বিষয়ঃ টঙ্গী ৩, ১৩২/৩৩/১১ কেভি গ্রীড উপকেন্দ্রের পাঞ্চ লিস্ট

Subject Sl Description
No
.
1 kVAR Reading of Incomings and GTs Are Not Equal in SAS
2 GT-2 pf Is Shown 0 (Zero) Sometimes
SAS Panel 3 GT-2 Check Meter Does Not Get Connection to SAS
4 1 (One) Mouse for HMI is not supplied
5 1 (One) Adapter for Connection to SAS with HMI is not Supplied. So One
Monitor is Dark

ACDBs 6 Labeling for Boost Mode in 110 V DC Charger-2 Is Not Correct


DCDBs 7 110 V Battery Chargers’ Boost Mode Voltage is 120 V DC
Chargers 8 110 V Charger-2 of 132 kV Floor Can Not be Set in Boost Mode
Manually
9 ACDB-1 , AC Incoming-2 ,Bus Tie, DC Charger-2(110 V, 132 kV
Control Room) Doors Lock Problem

10 K01 Protection Meter Problem


11 kV & 33 11 K16 AC power Fail Alarm
kV Control 12 K19 Alarm Problem
Panel 13 K01 & K25 LED Lamp
14 K25 CB Control Cable Smashed
15 K01 Protection Relay Problem

132 kV 16 GT-1 Multifunction Meter Shows Negative Voltage


Control Panel

CCTV 17 Monitor Mouse Does Not Work


Camera 18 Only Camera 4 Shows Recording

19 TR-3 Fan Group-1 MCB Trips Frequently and Tap Changer MCB
Transformers Problem
20 Breather Indicator LEDs of GT-1 ,GT-2, TR-1 and TR-2 Don’t Lit
21 Temperature Indicator Problem TR-1 ,TR-3 and GT-2
22 TR-3 Oil Monitor is Broken

23 Main Glass Door Can Not be Locked by Key


24 Water need to be Poured in Water Pump to Start it.
Miscellaneous 25 Yard Light MCB’s Current Rating Need to be Heighten
26 4 (Four) Nos DC Lights are Damaged
27 One Wall Mounted Shelf Need to Set
28 Water Percolate in 132 kV Control Room During Rain Due to Leakage in
the Roof.