I/A Series® HARDWARE

Product Specifications

PSS 21H-2Y14 B4
FEM100 Fieldbus Expansion Module

The Fieldbus Expansion Module (FEM100) provides four Expanded Fieldbuses to the Field Control Processor
270 (FCP270). Each of the four Expanded Fieldbuses can accommodate up to thirty-two 200 Series
Fieldbus Modules (FBMs).

FEATURES
 For typical control usage enables a FCP270 to  Two-slot Expansion Baseplate accommodates
communicate with up to 128 of the 200 Series FEM100 modules only, used to upgrade existing
FBMs, over four Expanded Fieldbuses FCP270 installations
 Redundancy minimizes communication  Four-slot Expansion Baseplate accommodates
interruption from Expanded Fieldbus 1 through 4 two FCP270 control processors and their fiber
optic splitter/combiners, plus two FEM100
 Two-Slot and Four-Slot FEM100 Expansion
modules, for new installations.
Baseplates both support the 2 Mbps Module
Fieldbus for 200 Series (or equivalent) FBMs  Harsh (Class G3 - ISA S71.04) contamination
protection.
PSS 21H-2Y14 B4
Page 2

OVERVIEW The FEM100s are installed in a DIN rail mounted


The FEM100 module provides four Expanded Modular Two-Slot or Four-Slot Expansion Baseplate
Fieldbuses to an I/A Series FCP270 to increase the for 2 Mbps communication between the FBMs and
number of 200 Series (or equivalent) FBMs FCP270 modules (see Figure 1 and Figure 2).
supported by the FCP270 modules. The FEM100
module supports the 2 Mbps HDLC module Fieldbus
for communication between the I/A Series® FCP270
and the 200 Series FBMs (see Figure 3 on page 5).

To/From Expanded FEM100 Module DIN Rail Two-Slot Expansion Baseplate


Fieldbuses 1-4 Redundant Vertical Mounted Only

To/From
Field
Control
Processor

Terminated
With
Terminator
P0916RB

Figure 1. Redundant FEM100 Modules on DIN Rail Mounted Modular Two-Slot Expansion Baseplate
PSS 21H-2Y14 B4
Page 3

FCP270 Fault-Tolerant Four-Slot Expansion Baseplate


To/From Control Network
Module Pair Vertical Mounted Only
Ethernet Fiber Switch 1/2

100 Mbps
Orange Fiber
Terminated
Cables

Splitter/
Combiner
Pair

To/From
Expanded
To/From Fieldbuses
Expanded 1-2
Fieldbuses
3-4
FEM100
FEM100 Module
(Bus B)
Module
(Bus A)

Figure 2. Redundant FEM100 Modules on DIN Rail Mounted Modular Four-Slot Expansion Baseplate

FEM100 MODULE DESIGN The FEM100 can be removed/replaced from an


FEM100 modules have a compact design, with a Expansion Baseplate without removing power. Light-
rugged extruded aluminum exterior for physical emitting diodes (LEDs) incorporated into the front of
protection of the electronics. Enclosures specially the FEM100 indicate module Fieldbus
designed for mounting of DIN rail mounted Fieldbus communications activity and module status.
equipment provide various levels of environmental The FEM100 communicates to the FCP270 over the
protection for the FEM100 modules, up to harsh 2 Mbps HDLC Fieldbus, as shown in Figure 3 on
environments per ISA Standard S71.04. page 5.
PSS 21H-2Y14 B4
Page 4

HIGH AVAILABILITY MODULE FIELDBUS COMMUNICATION


A pair of FEM100 modules provides redundancy for The Expansion Baseplates support the 2 Mbps
the Extended Fieldbuses to maintain very high module Fieldbus. They connect to the 2 Mbps
subsystem availability. When both modules are module Fieldbus for communication to all 200 Series
active, the FCP270 sends and receives DIN I/O FBMs, the Siemens APACS+™ and
communications across both A and B buses. In the Westinghouse competitive migration modules (see
case of a FEM100 module failure, the FCP270 “Devices Supported” on page 7).
switches all traffic to the bus with the available The 2 Mbps module Fieldbus is redundant and all
FEM100 module until the failed module is replaced. 200 Series modules can receive/transmit messages
Either module may be replaced without upsetting over both A and B buses.
input or output communications to the other module.

EXPANSION BASEPLATE MOUNTING


The FEM100 modules mount on either the Two-Slot
or Four-Slot Expansion Baseplate. These baseplates
are DIN rail mounted and vertically oriented only.
These baseplates include signal connectors for the
FEM100s, redundant independent dc power
connections, and four cable connections to the
2 Mbps HDLC Expanded Fieldbuses.
The Two-Slot Expansion Baseplate includes a
redundant I/O cable connection to the FCP270s.
One connector supports both A and B buses, while
the other is terminated. Alternatively, both connectors
can be used in conjunction with a Fieldbus
Splitter/Terminator (P0926KW).
The Four-Slot Expansion Baseplate includes two
slots for mounting a fault-tolerant pair of FCP270s
and their fiber optic splitter/combiners.
For more information on these baseplates, refer to
DIN Rail Mounted Modular Baseplates
(PSS 21H-2W6 B4).
PSS 21H-2Y14 B4
Page 5

F F FCP270 Either in Modular Baseplate or


C C in Four-Slot Expansion Baseplate with FEM100s
P P
2 2 FCP270 Control Processor
7 7 (Fault-Tolerant)
0 0

2 Mbps HDLC Module Fieldbus


(Shielded Twisted Pair Cables)
Includes Fieldbus A and B
FEM100s Either in Two-Slot Expansion Baseplate
or with FCP270(s) in Four-Slot Expansion Baseplate F F 2 Mbps HDLC Expanded Module Fieldbus
E E (Shielded Twisted Pair Cables)
FEM100 Modules M M Includes Fieldbus A and B
(Redundant) 100 100 Total length (CP-to-last baseplate) is
up to 305 m (1000 ft) Module Fieldbus Cables
DIN Rail Mounted 200 Interconnect Baseplates
Series FBMs or Competitive Each Chain Total Length
Migration Modules (See Up to 60 m (198 ft)
“Devices Supported” on
Baseplate or
page 7.) Equipment Rack

Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus

F F F F F F F F F F F F
B B B B B B B B B B B B
M M M M M M M M M M M M

Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus

F F F F F F F F F F F F
B B B B B B B B B B B B
M M M M M M M M M M M M

Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus

F F F F F F F F F F F F
B B B B B B B B B B B B
M M M M M M M M M M M M

Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus Redundant Fieldbus

F F F F F F F F F F F F
B B B B B B B B B B B B
M M M M M M M M M M M M

EXPANDED FIELDBUS 1 EXPANDED FIELDBUS 2 EXPANDED FIELDBUS 3 EXPANDED FIELDBUS 4


NOTE: First and Last Fieldbus Connector in each Chain must be terminated (P0916RB).

Figure 3. Typical Expanded Fieldbus Network Configuration (Simplified) With Four Expanded Baseplate Groups
PSS 21H-2Y14 B4
Page 6

EXPANDED FIELDBUS EXTENSION VIA The FCM2Fs are mounted on any baseplate which
FCM2F2/FCM2F4/FCM2F10 FIELDBUS accepts both FCMs and FBMs. For the Expanded
COMMUNICATIONS MODULES Fieldbuses, FCM2Fs must be installed redundant,
The FCM2F2/FCM2F4/FCM2F10 Fieldbus one on each end of one of the “A” and “B” cables of
Communications Modules provide baseplate-to- the Expanded Fieldbuses (four FCM2Fs total).
baseplate fiber optic extension of the Expanded The FCM2Fs can extend any of the Expanded
Fieldbuses. This allows DIN rail mounted Fieldbus
Fieldbuses between the FEM100 baseplate and the
Modules (FBMs) to be locally, or remotely distributed FBM baseplates. The redundant FCM2F pair on the
in multiple enclosures for strategic placement of baseplate-side of the fiber optic extension may be
input/output points.
installed on the first FBM baseplate in the chain, or
The three versions of the FCM2Fs – FCM2F2, on a separate baseplate, such as an FCM/FBM 2-
FCM2F4, and FCM2F10 – offer three different position baseplate. Keeping the FCM2F pair on a
maximum baseplate-to-baseplate fiber optic cabling separate baseplate allows the baseplate chain to use
distances: up to 2 km (1.24 mi), up to 4 km (2.48 mi), all 32 possible slots for FBMs, while including the
and up to 10 km (6.2 mi), respectively. FCM2F2 and FCM2F pair on the first baseplate in the chain leaves
FCM2F4 are used with multimode graded-index fiber 30 slots for FBMs. Figure 4 illustrates this
cable, and FCM2F10 is used with single-mode fiber configuration for the first Expanded Fieldbus.
cable.
PSS 21H-2Y14 B4
Page 7

2 Mbps HDLC Module Fieldbus (Shielded Twisted Pair Cables) Includes Fieldbus A and B

FCP270 Control F F FEM100s (Redundant)


Processor C C F F
(Fault-Tolerant) P P E E
2 2 M M
2 Mbps HDLC Expanded Module Fieldbus
7 7 100 100
(Shielded Twisted Pair Cables)
0 0 Includes Fieldbus A and B
(Four Expanded Fieldbuses)
OR
A B
B A
F F F F
FCM2F2/4/10s FCM2F2/4/10s
C C C C
(Redundant) In (Redundant) In
M M M M
FCM/FBM 2-Position FCM/FBM 2-Position
2 2 2 2
Baseplate Baseplate
F F F F

Fiber Optic Cables


(A and B) First FCM/FBM Baseplate
F F In Chain
C C
First FCM/FBM Baseplate M M Redundant Fieldbus
In Chain 2 2
F F F F
F
C C
Redundant Fieldbus B
M M
M
2 2
F F F F F
Shielded Twisted
B B B
Pair Cables
M M M Fiber Optic Cables
(A and B)
(A and B)
To Next Baseplate in Chain To Next Baseplate in Chain
(Chain has up to four Baseplates, (Chain has up to four Baseplates,
32 FBMs total) 30 FBMs total)

EXPANDED FIELDBUS 1 EXPANDED FIELDBUS 1


(Similar for Expanded Fieldbuses 2-4) (Similar for Expanded Fieldbuses 2-4)

Figure 4. FCM2F2/FCM2F4/FCM2F10 Fieldbus Communications Modules on Expanded Fieldbus

DEVICES SUPPORTED  Field Device Systems Integrator (FDSI) modules


The FEM100 supports the following devices on the  DCS Fieldbus Modules for Siemens APACS+
2 Mbps module Expanded Fieldbus: systems
 All 200 Series DIN rail mounted FBMs (FBM201,  DCS Fieldbus Modules for Westinghouse
FBM202, and so forth) WPDF® systems.
 Fieldbus Communications Modules,
FCM2F2/FCM2F4/FCM2F10, for remote
Fieldbuses
PSS 21H-2Y14 B4
Page 8

NOTE
Existing 200 Series FBMs must be upgraded
with I/A Series system 8.3 release IOM files
to support the Expanded Fieldbus.

LED INDICATORS
Light-emitting diodes (LEDs) on the front of the
FEM100 module provide visual indication of the:
 FEM100 operational status - power and watch
dog timer
 HDLC transmit/receive - for Field Control
Processors
 HDLC transmit/receive - for Expanded Fieldbuses
1-4

F U N C T I O N A L S P E C I F I C AT I O N S

Process I/O Communications FCP270 Fieldbus and Expanded Fieldbuses


MODULE FIELDBUS COMMUNICATIONS (1-4) with FCM2Fs
Transmission Rate The cable (not counting the fiber optic
2 Mbps for 200 Series DIN FBMs cabling provided by the FCM2F2/4/10
modules) cannot exceed 60 m (198 ft)
Process I/O Capacity (2 Mbps Fieldbus) (see Figure 6)
CABLE LENGTH
FCP/FEM FCP
FCP270 Fieldbus and Expanded Fieldbuses FCP FCP Baseplate Baseplate FCP FCP
(1-4) without FCM2Fs 60 m
FEM (198 ft)
The cable length of the Fieldbus cannot FEM FEM Baseplate FEM FEM
exceed 60 m (198 ft) (see Figure 5)
FCM FCM FCM FCM
FCP/FEM FCP 2Fx 2Fx 2Fx 2Fx
10 km* 10 km*
FCP FCP Baseplate Baseplate FCP FCP (6.2 mi) (6.2 mi)
60 m FCM FCM FCM FCM
FEM (198 ft) 2Fx 2Fx 2Fx 2Fx
FEM FEM Baseplate FEM FEM
First First
FBM FBM FBM FBM
First First Base Base Base Base
FBM FBM FBM FBM Plate Plate Plate Plate
60 m 60 m
Base Base Base Base
(198 ft) (198 ft)
Plate Plate 60 m Plate Plate 60 m Last Last
(198 ft) (198 ft) FBM FBM in FBM FBM in
Last Last Base Base Chain Base Base Chain
FBM FBM in FBM FBM in Plate Plate Plate Plate
Base Base Chain Base Base Chain * 20 km distance is allowed through
Plate Plate Plate Plate the use of four pairs of FCM2F10s.

Figure 5. Expanded Fieldbus Cable Length Restrictions Figure 6. Expanded Fieldbus Cable Length Restrictions
w/FCM2Fs
PSS 21H-2Y14 B4
Page 9

F U N C T I O N A L S PE CI F I C AT I O N S ( C O N T I N U E D )

200 SERIES FBMS ELECTROMAGNETIC COMPATIBILITY (EMC)


32 (maximum) Fieldbus Modules per Expanded (CONT.)
Fieldbus (four per FEM100 pair). IEC 61000-4-8 Power Frequency Magnetic
Up to 128 FBMs for typical control usage. Field Immunity
Number of FBMs depends on control processor 30 A/m at 50 and 60 Hz
sizing constraints (refer to FCP270 Sizing PRODUCT SAFETY
Guidelines (B0700AV)). Underwriters Laboratories (UL) for U.S. and
Power Requirements Canada
INPUT VOLTAGE RANGE UL/UL-C listed as suitable for use in
21 to 26 V dc UL/UL-C listed Class 1, Groups A-D;
Division 2; temperature code T5 enclosure
CONSUMPTION
based systems. These modules are also UL
2.2 W (maximum)
and UL-C listed as associated apparatus for
Regulatory Compliance supplying non-incendive communication
ELECTROMAGNETIC COMPATIBILITY (EMC) circuits for Class 1, Groups A-D hazardous
European EMC Directive 89/336/EEC locations when connected to specified
Meets: EN 50081-2 Emission standard I/A Series processor modules as described
EN 50082-2 Immunity standard in the I/A Series DIN Rail Mounted
EN 61326 Annex A (Industrial Levels) Subsystem User’s Guide (B0400FA).
CISPR 11, Industrial Scientific and Medical Communications circuits also meet the
(ISM) Radio-frequency Equipment - requirements for Class 2 as defined in
Electromagnetic Disturbance Characteristics Article 725 of the National Electrical Code
- Limits and Methods of Measurement (NFPA No.70) and Section 16 of the
Meets: Class A Limits Canadian Electrical Code (CSA C22.1).
IEC 61000-4-2 ESD Immunity Conditions for use are as specified in the
6 kV current discharge I/A Series DIN Rail Mounted Subsystem
IEC 61000-4-3 Radiated Field Immunity User’s Guide (B0400FA).
10 V/m at 26 to 1000 MHz European Low Voltage Directive 73/23/EEC
IEC 61000-4-4 Electrical Fast and Explosive Atmospheres (ATEX) directive
Transient/Burst Immunity 94/9/EC
2 kV on I/O, dc power and communication CENELEC (DEMKO) certified as EEx nA IIC
lines T4 for use in CENELEC certified Zone 2
enclosure certified as associated apparatus
IEC 61000-4-5 Surge Immunity
for supplying non-incendive field circuits for
2kV on ac and dc power lines; 1kV on I/O
Zone 2, Group IIC, potentially explosive
and communications lines
atmospheres when connected to specified
IEC 61000-4-6 Immunity to Conducted
I/A Series processor modules as described
Disturbances Induced by Radio-frequency
in the I/A Series DIN Rail Mounted
Fields
Subsystem User’s Guide (B0400FA).
10 V (rms) at 150 kHz to 80 MHz on I/O,
dc power and communication lines Calibration Requirements
Calibration of the module is not required.
PSS 21H-2Y14 B4
Page 10

E N V I R O N M E N TA L S P E C I F I C AT I O N S ( 1 )

Operating RELATIVE HUMIDITY


TEMPERATURE 5 to 95% (noncondensing)
-20 to +70°C (-4 to +158°F) ALTITUDE
RELATIVE HUMIDITY -300 to +12,000 m (-1,000 to +40,000 ft)
5 to 95% (noncondensing) Contamination
ALTITUDE Suitable for Class G3 (Harsh) environments as defined
-300 to +3,000 m (-1,000 to +10,000 ft) in ISA Standard S71.04, based on exposure testing
Storage according to EIA Standard 364-65, Class III.
TEMPERATURE Vibration
-40 to +85°C (-40 to +185°F) 0.75 g from 5 to 500 Hz

P H Y SI C A L S P E C I F I C AT I O N S

Mounting Dimensions
The redundant installation consists of two modules. A HEIGHT
single module can also be used. 99 mm (3.9 in)
114 mm (4.5 in) including mounting lugs
FEM100 mounts on a Two-Slot (P0973CG) or WIDTH
Four-Slot (P0973CN) Expansion Baseplate. These 44.6 mm (1.75 in)
baseplates can be mounted on a vertical DIN rail.
DEPTH
Refer to PSS 21H-2W6 B4 for details.
105 mm (4.12 in)

Mass
0.6 kg (1.3 lb) approximate (each module)
Part Number
P0973CA

(1) The environmental limits of this module may be enhanced by the type of enclosure containing the module. Refer to the applicable
Product Specification Sheet (PSS) which describes the specific type of enclosure that is to be used.
PSS 21H-2Y14 B4
Page 11

FOR MORE INFORMATION


For more information refer to the following Product
Specification Sheets (PSS):

PSS Number Description

PSS 21H-1B9 B3 Field Control Processor 270 (FCP270)


PSS 21H-2W1 B3 DIN Rail Mounted Subsystem Overview
PSS 21H-2W6 B4 DIN Rail Mounted Modular Baseplates
PSS 21H-2Y3 B3 Fieldbus Communications Module,
FCM2F2/FCM2F4/FCM2F10
PSS 21H-2Y14 B4
Page 12

Invensys Operations Management Invensys, Foxboro, I/A Series, Iand the Invensys logo are
5601 Granite Parkway Suite 1000 trademarks of Invensys plc, its subsidiaries, and affiliates.
Plano, TX 75024 All other brands and product names may be the
United States of America trademarks of their respective owners.
http://iom.invensys.com
Copyright 2005-2011 Invensys Systems, Inc. All rights
reserved. Unauthorized duplication or distribution is strictly
Global Customer Support prohibited.
Inside U.S.: 1-866-746-6477
Outside U.S.: 1-508-549-2424 or contact
your local Invensys representative.
Website: http://support.ips.invensys.com MB 21A 1111