RCBO’s classification according to EN 61009-1 Ed.

2012
RCBO’s may be classified according to: Type A
• The behavior in presence of dc current Certain devices during faults can be the source
(types for general use). of non-sinusoidal earth leakage currents
- Type AC (DC components) due to the electronic
- Type A components e.g.: diodes, thyristors…..
• The time-delay (in presence of residual current) The type A RCBO’s are designed to ensure that under
- RCD’s without time delay: Type for general use this conditions the residual current devices operate
- RCD’s with time delay: Type S for selectivity on sinusoidal residual current and also with
Type AC pulsating direct current(*) which occur suddenly
The type AC RCBOs are designed to release with or slowly rise in magnitude.
sinusoidal residual currents which occur suddenly or (*) Pulsating direct current: current of pulsating wave form which assumes, in

slowly rise in magnitude. each period of the rated power frequency, the value 0 or a value not

exceeding 0.006 A dc during one single interval of time, expressed in

angular measure of at least 150º.


Type Ai Selectivity
Type AI and ACI (High immunity to nuisance Vertical selectivity
tripping) In an installation with RCBO’s installed in series we
Electric equipment incorporates more and more need to pay special attention to the vertical
electronic components which causes nuisance selectivity, in order to ensure that in case of earth
tripping to the conventional 30mA RCBO’s type A leakage only the RCBO which is immediately
or AC (always in the most critical moment like upstream of the fault point will operate.
weekends, areas with no people presence…) due Selectivity is ensured when the characteristic
to overvoltages or high frequency currents produced time/current of the upstream RCD (A) is above the
by atmospheric disturbances, lighting equipment characteristic time /current of the downstream RCBO
(electronic balasters), computers, appliances, (B). To obtain vertical selectivity we should take into
connections to long cables which induce a high consideration the following parameters:
capacity to ground, etc. The RCD placed at the top of the installation shall
Some times the filter incorporated on the standard be Type S. The residual operating current of the
RCBO’s type AC which are protected to prevent RCBO installed downstream shall have a lower
nuisance tripping against peak currents up to 250 A residual operating current than the RCD installed
8/20 μs, does not avoid 100% unwanted tripping. upstream according to:

Installations with lighting equipment incorporating


electronic balasters or computers.
The most typical problem in these installations is the
tripping of the RCBO when switching the equipment
ON-OFF. It is recommended that, in case several
devices are installed in the same line, the sum of all
leakages shall not exceed 1/3 lΔn since any
disturbance in the line can trip the RCBO. For this kind
of installation it is recommended to split up circuits.

RCBO’s type AI have a tripping characteristic


according to EN 61009-1 2012.

Type AC .....................250 A 8/20 μs Horizontal selectivity


Type A,Ai ..........................3000 A 8/20 μs To have horizontal selectivity in an installation with
RCBO’s we need to avoid the use of RCBO’s in
cascading. Every single circuit of the installation
shall be provided with an RCBO of the appropriate
residual operating current.
Characteristics according to IEC/EN 60898-1 Thermal release according Norway NEK400:2010 installation rules
Residual Current circuit Breaker with Overcurrent Protection (RCBO) Exmaple of C curve In=10, 16, 20 A
are intended for the protection of wiring installations against
both overloads and short-circuits in domestic or commercial
wiring installations where operation is possible by uninstructed 10
people.

100
C10 Min
C10 Max
C16 Min
10 C16 Max
C20 Min
C20 Max

0.1
Magnetic release
An electromagnet with plunger ensures instanta neous
tripping in the event of short-circuit. The standard
distinguishes two different types, follo wing the current
for instantaneous release: type B and C.

0
1 10 100

Infl uence of ambient air


temperature on the rated current
The maximum value of the current which can flow
through an RCBO depends of the nominal current of the
Thermal release* RCBO, the conductor cross-section as well as of the
The release is initiated by a bimetal strip in case of ambient air temperature.
overload. The standard defi nes the range of releases for The values shown in the table below are for devices in
specifi c overload values. free air. For devices installed with other modular devices
Reference ambient temperature is 30°C. in the same switchboard a correction factor (K) shall be
applied relative to the mounting situation of the RCBO, the
ambient temperature and the number of main circuits in
the installation (EN 60439-1):

* From 10A to 20A special thermal tripping curves adapted


to according Norway NEK400:2010 installation rules
Calculation example
Within a distribution panel consisting of eightRCBO’s
2PC16 with an operating ambient temperature of 45°C,
which is the highest temperature at which the RCBO can
operate without unwanted tripping.
Calculation
The correction factor K=0,7, for use in an eight circuit
installation: 16A x 0,7= 11,2A
As the RCBO is working at 45°C, another factor shall be
applied (90% = 0,9):
In at 45°C = In at 30°C x 0,9 = 11,2A x 0,9 = 10,1A
The thermal calibration of the RCBO’s was carried out at an
ambient temperature of 30°C. Ambient temperatures different
from 30°C infl uence the bimetal and this results in
earlier or later thermal tripping.
Tripping current as a function of the frequency Toggle
The toggle permits to switch the RCBO ON or OFF
All RCBO’s are designed to work at frequencies of 50-60 Hz, Printing on the toggle provides information of the real
(AC: 50 Hz, A, Ai: 50/60Hz) contact position.
therefore to work at different values, consideration must
be given to the variation of the tripping characteristics. 0-OFF
The thermal tripping does not change with variation of Contacts in open position.
the frequency but the magnetic tripping values can be Ensures a distance between
up to 50% higher than the ones at 50-60 Hz. contacts > 5mm in the
For DC current magnetic tripping is 50% higher. Unibis™ Compact RCBO range.
Tripping current variations
I-ON
Contacts in closed position.
Power losses Ensures continuity in the
main circuit.

Power Losses
The power losses are calculated by measuring the voltage
drop between the incoming and the outgoing terminals of
the device at rated current.
Association (Back-up protection)
Association consists the use of an MCB with lower
breaking capacity than the presumed one at the
place of its installation. If another protective device
installed upstream is co-ordinated so that the
energy let-through by these two devices does
not exceed that which can be withstood without
damage by the device placed downstream and
the conductor protected by these devices.
In the event of short-circuit, both protective devices
will disconnect, therefore the selectivity between
them is considered as partial.
Association reduces the cost of the installation in
case of high short-circuit currents.
To obtain association between a breaker and a
protective device, several conditions linked to the
components characteristic must be fullfilled. Those
have been defined by calculation and testing.
Back-up protection (association)
Back Up Protection Tables valid for use with modular devices.

Back-up: Upstream MCB's ElfaPlus(RED LINE)/Downstream Unibis Compact


230V Icc Max (kA)
Upstream Elfa+/Red Line

G60
EP60/

G100
EP100/

GT25
EP250/

GT25
EP250/

GT25
EP250/

Hti
80-125
0,5-63

0,5-63
230 V

32-40

50-63
<32
In
Downstream Icu 20 30 50 40 30 15
Unibis Compact Icn
EPCN31 - EPC30 2-40 4,5 3 10 12.5 12.5 12.5 12.5 --
EPCN451 - EPC45 2-40 6 4,5 22 25 25 25 25 15
EPCN61 - EPC60 2-40 10 6 25 30 30 30 30 15
DP60 4-40 10 6 15 15 15 15 15 --
DP100 4-40 15 10 -- -- 50 40 30 --
DPC45 6-40 -- 4,5 22 25 25 25 25 15
DPC60 6-40 -- 6 25 30 30 30 30 15
DPC100 6-40 -- 10 25 30 30 30 30 15
EP30/G30 15 20 22 22 22 15
EP45/G45 6-40 6 4,5 15 20 22 22 22 15
EP60/G60 0,5-63 20 6 -- 30 50 40 30 --
EP100/G100 0,5-63 30 10 -- -- 50 40 30 --

Back-up: Upstream MCB's ElfaPlus(RED LINE)/Downstream Unibis/Elfa Plus/Red Line


400/415VIcc Max (kA)
Upstream
G60
EP60/

100
EP100/G

T25
EP250/G

T25
EP250/G

T25
EP250/G

Hti
80-125
0,5-63

0,5-63

32-40

50-63

400/415V
<32

In
Downstream Icu 10 15 25 20 15 10
Unibis/G/EP Icn
EPC45 2-40 6 4,5 10 15 25 20 15 10
EPC60 2-40 10 6 10 15 25 20 15 10
EP45/G45 6-40 6 4,5 10 15 25 20 15 10
EP60/G60 0,5-63 10 6 -- 15 25 20 15 --
EP100/G100 0,5-63 15 10 -- -- 25 20 15 --
Back-up protection (association)
Back up Record Plus Moulded Cases Circuit Breakers/ Modular Protection 1-pole + N / 2-pole 230/240V IEC 947-2

Upstream Record PlusTM type

FD160C

FD160E

FD160S

FD160N

FD160H

FD160L

FE160N

FE160H

FE160L

FE250V
FE250N

FE250H

FE250L

FG400N

FG400H

FG400L

FG630N

FG630H

FG630L

FK800N

FK800H

FK800L

N
FK1250

H
FK1250
L
FK1250
N
FK1600

H
FK1600
230 V
IEC 60898/61009-1 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
Downstream IEC 60947-2 25 40 50 85 100 200 85 100 200 65 85 100 200 85 100 200 85 100 200 85 100 170 85 100 170 85 100
Red line/Elfa+ Curves
EPC30 3 3 B,C 15 15 15 15 15 15 12 12 12 10 10 10 10 -- -- -- -- -- -- -- -- -- -- -- -- -- --
EPC451N/EPC45 5 5 B,C 15 18 18 18 18 18 15 15 15 12 12 12 12 -- -- -- -- -- -- -- -- -- -- -- -- -- --
EPC61N/EPC60 6 10 B,C 16 20 23 23 23 23 20 20 20 16 16 16 16 -- -- -- -- -- -- -- -- -- -- -- -- -- --
DM60/DP60 6 10 B,C 22 25 30 36 85 85 36 85 85 30 36 65 65 16 16 16 14 14 14 -- -- -- -- -- -- -- --
DM100/DP100 10 15 B,C 25 36 42 50 100 100 42 100 100 30 36 65 65 18 18 18 16 16 16 -- -- -- -- -- -- -- --
DPC45 4.5 -- B,C 15 18 18 18 18 18 15 15 15 12 12 12 12 -- -- -- -- -- -- -- -- -- -- -- -- -- --
DPC60 6 -- B,C 16 20 23 23 23 23 20 20 20 16 16 16 16 -- -- -- -- -- -- -- -- -- -- -- -- -- --
DPC100 10 -- B,C 25 36 42 50 100 100 42 100 100 30 36 65 65 18 18 18 16 16 16 -- -- -- -- -- -- -- --
G45/EP45 4.5 10 B,C,D 22 25 30 36 85 85 36 85 85 36 36 65 65 16 16 16 14 14 14 -- -- -- -- -- -- -- --
G60/EP60 6 20 B,C,D 25 36 42 50 100 100 50 100 100 36 42 85 85 22 22 22 18 18 18 -- -- -- -- -- -- -- --
G100/EP100 10 30 B,C,D -- 42 50 65 100 100 65 100 100 42 50 85 85 -- -- -- -- -- -- -- -- -- -- -- -- -- --
GT25/EP250 <32A 50 B,C,D -- -- -- 65 100 100 65 100 100 -- 65 100 100 -- -- -- -- -- -- -- -- -- -- -- -- -- --
GT25/EP250 32A&40A 40 B,C,D -- -- 50 65 100 100 65 100 100 42 50 85 85 -- -- -- -- -- -- -- -- -- -- -- -- -- --
GT25/EP250 50A&63A 30 B,C,D -- 42 50 65 100 100 65 100 100 42 50 85 85 -- -- -- -- -- -- -- -- -- -- -- -- -- --
Hti 15 B,C 22 36 42 85 100 100 50 100 100 36 42 80 80 -- -- -- -- -- -- -- -- -- -- -- -- -- --

Back up Record Plus Moulded Cases Circuit Breakers/ Modular Protection 400/415V IEC 947-2 230/240V IEC 947-2

Upstream Record PlusTM type


FD160C

FD160E

FD160S

FD160N

FD160H

FD160L

FE160N

FE160H

FE160L

FE250V
FE250N

FE250H

FE250L

FG400N

FG400H

FG400L

FG630N

FG630H

FG630L

FK800N

FK800H

FK800L

FK1250N

FK1250H

FK1250L

FK1600N

FK1600H
400/415V
IEC 60898 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
Downstream IEC 60947-2 18 25 36 50 80 150 50 80 150 36 50 80 150 50 80 150 50 80 150 50 80 150 50 80 150 50 80
Red line/Elfa+ Curves
EPC32, 33 & 34 3 4.5 B,C 15 18 22 25 30 36 25 30 36 18 22 25 30 12 12 12 10 10 10 -- -- -- -- -- -- -- --
EPC452, 453 & 454 4.5 6 B,C 15 18 22 25 30 36 25 30 36 18 22 25 30 12 12 12 10 10 10 -- -- -- -- -- -- -- --
EPC 62,63 & 64 6 10 B,C 16 20 23 25 34 40 28 34 40 20 25 30 32 15 15 15 10 10 10 -- -- -- -- -- -- -- --
G32, 33 & 34/EP30 3 5 B,C 15 18 22 25 30 36 25 30 36 18 22 25 30 12 12 12 10 10 10 -- -- -- -- -- -- -- --
G452, 453 & 454/EP40 4.5 6.0 B,C 15 18 22 25 30 36 25 30 36 18 22 25 30 12 12 12 10 10 10 -- -- -- -- -- -- -- --
G60/EP60 6 10 B,C,D,K 18 22 25 30 36 43 30 36 42 22 30 36 36 16 16 16 12 12 12 -- -- -- -- -- -- -- --
G100/EP100 10 15 B,C,D,K 18 25 30 36 42 50 36 42 50 25 30 36 36 22 22 22 16 16 16
GT25/EP250 <=25A -- 25 B,C,D -- -- 30 36 42 50 36 42 50 -- 36 42 42 -- -- -- -- -- -- -- -- -- -- -- -- -- --
GT25/EP250 32 & 40A -- 20 B,C,D -- -- 30 36 42 50 36 42 50 -- 36 42 42 -- -- -- -- -- -- -- -- -- -- -- -- -- --
GT25/EP250 50 & 63A -- 15 B,C,D 18 25 30 36 42 50 36 42 50 25 30 36 36 -- -- -- -- -- -- -- -- -- -- -- -- -- --
Series HTI -- 10 B,C,D 15 18 25 30 36 42 30 36 42 18 30 36 36 -- -- -- -- -- -- -- -- -- -- -- -- -- --
Selectivity Total selectivity
An installation with some protective devices in Selectivity is total in the event of a short-circuit
series (a protective device must be placed at the fault and only disconnects the protective device B
point where a reduction of the cross sectional area immediately upstream of the fault point.
of the conductors or another change causes The let-through energy (I2t) of the downstream
modification in the characteristics of the installation) protective device shall be lower than the one of the
is considered as selective when, in the event of upstream protective device.
short-circuit, the installation is interrupted only by
the device which is immediately upstream of the
fault point. Selectivity is ensured when the
characteristic time/current of the upstream MCB (A)
is above the characteristic time /current of the
downstream MCB (B). Selectivity may be total or
partial.

Partial selectivity
Selectivity is partial when the disconnection of the
protective device (A) is ensured only up to a certain
level of the current.
Selectivity Tables valid for use with modular devices.
Upstream C Curve Downstream B Curve
Upstream
C Curve
EP60 EP100 EP250 G60 G100 GT25 Hti
Downstream In 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A
B Curve 6A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
10A 0.15 0.18 0.23 0.27 0.35 0.45 T T T
EPCN45 16A 0.23 0.27 0.35 0.45 4 T T
EPCN60 20A 0.27 0.35 0.45 4 T T
DPC45 25A 0.27 0.35 0.45 3.5 1.5 1.5
DPC60 32A 0.35 0.45 3.5 1.5 1.5
DPC100 40A 1.5 1.5

Upstream C Curve Downstream B Curve


Upstream
C curve
EP60 EP100 EP250 G60 G100 GT25 Hti
Downstream In 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A
B Curve 6A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
10A 0.15 0.18 0.23 0.27 0.35 0.45 6 T T
EP60/G60 16A 0.23 0.27 0.35 0.45 4 6 6
EP100/G100 20A 0.27 0.35 0.45 4 6 6
EP250 25A 0.27 0.35 0.45 3.5 6 6
GT25 32A 0.35 0.45 3.5 6 6
40A 1.6 5 5
50A
63A

Upstream C Curve Downstream C Curve


Upstream
C Curve
EP60 EP100 EP250 G60 G100 GT25 Hti
Downstream In 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A
C Curve 2A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
3A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
4A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
EPCN45 6A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 4.5 T T
EPCN60 10A 0.15 0.18 0.23 0.27 0.35 0.45 4.5 T T
DP60/DM60 16A 0.23 0.27 0.35 0.45 2 5 5
DP100/DM100 (2) 20A 0.27 0.35 0.45 2 5 5
DPC45 25A 0.27 0.35 0.45 1.5 4.5 4.5
DPC60 32A 0.35 0.45 1.5 2.3 2.3
DPC100 (2) 40A 0.45 2.3 2.3

Upstream C Curve Downstream C Curve


Upstream
C Curve
EP60 EP100 EP250 Hti
Downstream In 10A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A
C Curve 0,5A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
1A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
2A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 T T T
3A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 9 T T
EP30 4A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 9 6 6
EP45 6A 0.07 0.1 0.15 0.18 0.23 0.27 0.35 0.45 4.5 6 6
EP60 10A 0.15 0.18 0.23 0.27 0.35 0.45 4.5 6 6
EP100 16A 0.23 0.27 0.35 0.45 2 5 5
EP250 20A 0.27 0.35 0.45 2 5 5
25A 0.27 0.35 0.45 1.5 4.5 4.5
32A 0.35 0.45 1.5 2.3 2.3
40A 0.45 2.3 2.3
50A
63A
(2) Icc limited to 10kA
T=Total: selectivity untill the Icu of the downstream device

Example
A combination of an MCB C20 with an upstream
MCB C100 guarantees selectivity up to a shortcircuit
level of 5 kA.
Selectivity Tables valid for use with Record Plus Moulded Case Circuit Breakers Low Amperages

Upstream FDC & FDE 160 LTM FDS, N, H & L 160 LTMD FE160N, H & L LTM FE160N, H & L SMR1
In (A) 16A 20A 25A 32A 16A 20A 25A 32A 25A 32A 40A 50A 25A

Downstream
Selectivity limit in kA *
Red Line/Elfa Plus < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 T
EPC30 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 T
G30 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 T
B/C curve 20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Red Line/Elfa Plus < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 T
EPC45/DPC45 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 T
G45/EP45 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 T
B/C curve 20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Red Line/Elfa Plus < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 T
EPC60 & DME60/DPC60 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 T
B/C curve 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 T
20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Red Line/Elfa Plus < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
DM60 & DMT60/DP60 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
DM100 & DMT100 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 6
B/C curve 20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Red Line/Elfa Plus < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
G60/EP60 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
DPC100 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 6
DME100/DP100 20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
B/C curve 25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Red Line/Elfa Plus < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
G100/EP100 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
GT25/EP250 & EP250M 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 6
B/C curve 20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Surion < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
GPS1BS & 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
GPS1MS 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 6
GPS2BS & 20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
GPS2MS 25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Surion < =6A 0.16 0.2 0.25 0.32 0.16 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
GPS1BH & 10A -- 0.2 0.25 0.32 -- 0.2 0.25 0.32 0.2 0.26 0.32 0.5 6
GPS1MH 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 6
GPS2BH & 20A -- -- -- -- -- -- -- -- -- -- 0.32 0.5 --
GPS2MH 25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Record PlusTM 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 6
FD160C & FD160E 20A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
LTM 25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Record PlusTM 16A -- -- -- 0.32 -- -- -- 0.32 -- 0.26 0.32 0.5 6
FD160S, N, H & L 20A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
LTM D 25A -- -- -- -- -- -- -- -- -- -- -- 0.5 --
Record PlusTM 25A -- -- -- 0.32 -- -- -- 0.32 -- -- -- 0.5 -- -- --
FE160 LTM 32A -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
* Where T is mentioned Selectivity is full up until the Icu of the downstream device
Remark; For MCB's with D type Curve assume a C curve type with a one step higher rating.
E.G. Selectivity FD160 80Amp LTM with downstream C Curve 40A MCB = 3kA, for D curve 40A, take the value mentioned for 50A C curve, here 1.2kA

555977799.xlsx- 11/11/2021 T12 Sélec R+ mod faible A 10/13


Selectivity Tables valid for use with Record Plus Moulded Case Circuit Breakers Medium Amperages

Upstream FDC & FDE 160 LTM FDS 160 LTMD FDN, H & L 160 LTMD
In (A) 40A 50A 63A 80A 100A 125A 40A 50A 63A 80A 100A 125A 40A 50A 63A 80A 100A 125A
Downstream 160A 160A 160A
Selectivity limit *
Red Line/E+ < =16A 0.6kA 2.5kA T T T T T T T T T T T T T T T T
EPC30 20A 0.6kA 2.5kA T T T T T T T T T T T T T T T T
G30/EP30 25A -- 0.8kA 1.2kA T T T 1.6kA T T T T T 1.6kA T T T T T
B/C curve 32A -- -- 1.2kA 3kA T T -- -- T T T T -- -- T T T T
40A -- -- -- 3kA T T -- -- -- T T T -- -- -- T T T
Red Line/E+ < =16A 0.6kA 2.5kA 6kA T T T T T T T T T T T T T T T
EPC45/DPC45/DP45 20A 0.6kA 2.5kA 3kA T T T 3.5kA T T T T T 3.5kA T T T T T
G45/EP45 25A -- 0.8kA 1.2kA T T T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T
B/C curve 32A -- -- 1.2kA 3kA T T -- -- T T T T -- -- T T T T
40A -- -- -- 3kA 4kA T -- -- -- T T T -- -- -- T T T
Red Line/E+ < =16A 0.6kA 2.5kA 6kA T T T T T T T T T T T T T T T
EPC60 & DME60/DPC60 20A 0.6kA 2.5kA 3kA T T T 3.5kA T T T T T 3.5kA T T T T T
B/C curve 25A -- 0.8kA 1.2kA T T T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T
32A -- -- 1.2kA 3kA T T -- -- T T T T -- -- T T T T
40A -- -- -- 3kA 4kA 6kA -- -- -- T T T -- -- -- T T T
Red Line/E+ < =16A 0.6kA 2.5kA 6kA 6kA T T T T T T T T T T T T T T
DM60 & DMT60/DP60 20A 0.6kA 2.5kA 3kA 6kA 8kA T 3.5kA T T T T T 3.5kA T T T T T
DM100 & DMT100 25A -- 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T
B/C curve 32A -- -- 1.2kA 3kA 6kA 8kA -- -- 10kA T T T -- -- 10kA T T T
40A -- -- -- 3kA 4kA 6kA -- -- -- T T T -- -- -- T T T
50A -- -- -- 1.2kA 1.5kA 6kA -- -- -- 3.5kA T T -- -- -- 3.5kA T T
63A -- -- -- -- 1.5kA 2kA -- -- -- -- 8kA T -- -- -- -- 8kA T
Red Line/E+ < =16A 0.6kA 2.5kA 6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T
G60 20A 0.6kA 2.5kA 3kA 6kA 8kA T 3.5kA 10kA T T T T 3.5kA 10kA T T T T
DPC100 25A -- 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T
DM100/DP100 32A -- -- 1.2kA 3kA 6kA 8kA -- -- 10kA 10kA T T -- -- 6kA 10kA T T
B/C curve 40A -- -- -- 3kA 4kA 6kA -- -- -- 10kA T T -- -- -- 10kA T T
50A -- -- -- 1.2kA 1.5kA 6kA -- -- -- 3.5kA 10kA T -- -- -- 3.5kA 10kA T
63A -- -- -- -- 1.5kA 2kA -- -- -- -- 8kA T -- -- -- -- 8kA T
Red Line/E+ < =16A 0.6kA 2.5kA 6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T
G100/EP100 20A 0.6kA 2.5kA 3kA 6kA 8kA T 3.5kA 10kA T T T T 3.5kA 10kA T T T T
GT25/EP250/EP250M 25A -- 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA 15kA T T T 1.6kA 3.5kA 15kA T T T
B/C curve 32A -- -- 1.2kA 3kA 6kA 8kA -- -- 6kA 10kA T T -- -- 6kA 10kA T T
40A -- -- -- 3kA 4kA 6kA -- -- -- 10kA 15kA T -- -- -- 10kA 15kA T
50A -- -- -- 1.2kA 1.5kA 6kA -- -- -- 3.5kA 10kA T -- -- -- 3.5kA 10kA T
63A -- -- -- -- 1.5kA 2kA -- -- -- -- 8kA T -- -- -- -- 8kA T
Series Hti 80A -- -- -- -- -- 1.9kA -- -- -- -- -- 2.5kA -- -- -- -- -- 2.5kA
C curve 100A -- -- -- -- -- 1.9kA -- -- -- -- -- 2.5kA -- -- -- -- -- 2.5kA
Series S90 <=25A -- 0.8kA 0.9kA 1.2kA 1.5kA 1.9kA -- 1kA 1.2kA 15kA 15kA 15kA -- 1kA 1.2kA 15kA 15kA 15kA
32A -- -- 0.9kA 1.2kA 1.5kA 1.9kA -- -- 1.2kA 15kA 15kA 15kA -- -- 1.2kA 15kA 15kA 15kA
40A -- -- -- 1.2kA 1.5kA 1.9kA -- -- -- 15kA 15kA 15kA -- -- -- 15kA 15kA 15kA
50A -- -- -- 1.2kA 1.5kA 1.9kA -- -- -- 15kA 15kA 15kA -- -- -- 15kA 15kA 15kA
63A -- -- -- -- 1.5kA 1.9kA -- -- -- -- 15kA 15kA -- -- -- -- 15kA 15kA
80A -- -- -- -- -- 1.9kA -- -- -- -- -- 15kA -- -- -- -- -- 15kA
100A -- -- -- -- -- -- -- -- -- -- -- 15kA -- -- -- -- -- 15kA
Surion <=20A 0.6kA 2.5kA 6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T
GPS1BS & 25A -- 1kA 1.2kA 6kA 6kA T -- 3.5kA 15kA 15kA T T -- 3.5kA 15kA 15kA T T
GPS1MS 32A -- -- 1.2kA 3kA 6kA 10kA -- -- 6kA 6kA T T -- -- 6kA 6kA T T
GPS2BS & 40A -- -- -- 3kA 4kA 6kA -- -- -- 6kA T T -- -- -- 6kA T T
GPS2MS 50A -- -- -- 1.2kA 1.6kA 6kA -- -- -- 3.5kA T T -- -- -- 3.5kA T T
63A -- -- -- 1.6kA 2kA -- -- -- -- 8kA T -- -- -- -- 8kA T
Surion <=20A T T T T T T T T T T T T T T T T T T
GPS1BH & 25A -- 2.5kA 15kA 15kA T T -- 3.5kA T T T T -- 3.5kA T T T T
GPS1MH 32A -- -- 6kA 6kA 8kA T -- -- T T T T -- -- T T T T
GPS2BH & 40A -- -- -- 6kA 8kA T -- -- T T T T -- -- T T T T
GPS2MH 50A -- -- -- -- 6kA T -- -- -- 3.5kA T T -- -- -- 3.5kA T T
63A -- -- -- -- -- T -- -- -- -- 8kA T -- -- -- -- 8kA T
Record PlusTM <=25A 0.4kA 0.5kA 0.6kA 0.8kA 1kA 1.3kA 0.6kA 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA 0.6kA 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
FD160E, S, N, H & L 32A -- 0.5kA 0.6kA 0.8kA 1kA 1.3kA -- 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA -- 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
LTM/MO/GTM 40A -- -- -- 0.8kA 1kA 1.3kA -- -- -- 1.2kA 1.5kA 3.5kA -- -- -- 1.2kA 1.5kA 3.5kA
50A -- -- -- 0.8kA 1kA 1.3kA -- -- -- 1.2kA 1.5kA 3.5kA -- -- -- 1.2kA 1.5kA 3.5kA
63A -- -- -- -- 1kA 1.3kA -- -- -- -- 1.5kA 3.5kA -- -- -- -- 1.5kA 3.5kA
80A -- -- -- -- -- 1.3kA -- -- -- -- -- 3.5kA -- -- -- -- -- 3.5kA
* Where T is mentioned Selectivity is full up until the Icu of the downstream device
Remark; For MCB's with D type Curve assume a C curve type with a one step higher rating.
E.G. Selectivity FD160 80Amp LTM with downstream C Curve 40A MCB = 3kA, for D curve 40A, take the value mentioned for 50A C curve, here 1.2kA
Selectivity Tables valid for use with Record Plus Moulded Case Circuit Breakers High Amperages

Upstream FE160N, H & L LTM FE160N, H & L LTMD FE160N, H & L SMR1 FE250V LTM FE250N, H & L LTMD FE250N, H & L SMR1
In (A) 63A 80A 100A 125A 160A 100A 125A 160A 63A 125A 160A 160A 200A 250A 125A 160A 200A 250A 125A 160A 250A
Downstream
Selectivity limit *
Red Line/E+ <=20A T T T T T T T T T T T T T T T T T T T T T
EPC30 25A 1.2kA T T T T T T T T T T T T T T T T T T T T
G30/EP30 32A 1.2kA T T T T T T T T T T T T T T T T T T T T
B/C curve 40A -- 3kA 4kA T T T T T -- T T T T T T T T T T T T
Red Line/E+ <=20A 6kA T T T T T T T T T T T T T T T T T T T T
EPC45/DPC45 25A 1.2kA T T T T T T T T T T T T T T T T T T T T
G45/EP45 32A 1.2kA 3kA T T T T T T T T T T T T T T T T T T T
B/C curve 40A -- 3kA 4kA T T T T T -- T T T T T T T T T T T T
Red Line/E+ <=20A 6kA 6kA T T T T T T T T T T T T T T T T T T T
EPC60 & DME60/DPC60 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
B/C curve 32A 1.2kA 3kA 6kA T T T T T T T T T T T T T T T T T T
40A -- 3kA 4kA 6kA 6kA T T T -- T T T T T T T T T T T T
Red Line/E+ <=20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
DM60 & DMT60/DP60 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
DM100 & DMT100 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T
B/C curve 40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T
50A -- -- 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T
63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T
Red Line/E+ <=20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
G60 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
DPC100< 40A 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T
DM100/DP100 40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T
B/C curve 50A -- 1.2kA 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T
63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T
Red Line/E+ <=20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
G100/EP100 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
GT25/EP250/EP250M 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T
B/C curve 40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T
50A -- -- 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T
63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T
Series Hti 80A -- -- 1.5kA 2kA 2kA -- T T -- T T 1.9kA 2.5kA 3kA T T T T T T T
C curve 100A -- -- -- -- 2kA -- -- T -- -- T 1.9kA 2.5kA 3kA -- T T T -- T T
125A -- -- -- -- -- -- -- -- -- -- -- -- -- 3kA -- T T T -- T T
Series S90 <=40A -- 1.2kA 1.5kA 1.9kA 1.9kA T T T T T T 1.9kA 2.5kA 3kA T T T T T T T
50A -- -- 1.5kA 1.9kA 1.9kA T T T -- T T 1.9kA 2.5kA 3kA T T T T T T T
63A -- -- -- 1.9kA 1.9kA -- T T -- T T 1.9kA 2.5kA 3kA T T T T T T T
80A -- -- -- -- 1.9kA -- -- T -- T T 1.9kA 2.5kA 3kA -- T T T T T T
100A -- -- -- -- -- -- -- -- -- -- T 1.9kA 2.5kA 3kA -- -- T T -- T T
Surion <=20A 6kA 6kA 10kA T T T T T T T T T T T T T T T T T T
GPS1BS & 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T
GPS1MS 32A 1.2kA 3kA 6kA 10kA 10kA T T T T T T 10kA T T T T T T T T T
GPS2BS & 40A -- -- 4kA 6kA 6kA T T T T T T 6kA 10kA T T T T T T T T
GPS2MS 50A -- -- 1.6kA 6kA 6kA T T T -- T T 6kA 6kA 10kA T T T T T T T
63A -- -- -- 2kA 2kA -- T T -- T T 2kA 6kA 6kA T T T T T T T
Surion <=20A T T T T T T T T T T T T T T T T T T T T T
GPS1BH & 25A 15kA 15kA T T T T T T T T T T T T T T T T T T T
GPS1MH 32A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T
GPS2BH & 40A -- 6kA 8kA T T T T T T T T T T T T T T T T T T
GPS2MH 50A -- -- 6kA T T T T T -- T T T T T T T T T T T T
63A -- -- -- T T -- T T -- T T T T T T T T T T T T
Record PlusTM <=40A -- 0.8kA 1kA 1.2kA 1.6kA T T T T T T 1.6kA 2kA 2.5kA T T T T T T T
FD160E, S, N, H & L 50A -- -- 1kA 1.2kA 1.6kA T T T -- T T 1.6kA 2kA 2.5kA T T T T T T T
LTM/MO/GTM 63A -- -- -- 1.2kA 1.6kA T T T -- T T 1.6kA 2kA 2.5kA T T T T T T T
80A -- -- -- 1.2kA 1.6kA -- T T -- -- T 1.6kA 2kA 2.5kA -- T T T T T T
100A -- -- -- -- 1.6kA -- -- T -- -- T 1.6kA 2kA 2.5kA -- -- T T -- T T
125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- T T -- -- T
160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- T -- -- T
Record Plus TM
<=40A 0.6kA 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA 36kA 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
FD160S, N , H & L 50A -- 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
LTMD 63A -- -- 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
80A -- -- -- 1.2kA 1.6kA -- 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
100A -- -- -- -- 1.6kA -- -- 30kA -- -- 36kA 1.6kA 2kA 2.5kA -- 42kA 42kA 42kA -- 50kA 50kA
125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- 42kA 42kA -- -- 50kA
160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- 42kA -- -- 50kA
Record PlusTM <=40A 0.6kA 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA 36kA 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
FE160 N, H & L 50A -- 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
LTM/MO/GTM 63A -- -- 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
80A -- -- -- 1.2kA 1.6kA -- 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA
100A -- -- -- -- 1.6kA -- -- 30kA -- -- 36kA 1.6kA 2kA 2.5kA -- 42kA 42kA 42kA -- 50kA 50kA
125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- 42kA 42kA -- -- 50kA
160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- 42kA -- -- 50kA
* Where T is mentioned Selectivity is full up until the Icu of the downstream device
Compact RCBO. Let-through energy I2t
The benefit of an RCBO in short-circuit conditions, is
its ability to reduce the value of the let-through energy
that the short-circuit would be generating.

Series DPC - Curve B Let-through energy at 230 V

Series DPC - Curve C Let-through energy at 230 V