Professional Documents
Culture Documents
se/std-601652
INTERNATIONAL
STANDARD
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION l EXAYHAPOAHA5I OPTAHW3AIJWII II0 CXAH&U’TW3ALUiH.ORGANISATION INTERNATIONALE DE NORMALISATION
Descriptors : aircraft, aircraft equipment, electrical cables, joints, mechanical crimping, specifications, tests.
FOREWORD
It was approved in May 1970 by the Member Bodies of the following countries :
France
U.S.A.
Printed in Switzerland
This preview is downloaded from www.sis.se. Buy the entire standard via https://www.sis.se/std-601652
1 SCOPE AND FIELD OF APPLICATION 2.5 cable splice connection : A permanent connection
formed by the ends of electrical cable conductors attached
1.1 This International Standard specifies the design to a cable splice.
requirements (and tests) for the crimping of insulated and
non-insulated terminations to general purpose electrical 2.6 crimping : A method of firmly attaching a terminal
cables for aircraft, with conductors of copper, copper alloy, end or cable splice to a conductor by re-shaping the barrel
aluminium or aluminium alloy, in locations in which the around the conductor to establish good electrical and
stabilized conductor temperature does not exceed the mechanical contact.
values specified for the relevant type of cable, i.e. 105 OC,
190 “C or 260 o C. The type of cable with which the 2.7 insulation grip : That part of a terminal barrel or cable
terminations are intended to be made has to be declared splice barrel into which the insulation of the cable is placed,
(see 3.1.5). and which by reforming grips the insulation.
1.2 The International Standard also contains 2.8 pre-insulated joint : A crimped connection formed
recommendations relating to the inspection of such with an insulated terminal end or insulated cable splice.
connections and the tools used to perform the crimping
operation. Since satisfactory crimping is dependent upon 2.9 post-insulated joint : An uninsulated crimped con-
the maintenance and setting of tools it also contains nection insulated after conductor crimping.
recommendations for tests to confirm their serviceability.
2.10 crimping tool : A manually operated or
1.3 Testing of crimped joints to assess their suitability for power-operated mechanical device for making a crimp or
aircraft shows that certain environmental conditions, for insulation grip.
example vibration, have no significant effect on the
performance of the joints. It has therefore not been
2.11 positioner : A locator, turret or other device
considered necessary to provide for such tests in this
permanently or removably attached to a crimping tool,
International Standard.
serving correctly to locate and control the position of the
crimp on the barrel.
2 DEFINITIONS
3 DESIGN REQUIREMENTS
2.1 termination : A permanent connection formed by the
end of an electrical cable conductor with a terminal end or 3.1 General
a pin or socket contact.
3.1.1 Terminal ends, pin or socket contacts and cable
2.2 terminal end : A connecting device with barrel(s) splices shall comply with the requirements of the
accommodating an electrical cable conductor with or appropriate national and international standards.
without additional provision to accommodate and secure
the insulation. 3.1.2 The protective treatment and surface finish of the
terminal end, pin or socket contact or cable splice shall be
2.3 pin or socket contact : A contact used in a plug or of such a quality that the completed crimped connection
socket (receptacle) with a barrel at one end to accommo- complies with the requirements of this International
date an electrical cable conductor with or without ad- Standard. The electrochemical potential difference between
ditional provision to secure the insulation. all conducting surfaces should not exceed 0,25 V.
2.4 cable splice : A connecting device with barrel(s) each 3.1.3 The design of the terminal end, pin or socket
accommodating an electrical cable conductor(s) with or contact or cable splice shall be such that adequate
without additional provision to accommodate and secure engagement of the cable conductor in the completed joint
the insulation. can be readily established by inspection.
1
This preview is downloaded from www.sis.se. Buy the entire standard via https://www.sis.se/std-601652
lSO1966-1973(E)
3.1.4 Any material used for pre- or post-insulation shall be 3.3.2 Tools shall be marked with the manufacturers name
non-corrosive, resistant to abrasion, fungus and aircraft and serial number. Dies for a particular tool should be
fluids and shall not support combustion. The insulation, interchangeable with other tools of that type. If they are
and internal sleeve if any, shall remain firmly fixed in its not interchangeable they shall be marked to identify the
correct position before and after crimping. The insulation tool for which they are suitable.
should be colour-coded in respect of its conductor size or
sizes in accordance with the relevant national standards. 3.3.3 The gauging method of tools and dies shall be
declared, and provision may be made for the use of test
3.1.5 The manufacturer shall make the following gauges or test bars.
information available :
2
This preview is downloaded from www.sis.se. Buy the entire standard via https://www.sis.se/std-601652
ISO1966-1973 (E)
8.2.5 The tests shall be made in the order shown in 8.4 Voltage drop test
Table 1 on sixteen specimens. If the tests in 8.5 and 8.6 are
made consecutively on the same specimens, eight specimens 8.4.1 The appropriate test current stipulated in Table 2 or
only are necessary. 3 at an open circuit voltage of not more than 30 V shall be
passed through the specimen. For type tests, precision class
measuring instruments shall be used.
TABLE 1 - Test sequence and number of specimens
for tests in clauses 8.3 to 8.7 8.4.2 For terminations other than pin or socket contacts
the voltage drop shall be measured between the intersection
Number of spec- of one palm and barrel and the corresponding point on the
Clause Test
imens for tests other terminal end, care being taken to avoid contact with
the conductor strands. For pin or socket contacts the
8.3 Inspection 1 to 16 measurement shall be taken between the intersection of the
8.4 Voltage drop 1 to16 shoulder and the crimped barrel of the pin or socket
8.5 Climatic lto 8 contacts. For cable splices, the measurement shall be
between the midpoints of two consecutive connectors. (See
8.6 Load and 9tol6
Figure 1.)
temperature cycling
Specimens shall be nu mbered on an area not involved in the 8.5.1 The specimens shall be subjected to the tropical
crimping 0 peration. exposure test described in IS0 . , ..’ )
8.2.7 The number of items to be tested in accordance with 8.5.2 Upon completion of the tests the specimen shall be
8.8 and 8.10 shall be as stated in the appropriate clause. examined and any visible signs of corrosion or other
The attached cable may be of any suitable length. damage shall be reported to the approving authority.
1) In preparation.
This preview is downloaded from www.sis.se. Buy the entire standard via https://www.sis.se/std-601652
ISO1966-1973 (E)
8.5.3 The specimens shall be subjected to the voltage drop Each end of the specimen shall be tested to destruction and
test as specified in 8.4. Any significant increase in reading shall not fail below the relevant load specified in ‘i*able 2
shall be reported to the approving authority. or 3.
8.5.4 At the conclusion of the climatic test cycles on 8.8 Insulation grip tests
insulated joints, the specimens shall be removed from the
Sixteen unstripped cables, of length not less than lO1,6 mm
chamber and allowed to recover at normal temperature and
(4 in), of the maximum and minimum size appropriate to
pressure. Within a period of l l/2 to 2 h the insulation
each size of insulation grip, shaL be fitted to the
resistance at 500 V d.c., measured between the exterior of
appropriate terminal ends or cable splices. The cable shall
the insulation and the palm, shall be not less than 100 Ma.
be inserted only into the insulation grip portion of the
terminal end and a crimp effected in the normal manner.
8.6 Load and temperature cycling tests Using a mandrel with a diameter equal to that specified for
the flexibility tests for the relevant type ant; eize of cable,
8.6.1 The specimens shall be placed in a suitable
each termination shall be tested as follows. With the
enclosure, the ambient temperature of which shall be the
termination or cable splice held tangential to the mandrel,
upper ambient limit implied by the relevant cable
and the cable end of the barrel in contact with it, the cable
specification, i.e. 65 OC, 150 ‘6 or 220 “C. 1 )
shall be wound round the mandrel at least one turn.
Tension shall be applied to the cable sufficie :t to keep it in
8.6.2 The appropriate test current stated in Table 2 or 3,
contact with the mandrel. This test shai; be mad2 in
as applicable, shall be applied to the “heat-on” period.*)
opposite directions in planes parallel to th..; axis of the
The time period of the “heat-on” cycle shall be such that crimp and mutually perpendicular. The com@tite test shall
not less than 95 % of the maximum temperature rise above be made twice, and the insulation shall not be punctured
the upper ambient limit, measured at the centre of the and shall remain in position in the insulation grip. (See
conductor, is attained for every size and type of cable being Figure 2.)
tested,
8.9 Tensile tests on conductor crimp alone
The enclosure heat and the applied current shall then be
removed from the specimens for a “heat-off” period, during For those types of terminations and cable splices having an
which the specimens shall cool to a temperature less than insulation grip, sixteen specimens shall be made of each and
30 Oc.3) - every combination of crimped barrel, conductor, tool, die
indenter or positioner required by 8.2 but using the
One cycle shall consist of a “heat-on” period followed by minimum size of conductor only,
a “heat-off” period.
The insulation grip shall be rendered ineffective by
8.6.3 Voltage drop readings shall be taken, with the cables removing the cable insulation. The specimens shall then be
at a temperature of not more than 30 OC, at intervals tested in accordance with 8.7,
throughout a test comprising not less than 1 500 cycles.
8.10 Additional tests for insulated joints
Readings shall be taken every 100 cycles during the first
1 000 cycles and subsequently at every 50 cycles, provided 8.10.1 Samples
that if instability is shown at any time during the test more
frequent readings are taken. During the last 500 cycles, or For the purposes of the tests described in 8.10.2 to 8.10.5,
as otherwise agreed with the approving authority, there sample crimped joints shall be made on each and every .
shall be no significant increase in the reading. combination of barrel type and size, crimped to a minimum
size of cable conductor, by each type of tool, die, indenter
8.6.4 Intermediate and final voltage drop readings per or positioner.
crimped joint shall not exceed 150 % of the relevant
maximum voltage drop figure listed in Table 2 or 3. 8.10.2 Fluid resistance
2) The enclosure ambient temperature may have a tolerance of + 5 “C from the values stated.
2) The time period may vary between different batches of sim ilar size and type of cable, and this should be hed minary
on a sample of the cable being tested, to the satisfaction of the a pprovin g authority.
3) Accelerated cooling is permissible.