Professional Documents
Culture Documents
Nitrogen Recharge
Nitrogen Recharge
Nitrogen Containers
FIKE CORPORATION NITROGEN CYLINDERS
4.0 GENERAL
Nitrogen (N2) cylinders, large or small, will need to be recharged after a system discharge, after repair of
a leaking cylinder valve, or after a hydrotest. This section covers the methods and procedures necessary
to complete a Nitrogen cylinder recharge.
WARNINGS: The cylinders associated with these procedures will be filled with a compressed gas, under
high pressure. Safe handling procedures, associated with pressurized cylinders, shall be
observed at all times.
Suitable safety relief devices shall be incorporated into the charging system to prevent
accidental over pressurization of the recharging piping system.
Safety glasses, gloves, and a full-face shield shall be worn at all times while pumping N2
gas. Failure to do so could result in serious personal injury.
Nitrogen gas (N2) is lighter than the atmosphere. However, filling areas must be well
ventilated at all times to reduce the potential for gas accumulating and displacing the
atmosphere/oxygen causing potential breathing problems.
CAUTION: NEVER handle, move or transport ANY pressurized cylinder without the “Safety / Shipping”
cap firmly in place. Failure to have this cap in place any time a cylinder is not in an
approved rack or storage location can result in serious damage and/or injury to persons in
the immediate area, or those handling the unprotected cylinder.
The following is a step-by-step procedure for recharging Nitrogen cylinders supplied with Fike’s
Micromist® Fire Suppression System packages:
A. Install a Fike Nitrogen Fill Valve Assembly, P/N 73-012, with straight Female threads, into the large
connection of the Fike Micromist® System valve inlet. See Figure 4.1-A, page 2, for Fill Valve
Assembly details.
B. Attached the cylinder, equipped with the Nitrogen Fill Valve Assembly, to a “pigtail” connection on the
Nitrogen-fill manifold.
C. Turn on the pump and allow Nitrogen to flow into the Fike N2 cylinder. Fill the cylinder to the desired
pressure, using the pressure gauge, temperature monitoring device, and the appropriate, approved,
fill chart having the correct final pressure(s) vs. cylinder (gas) temperature(s). Large Nitrogen (N2)
containers are filled to a pressure of 1,920 psi at 70ºF (13,238 kPa at 21ºC). Refer to Figure 4.1-B,
page 5, for an approved fill chart.
D. Stop the pump, shut off the Nitrogen inlet to the manifold, and open the ¼ turn valve on the Nitrogen
Fill Valve Assembly to vent the remaining Nitrogen pressure in the supply hose. Confirm that the Fike
cylinder valve has closed.
Revised Date: January, 2004 Container Recharge (Fill) Manual Section 4 / Page 1 of 10
Revision: B Manual P/N: 06-211
NITROGEN CYLINDERS FIKE CORPORATION
NOTES: A valve that fails to close can be detected by a drop in the cylinder temperature, i.e. as
Nitrogen flows out of the cylinder, the cylinder will cool to an easily detectable level.
Mark and reject any cylinder whose valve fails to close securely. Tag for repair and set
aside in an approved, secure, cylinder storage area.
E. Leak test the cylinder using a leak detecting product such as “Snoop”. Check carefully at the cylinder
neck, where the valve threads into the cylinder, and at the valve outlet and safety assemblies. Mark
and reject any cylinder found to be leaking. Tag for repair and set aside in an approved, secure
cylinder storage area.
WARNING: Be sure that the system pressure is depleted before disconnecting the cylinder. Excessive
pressure remaining in the manifold will cause the “pigtail” connection to “whip” when
released from the cylinder. This whipping action can cause serious injury or death to those
in the immediate area.
F. Disconnect the cylinder from the manifold “pigtail” and remove the Fike Nitrogen Fill Valve Assembly.
Install the Safety/Shipping cap on the cylinder. Move the cylinder to a safe, secure area in
accordance with OSHA and local codes.
NOTE: Large capacity (300 SCF) Nitrogen cylinders used in water mist systems SHALL not be
recharged without a hydrostatic test and remarking, if more than five (5) years have
elapsed from the date of the last test. Cylinders that have been in continuous service
without discharging shall be permitted to be retained in service for a maximum of twelve
(12) years, after which they shall be discharged and retested before being returned to
service. Reference: NFPA No. 750, Section 10-2.4, latest edition.
NITROGEN VALVE
HOSE FROM
C02 SUPPLY
FIGURE 4.1-A
Section 4 / Page 2 of 10 Container Recharge (Fill) Manual Revised Date: January, 2004
Manual P/N: 06-211 Revision: B
FIKE CORPORATION NITROGEN CYLINDERS
NOTE: Small capacity (Medical “D” size) Nitrogen cylinders, used in Fike’s Marine HFC-227ea and
CO2 systems, shall be hydrotested every five (5) years, in accordance with NFPA No. 10
and D.O.T. Regulation CFR Title 40, Paragraph 173.34. The cylinder must be tested
immediately if the cylinder shows evidence of distortion, damage, cracks, corrosion, or
mechanical damage. Cylinders failing the hydrostatic testing SHALL be destroyed.
The small (Medical “D” size) Nitrogen cylinders, covered under the hydrotest requirements noted above,
include:
4.2.2 RECHARGE PROCEDURE – REMOTE ACTUATION CYLINDERS - P/N C70-233 & P/N N70-233
The Remote Pneumatic Actuator Cylinders, P/N C70-233 and P/N N70-233, are identical devices but
used on different fire suppression systems (see Section 4.2). They are fitted with a quick opening lever
operator with a safety ring pin on top of the cylinder/valve assembly. The following is a step-by-step
procedure required to recharge these cylinders:
A. Secure the Remote Pneumatic Actuator cylinder in a vise, or other de-valving device. Remove the
Safety/Shipping cap and set aside.
B. Remove the top lever operator w/ safety ring pin and set aside.
C. Install a Fike Nitrogen Fill Valve Assembly, P/N 73-012, with straight Female threads, into the pilot
valve connection inside the cylinder valve. See Figure 4.2-A, page 7, for Fill Valve Assembly details.
D. Attached the cylinder, equipped with the Nitrogen Fill Valve Assembly, to a “pigtail” connection on the
Nitrogen-fill manifold.
E Turn on the pump and allow Nitrogen to flow into the Pneumatic Actuator cylinder. Fill the cylinder to
the desired pressure, using the pressure gauge, temperature monitoring device, and the appropriate,
approved, fill chart having the correct final pressure(s) vs. cylinder (gas) temperature(s). The normal
operating pressure for the small (Medical “D” size) Nitrogen (N2) cylinders is 1,800 psig at 70ºF
(12,410 kPa at 21ºC). Refer to Figure 4.1-B, page 5, for an approved fill chart.
F. Stop the pump, shut off the Nitrogen inlet to the manifold, and open the ¼ turn valve on the Nitrogen
Fill Valve Assembly to vent the remaining Nitrogen pressure in the supply hose. Confirm that the Fike
cylinder valve has closed.
Revised Date: January, 2004 Container Recharge (Fill) Manual Section 4 / Page 3 of 10
Revision: B Manual P/N: 06-211
NITROGEN CYLINDERS FIKE CORPORATION
NOTES: A valve that fails to close can be detected by a drop in the cylinder temperature; i.e. as
Nitrogen flows out of the cylinder, the cylinder will cool to an easily detectable level.
Mark and reject any cylinder whose valve fails to close securely. Tag for repair and set
aside.
G. Leak test the cylinder using a leak detecting product such as a hydrosonic leak detector. Check
carefully at the cylinder neck, where the valve threads into the cylinder, and at the valve outlet and
safety assemblies.
WARNING: Be sure that the system pressure is depleted before disconnecting the cylinder. Excessive
pressure, remaining in the manifold, will cause the “pigtail” connection to “whip” when
released from the cylinder. This whipping action can cause serious injury or death to those
in the immediate area.
H. Disconnect the cylinder from the manifold “pigtail” and remove the Fike Nitrogen Fill Valve Assembly.
I. Replace the lever operator top of the valve assembly and tighten securely. Be sure the safety ring
pin is in place and sealed with a lead/wire seal, or other appropriate sealing device.
J. Install the Safety/Shipping cap on the cylinder. Move the cylinder to a safe, secure area in
accordance with OSHA and local codes.
A. Using an accurate gauge, check the pressure in the Fike Nitrogen cylinder.
B. Determine the cylinder temperature. After determining the temperature, check the nominal cylinder
pressure, according to the chart in Figure 4.1-B on page 5. Large capacity Nitrogen cylinders
(Micromist® filled to a nominal operating pressure of 1,920 psi at 70ºF (13,238 kPa at 21ºC), the
allowable range SHALL be:
1. No more than 45 psi (310.3 kPa) over the nominal pressure, and
2. No more than 55 psi (379.2 kPa) under the nominal pressure.
See Figure 4.1-B, page 5, for pressure vs. temperature table for Large (300 SCF) N2 cylinders.
C. Small capacity (Medical “D” size) cylinders, filled to a nominal operating pressure of 1,800 psig at
70ºF (12,410 kPa at 21ºC), the allowable range SHALL be:
1. The cylinder pressure MUST fall within +/- 10% of the nominal pressure at 70º F (21º C).
2. At temperatures other than 70ºF (21ºC), first determine the nominal pressure for the specific
temperature and apply the +/- 10% tolerance to that number.
See Figure 4.2-A, page 6, for pressure vs. temperature table for Small (Medical “D” size) N2 cylinders.
Section 4 / Page 4 of 10 Container Recharge (Fill) Manual Revised Date: January, 2004
Manual P/N: 06-211 Revision: B
FIKE CORPORATION NITROGEN CYLINDERS
FIGURE 4.1-B – LARGE CAPACITY (300 SCF) Micromist® NITROGEN CYLINDER FILL CHART
The following is a fill chart showing temperature vs. pressure for 100% Nitrogen.
NOTE: Final density is 0.3359 lb.-moles/ft3 = 0.0752 SCF/in3 = 9.4098 lb./ft3 (150.73 kg/m3)
Revised Date: January, 2004 Container Recharge (Fill) Manual Section 4 / Page 5 of 10
Revision: B Manual P/N: 06-211
NITROGEN CYLINDERS FIKE CORPORATION
FIGURE 4.2-A – SMALL (Medical ”D” Size) NITROGEN CYLINDER FILL CHART
The following is a fill chart showing temperature vs. pressure for 100% Nitrogen.
NOTE: Final density is 0.3359 lb.-moles/ft3 = 0.0752 SCF/in3 = 9.4098 lb./ft3 (150.73 kg/m3)
Section 4 / Page 6 of 10 Container Recharge (Fill) Manual Revised Date: January, 2004
Manual P/N: 06-211 Revision: B
FIKE CORPORATION NITROGEN CYLINDERS
FILL ADAPTER
PRESSURE GAUGE
Figure 4.2-A
Revised Date: January, 2004 Container Recharge (Fill) Manual Section 4 / Page 7 of 10
Revision: B Manual P/N: 06-211
NITROGEN CYLINDERS FIKE CORPORATION
A. Place the cylinder in a secure area, restraining the cylinder in a vise, clamp, or other safe device,
in accordance with local codes and OSHA requirements. Remove the Safety/Shipping cap and set
aside for later use.
CAUTION: NEVER move, handle, transport, or store any Nitrogen, or other pressurized gas cylinder,
without the Safety/Shipping cap firmly in place. Failure to do so can result in serious
damage or injury to area personnel or those handling the unprotected cylinder.
B. Attach a control valve to the Nitrogen cylinder discharge adapter, P/N C85-1092, and attach a
discharge hose to the control valve. The control valve will regulate the flow of N2 being released from
the cylinder and the discharge hose is used to insure that the N2 discharge is properly vented to the
outside atmosphere.
NOTE: Place Teflon® tape on both threaded ends of the discharge adapter, P/N C85-1092, before
connecting.
C. Insure that the control valve is closed tightly, then attach the discharge adapter assembly to the brass
Nitrogen cylinder valve by threading the 1/8” NPT (4mm) end into the Nitrogen valve fill port, opening
the check inside the valve. Place the discharge hose so that it will discharge the N2 gas to the
outside atmosphere.
CAUTION: Be sure to restrain the discharge end of the hose, as discharging N2 velocity will cause the
hose end to whip with a potential to cause damage, or injury, to materials or personnel in
the immediate area.
D. Slowly open the control valve to release the N2 to the atmosphere. Regulate the flow to depressurize
the cylinder without discharging at an excessive velocity.
E. After the N2 gas has been expelled from the cylinder, close the control valve, disconnect the
discharge hose, and remove the discharge adapter assembly from the Brass Nitrogen cylinder valve.
F. Perform the required service or replace the Safety/Shipping cap and store the cylinder in a secure
area, restraining it in accordance with OSHA and local requirements. See Figure 4.4-A, page 9, for a
pictorial view of the depressurization assembly connections.
Section 4 / Page 8 of 10 Container Recharge (Fill) Manual Revised Date: January, 2004
Manual P/N: 06-211 Revision: B
FIKE CORPORATION NITROGEN CYLINDERS
NITROGEN VALVE
ADAPTER C85-1092
CONTROL VALVE
DISCHARGE HOSE
(TO OUTSIDE)
FIGURE 4.4-A
The Small (Medical “D”) Nitrogen cylinders use two (2) different valve actuating systems and the
procedures required for each valve system follow;
NOTE: Follow the Safety rules and guidelines outlined in section 4.4, page 8, at all times when
handling these cylinders.
Revised Date: January, 2004 Container Recharge (Fill) Manual Section 4 / Page 9 of 10
Revision: B Manual P/N: 06-211
NITROGEN CYLINDERS FIKE CORPORATION
A. Place the cylinder in a secure area, restraining the cylinder in a vise, clamp, or other safe device,
in accordance with local codes and OSHA requirements. Remove the Safety/Shipping cap and set
aside for later use.
CAUTION: NEVER move, handle, transport, or store any Nitrogen, or other pressurized gas cylinder,
without the Safety/Shipping cap firmly in place. Failure to do so can result in serious
damage or injury to area personnel or those handling the unprotected cylinder.
B. Attach a control valve to the cylinder valve 1/8” (4mm) discharge port and attach a discharge hose to
the control valve. The control valve will regulate the flow of N2 gas being released from the discharge
cylinder and the hose is used to insure that the N2 discharge is properly vented to the outside
atmosphere.
C. Be sure to restrain the discharge end of the hose, as discharging N2 velocity will cause the hose end
to whip with a potential to cause damage, or injury, to materials or personnel in the immediate area.
D. When the cylinder has been prepared, remove the safety pull pin and operate the lever on top of the
cylinder valve.
E. Slowly open the control valve to release the N2 to the atmosphere. Regulate the flow to depressurize
the cylinder without discharging at an excessive velocity.
F. After the N2 gas has been expelled from the cylinder, close the control valve, disconnect the
discharge hose, and remove the control valve/discharge hose assembly from the cylinder valve.
G. Perform the required service or replace the Safety/Shipping cap and store the cylinder in a secure
manner in accordance with OSHA and local requirements.
H. See Figure 4.5.2-A, page 11, for a pictorial view of the depressurizing assembly connections.
ADAPTER C85-1092
CONTROL VALVE
DISCHARGE HOSE
(TO OUTSIDE)
PRESSURE GAUGE
FIGURE 4.5.2-A
Section 4 / Page 10 of 10 Container Recharge (Fill) Manual Revised Date: January, 2004
Manual P/N: 06-211 Revision: B