Summary
1 80%
Lower minimum 60%
load …
… saves fuel 40%
(costs) and CO2 3
emissions 20% Early start-ups…
will cover residual
0% demand best
Without increased flexibility
With increased flexibility
2
Lower minimum load (instead of no load) …
… saves start-up costs and contributes to grid stability
Criteria
– Existing plants in Germany with
sufficient remaining life time
– Sufficient data available
– Hard coal and lignite
Targets
Building of the stationary and dynamic overall system models
Integration of thermal storages into the power plant process
Simulations of several strategies/measures to increase the power plant flexibility
(minimum load reduction, increasing load change rates, etc.)
Applicability of the results to existing and new power plants
10 6 8 9 1
Dampferzeuger 2
7 5
11 3 4
100%
load reduction minimum load load increase
90%
80%
Power output [%]
70%
60%
50%
40%
Measurement power output
30%
Simulation power output
20%
0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 8:00
Targets
Development of technical solutions to reduce minimum boiler load
Higher load ramp up/down rates can be achieved by installation of an indirect firing
system
Benefits:
Shorter inspection times (up to 50 %)
Summary
Due to the remaining residual load security of supply on the basis of renewable
energy sources (RES) is technically not feasible in the next decades
Use of the existing fleet of thermal power plant capacity is an efficient solution to
support an increased share of RES