Ministry of Higher Education Subject: A.C.

System Design
and Scientific Research Year: Four\ Air-conditioning &
University of Kufa Refrigeration Branch
Faculty of Engineering Time: Two Hours
Mechanical Engineering Department Examiner:Lec. Sahib Sh. Ahmed
Examination pipe design
(2020–2021)
Note: Attempt all questions

Q1- Draw the complete system with all components such as valves, fittings,
equipment and all other necessary accessories to design a piping system to supply
the chilled water for the six fan coil units as shown in figure (1). By using the attached
information in table below, two pipe system, reverse return pipe, water temperature
rise in the coil is 6.5 0C specific heat (4.19 KJ/kg.k), efficiency of the water pump
(80 %), and water pressure losses in the chiller (50 kpa) and in the cooling coil (15
kpa) also find the following:
1- The diameter of the pipe, water velocity and water pressure losses for each section
in the system.
2- Head pressure in H2O and power of pump.

The following loads are for each fan- coil


RSL RLL OASL OALL
11KW 4KW 2.5KW 1.5KW
Where RSL=Room Sensible Cooling Loads
RLL= Room Latent Cooling Loads
OASL=Outdoor Air Sensible Loads and OALL= Outdoor Air Latent Loads.

WITH MY BEST WISHES


2m
10m 15m

Fan-coil unit 5 Fan-coil unit 6

4m

Second floor

Fan-coil unit 3 Fan-coil unit 4

4m
Shaft

First floor

Fan-coil unit 1 Fan-coil unit 2

4m

Ground floor

Mechanical Room
Condenser
4m
Evaporator
Pump
Chiller

Figure (1)

WITH MY BEST WISHES