA through 10,000 kVA up to 34.5 kV High Voltage Winding

Client PDVSA Engineering Org.       Spec. No. BE-88919


Project Title GAS-ANACO Location San Joaquin Date Jun. 03, 2003
Project Location ANACO Contract No       Equip. No.      
Proj. No. FS0127 Specifier Name       Tele. No.      
P.O. No.      
Refer to Specification No. ELSTR01 For General Requirements
Applicable State & Local Codes:      

Data Provided By  Buyer  Bidder With Proposal  Seller After Order


Site Conditions: Accessories:
Altitude 3300 Ft Seismic Zone 4
Current Transformers (per Section 5.7.2)
Ambient Temperature: Max 40 C Min 15 C
Other unusual conditions:      
H.V. Quantity       Ratio       Acc.Class      
Rating : L.V. Quantity       Ratio       Acc.Class      
OA Rating KVA (as per Section 5.1.2) Quantity Ratio
      Neutral 1 600/5 Acc.Class      
Other Dissolved Gas Monitor (as per Section 5.7.4)
Sudden Pressure Relay (as per Section 5.7.5)
System parameters and Windings: Alarm/Auxiliary Relay Control Voltage 120 Volts
High Voltage 13.8 kV 3 Phase 60 Hertz
Delta Wye Insulating Liquid and Preservation System (per Section 6):
Solidly Grounded Resistance Grounded Ungrounded Mineral Oil (Type II as per ASTM D3487-88) (as per Section 6.1.2)
Copper Other       Other PURAMIN AD66 (as per Section 6.1.3)
Low Voltage 0.48 kV 3 Phase 60 Hertz Sealed Tank System with Purge Nozzle and Shutoff Valve
Delta Wye Inert Gas Pressure System (as per Section 6.2.2)
Solidly Grounded Resistance Grounded Ungrounded
Copper Other       Special Requirements:
Transformer will supply Single Large Motor as Follows:
Impedance: Standard (as per Section 5.1.11) Other 5.75 HP       Voltage       Full Load       Amps
Bushing Location and Connection Method: Locked Rotor       Amps Acceleration Time       Seconds
High Voltage Line Top Mounted Air Terminal Chamber Other      
Flanged Throat Other  Test as listed in this Practice Witnessed Not Witnessed
Witnessed
     
High Voltage Neutral Temp Rise Lightning Impulse Temp Switching Impulse
 Switching
Impulse
 Lightning
Impulse
 Switching
Top Mounted Air Terminal Chamber Impulse
Flanged Throat Other       Front of Wave Radio Influence Voltage
Low Voltage Line Top Mounted Air Terminal Chamber Audible Sound Level Mechanical Pressure Test
Flanged Throat Other       Other ANSI Routing test
Low Voltage Neutral Top Mounted Air Terminal Chamber
Flanged Throat Other       Documentation:
 Electronic Document Format .dxf Other      
Space Heaters in Air Terminal Chambers: Seller to provide:
Thermostats Required Not Required 3 no. of copies of all documentation plus
3 no. of copies of the operating manuals.
Cooling Fans:
Voltage 460 Volts Remote Contact (as per Section 5.5.11) Efficiency Considerations (per Section 5.2):
Fan Failure Alarm Required (as per Section 5.7.3) Seller Shall Optimize Efficiency Based on:
Other       Average Load: %     Other %    
Load (Copper) Losses: US$ / kw:      
Alarm and Monitoring: Core (Iron) Losses: US$ / kw:      
Voltage 120 Volts
Other Requirements:
Note 1.- Blank Space to be completed by Vendor
     
     