Project: Neelam Redevelopment Project

Technical Specifications

1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):

1.1.1 Technical Requirements & Specifications (Foundation Field bus based):


1 Offered Transmitters shall be Foundation Fieldbus type and shall be used for
unmanned wellheads.

2 All Field bus transmitters shall satisfy, as minimum, the requirement of the Field bus
registration laboratory and in case of Field bus Foundation, shall have FF "tick mark".
All FF transmitters shall be registered with Field bus Foundation having passed the
interoperability tests as per ITK 4.01 as minimum.

2 Field bus electronic transmitters shall be Foundation Field bus H1 compliant bus
powered device having output as FF compliant digital communication and shall have
LAS (Link Active Scheduler) capability to ensure communication during primary LAS
failure (LAS backup).

4 Foundation Field bus transmitters shall comply with ISA S50.02 and IEC-61158
standard.

5 Foundation Field bus transmitter shall be compatible to use along with Foundation
Field bus accessories such as FISCO power supply, spur connector, short circuit
protectors, bus terminator etc. for Intrinsically safe H-1 field bus implemented using
Field bus Intrinsically Safe Concept (FISCO).

6 Foundation Field bus transmitters shall have intrinsically safe/ FISCO (Field bus
Intrinsic Safety Concept) approval from statutory body and shall be suitable for use in
Class I, Division 1, Group B, C, D, temperature class T3 hazardous area.

7 Field bus transmitters shall be polarity insensitive to communication signal. (Polarity


insensitive termination).

8 Field bus transmitter shall work with voltages of 9-32 VDC. Transmitters shall be
compatible with FISCO power supply module and should function satisfactorily with
such power supply modules.

9 Field bus transmitter shall have short circuit protection.

10 Field bus transmitter shall have standard function blocks including AI (Analog Input) as
minimum.

11 DD and CFF files for field bus transmitter according to foundation field bus FF-524 and
FF-103 respectively shall be provided.
Project: Neelam Redevelopment Project

Technical Specifications

1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):

1.1.1 Technical Requirements & Specifications (Foundation Field bus based):


12 Transmitter shall be microprocessor based and it shall incorporate a non-volatile
memory, which shall store complete configuration data of transmitter. All necessary
signal conversions, including conversion to produce output with the required protocol
shall be carried out in the transmitter electronics.

13 Transmitter shall run complete diagnostic routine. In the event of detection of failure,
the output shall be driven to predefined value.

14 Transmitter shall be configured to store its tag number, calibration range & other
specifications / data which will be useful for history record purpose.

15 Built in temperature sensors shall be provided to compensate for ambient temperature


variations.

16 The transmitter shall be so constructed that in case of a pressure sensing element


failure, the process material will not enter the wiring conduit / enclosure.

17 Transmitter shall be provided with external zero adjustment and shall have integral
vent/drain.

18 Transmitter shall be immune to rf interference due to microwave, hf, vhf radio


communication etc.

19 Transmitters shall be in compliance with the electromagnetic compatibility


requirements as per IEC-801. Electronic modules shall be designed for short circuit
protection.

20 The material of elastomers used in instruments shall be suitable for the specified
service. Use of asbestos or asbestos-bearing materials shall not be used.

21 For all instruments, all materials of construction shall meet the requirements specified
in nace mr-01-75 latest edition wherever applicable.

22 Transmitter’s meter body and electronics housing material shall be SS-316 and it shall
resist shock, vibration, corrosion and moisture.

23 Transmitter Software Security & Upscale/Downscale Shall Be User Selectable.

24 Function Transmit & Indicate


Project: Neelam Redevelopment Project

Technical Specifications

1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):

1.1.1 Technical Requirements & Specifications (Foundation Field bus based):


25 Type Electronic, Smart (FF Bus Based)

26 Reference Accuracy ± 0.075% of calibrated range or better

27 Rangeability 60: 1 or better

28 Stability Of Calibration 0.15% of URL for 36 months

29 Over Range Protection 130% of range or design pressure whichever is


higher

30 Measuring Principle Capacitance/ Piezo-Resistive/ Silicon Resonance

31 Fill Fluid Silicone Oil

32 Process Connection 1/2", NPT (F)

33 Safety Requirement Intrinsically safe.

34 Enclosure Class Weather proof to IP-65 or better as per IEC-60529.

35 Area Classification Suitable for Class I, Division 1, Group D, Temp


Class T3

36 Cable Entries 2 Nos. of 1/2" NPT (F), spare entry shall be


plugged with SS-316 plug approved for use in
hazardous area.

37 Integral, Intrinsically Safe Output Required, LCD, 4 1/2 digit display in engg. Units
Meter selectable by user and diagnostics message for
local troubleshooting.
Project: Neelam Redevelopment Project

Technical Specifications

1.1 Specifications for Pressure Transmitter (A1, A2, A3, A6 & A7 Types):

1.1.1 Technical Requirements & Specifications (Foundation Field bus based):


38 2-Valve Manifold Each transmitter shall be provided with one
number of 2-way manifold which shall be forged
type and capable of withstanding 1.5 times the
design pressure.

2-way manifolds shall be of the same material as


the body material.

Process connection shall be 1/2" NPT (F).


The manifold shall be factory fitted and all tests
shall be conducted along with manifold. Spare ‘O’
ring set shall be supplied.

39 Mounting Accessories Required, which shall be suitable for 2" stanchion


mounting. Vendor to provide complete mounting
accessories (nuts, bolts, U clamps, brackets etc) of
material SS-316 minimum.

40 Name Plate Tag plate of SS 316 with following details shall be


provided.

- Manufacturer's name, model no. & serial no.


- Calibration / span range
- Body & element material
- Certification.
Project: Neelam Redevelopment Project Volume - 2
Technical Specifications Doc. No. : OSW-SG-J0-001
Rev No : 1

2.0 Specifications for Temperature Transmitter (Foundation Field bus):

2.1 Technical Requirements & Specifications (B-1 Type):


B1
2.1.1 Technical Requirements :

1 Offered Transmitters shall be Foundation field bus type and shall be used at
unmanned.

2 All Field bus transmitters shall satisfy, as minimum, the requirement of the Field bus
registration laboratory and in case of Field bus Foundation, shall have FF "tick mark".
All FF transmitters shall be registered with Field bus Foundation having passed the
interoperability tests as per ITK 4.01 as minimum. Documentary evidence to this effect
shall have to be submitted.

3 Field bus electronic transmitters shall be Foundation Field bus H1 compliant bus
powered device having output as FF compliant digital communication and shall have
LAS (Link Active Scheduler) capability to ensure communication during primary LAS
failure (LAS backup).

4 Foundation Field bus transmitters shall comply to ISA S50.02 and IEC-61158
standard.

5 Foundation Field bus transmitter shall be compatible to use along with Foundation
Field bus accessories such as FISCO power supply, spur connector, short circuit
protectors, bus terminator etc. for Intrinsically safe H-1 field bus implemented using
Field bus Intrinsically Safe Concept (FISCO).

6 Foundation Field bus transmitters shall have intrinsically safe/FISCO (Field bus
Intrinsic Safety Concept) approval from statutory body and shall be suitable for use in
Class I, Division 1, Group D, temperature class T3 hazardous area.

7 Field bus transmitters shall be polarity insensitive to communication signal. (polarity


insensitive termination).

8 Field bus transmitter shall work with voltages of 9-32 VDC. Transmitters shall be
compatible with FISCO power supply module and should function satisfactory with
such power supply module.

9 Field bus transmitter shall have short circuit protection.

10 Field bus transmitter shall have standard function blocks including AI (Analog Input) as
minimum.
Project: Neelam Redevelopment Project Volume - 2
Technical Specifications Doc. No. : OSW-SG-J0-001
Rev No : 1

2.0 Specifications for Temperature Transmitter (Foundation Field bus):

2.1 Technical Requirements & Specifications (B-1 Type):


B1
2.1.1 Technical Requirements :

11 DD and CFFf files for field bus transmitter according with foundation field bus FF-524
and FF-103 respectively shall be provided.

12 Transmitter shall be microprocessor based and it shall incorporate a non-volatile


memory, which shall store complete configuration data of transmitter. All necessary
signal conversions, including conversion to produce output with the required protocol
shall be carried out in the transmitter electronics.

13 Transmitter shall run complete diagnostic routine. In the event of detection of failure,
the output shall be driven to predefined value.

14 Transmitter shall be configured to store its tag number, calibration range & other
specifications / data which will be useful for history record purpose.

15 Built in temperature sensors shall be provided to compensate for ambient temperature


variations.

16 Transmitter shall be immune to rf interference due to microwave, HF, VHF radio


communication etc.

17 Transmitters shall be in compliance with the electromagnetic compatibility


requirements as per IEC-801. Electronic modules shall be designed for short-circuit
protection.

18 The material of elastomers used in instruments shall be suitable for the specified
service. Use of asbestos or asbestos-bearing materials shall not be used.

19 Transmitter’s meter body and electronics housing material shall be SS-316 and it shall
resist shock, vibration, corrosion and moisture.

20 Transmitter Software Security & Upscale/Downscale shall be user selectable.

21 Function Transmit & Indicate

22 Type Electronic, Smart (Foundation field bus based),


Remote mounted (not head mounted).
Project: Neelam Redevelopment Project Volume - 2
Technical Specifications Doc. No. : OSW-SG-J0-001
Rev No : 1

2.0 Specifications for Temperature Transmitter (Foundation Field bus):

2.1 Technical Requirements & Specifications (B-1 Type):


B1
2.1.1 Technical Requirements :

23 Accuracy
+ 0.25 Degree c or better
24 Stability Of Calibration 0.15% of URL for 36 months

25 Update Time At least 2 times per second

26 Burnout Drive Selectable upscale or downscale

27 Linearization Built in linearization function to provide output


linear to temperature range.

28 Input / Output Isolation Required

29 Input Type All types of thermocouple and RTDs (Pt-100, 3-


wire)

30 Lead Resistance Compensation Required

31 Safety Requirement Intrinsically Safe

32 Enclosure Class Weather proof to IP-65 or better as per IEC-


60529
33 Area Classification Suitable for Class I, Division 1, Group D, Temp
Class T3

34 Cable Entries 2 Nos. of 1/2" NPT (F), spare entry shall be


plugged with SS316 plug approved for use in
hazardous area.

35 Integral, Intrinsically Safe Output Required, LCD, 4 1/2 digit display in engg units
Meter selectable by user and diagnostics message for
local troubleshooting.
Project: Neelam Redevelopment Project Volume - 2
Technical Specifications Doc. No. : OSW-SG-J0-001
Rev No : 1

2.0 Specifications for Temperature Transmitter (Foundation Field bus):

2.1 Technical Requirements & Specifications (B-1 Type):


B1
2.1.1 Technical Requirements :

36 Mounting Accessories Required which shall be suitable for 2" stanchion


mounting. Vendor to provide complete mounting
accessories (nuts, bolts, U clamps, brackets etc)
of material SS316 minimum.

37 Name Plate Tag plate of SS 316 with following details shall


be provided.

- Manufacturer's name, model no. & serial no.


- Calibration / span range
- Body & element material
- Certification