Professional Documents
Culture Documents
EEL 6266 Power System Operation and Control: Unit Commitment
EEL 6266 Power System Operation and Control: Unit Commitment
Chapter 5
Unit Commitment
Load Demand Cycles
Human activity follows cycles
systems supplying services will also experience usage cycles
transportation, communication, and electric power systems
electric power consumption follows a daily, weekly, and
seasonal cycles
high power usage during the day and evening hours
industrial and commercial operations and lighting loads
lower usage on the weekends
higher usage during the summer and winter
greater temperature extremes
Load cycles create economic problems for power generation
it is quite expensive to continuously run all generation, which
is needed to meet the peak power demands
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 2
Load Demand Cycles
Definition
commitment means to turn-on a given generation unit
have the prime mover operating the unit at synchronous speed
synchronize and connect the unit to the network grid
Economics
savings are gained by decommitting some of the generation
units when they are not need to meet the current load demand
the engineering problem is committing enough units to meet
current and future load demands while minimizing starting and
operating costs
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 3
Load Demand Cycles
Example
consider the cost for operating three generation units
Unit 1: F1(P1) = 561 + 7.92 P1 + 0.001562 P12 150 ≤ P1 ≤ 600
Unit 2: F2(P2) = 310 + 7.85 P2 + 0.00194 P22 100 ≤ P2 ≤ 400
Unit 3: F3(P3) = 93.6 + 9.56 P3 + 0.005784 P32 50 ≤ P3 ≤ 200
Unit 2
Unit 3
Ftotal
Max
Gen
Gen
Min
P1
P2
P3
F1
F2
F3
Off Off Off 0 0 Infeasible
Off Off On 200 50 Infeasible
Off On Off 400 100 Infeasible
Off On On 600 150 0 400 150 0 3760 1658 5418
On Off Off 600 150 550 0 0 5389 0 0 5389
On Off On 800 200 500 0 50 4911 0 586 5497
On On Off 1000 250 295 255 0 3030 2440 0 5471
On On On 1200 300 267 233 50 2787 2244 586 5617
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 4
Load Demand Cycles
Example
notes:
the least expensive way to supply the generation is not with all
three units running or with any combination involving two units
the optimal commitment is to only run unit #1, the most
economic unit
by only running the most economic unit, the load can be supplied
by that unit operating closer to its best efficiency
if another unit is committed, both unit #1 and the other unit will be
loaded further from their best efficiency points, resulting in a
higher net cost
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 5
Load Demand Cycles
Daily load patterns
consider the load demand with a simple peak-valley pattern
in order to optimize the operation of the system
units must be shut down as load goes down
then the units must be recommitted as load goes back up
simple approach to the solution is a simple priority list scheme
1500 MW
1150 MW Peak Load
Total Loading
1000 MW
500 MW
3 PM 9 PM 3 AM 9 AM 3 PM
Time of day
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 6
Load Demand Cycles
Example
use a brute force technique to obtain a “shut-down rule” for the range of
loads from 1200 to 500 MW in steps of 50 MW
when load is above 1000 MW, run all three units
1050 on on on
200 MW Unit #3
1000 MW 1000 on on off
400 MW 950 on on off
Unit #2 900 on on off
850 on on off
500 MW 600 MW 800 on on off
Unit #1 750 on on off
700 on on off
650 on on off
3 PM 9 PM 3 AM 9 AM 3 PM 600 on off off
Time of day 550 on off off
500 on off off
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 7
Constraints in Unit Commitment
Primary constraints
enough units are committed to supply the load economically
Spinning reserve constraints
spinning reserve definition
the total amount of on-line, synchronized generation power
committed less the current loading and power losses supplied
protects the network from an unexpected loss of one or more
generation units
typical spinning reserve rules
the reserve is a given percentage of the forecasted demand
must be capable of making up the loss of the most heavily
loaded generation unit
reserves must be spread around the system to avoid transmission
limitations (bottling) and permit parts of the system to run as
“islands”
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 8
Constraints in Unit Commitment
Example
consider a power system consisting of two isolated regions
transmission tie-lines join the regions and may transfer power up
to a maximum of 550 MW in either direction
five units have been committed to supply 3090 MW of loading
Interchange
Unit Output
Generation
Load (MW)
Regional
Regional
Capacity
Spinning
Reserve
Region
(MW)
(MW)
(MW)
(MW)
(MW)
Unit
Unit
Western region
Units 1, 2 & 3
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 9
Constraints in Unit Commitment
Example
verify the allocation of spinning reserves in the system
western region
generation of largest unit: 900 MW
available spinning reserve
• local: 760 MW; tie-line capacity: 390 MW; eastern region: 450 MW
• total: 1150 MW - load can be supplied
eastern region
generation of largest unit: 1040 MW
available spinning reserve
• local: 450 MW; tie-line capacity: 550 MW; western region: 700 MW
• total: 1000 MW - load can not be completely supplied
lack 40 MW of spinning reserve in the eastern region
commit 40 MW of new generation within the eastern region
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 10
Constraints in Unit Commitment
Thermal unit constraints
a thermal unit can undergo only gradual temperature changes
results in a time period of several hours to bring a unit on-line
minimum up time: it should not be turned off immediately
minimum down time: once decommitted, the minimum time
before a unit can be recommitted
crew constraint: at a multiple unit plant, there is usually only
enough personnel to start one unit at at time
a certain amount of energy is expended to bring a unit on-line
to slowly bring up the temperature and pressure
this energy does not result in any power delivered from the unit
the energy cost is brought into the unit commitment problem as
a start-up cost
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 11
Constraints in Unit Commitment
Start-up costs
the start-up cost can vary from a maximum
cold-start value to a much smaller warm-start value
warm unit: a recently turned-off unit with latent heat
that is near the normal operating temperature
two approaches available to treating a thermal unit during its
down time
allow the boiler to cool down and then heat it back up to
operating temperature in time for a scheduled turn-on
provide enough fuel to supply sufficient energy to the boiler to
just maintain the operating temperature
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 12
Constraints in Unit Commitment
Start-up cost comparison
cooling
allowing the unit to cool down
Cstart-up
start-up cost function:
cooling
− t shut − down
= H cold 1 − e α
Ccold F fuel + C fixed break-even
banking point
banking Cfixed
input sufficient energy into
the boiler to just maintain
the operating temperature
banking cost function:
0
Cbank = H bank F fuel tshut −down + C fixed 0 1 2 3 4 5 6 7 hr
Time-dependent start-up costs
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 13
Unit Commitment Solution Methods
Typical utility situation involving the commitment problem
must establish a loading pattern for M periods
have N generation units available to commit and dispatch
the M load levels and operating limits on the N units are such
that any one unit can supply the load demand and any
combination of units can also supply the loads
Commitment by enumeration
a brute force method
total combinations to investigate: 2N – 1
for the total period of M intervals, the maximum number of
possible combinations is: (2N – 1)M
example: for a 24-hour period made up of 1-hr intervals,
a 5 unit network become 6.2 × 1035 combinations
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 14
Unit Commitment Solution Methods
Priority-List Methods
consist of a simple shut-down rule
obtained by an exhaustive enumeration of all unit combinations
at each load level
or obtained by noting the full-load average production cost of
each unit
the full-load average production cost is the net heat rate at full load
multiplied by the fuel cost
various enhancements can be made to the priority-list scheme
by the grouping of units to ensure that various constraints are
met
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 15
Unit Commitment Solution Methods
Typical shut-down rules
at each hour when load is dropping, determine whether
dropping the next unit on the list leaves sufficient generation
to supply the load plus the spinning-reserve requirements
if the supply is not sufficient, keep the unit committed
determine the number of hours before the unit is needed again
if the time is less than the minimum shut-down time for the unit,
keep it committed
perform a cost comparison
the sum of the hourly production costs for the next number of
hours with the next unit to be dropped being committed
and the sum of the restart costs for the next unit based on the
minimum cost of cooling the unit or banking the unit
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 16
Unit Commitment Solution Methods
Example
construct a priority list for the units in the first example using
the same cost equations
Unit 1: F1(P1) = 561 + 7.92 P1 + 0.001562 P12 150 ≤ P1 ≤ 600
Unit 2: F2(P2) = 310 + 7.85 P2 + 0.00194 P22 100 ≤ P2 ≤ 400
Unit 3: F3(P3) = 93.6 + 9.56 P3 + 0.005784 P32 50 ≤ P3 ≤ 200
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 17
Unit Commitment Solution Methods
Example
the commitment scheme
ignoring minimum up/down times and start-up costs
Combination Min MW Max MW
1+2+3 300 1200
1+2 250 1000
2 100 400
notes
this scheme does not completely parallel the shut-down
sequence described in the first example
there unit 2 was shut down at 600 MW leaving unit 1
here unit 1 is shut down at 400 MW leaving unit 2
why the differences? where is the problem?
© 2002, 2004 Florida State University EEL 6266 Power System Operation and Control 18