TECHNICAL REQUIREMENTAND GUARANTEE SCHEDULEFOR OLTC

TYPE 33/11.55kV 10/14 MVA POWER TRANSFORMERS


Date: 01.04.2019
sDescription Unit REB Requirement Bidders Guaranteed
Values
1. Manufacturer’s Name Required Danish Private Limited
2. Manufacturer’s Address Required Jaipur, India
3. Applied Standard Required IEC 60076
4. Type Outdoor Oil immersed Outdoor Oil immersed
(a) Rated power MVA ONAN/ONAF 10/14 ONAN/ONAF 10/14 MVA
MVA three phase three phase
5. Overload capability In Accordance with IEC As per IEC 60354
603564
6. Number of Phase Three Three
7. Rated Voltage, Phase to phase Required 33/11.55 KV
High Voltage Winding KV 33 33
Low voltage Winding KV 11.55 11.55
8. Rated Frequency Hz 50 50
9. Rated Insulation level Required In accordance with
IEC 60076
a. Impulse withstand, full wave
High voltage Winding KV 170 170
Low Voltage Winding KV 75 75
Neutral side Full Insulation Full Insulation
b. (b) AC withstand Voltage
High voltage Winding KV 70 70
Low Voltage Winding KV 28 28
10. Vector diagram (IEC-76-4) Dyn1 Required Dyn1

11. Type Of Cooling ONAN/ Required ONAN/ONAF


ONA
F
12. On Load tap Changer MR Required On Load tap Changer MR
Germany/ABB Sweden with vacuum Germany/ABB Sweden
Switches with Oil switch type
Type Required Oil Switch type
Rated Capacity In Amps Required 200 A
Rated Tap KV 33 33
Tap range % -18 to +6 -18 to +6
Numbers of Tap Taps 17 17
Tap Step % 1.5 1.5
Location of tap Primary Side Primary Side
Rated Short time current KA Required 4 kA/3sec.
Oil volume Liter Required 125 Ltr. Approx.
Duration of one step change Sec Required 5.4 Sec Approx.

F-679, 680, G-694Sitapura Industrial Area, JAIPUR, 302022 INDIA


Tel.# 91-141-5164500 Fax # 91-141-5164501 Email: sales@danish.co.in Web: www.danish.co.in
Page 1 of 5
Motor rating KW Required 0.75 KW
13. Impedance voltage at 75º C and at 8% (with
nominal ratio and 100% rated power tolerance Required 8% (with tolerance of
at principal tap (with Tolerance of of +10%)
+10%) +10%)
14. Temperature Rise at rated power Required
(max. ambient temperature: 40º C)
Oil by thermometer Deg C. 55 55
Winding by resistance measurement Deg C. 60 60
Winding hot spot temperature on Deg C. 140 140
emergence overload
Maximum hotspot temperature when Deg C. 118 118
loaded in
15. System symmetrical fault level as KA
terminal of
33 KV KA 31.5 31.5
11KV 31.5 31.5
Duration of symmetrical short sec 2 2
circuit current for which the
transformer is to be designed
16. Transformer core: Type of core,
max. flux density At nominal Tesla ≤ 1.6 ≤ 1.6
voltage
17. Transformer Bushings
(a) H.V. Bushing
Voltage Class Required 36 KV
Cantilever Strength Required As per IEC 60137, vertical
mounting
Transformer Bushing HV CT Required Yes
Current Ratio A 400/5 400/5
Rated Burden VA 20 20
Accuracy 5P20 5P20
(b)
a. L.V Bushing
Voltage
b. class Required 12 KV
Cantilever
c. Strength Required As per IEC 60137, vertical
Mounting
Transformer
d. bushing LV CT Required Yes
(c)
e. Neutral Bushing
Voltage
f. glass Required 12 KV
Cantilever
g. strength Required As per IEC 60137, vertical
Mounting
18. Conservator Required Yes, conservator type
19. Auxiliary circuit voltage for fan, etc, V 415/240 AC 415/240 AC
3pahse – 4 wire
20. Control voltage V 110 DC 110 DC
21. Sound Level (IEC 60551)
ONAN (0.3m) dB Required ≤ 75

F-679, 680, G-694Sitapura Industrial Area, JAIPUR, 302022 INDIA


Tel.# 91-141-5164500 Fax # 91-141-5164501 Email: sales@danish.co.in Web: www.danish.co.in
Page 2 of 5
ONAF (2 m) dB <80 ≤ 80
22. Transformer Bushing CT
HV Side
On phase “a, b & c” (Differential)
- Current Ratio A 400/5 400/5
- Rated Burden VA 20 20
- Accuracy 5p20 5P20
- Short Time current Required 25kA/3sec.
LV Side
On phase “a, b & c”
- Current Ratio A 1200/5 1200/5
- Rated Burden VA 20 20
- Accuracy 5p20 5P20
- Short Time current Required 25kA/3sec.
On Phase “a” (OLTC)
- Current Ratio A 1200/5 1200/5
- Rated Burden VA 20 20
- Accuracy 5P20 5P20
- Short Time current kA Required 25kA/3sec.
On Phase “b” (WTI)
- Current Ratio A 1200/5 1200/2
- Rated Burden VA 20 20
- Accuracy Class 5P20 Class 5P20
- Short Time current kA Required 25kA/3sec
Neutral Bushing CT for REF:
- Current Ratio A 1200/5 1200/5
- Rated Burden VA 20 20
- Accuracy Class 5p20 5P20
Neutral Bushing CT for stand by
earth fault
- Current Ratio A 1200/5 1200/5
- Rated Burden VA 20 20
- Accuracy Class 5P20 5P20
- Short Time current KA Required 25kA/3sec
23. Number of cooling fan Nos. Required 8 No. (6 Nos. running + 2
Nos. stand by)
24. Rating Fan motors kW Required 0.25 KW
25. Cooling fan losses at full ONAF kW Required+2 1.5 kW approx.
capacity operation
26. Core loss at rated frequency and kW Required 5.95 kW
rated voltage at nominal tap
27. Copper Loss at full load, at rated Required
frequency and at 75 º C
(i) At ONAN
(a) At Maximum Tap kW Required 43.25 kW

F-679, 680, G-694Sitapura Industrial Area, JAIPUR, 302022 INDIA


Tel.# 91-141-5164500 Fax # 91-141-5164501 Email: sales@danish.co.in Web: www.danish.co.in
Page 3 of 5
(b) At Nominal tap kW Required 43.30 kW
(b) At minimum Tap kW Required 57.00 kW
(ii)
a. At ONAF
(a)At
b. Maximum Tap Required 86.5KW
(b)At
c. Nominal Tap Required 95KW
(c)At
d. Minimum Tap Required 114KW
28. Exciting current at nominal Tap and A Required 7.87 at 10 MVA
rated voltage
29. Dimensions and Weight Required
Maximum size for transport (L X W mm Required 4260 x 2000 x 3365 mm
X H) approx.
Heaviest weight for transport Kg Required 19500 Kgs approx.
Overall height mm Required 3365mm approx
Oil volume Liter Required 6400 Ltrs approx.
Weight of Oil Kg Required 5120 Kgs approx.
Weight of core Kg Required 6880 Kgs approx.
Total weight Kg Required 23725 Kgs approx.
30. Oil level indicator
Type and model Required Maier/ABB/MR
31. Pressure relief device
Type and model Required Maier/ABB/MR
32. Buchholz relay
Type and model Required MR/ABB
Float type
Petcock is provided for testing by Yes Yes
injecting air
Pipe arrangement for gas release Yes Yes
and oil collection from ground
level.
Oil surge protection Yes Yes
Oil drain screw provided Yes Yes
33. Oil and winding temperature
Indicator
Type and model Required ABB comenitaly / ABB
Elmek Turkey / Maier
34. Efficiency at 75Deg C & Unity
power factor
a) At 14MVA Load % Shall be Provided 99.33% (Normal Tap)
b) At 10MVA Load % Shall be Provided 99.51% (Normal Tap)
35. Transformer Tank Shall be Shall be high tensile steel Yes
Provided plate
36. Pressure release device for both Shall be Provided Ye
main and OLTC Tank
37. Winding shall be electrolytic copper Shall be electrolytic Yes
copper
38. Pressure release device, temperature Shall be Shall be from MR Yes

F-679, 680, G-694Sitapura Industrial Area, JAIPUR, 302022 INDIA


Tel.# 91-141-5164500 Fax # 91-141-5164501 Email: sales@danish.co.in Web: www.danish.co.in
Page 4 of 5
indicating device and bucholz relay provided Germany or Equivalent
shall be from MR Germany and Europe origin
Equivalent Europe origin
39. Manual Shall be Provided Yes, provided