You are on page 1of 10

setting of instant short circuit tripping of C.

B/ selection of circuit fuse

Instant.Short Circuit Tripping Setting of C.B Cu Selection of Circuit Fuse


Alu
Phase Circuit Wire Size
Voltage(L-L) 440 Volt
Voltage(L-N) 230 Volt Circuit Fuse Size(Max)
Instantaneous Short-Circuit Triping Set 100 Amp
Accuracy 20 %
Cable Size 3cx4 4 0
Cable Material Cu Search Cable Amper Rating (Appro
Actual Length of Cable 5 Meter
Type of Cable
Max.Length of Cable for your Tripping setting 133 Mt.
Your Tripping Setting of C.B is OK Current Capacity of Cable
circuit fuse
Jignesh.Parmar www.electricalnotes.wordpress.com jiguparmar@yahoo.com

Selection of Circuit Fuse


Date 6-Nov-21
mm2 55

325 Amp

earch Cable Amper Rating (Appro)

AL HRPVC 1cx240

acity of Cable 409 Amp


CABLE DATA
CURRENT RATING AT 40 DEG
AWG 55 X-SECTION PVC HRPVC
mm2 AL CU AL
AL 1 3cx1.5 14 17 16
CU 2 3cx2.5 18 24 22
PVC 3 3cx4 23 30 28
HRPVC 4 3cx6 30 39 37
LT XLPE 5 3cx10 39 57 49
HT XLPE 6 3cx16 50 65 62
EPR CSP 7 3cx25 63 66 85
8 3cx35 77 110 105
9 3cx50 95 135 128
10 3cx70 130 155 159
11 3cx95 155 200 189
12 3cx120 180 230 220
13 3cx150 205 255 250
14 3cx185 240 305 293
15 3cx225 255 335 323
16 3cx240 280 355 342
17 3cx300 315 400 384
18 3cx400 375 455 458
19 3cx500 425 521 519
20 3cx630 480 674 586
21 1cx120 220 280 268
22 1cx150 250 320 305
23 1cx185 290 370 354
24 1cx225 315 400 390
25 1cx240 335 425 409

26 1cx300 380 475 464

27 1cx400 435 550 531


28 1CX500 480 590 586
29 1cx630 550 660 671

AL CU 409
PVC 0 0
HRPVC 409 0
LT XLPE 0 0
HT XLPE 0 0
EPR CSP 0 0
CABLE DATA Mo
NT RATING AT 40 DEG (LAID IN TUNNEL)
HT XLPE -upto
HRPVC LT XLPE EPR CSP Full Voltage Starting
6.6kv(E) NEMA Size
CU AL CU AL CU CU 230V
21 oo 1.5 Hp
29 26 oo 3 Hp
37 31 36 35 1 7.5 Hp
48 50 47 46 2 15 Hp
63 67 62 64 3 30 Hp
81 70 79 85 4 50 Hp
110 96 108 100 115 114 5 100 Hp
134 117 132 121 140 140 6 200 Hp
165 142 162 145 175 175 7 300 Hp
201 179 198 181 215 216 8 450 Hp
244 221 240 221 255 260 9 800 Hp
281 257 276 254 290 303
323 292 318 290 335 349
372 337 366 330 370 398
407 379 402 369 415 372
433 399 426 390 440 348
488 455 480 450 505 325
555 530 546 525 600 304
635 612 612 609 714 284
759 707 685 706 850 265
342 268 336 277 368 299
390 309 384 318 422 343
451 360 444 370 490 391
483 408 479 412 547 366
519 433 510 440 580 342

580 501 570 509 665 320

671 596 660 600 805 299


720 693 708 700 900 279
805 814 825 817 1030 261
Motor starter Selection

Full Voltage Starting Auto Transformer Starting Part Winding Starting Star-Delta Starting Hp
440V 230V 440V 230V 440V 230V 440V
2 Hp
5 Hp
10 Hp 7.5 Hp 10 Hp 10 Hp
25 Hp 15 Hp 25 Hp 25 Hp
50 Hp 30 Hp 50 Hp 50 Hp
100 Hp 50 Hp 100 Hp 75 Hp
200 Hp 100 Hp 200 Hp 150 Hp
400 Hp 200 Hp 400 Hp 300 Hp
600 Hp 300 Hp 600 Hp 450 Hp
900 Hp 450 Hp 900 Hp 700 Hp
1600 Hp 800 Hp 1600 Hp 1300 Hp
FLA Instantanous C.B Time Delay Fuse
motor details

Motor Data

Motor Rating 10 Kw 10.00


System Voltage V (L-L) 240 Volt 1 Ph
Supplay Frequency 50 Hz
Pole 4 No
Motor Spped 1000 Rpm
Locked Rotor Code B
Motor Demand Factor 1
Motor Service Factor 2
Motor Operating Temperature 30 C
Motor Starting Method Dol
Motor Starting P.F
Motor Running P.F 0.8
Motor Full Load Efficiency 100 % 1
Date
Jignesh.Parmar www.electricalnotes.wordpress.com 6-Nov-21
jiguparmar@yahoo.com

Motor Details

Motor Consumed Load 10.00 Kw 7.46


Motor Starting Current 520.83 Amp
Motor Full Load Current 52.08 Amp
Syncronus Spped(Ns) 1500 Rpm
Slip 33.33 %
Locked Rotor Current (LRA) 104.13 Amp

Maximum Size of OverLoad Perotection 65.10 Amp

Standared(On Time Delay) Fuse (Max) 156.25 Amp


On Time Delay Fuse (Max) 91.15 Amp
Instantaneous Trip C.B(Max) 416.67 Amp
Inverstime C.B(Max) 130.21 Amp
Dol
Y-D
Hp Auto Tra.
Kw Soft
1 Ph Freq.Conv
3 Ph 3.35
A 0
B 3.15
C 3.55
D 4
E 4.5
F 5
G 5.6
H 6.3
J 7.1
K 8
L 9
M 10
N 11.2
P 12.5
R 14
S 16
T 18
U 20
V 24
3.15
3.55
4
4.5
5
5.6
6.3
7.1
8
9
10
11.2
12.5
14
16
18
20
24