Professional Documents
Culture Documents
Original Russian Text © V.V. Zhigunov, I.A. Shavochkin, 2011, published in Teploenergetika.
Abstract—Different versions of systems for automatic closedloop control of the power output of power units
are analyzed. A new version of the automatic power control system is proposed together with a method for
tuning it. Results from model studies and tests of the proposed automatic power control system structure at a
real plant are presented.
DOI: 10.1134/S0040601511100132
Much attention is now paid to the quality of main will relate all local automatic closedloop systems
taining the frequency and power in power systems in (LACSs) for control of process parameters, including
Russia like around the world. To this end, a number of subordinated ones (except with the LACSs for control
orders and guiding documents on selective primary of the power unit output and steam pressure upstream
and automatic secondary control of frequency have of the turbine) to a plant that can in the given case be
been issued in the power industry in the past years represented as a quadripole (Fig. 1).
[1, 2]. In parallel with this, more stringent require
ments have been imposed on the quality of load con The generator’s active power and steam pressure
trol while ensuring highaccurate maintenance of upstream of the turbine are the output controlled
other process parameters of a power unit, such as live quantities of this quadripole, and the generalized
steam pressure upstream of the turbine. assignment for the position of turbine control valves
In accordance with the new requirements, the load and the generalized boiler control member producing
of a steampower unit must be maintained with accu control outputs to the subordinated controllers of
racy of 1% of the nominal value. The pressure is feedwater, fuel, and air are its input parameters. Here
regarded as being maintained satisfactorily if it does and henceforth, the quadripole input and output
not reach the threshold values at which the watchdog parameters are treated in dimensionless form as incre
controllers come into action (except with emergency ments and are denoted by the following variables: N
disturbances). In this connection, new solutions need for the generator active power, p 't for steam pressure
to be worked out for constructing multiply connected
automatic closedloop control systems (MACSs) for upstream of the turbine, μb for the generalized boiler
power units, in particular, automatic power control control member, and Ht for the generalized assign
systems (APCSs). ment of turbine valve position. The combined effect
Below, an APCS structure is considered that is from the disturbance of boiler control output μb and
somewhat different from the traditional structure, its internal disturbance λb is denoted by μ.
analysis is presented, and an example of calculating
the tuning parameters of the obtained structure is
given. The results from putting the new scheme (the λb
tests of which were carried out in November 2010) into μb μ Wµp (s) p't
operation in the 330MW Unit 3 at the Kashira district
power station are presented.
WNµ (s) WHp (s)
859
860 ZHIGUNOV, SHAVOCHKIN
(a) (b)
– p't – p't
pref pref
TPrC BPrC
TCVs
TCVs
λb λb
μb μ μ
G G
μb
– N –
BPC Nref TPC Nref
(c) (d)
p't
N
p't t N t
Fig. 2. Structures of systems for automatically controlling the power unit output/steam pressure. (a) APCS1 and (b) APCS2.
Comparison between the quality of maintaining power N and steam pressure p 't when using ACSs constructed according to the
schemes of APCS1 (c) and APCS2 (d). TPrC is the turbine pressure controller, BPrC is the boiler pressure controller, BPC is
the boiler power controller, TPC is the turbine power controller, TCVs are the turbine control valves, and G is the generator.
The plant whose pressure and power output have to trohydraulic converters—are used in the hydraulic
be controlled when a change occurs in the boiler load part of turbine governors, the full stroke of which is
(μ) is characterized by large inertia determined by the performed for a few tenths of a second, the character
boiler dynamic characteristics. The plant’s time con istics of turbine controllers are close to the ideal ones.
stants by these channels are as large as a few minutes. This allows the following assertion to be made. If
The dynamics of the controlled plant in response to a steam pressure is maintained by the turbine controller
disturbance applied by the turbine control valves is and the power unit output is maintained by the boiler
characterized by essentially smaller inertia: the time controller producing commands to the generalized
constants of the initial parts of transient characteris boiler control member (Fig. 2a), deviations of pressure
tics, which determine the tuning of the controllers, are in such a system, called APCS1, will be minimal, and
as small as a few seconds. disturbances will be responded to in a sufficiently
1
As is well known, controllers for lowinertia plants quick manner. At the same time, the power will be
(which are often called highspeed controllers) feature controlled in step with the boiler dynamics with tak
high accuracy with which the parameters are main ing its inertia into account. Hence, deviations of
tained. Quite a lot of methods for tuning these con this parameter will be larger than pressure devia
trollers are available, e.g., [3]. This class of controllers tions (Fig. 2c).
includes automatic closedloop systems for control
ling gas flowrate or pressure, feedwater flowrate, air In the inverse scheme, called APCS2 (Fig. 2b), in
flowrate, rarefaction in the furnace, etc. The turbine which the pressure controller’s output is applied to the
controller, which produces commands to the turbine generalized boiler control member and the power con
control valves, is also a lowinertia one, because, as 1 The
APCS1 and APCS2 schemes are considered here in pure
was mentioned above, the initial parts of the transient form, i.e., without additional forcing signals or compensation
characteristics have very small time constants. More devices. The analysis is carried out for a power unit operating at
over, if modern actuators—electromechanical or elec nominal pressure.
(a) (c)
pref εp pref
WBPrC (s) WBPrC (s)
– – –
WD(s)
μb μb
λb Wµp (s) p't λb Wµp (s) p't
μ μ
WNµ (s) WHp (s) WNµ (s) WHp (s)
Ht N Ht N
WHN (s) WHN (s)
α α
– – Nref – – Nref
WTPC (s) WTPC (s)
(b) Kc /Ti (d)
lm(ω)
α=1 1
0.02
α = 0.7 Re(ω)
3
α = 0.4
0.01
2
α=0
0 2 4 6 8 Kc
Fig. 3. Scheme of APCS2 with the additional signal αεc applied to the TPC (a), family of complex frequency responses of the
equivalent plant controlled by the BPrC with the TPC switched into operation and with different values of α (b), scheme of
APCS2 with an additional D component produced from the signal p 't and applied to the BPrC (c), and BPrC stability margin
regions. (1) α = 1 and D is disconnected, (2) α = 0 and D is disconnected, and (3) α = 0 and D is switched into operation. Kc is
the controller’s transfer gain, and Ti is the integrator time constant.
troller’s output is applied to the turbine control valves, which can be applied to the input of these controllers or
the opposite is the case: the power unit output is main directly to the control members [4, 5].
tained quickly and with high accuracy, whereas the
pressure upstream of the turbine is maintained with We consider here an alternative solution of the
essentially poorer quality (Fig. 2d). As will be shown problem, namely, application of the APCS2 scheme
below, the quality with which pressure is maintained in and its modernization for achieving that the boiler
the APCS2 scheme is considerably poorer than the controller maintains steam pressure upstream of the
quality with which power is maintained in the APCS turbine with sufficient quality and the turbine control
1 scheme in response to the same disturbances (see ler maintains the preset power with high accuracy.
Figs. 2c, 2d). Therefore, since live steam pressure is
one of the most important process parameters, the Figure 3a shows the APCS2 scheme in a some
control quality of which must comply with very strin what modified version in which an inverse (opposite
gent requirements, the APCS2 scheme has not hith polarity) pressure mismatch signal is applied to the
erto been widely used in power units equipped with turbine power controller with some gain α. The pres
oncethrough boilers. sure mismatch signal is also applied to the boiler pres
Therefore, in order to meet the modern requirements sure controller. We assume that the doubly connected
for control of frequency and power, the APCS1 scheme controlled plant has the following transfer functions
is presently used in the majority of cases for control of approximating its behavior in response to disturbances
power unit output/steam pressure with the use of addi caused by changing the position of the turbine control
tional forcing signals in the boiler and turbine controllers, valves and the boiler load (μ):
p
— W µ μ(s) is the transfer function via the μb p 't ters ( p 't and N) will reach new steadystate values. In
channel; this case, no change will occur in the position of the
N
turbine control valves with respect to the initial state.
— W µ (s) is the transfer function via the μb N
At α = 0, the turbine PI controller maintains the
channel; power output strictly equal to its setpoint (reference)
p
— W H (s) is the transfer function via the Ht posi value Nref. This means that when the turbine generator
operates in a steady mode, it consumes certain con
tion p 't channel; and stant power arriving from the boiler. If a disturbance is
N
applied through the μ channel, additional thermal
— W H (s) is the transfer function via the Ht posi energy appears, which is produced by the boiler as a
tion N channel. result of firing additional fuel. This additional energy
The transfer function of the turbine proportional is not consumed by the turbine generator but is accu
integral (PI) controller is denoted by WTPC(s) and that mulated (integrated) as an increment of steam
of the boiler PI controller, by WBPrC(s). enthalpy, which is seen by the boiler pressure control
ler as an equivalent plant without selfbalancing (see
With the TPC switched into operation, the expres the curve α = 0 in Fig.3).
sion for the transfer function of the equivalent plant
for the boiler controller depending on α takes the form Thus, in the case of using a boiler controller con
structed according to the “pure” APCS2 scheme, we
deal with an integrating plant. Attempts to use of a PI
eq
W pl ( s, α ) control law for such plants have always encountered
considerable difficulties, because the tuning parame
p N N
W µ ( s ) [ 1 + W TPC ( s )W H ( s ) ] – W µ ( s )W H ( s )W TPC (s )
p ters for such plants have an extremely small region of
=
N
p
. stable operation. The gains of the controllers are low,
1 + W TPC ( s )W H ( s ) – αW TPC ( s )W H ( s ) and the integration time constants are high; hence, the
quality with which the controlled parameters of plants
without selfbalancing are maintained is considerably
Figure 3b shows the family of complex frequency poorer than that in selfbalanced plants with similar
responses (CFRs) of the equivalent plant for the boiler characteristics. In addition, it should be pointed out
pressure controller at different values of α. that such systems become unstable already when a
An analysis of the dependence W pl (s, α) shows
eq comparatively small change occurs in the plant char
acteristics; i.e., they feature low robustness.
that at α = 1, the transfer function of the equivalent
eq One way in which the system can be made more
plant W pl (s, α), which is the transfer function of a sys stable consists in introducing a differential (D) com
tem with a closed loop containing the TPC, is approx ponent into the control law. Below, the use of this
imately equal to the transfer function of the plant approach to the boiler pressure controller is consid
p
W µ (s) via the μb p 't channel, as would be with the ered as applied to the “pure” APCS2 scheme (with
disconnected TPC. Indeed, with 0 < α ≤ 1, the PI con α = 0) with the turbine power controller switched into
troller of turbine power output WTPC(s) becomes operation.
embraced by the p 't negative pressure feedback signal
p THE SCHEME OF THE MACS
through the lowinertia channel W H (s). Under such FOR THE POWER UNIT OUTPUT/STEAM
conditions, the turbine controller is transformed with PRESSURE WITH AN ADDITIONAL
respect to the power N signal into an equivalent con DCOMPONENT FOR p t' IN THE BPRC
troller approximately described by a P control law, the ALGORITHM
proportionality gain of which increases as α decreases
and becomes zero at α = 1. Physically, this is explained Figure 3c shows the MACS of pressure and power,
as follows. Since the mismatches of pressure and which differs from the APCS2 scheme shown in Fig.
power expressed in percentage terms are almost equal 3a by having the pressure derivative signal, an addi
to each other when a disturbance is applied by chang tional control variable applied to the BPrC input from
ing the boiler load (μ) and since they arrive to the TPC the real differentiation unit D, whose transfer function
with opposite signs, the turbine controller does not has the form
respond to such disturbance at α = 1; i.e., the TCP is
invariant to disturbances changing the boiler load. Kd Td s
Wd(s) =
,
Therefore, if we change the set point of boiler load (μ) 1 + Td s
in this mode, the change of pressure will result in that
the power output will also change in few minutes in where Kd and Td are the transfer gain and differentia
step with the boiler dynamics, and these two parame tion time constant.
lm(ω) Ares
2 3.0
Mcircle
2.5
3
0
2 2.0
2
M
–2 3 1.5 1
1
1.0
–4 20 40 60 80 100 Kd /Td
–6 –4 –2 0
Re(ω)
Fig. 4. Complex frequency response of the openloop sys Fig. 5. Dependence of Ares(jω) in the openloop system on
tem with the optimal tunings of the BPrC. The meaning of Td at different values of the product KdTd. The values of
(1)–(3) is the same as in Fig. 3. Td, s: (1) 5, (2) 9.5, and (3) 15.
We now consider the properties of this system, as At the first stage, the boiler PI controller is tuned at
well as methods for tuning it taking as an example the 2
transfer functions obtained from approximation of the α = 1 and with the disconnected differentiator. As was
transient characteristics taken in Unit 3 at the Kashira shown earlier, the equivalent plant for such a controller
district power station (DPS) during its operation on has the form of a selfbalanced plant (see Fig. 3b). There
gas at nominal load: are a lot of methods for tuning such systems, e.g., the
frequency method [6]. The stability margin region of
– 5s the boiler controller obtained using this method and
p 1.14e
W µ ( s ) = 2 ; corresponding to the damping ratio ψ = 0.9 (for which
( 1 + 75s ) the frequency indicator of oscillatory behavior is M =
1.55) is shown in Fig. 3d (curve 1). The optimal
N 1.05e
– 5s parameters of the controller corresponding to the
W µ ( s ) =
;
2
minimum of the linear integral quality criterion with
( 1 + 90s ) ( 1 + 20s ) the preset damping ratio (the maximal value of the
Kc/Ti ratio at the stability margin curve) are Kc = 3.36
p 0.27 +
W H ( s ) = – 1.46 0.73 ; and and Ti = 127 s.
( 1 + 2s )
2 ( 1 + 90s ) ( 1 + 10s ) The complex frequency response the openloop
system with the boiler controller has with the obtained
N
WH ( s ) tuning parameters is shown in Fig. 4 (curve 1). If we set
α = 0 with the same parameters of the BPrC, the CFR
0.6 +
= 0.7 0.4 1 –
1 . of the openloop system will turn clockwise and go
2 4
( 1 + 2s ) 1 + 40s ( 1 + 11s ) ( 1 + 110s ) beyond the region of the preset oscillatory behavior
and intersect the M circle (see curve 2 in Fig. 4).
The transfer gains were calculated as applied to the
input and output parameters expressed in percentage Having specified a certain value of the differentia
terms with respect to their nominal values. tion time constant Td and gradually increasing the dif
ferentiation transfer gain Kd, we can return the CFR of
The tuning parameters obtained at the Kashira the openloop system corresponding to α = 0 and with
DPS for the controller regulating the pressure before the BPrC tunings obtained for α = 1 into the region
itself and producing commands to the turbine control with the preset stability margin. In this case, as the Kd
valves with the disconnected power controller were value increases, the CFR of the system will first turn
taken as the turbine controller’s parameters. Studies counterclockwise approaching the imaginary axis, and
showed that exact selection of the TPC parameters is then it will again return and go into the oscillatory
not so important for the BPrC tuning because these region.
controllers have different resonance frequencies. The
TPC transfer function is given by the formula This process can be observed most clearly from the
curves in Fig. 5, which show the peak of the ampli
WTPC(s) = 0.6 ⎛ 1 + 1 ⎞ . 2 Here
⎝ 3s⎠
and henceforth, the turbine power controller is switched
into operation.
fref = 50 Hz
f –+
Δf
Dead band
adjuster
Adjuster of
frequency
deviation ++
simulator
Droop adjuster
Ultimate
power
SCRL N
setpoint
adjuster
Rateofchange
adjuster
Accounting FSC
of TCs
ΔNref
pr
ΔN ref
sec
p't d N –+ ++
dt
Setpoint ΔN
adjuster for
SCRL p
ultimate
pressure – + Maximal
upstream of the + + p't pressure
turbine watchdog
Rateofchange Δp't controller
adjuster
Accounting
of TCs PI BPrC p't
Maximal
pressure
watchdog
Ffw.ref controller
Boiler A Boiler B
++
ASLA of b. A
ASLA of b. B
Fig. 7. Structure of the APCS of Unit 3 at the Kashira DPS. FSC is a frequency secondary controller, SCRL is a set point change
rate limiter, TCs are technological constraints, TSG is a turbine speed governor, ASLA is an automatic boiler shell load setpoint
adjuster, and TCV is a turbine control valve.
26 ASLA (µb) of b. A
400 300 75
TCV(Ht)
200 Simulator of network
25 280 frequency deviation, f, mHz
p't
0 200 50
260
–200 24
Nref p't.ref
240 N
–400 100 25
23 220
200 t1 t2 t3
0 22 0
02:32:00 02:36:00 02:40:00 02:44:00 02:48:00 02:52:00
02:34:00 02:38:00 02:42:00 02:46:00 02:50:00
Time, h:min:s
μb, t/h (b) Ht, %
f, mHz p' t, MPa
27 N, MW 100
ASLA (µb) of b. A
ASLA (µb) of b. B
400 26
400 75
25 p't TCV(Ht)
200 pt.ref
300 24
0 50
300 Simulator of network
23 frequency deviation, f, mHz
–200 280
–400 200 22 260 25
240 Nref
21 N
t1 t4 t5
220 t2 t3
100 20 200 0
06:34:00 06:42:00 06:50:00 06:58:00 07:06:00
06:38:00 06:46:00 06:54:00 07:02:00 07:10:00
Time, h:min:s
Fig. 9. Results of APCS tests. (a) Checking the joint effect from primary and secondary control with the specified droop equal to
6% (t1—disturbance applied by changing the power setpoint of the secondary component by –17.6 MW for 5 min, t2—simulating
the deviation of network frequency by 0 160 mHz, t3—removing the simulated frequency deviation 160 0 mHz simul
taneously with a disturbance applied by changing the power set point of the secondary component by 17.6 MW for 5 min); (b)
checking the joint effect from primary, secondary, and tertiary control with the specified droop equal to 6% (t1—disturbance
applied by changing the power set point of the tertiary component by +70.4 MW for 40 min, t2—disturbance applied by changing
the power set point of the secondary component by +35.2 MW for 10 min, t3—simulating the deviation of network frequency by
0 –160 mHz, t4—removing the simulated frequency deviation –160 0 mHz, and t5—disturbance applied by changing
the power setpoint of the secondary component by –35.2 MW for 10 min). Dashed curves show the boundaries of possible devi
ation of the power unit output.
2.5 of the difference between its initial and steady Kd corresponding to the minimal possible amplitude
state values. To do so, the differentiator time constant peak of the closedloop system Ares was recalculated,
Td was increased, and the differentiator transfer gain and then the controller parameters Kc and Ti corre
sponding to the specified damping ratio and minimal “pure” scheme of APCS2; hence, its implementation
integral criterion were determined. The new tuning using any equipment should not be a problem.
parameters of the BPrC determined for the considered (ii) There is no need to use any additional compen
plant are as follows: Kd = 0.97, Td = 40 s, Kc = 1.3, and sating or forcing sections, the tuning parameters of
Ti = 188 s. which are rigidly linked to the properties of the plant,
Figure 8 shows the simulated graphs of transients in the characteristics of which always vary with time.
steam pressure p 't and assigned boiler load μb in (iii) The scheme is convenient for tuning (it is easy
to elaborate an algorithm for calculating the BPrC
response to a stepped disturbance applied by changing tuning parameters or for determining them experi
the set point of the power unit’s output Nref by 5% with mentally).
two versions of the BPrC tunings calculated with and
(3) The results obtained from simulation, tests, and
without taking into account the constraint for devia
operation at real facilities (including those obtained
tion of μb. It can be said from making a comparison
from longterm operation in Unit 8 at the Zmiev TPS
between the presented graphs that the control pro for 8 years) show that the proposed APCS scheme
cesses in the system with the BPrC tunings calculated copes with the tasks imposed on it, namely, maintain
taking into account the constraint for deviation of μb ing the power unit output and steam pressure, which
feature a smoother change in the boiler load, a some are the most important process parameters, in compli
what larger mismatch of control by pressure, and a ance with the quite stringent quality criteria that are
longer duration of the process; however, the quality presently in force, fulfilling them with certain margin.
with which this parameter is maintained is in compli
ance with the specified criteria.
REFERENCES
Figure 9 shows the graphs of control processes
obtained during the preliminary tests of the APCS of 1. Standard of OAO Unified Energy System’s System Opera
Unit 3 at the Kashira DPS for compliance with the tor—Central Dispatch Control Board STO
requirements of the relevant standard. The require 59012820.27.100.0022005 (SOCDCB UES 0012005,
IDN): Norms for Participation of Power Units at Thermal
ments imposed on the quality of maintaining the con Power Stations in Selective Primary and Automatic Sec
trolled parameters are fully complied with in all tests ondary Control of Frequency (Moscow, 2005) [in Rus
that were carried out. sian].
2. Order of RAO Unified Energy System of Russia No. 524 of
September 18, 2002.
CONCLUSIONS 3. N. D. Aleksandrova and N. I. Davydov, “Tuning
(1) There are a number of schematic versions con Impulse Relay Regulators for LowInertia Controlled
structed on the basis of APCS1 the use of which Objects,” Teploenergetika, No. 5, 54–57 (2002)
[Therm. Eng., No. 5, 408 (2002)].
makes it possible to fulfill the modern requirements
imposed on selective primary and automatic second 4. N. I. Davydov, A. D. Melamed, M. D. Trakhtenberg,
and L. P. Fotin, “A System for Automatic Control of
ary control of frequency [1, 2]. As a rule, this is Frequency and Power at UnitType Thermal Power
achieved by introduction of additional units that pro Stations Equipped with OnceThrough Boilers,”
duce forcing control actions. Therm. Eng., No. 8 (1979).
(2) The use of the proposed scheme constructed on 5. V. A. Bilenko. A. D. Melamed, E. E. Mikushevich,
the basis of APCS2 also makes it possible to fulfill all et al., “Development and Application of Automatic
the necessary requirements and has the following Frequency and Power Control Systems for Large Power
advantages: Units,” Teploenergetika, No. 10, 14–27 [Therm. Eng.,
No. 10, 824 (2008)].
(i) The scheme is simple (only one device, namely, 6. V. Ya. Rotach, Automatic Control Theory (MEI, Mos
a differentiator of pressure signal) is added to the cow, 2004) [in Russian].