Code  Description 

ACP52TR  Model: EAC624-1S-DQ  This products manimum time 1


DESIGN PARAMETERS:  month after reciving work order
1) Refrigeration Capacity: 157,248 K.
Cal./Hr./182 KW (Nominal) 
2) Inlet/Output Water Temperature:
12°C/7°C 3) Minimum water flow through
Chiller: 520LPM 4) Air flow through
Condenser: 48,256 CFM 5)
Refrigerant(Gas): R134a 
6) Refrigeration Cooling Medium: Air 
7) Temperature Difference: 5°C at above flow
(nominal rating) 
8) Maximum Ambient Condition: 38°C 
9) Power Supply: 4 Wires, 3 Phases, 415V,
50 Hz 10) Power Consumption of Chiller:
65.7 KW 

MECHANICAL SECTION: 
1) Capacity of Each Compressor: 52TR 
2) Number of Refrigeration Circuit : 1 (one) 
3) Screw Compressor : Refcomp - Italy
(Assemble in China) 
4) Air Cooled Condenser: Aluminium-finned
copper tubing coil with axial flow suction through
fan –earnest 5) Evaporator: Copper Tubing in
CS Shell (Shell & Tube)-earnest 
6) Expansion Devices: Thermostatic Type – 
Emerson/Equivalent 
7) Filter/Dryer: Danfoss/Equivalent 
8) Flow Switch: Honeywell/Equivalent 

ELECTRICAL SECTION: 
1) Power Contractors, Thermal Overload
Relays Schneider 
2) Voltage Scanner (OV/UV/SPP/PS)-
Selec / Equivalent 
3) Temperature Controller With HMI : Sub-Zero-
India

ACP40TR Air Cooled Scroll Chiller


Model: EAC480-2L-BQ) DESIGN
PARAMETERS: 
1) Refrigeration Capacity: 1,20,960 K.
Cal./Hr./140 KW (Nominal) 
2) Output Water Temperature range: + 7°C to +
20°C 3) Minimum water flow through Chiller:
400 LPM 4) Air flow through Condenser: 36,000
CFM 5) Refrigerant(Gas): R407C 
6) Refrigeration Cooling Medium: Air 
7) Temperature Difference: 5°C at above flow
(nominal rating) 
8) Maximum Ambient Condition: 38°C 
9) Power Supply: 4 Wires, 3 Phases, 415V,
50 Hz 10) Power Consumption of Chiller:
48.6 KW 

MECHANICAL SECTION: 
1) Capacity of Each Compressor: 20 TR 
2) Number of Refrigeration Circuit : 2 (two) 
3) Scroll Compressor : Emerson - 
Copeland/Danfoss/Equivalent 
4) Air Cooled Condenser: Aluminium-finned
copper tubing coil with axial flow suction through
fan –earnest 5) Evaporator: Copper Tubing in
CS Shell (Shell & Tube)-earnest 
6) Expansion Devices: Thermostatic Type – 
Emerson/Equivalent 
7) Filter/Dryer: Danfoss/Equivalent 
8) Flow Switch: Honeywell/Equivalent 

ELECTRICAL SECTION: 

1) Power Contractors, Thermal Overload Relays


Schneider

2) Voltage Scanner (OV/UV/SPP/PS)- Selec /


Equivalent

3) Temperature Controller : Sub-Zero- India

ACP30TR Air Cooled Scroll Chiller (Model: EAC360-1L-BQ) This product ready Stock .
DESIGN PARAMETERS:
1) Refrigeration Capacity: 90,720 K. Cal./Hr./105 KW
(Nominal)
2) Output Water Temperature range: + 7°C to + 20°C
3) Minimum water flow through Chiller: 300 LPM
4) Air flow through Condenser: 27,000 CFM
5) Refrigerant(Gas): R407C
6) Refrigeration Cooling Medium: Air
7) Temperature Difference: 5°C at above flow (nominal
rating)
8) Maximum Ambient Condition: 38°C
9) Power Supply: 4 Wires, 3 Phases, 415V, 50 Hz
10) Power Consumption of Chiller: 24KW
MECHANICAL SECTION:
1) Capacity of Each Compressor: 30 TR
2) Number of Refrigeration Circuit : 1 (one)
3) Scroll Compressor : Emerson -
Copeland/Danfoss/Equivalent
4) Air Cooled Condenser: Aluminium-finned copper
tubing coil with axial flow suction through fan –earnest
5) Evaporator: Copper Tubing in CS Shell (Shell &
Tube)-earnest
6) Expansion Devices: Thermostatic Type –
Emerson/Equivalent
7) Filter/Dryer: Danfoss/Equivalent
8) Flow Switch: Honeywell/Equivalent
ELECTRICAL SECTION:
1) Power Contractors, Thermal Overload
RelaysSchneider
2) Voltage Scanner (OV/UV/SPP/PS)- Selec
3) Temperature Controller : Sub-Zero- India
COMMERCIAL TERMS & CONDITIONS

a) Price is up to Earnest Factory

b) VAT is included

c) Delivery: 10 to 15 days Working days from the Date of PO & Advance.

d) Mode of Payment: Through 60% Advance with work order, 40% products before product delivery
by Cash or Cheque in the

name of “Earnest Engineering Works (Pvt.) Ltd.

e) Offer Validity: One month from the date hereof.

f) Installation & Commissioning: Free of Cost Upto 3 days. If needed more days then charge will be
allow. Conveyance & food

expenses to be payable by the customer, at actual.

g) Warranty: Eighteen months from the date of dispatch or Twelve months from the date of
installation & commissioning *

(which subject is earlier),* against defective parts & workmanship - except consumables like
refrigerant gas, lubricant etc.

h) Brand: EARNEST, Country of Origin: Bangladesh

PROVISION TO BE MADE BY CUSTOMER

a) Electrical connection with Main Switch, Cables etc. to the Control panel.

b) All kind of pump, pipeline, Water storage Tank, Insulating Water line from Chilling Plant to
application point.
c) Our engineers food, accommodation and others

d) Machine Unload & Placement by customers own responsibility.

e) Any Civil & MS Construction Work.

f) And any others not covered in our scope of supply.

OVERALL SAFETY FEATURES

For Scroll Chiller

A) High-pressure & Low-pressure alarm

B) Current overload alarm

C) Over (OV), Under (UV) Voltage, Phase Sequence and Phase Loss Alarm

D) Antifreeze Alarm

E) Evaporator & Condenser Flow Switch alarm

F) High water inlet temp. alarm

SPECIALTY OF EARNEST

a)Energy-efficient power-saving plant.

b)Centrally Controlled with CT & Water Pump.

c)High tech & long-lasting compressor.

d)Heat transfer ratio is good, as it is 100% pure copper tube.

e)Heavy thickness copper tube.

f)Delivery up to buyer factory.

g)Free installation & commissioning.

h)One Year product replacement guarantee.

i)Eighteen month routine visit & service warranty.

j)Within 24 Hr. Service support availability in site.

k)Free Training Facility for customer end.

l)Free Drawing for Installation & Pipe line work.


m)Three days free engineer support for guideline & follow-up for pipe line installation work to
customer end.

n)Proper solution based on factory/site visit.

o)Annual Maintenance Contact support available

You might also like