Air conditioning systems lecture No.(2)part two
8) Next the fan is selected to suit the index run with the highest pressure
loss. Dampers are installed in all the duct runs to balance the total
pressure loss.
Equal friction method is simple and is most widely used conventional
method. This method usually yields a better design than the velocity method
as most of the available pressure drop is dissipated as friction in the duct
runs, rather than in the balancing dampers. This method is generally suitable
when the ducts are not too long, and it can be used for both supply and return
ducts. However, similar to velocity method, the equal friction method also
requires partial closure of dampers in all but the index run, which may
generate noise. If the ducts are too long then the total pressure drop will be
high and due to dampering, ducts near the fan get over-pressurized.
Ex. Calculate the dimensions of the main duct and branches using the
𝒑𝒂
equal friction method, let pressure drop is 𝟏
𝒎
Solution:
23
Air conditioning systems lecture No.(2)part two
section L Q ∆𝒑 V D
(m) (𝒎𝟑 /𝒔) (𝒑𝒂/𝒎) (m/s) (m)
A-B 30 8 1 10.5 0.98
B-C 15 7 1 10 0.93
B-E 30 1 1 3.7 0.18
C-F 15 3 1 8.3 0. 68
C-D 75 4 1 9 0.76
Fig.(2)
24
Air conditioning systems lecture No.(2)part two
Solution:
Length of duct(A − D) = 30 + 15 + 60 + 15 = 120m
∆𝑝𝑡 = (120 × 1 ) + 25 + 10 = 155𝑝𝑎
∆𝑝𝐴−𝐷 = ∆𝑝𝐴−𝐹 = ∆𝑝𝐴−𝐸
The loss A-C = 45pa
𝐿𝑜𝑠𝑠𝐶−𝐹 = 155 – 25 − 10 − 45 = 75𝑝𝑎
75 𝑝𝑎
𝑓𝑟𝑖𝑐𝑡𝑖𝑜𝑛 𝑙𝑜𝑠𝑠𝐶−𝐹 = = 5 ⁄𝑚
15
D = 0.47m 𝑣 = 15.5 𝑚⁄𝑠
25