SICAM PAS
Complete Training
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Summary Slide
1. Introduction
2. System functions
3. System components
4. Software installation
5. Licensing
6. UI User Interface
7. Software installation
8. UI Operation
9. Value Viewer
10. Telecommunication with IEC 60870-5-101
11. Communication with a Control Center using IEC 60870-5-101 Slave
12. Interface Tester IECTEST for IEC 60870-5-101/104
13. Siemens Serial Hub 7XV5655
14. Connection of a Field Device with IEC 60870-5-103
15. SICAM PAS CFC Logic Function
16. IEC61850 Communication Standard for Substations
17. Configuring IEC 61850 IEDs
18. SNMP Simple Network Management Protocol
19. HMI-Interface and Topology
20. Introduction to SICAM PAS CC
SICAM PAS
1. Introduction
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
What is SICAM PAS?
S Substation
I Information
C Control
A Automation
SICAM PAS / PQS
M Monitoring V7.0
Power Automation System
Power Quality System
P Power
A Automation
S System
TeleControlCenter
Control center level, SCADA
(Supervisory, Control And Data Acquisition)
SICAM PAS
IEC 101 / 104 • filters information, which is not used in SCADA
• understands / converts various protocols
Station level (SICAM PAS)
• is able to (time-) synchronize all connected IEDs
PROFIBUS FMS
3 IE
10 C
IE
0
85 10
C
C 4
IE
61
10
1
C
IE
Bay level
Process level
TeleControlCenter
Control center level, SCADA
SICAM SCC
(Supervisory, Control And Data Acquisition)
(SICAM Substation Control Center)
PROFIBUS FMS
3 IE
10 C
IE
0
85 10
C
C 4
IE
61
10
1
C
IE
Bay level
Process level
Control Control
Center Center
RTU
AI
SAS (PAS)
Distributor bank
copper wires
Communication Module Communication Module
Protection Relais
SICAM SICAM
Diamond PAS CC
SICAM
PAS
SICAM
SIPROTEC
1703 AK
SICAM
SICAM
230
230
SICAM SICAM
1703 BC 1703 TM
SICAM
1703 MIC
2.TeleControlCenter
SICAM PAS
TeleControlCenter SICAM PAS CC Stand-alone
IEC 60870-5-104 system
Timesignal
IEC 60870-5-101
DNP V3.00
Full Server
2.TeleControlCenter
Modbus/Profibus DP
IEC 60870-5-101
DNP V3.00
Profibus FMS
IEC 60870-5-103
HMI Clients
SICAM PAS
TeleControlCenter Redundant
System
Ethernet
PAS PAS
Full Server Full Server
Stationbus
IEC 61850
or
Profibus FMS
SICAM PAS
SICAM PAS CC
TeleControlCenter IT World
IEC 60870-5-104
TCP/IP Timesignal
TeleControlCenter PAS
Full Server
Ethernet
OPC
IEC 60870-5-101/DNP V3.00 SIMATIC
SPS
Profibus FMS/IEC 60870-5-103
Tele
Control
Center
PAS
Full Server
IEC 60870-5-101
Switch
Station - LAN
IEC 61850; Ethernet 100Mbps
Fiber optic double loop with redundancy function
Switch Switch
... ...
Tele
Control
Center
PAS
Full Server
IEC 60870-5-101
Switch
Tele
Control
Center
Time-Server
Redundant
HMI Server
IEC 60870-5-101
Redundant
PAS Full Server
Tele
Control
Center
Time-Server
Redundant
HMI Server
IEC 60870-5-101
Redundant
PAS Full Server
NCC DCC
Hardcopy HMI HMI Engineering PC
printer
Online
printer
Operator Log
WAN
GPS
WAN
Gateway 1 Gateway 2
IED-LAN IED-LAN
IEC 61850; Ethernet 100Mbps ... IEC 61850; Ethernet 100Mbps
Fiber optic double loop with redundancy function Fiber optic double loop with redundancy function
The goal is to increase the supply security by avoiding system outages through break
down of power supply.
Voltage change
SICAM PAS
2. System functions
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Scalability - Configuration
TCP/IP - connection
TCP/IP - connection
several stations
independent parts of
Full Server (aktiv) Full Server (standby)
substations
redundant PAS Full Server
Redundant PAS CC Server
Client/Server
Corporate
Network TCP/IP
Control Center
Redundant HMI
IEC 101
Station bus
Profibus FMS
IEDs with Profibus FMS
DIGSI Software:
All software components of SICAM PAS/PQS are available at the SICAM PAS/PQS-DVD.
You can decide which components shall be activated by using the dongle and the related license
cards.
SICAM PAS
SICAM PAS / PQS V7.0
V7.0
Power Automation System
Power Quality System
ket
IEC
pac
basis
Automatisie-
IEC
PAS
IEC
OPC
61850
PQS
103
101
IEC104
rung
i on
Opt PC tion ation
O p
IEC O om
t
Au
i on
Opt 01
1
IEC
Small: up to 4 IEDs
Medium: up to 15 IEDs (data points unlimited) or up to 2000 data points (IEDs unlimited)
Large: unlimited
DIP
Runtime
RT&Config
TeleControlCenter
Licenses for connection of Tele Control Centers
IEC 61850 Server
IEC 60870-5-101 Slave
IEC 60870-5-104 Slave
DNP V3.00
TG 8979
CDT
Modbus Slave
TeleControlCenter
TeleControlCenter
TeleControlCenter
61850 Client
Time synchronization
Control
Select before Operate (SBO) with
extended safety all commands to high
voltage devices
Direct Control with normal safety all
other commands
Information Report
all information in monitoring direction to
PAS
GOOSE
Inter device communication
interlocking, blocking etc.
File Transfer
61850 Server 61850 Server 61850 Server Alarm lists, Event lists
Transmission of fault records
Time Synchronisation
Operating modes
• Balanced IEC
PAS CC
60870-5-101
• Unbalanced (up to 16 RTUs) Master
• Operating modes
• Unbalanced ( miniRTU)
Modem Modem
• Balanced RTU
Recommended modems: Company
INSYS Public
telephone
• Backup- Modem possible
Modem Modem
Serial interface
see IEC 60870-5-103 RTU RTU
Recommendation:
max. 8 substations per ‘PAS-Modem’
PAS Server
Ethernet TCP/IP
Serial Hub
RS485, RS232
COM Expander
Data exchange and communication with OPC Server using the OPC Client
The communication partner OPC Server can be located
on the same PC or on another PC connected with TCP/IP (Ethernet) OPC
The open communication can especially be used for the data exchange with Client
automation devices e.g. SIMATIC
Example: A SIMATIC S7-400 is connected to a SICAM PAS Station Unit through
a CP1613 and via the Ethernet. The communication used between the S7-400
and the CP1613 is the S7 protocol. An OPC server for the CP1613 card is
available from SIMATIC. In this way data can be exchanged with the SICAM PAS
OPC Client.
CP
OPC
1 Ethernet, S7-Protocol
OPC OPC 6
Client Server 1
3
Control Center exchange between SICAM PAS and any OPC XML Server
OPC XML-DA Client
XML-DA Client works with the
OPC XML-DA Server.
OPC XML-DA Server and OPC XML-DA Client are
LAN, WAN /
Internet installed on different PCs, the communication of the
OPC XML-DA Servers with SICAM PAS works via
TCP/IP. This open communication is applicable for data
SICAM PAS
IIS Microsoft exchange between SICAM PAS and other systems
Webserver
based on Microsoft Windows as well as LINUX or other
operating systems.
OPC XML-DA
Server The OPC XML-DA Server allows the data exchange of
structured data via the internet with XML (eXtendensible
Markup Language).
With the OPC XML-DA Server the OPC XML-DA Client
Restricted © Siemens AG 2013 All rights reserved. can setContent
protocol parameters and can read and write all
F02_Page 42 Siemens Power Academy TD
settings which are mapped from SICAM PAS UI to OPC
Automation
CFC function blocks for typical substation automation tasks are available
Command processing (Command execution and Command derivation)
Signal processing
Signal derivation
Signal filtering
Switching sequences
Restricted © Siemens AG 2013 All rights reserved. Content
F02_Page 44 Siemens Power Academy TD
Time synchronization
Use of a „time-synchronization module“ in the SICAM PAS computer e.g. Hopf card (DCF77 or
GPS)
The SICAM PAS takes over the time synchronization
for the connected devices (if the communication protocol supports) and
for the HMI PC connected via Ethernet (SICAM SCC)
SCC
DCF / GPS Antenna
Ethernet (TCP/IP)
IEC 61850
A separate time master can especially be used in configurations with an Ethernet station bus (IEC
61850). This is an SNTP-Server (Simple Network Time Protocol), which synchronizes all
connected devices (SNTP-Clients), incl. the SICAM Station Unit
The SICAM PAS is the time master for all other devices not connected to LAN
Antenna
SCC
IEC 61850
Ethernet (TCP/IP)
T101
Profibus FMS
T103
Even time synchronization from Tele Control Center (e.g. via IEC101 telegrams) is supported.
IEC 101
SCC
IEC 61850
Ethernet (TCP/IP)
T101
Profibus FMS
SICAM PAS supports several time masters and T103
In case of maintenance works in the switchgear it may be useful not to display the messages
caused by the works in the event and alarm list of the local HMI and remote control center as well.
Bay blocking woks device specific. The image of the field device appears like „frozen“ for all users.
All messages are put into a virtual waste basket. Commands are suppressed.
Local Control Station SICAM SCC
TeleControlCenter
Bay Blocking
Mr. Maintenance
Restricted © Siemens AG 2013 All rights reserved. Content
F02_Page 48 Siemens Power Academy TD
Telecontrol Blocking
Telecontrol
Blocking
Mr. Maintenance
Restricted © Siemens AG 2013 All rights reserved. Content
F02_Page 49 Siemens Power Academy TD
Switching Authority
Substations can be monitored and controlled not only by one telecontrol center. There can be
several TCCs or even more local HMIs.
For security reasons only one control station should have the switching authority. All other
control stations are not able to control anything (but they still receive data)
SICAM PAS has a logical „torque switch“ which allows to define which control station shall get
the switching authority.
Example without switching authority Example with switching authority for HMI 1
2 1
3 1 2 1
4 2 3 1
5 3 4 2
5 3
SICAM PQ Collector automatically transmits the fault records from the SICAM
Station Units to a higher level PQ archive.
With the Incident Explorer you can easily administer the fault record files.
Comtrade Viewer allows an analysis of the fault records.
Ethernet TCP/IP
SIMEAS Q80
Power Quality Recorder to analyse the Net
quality according to EN50160
SIMEAS R
Fault Recorder, Power Quality Recorder and
Phasor Measurement Unit (PMU) according
to IEEE C37.118
Protection Relays
Provide Fault Records in pre-defined formats
SICAM PQ Analyzer
PQ Inspector
Simple time related overview of PQ status of pre-defined groups of measurands Creating Reports
SICAM PQS
● Incident Explorer
Replacing RECPRO – Display of PQ Archive -- PDR (PostDisturbanceRecorder)
● PQ-Events
PQ Archive ● Fault Records
● Reports
● Topology
Config&RT: Automatic Fault Locating & Export Automatic Grid Code Evaluation
Scheduled PQ Reports Automatic Import of Comtrade Automatic Import of PQDIF
PQDIF
PQ Analyzer Clients
Protection Relays
SIMEAS R PAR is part of PAS-PQS installation. Creating a SIMEAS R, the tool opens
automatically
SIMEAS Q80 Manager is a comprehensive Software tool for parameterisation, broad evaluation
and analysis. It provides the evaluation and analysis of more than 500 data sets from Power
Quality Recorder SIMEAS Q80.
SIMEAS Q80 Manager is an independent Software package and has to be installed additionally to
SICAM PAS PQS, if Q80 is to be used. It can be opened from SICAM PAS UI Configuration tool.
Shows an overview with all automatically created reports with time ranges and the evaluation
of the results.
“Select Time Range” shows condensed group of measurement points for this configuration and
leads through analysis of faults
“Select Diagram” allows definition and configuration of PQ reports with the appropriate
diagrams
Operating systems
• Windows XP professional SP3
• Windows 2003 Server
• Windows 7 Professional (only with the design Windows – classic)
• Windows Server 2008 Standard Edition (32-Bit) without Hyper-V
• Windows XP embedded
• Windows Embedded Standard
Slave Info
Master info
IEDs degress data points
ingress data points
(mainly to HMI and
(mainly from IEDs)
SCADA)
1 Full Server with 1 core or
150 10.000 20.000
2 core processor
1 FS (4core processor) 180 10.000 20.000
1FS (1core processor) and
250 10.000 20.000
1DIP
1 FS (4core processor) and
350 20.000 40.000
5 DIPs
SICAM PAS
3. System components
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
SICAM PAS Station Unit
Design:
• with / without PCI-Bridge (for 4 standard-PCI-cards)
• Optional COM-expander-cards with 8 interfaces
• Optional 2 I/O cards each with 32 digital in- or outputs
Power Supply Control Module 2x internal USB 4x external USB 1x RS232 2x LAN
IEC 101
IEC 103
DNP 3
Modbus
Tx
“primary Full Server” Rx “secundary Full Server”
GND
serial serial
Tx Tx
Rx Modem Rx
GND GND
Splitter
With the modem splitter both servers can „see“ the actual image of the field device
But only the active server can send commands
RS232
interface
TTY 20 mA
interface
Ethernet
NTP
Especially for configurations with ethernet (IEC 61850) a separate time master can be used via
NTP-server (Network Time Protocol).
Synchronizes all connected devices (NTP-Clients)
Industrial Rack PC
SIMATIC rack PC 847B
19”-rack platform
High performance under harshest conditions
Up to 4 Gbyte main memory
Integrated security function (watchdog, temperature and fan control)
Server PC in a SICAM PAS CC Client/Server – HMI System
Operator desk in a SICAM PAS CC Single user system
CELSIUS Workstation
Type V series
Max 64 GB main memory
Client PC in a SICAM PAS CC Client/Server – HMI System
Operator desk in a SICAM PAS CC Single user system
Engineering Desk
Restricted © Siemens AG 2013 All rights reserved. 3. System components
F02_Page 78 Siemens Power Academy TD
Com-Expander: Comtrol Rocket Port
PCI-card for PC
Ethernet TCP/IP
Serial modem
RS485 or RS232
Converter 7XV5650
Establishes an optical connection between star coupler
and electrical field device
Supports RS485 bus structure
DIGSI
RS-232
FO
RS485 – FO-
Converter
RS-485
TP TP No redundancy
62,5µ or 50µ fiber Cost optimized
100 Mbit/s redundant switched ethernet loop
100 Mbit/s redundant switched
Field devices with electrical communication modules ethernet loop
Cu Twisted Pair (TP)
Field devices with optical communication Shielded cable
modules
max. 20m
s
TP TP TP a tion
st
e sub
ta g
v ol
di um
e
a ll m
sm
cubicle
Ethernet-Modul EN
100
Operating Temperature:
-40°C to +85°C
Optical Tranceivers
multimode
singlemode
8 Ports:
RJ45 connectors
LC, SC, ST, MTRJ
Cu Shielded Pair
max. 20m
Operating modes
Unbalanced ( Use of SICAM
miniRTU)
Balanced
Applications:
IO-Expander for 6MD66 (up to 80 BI+53 BO)
IO-Expander for all
SIPROTEC protection devices
Central process connection for
SICAM PAS
Advantages:
Cost optimized because use
of available technology
Support of the protocols
IEC61850
IEC60870-5-103
Profibus FMS/DP
Flexible mounting possibilities (no Operator Keyboard, no Display)
Simple system configuration (no CFC)
Synchrocheck function
TAPCON 260
REG-DA
REINHAUSEN
Low High
Compact
Compact Remote
Remote
Terminal
Terminal Unit
Unit (RTU)
(RTU)
TM 1703 mic
Universal system, applicable for electrical substations, at the object protection and for alarm
transmitter
Communication via IEC 60870-5-101/104
Easy engineering via web browser, no special tools or licenses necessary
Engineering also possible with TOOLBOX II
Low High
Processing
Processing from
from aa small
small up
up to
to aa
medium
medium number
number of
of data
data points
points
TM 1703 ACP
Low High
BC 1703 ACP
Field
Field Device,
Device, protection
protection integrated
integrated
Supports applications as gateway and subnodes, e.g. for communication with older protection
devices with IEC 103 to a modern stion bus with IEC 61850
Applicable for medium voltage up to highest voltage
Up to 500 I/O signals
Low High
AK 1703 ACP
RTU
RTU from
from aa medium
medium upup to
to aa
large
large number
number of
of data
data points
points
SICAM PAS
4. Software installation
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Starting Setup.exe
The selection PAS or PQS will install exactly the same components, the difference is just the „Branding“
Standard path
Custom offer to un-select single components. However, the full installation would usually be preferred.
Standard path
The standard installation path should only be changed, if there are certain reasons for, e.g. some
types of the SICAM Station Unit require other paths.
Standard path
Demo means without a dongle, provides the full functionality of the system, but limits the Runtime
System to 3 hours. After that, the RT can be restarted again (for the next 3 hours).
First part finished successfully, now the SICAM PAS itself is being installed
A window may pop up after having re-booted the computer, if there was more than one
ethernet-adapter. The adapter, which is to be used with SICAM PAS, has to be added to the
medium window pane.
All software is split up into 5 paths. One reason is the ability also to install the package
without having admin rights.
If SICAM PAS should once be de-installed completely, use the “Add/Remove Programs”
window, and afterwards delete these 5 paths manually.
SICAM PAS
5. Licensing
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Licensing
DIGSI software:
In order to run SICAM PAS you need a dongle and password cards.
Together with the dongle you get password cards with all services (protocols) which you purchased.
Later, to add another service, you just need another password card
License Card for Runtime License Card for Configuration License Card for IEC 61850
......
To enable a certain
application, a password
has to be entered.
A unique password list comes
along with the Dongle.
Even if you have no configuration license but a runtime license you can do some
(limited)parameterization in the UI-Configuration tool.
You can add new applications, mainly für PQS applications. In this case IEC 103 and
IEC61850 protocols belong to these applications.
Even if you would have no Configuration License but a Runtime License you can perform some
(restricted) changes in the UI-Configuration tool:
You can:
change parameters
You cannot:
Restrictions :
You can only use services which you have purchased and activated in the
Feature Enabler
Small: up to 4 IEDs
Medium: up to 15 IEDs (data points unlimited) or up to 2000 data points (IEDs unlimited)
Large: unlimited
DIP
Runtime
RT&Config
SICAM PAS
6. UI User Interface
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
UI - User Interface - 3 Tools
If the owner uses passwords for each user, here you could see the login name
Here you can see the license size (Medium, Large)
To configure…
Applications (IED-Protocols, control centres, HMI, automation, OPC)
Interfaces (serial interfaces, Ethernet, Profibus DP)
Devices (Bay units and protection devices, tap changers, power meters)
Based on templates
device and project specific device descriptions
and templates for normalisation
can be defined.
In terms of consideration of typical
names of information can be
defined project specific
define feedback indications
to commands
Reports
In this viewyou can configure templates for reports which will be generated cyclic.
The templates contain selected measurement values which are used for evaluation of the network
quality. The report templates are created as a txt file and imported into the SICAM PAS/PQS.
Point of time and cycle when the report shall be created can be adjusted in the report template.
Grid Code
Here you can define the thresholds which the grid has to keep. These Grid Codes are the basis
for the evaluation of the PQ measuerement data quality of the system.
SICAM Substations Migration SINAUT LSA Protection devices / Protection devices / Protection devices /
Bay Controllers Bay Controllers Bay Controllers
Export of T101- Export of ILSA- Export of T103- Export of Profibus FMS- Export of IEC 61850 -
parameter data parameter data parameter data parameter data parameter data
XML- XML- DBase- XML- SCD- File
Export file Export file Export file Export file XML-Export file
SICAM plusTOOLS > V4.0 LSA Converter DIGSI 4 DIGSI 4 DIGSI 4
SICAM
- SAS
LSA 678 and SINAUT LSA
- RTU, eRTU
- miniRTU
SIPROTEC 4 SIPROTEC 4 SIPROTEC 4 and
SICAM PCC, SICAM PAS 3rd party devices
User friendly
Imported data can be updated later, e.g. after modifications
OPC Client
The OPC-server publishes data online. I.e. there is no export file,
but the running server has to be connected to the network of the
configuration computer
The plausibility of the data input is immediately checked, faulty entries are
visualised.
In the configuration view a short help text is displayed and a corresponding note is
displayed directly in case of missing inputs.
Faulty cells or lines are immediately marked red colour. A tool tip helps to correct.
The user gets an overview about the status of his runtime environment
The Tree view offers a fast view of the status of the components
(application, interface, devices) by using different symbols and colours.
The SICAM PAS Value Viewer is an important tool for engineering, testing,
commissioning and operation.
It allows the visualization of the process and system information without additional
engineering and provides information about current status and quality.
SICAM PAS
7. Starting project
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Our desired configuration
IEC 101
To enable a certain
application, a password
has to be entered.
The unique password list
comes together with your
dongle.
The installation (it is just the password to be installed) just takes a second.
Help
Current tree view properties Information
view
Restricted © Siemens AG 2013 All rights reserved. 8. UI Operation
F02_Page 144 Siemens Power Academy TD
Creating a Full Server Computer
System = Computer
Imported messages
appear in Mapping
Ticking USE means to make a message available for further processing, i.e. to send
to an HMI-system, to send to a telecontrol center, to process in logic functions etc.
Example: We are going to disable all commands with the address 99999999
1. Open drop-down-menu in Telegram Address column and select 99999999.
Restricted © Siemens AG 2013 All rights reserved. 8. UI Operation
F02_Page 154 Siemens Power Academy TD
How to select a group Filter
2. Select the headline “Use” to mark the whole column (blue colour)
3. Move the mouse pointer into the blue marked area
4. Press the right-hand mouse button to select “No”
5. Disable the filter
SICAM PAS
8. UI Operation
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Starting UI-Operation
If settings were changed in UI-Configuration (new application, changing parameters, etc.), we have
to activate these changes in UI-Operation.
If parameters of a CFE
component were modified in
UI Configuration, e.g.
Baudrate of an interface,
changes have to be taken
over into the Runtime system
by Activate Changes.
If a Non-CFE-component
modified, changes have to
be activated by Stopping
and Re-Starting the
application
On every update, a
Report window logs each
single step
Each level shows the current state and can manually be started or stopped
The IED level additionally contains buttons for General Interrogations as well as
for Bay-Blocking and Telecontrol-Blocking
Restricted © Siemens AG 2013 All rights reserved. 8. UI Operation
F02_Page 166 Siemens Power Academy TD
Operation - functions
all sublevels
are included
With the context menu we also can start or stop including all the sublevels
After a few seconds all the levels have started and are running now
Even after shutting down and restarting the computer, the runtime
system will automatically start
SICAM PAS
9. Value Viewer
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
What is a Value Viewer for?
•Every line represents an information point, e.g. SP, DP, ME_FL, IT...
•Various components are displayed in columns, e.g. Value, Cause, Validity
The selection of the top level would display all information in the entire substation
The properties pane is for manual data modification for test purposes
The Value Viewer allows us to test all information without using an HMI system or
telecontrol interface.
We even can simulate certain messages or values, which usually may not appear.
SICAM PAS
10. Telecommunication with
IEC 60870-5-101
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Tele-Communication – What´s that?
Control Center
Telecontrol Channel
Transfer of the actual process information
(monitoring direction) and control of the
equipment (control direction). Communication via
different types of media with standard (IEC)
telecontrol protocols
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 183 Siemens Power Academy TD
What do we need for?
Telecontrol Channel
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 184 Siemens Power Academy TD
Which types of data transfer units are available?
Analog:
VFT Voice Frequency Telegraphy (multi channel
telegraphy)
Modem Modulator/Demodulator
Digital:
PCM-Multiplexer up to 64kBaud
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 185 Siemens Power Academy TD
Which kinds of communication media can be used?
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 186 Siemens Power Academy TD
Telecontrol Standards
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 187 Siemens Power Academy TD
IEC - Standards
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 188 Siemens Power Academy TD
IEC 60870 – 5 – 101 - The most important features
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 189 Siemens Power Academy TD
IEC 60870-5-101 Protocol
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 190 Siemens Power Academy TD
IEC 60870-5-101 – Telegram Types
Information
object
Checksum
hb_sy_st
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 191 Siemens Power Academy TD
Structure of the service data unit
optional per
Information object n system
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 192 Siemens Power Academy TD
Type Identification in monitoring direction
Length of
Value Type of Informationobject
Info-Object
0 Not defined
1 Single-point indication 1
Single-point indication with time
2 4
stamp
3 Double-point indication 1
Double-point indication with time
4 4
stamp
5 Tap position indication 2
Tap position indication with time
6 5
stamp
7 Bit pattern 5
8 Bit pattern with time stamp 8
9 Measured value, normalized 3
Measured value, normalized with
10 6
time
11 Measured value, scaled 3
12 Measured value, scaled with time 6
13 Measured value, floating point 5
Restricted
Measured value, floating point 10. Telecommunication
14 © Siemens AG 2013 All rights reserved. 8 IEC 101
with
F02_Page 193 with time Siemens Power Academy TD
15 Metered value 5
Type Identification in command direction
Length of
Value Type of Informationobject
Info-Object
52…6
Reserved for extensions
9
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 194 Siemens Power Academy TD
Type Identification for organization objects
Length
of
Value Type of Informationobject
Info-
Object
70 End-of-initialization 1
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 195 Siemens Power Academy TD
Type Identification for parameters
Length of
Value Type of Informationobject
Info-Object
Parameter for meas.
110 3
values, normalized value
Parameter for meas.
111
values, scaled value
Parameter for meas. values
112 3
floating point
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 196 Siemens Power Academy TD
Transmission lists, priorities, functions
Prio:
9 ... 13 Start by a spontaneous
Spontaneous lists
Telegram image, process information
Prio: Telegram buffer
9 ... 13
Organisation list Start by CPU
System indications if an internal
Prio: indication will
1 ... 8
occur
Prio:
always 0
high *) with raising priority
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 197 Siemens Power Academy TD
Transmission lists, important lists
Basic cycle list Only for point-to-point traffic, to supervise the communication channel
Periodic list
Time- / counter-
controlled list
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 198 Siemens Power Academy TD
Spontaneous lists
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 199 Siemens Power Academy TD
Cause of Transmission
Time mark ms
10 Conclusion of the activation
Time mark ms 11 Process feedback (e.g. from contr. center)
IV Res Time mark min 12 Process feedback (local command)
13 File Transfer
20 Response to general interrogation
Information object n
21-36 Response to group scan 1-16
Cause of transmissions contains information for
the Control Center, how to compute this message!
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 200 Siemens Power Academy TD
Quality Information
Type of information IV NT SB BL EI CY CA OV T
Single indications x x x x
Double indications x x x x
Transformer taps x x x x x x
Bit pattern x x x x
Measured values x x x x x
Metered values x x x
Protection indications x x x x x
Legend:
IV Invalid
NT Not topical
SB Substituted
BL Blocked
EI Elapsed time invalid
CY Carry during the specific integration period
CA Presetting since the last reading of the counter
OV Overflow
T Transient state
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
F02_Page 201 Siemens Power Academy TD
Quality Information
Abbr
Name Explanation
.
Invalid value, e.g. Invalid transformer tap
IV Invalid
position
Not topical, e.g. because of a I/O hardware
NT Not topical
problem
SB Substituted e.g. if a switch position has been substituted
e.g. because of bay blocking or telecontrol
BL Blocked
blocking
Only for protection indication if relative time is
EI Elapsed time invalid
invalid
Carry during the specific integration Only for counters, counter counts from
CY
period maximum to 0
Presetting since the last reading of the
CA Only for counters, if value was substituted
counter
Overflow, e.g. more than 24mA on a 20mA-
OV Overflow
input
10. Telecommunication
Restricted © Siemens AG 2013 All rights reserved. with IEC 101
T
F02_Page 202
Transient state Motor-drive-running-indication for Tap positions
Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
11. Communication with a Control
Center using IEC 60870-5-101 Slave
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Tele communication with a Control Centre
Control Centre
States, alarms, analogs
Commands
Switchgear
Parameters
have to match
settings in the
Control Centre
Here we can
set time stamp
parameters for
each data type
Parameters
have to match
settings in the
Control Centre
This is the
Substation Address (!)
Parameters
have to match
settings in the
Control Centre
Select Control Center, Mark the whole List-column, Select Yes for all (except IT type)
Mark the Telegram Address column, Select Automatic Value Input, Enter a start value for
calculation
11. TCC using IEC 101
Restricted © Siemens AG 2013 All rights reserved. Slave
F02_Page 210 Siemens Power Academy TD
Command Direction has to be defined as well
After having updated the system, the new application always appears first time in
“Stop” mode. Starting the IEC101-Slave including the sublevels, the slave
changes to “Pending Up” mode.
As no Control Center is connected, the communication will not yet run.
RTU
SICAM PAS
12. Interface Tester IECTEST
for IEC 60870-5-101/104
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Brief description
COM-Port used by
IECTEST (not PAS!!)
Dircection Bit
Communication
mode Balanced /
Unbalanced
Usage of Single
Characters
IEC 101
COM-Port
Sent requests
(orange) and
responses from
substation (green)
Communication protocol
12. Interface tester
Restricted © Siemens AG 2013 All rights reserved. IEC test
F02_Page 222 Siemens Power Academy TD
Starting communication
1.
2.
Either here…
or via menu
Windows /
Frame Interpreter
Message in
Structured or un- hexadecimal code
structured address
Received / Transmitted Cause of Transmission Quality Bits
Type Identifier Substation address Value Time stamp
12. Interface tester
Restricted © Siemens AG 2013 All rights reserved. IEC test
F02_Page 225 Siemens Power Academy TD
Command Settings
Normal
commands
like single- or
double
commands
Analog Setpoints
Digital Setpoints
Switching direction
OFF (Open)
ON (Close)
Type identifier
TK45=Single Cmd
Activation
TK46=Double Cmd
Abortion (for static Cmds)
TK47=Tap Changer Cmd
Execution of Cmds
Execute command
Select before operate SBO
(2-step-command-ouput)
Time synchronization
IEC 104
Switch
LAN-interface
LAN-interface
LAN Cable
Start DT will be
sent automatically
Export Names
Chose file
Imported messages
split up into
monitoring and
control direction
SICAM PAS
13. Siemens Serial Hub 7XV5655
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Our desired configuration
PAS Server
PAS Server
SIPROTEC
Serial Hub
7XV5655
Mini Bay Unit
6MB525
Choose „Accessories“
and then „7XV5655“
13. Siemens serial Hub
Restricted © Siemens AG 2013 All rights reserved. 7XV5655
F02_Page 243 Siemens Power Academy TD
Software components
The configuration tool has to be installed, to set the necessary parameters in the hub.
The firmware is usually not necessary, as it was already loaded by the factory.
After extraction
The name should be entered to identify the hub, especially if several hubs were
existing in your network.
TC57 is a technical commission within the IEC (International Electrotechnical Commission) responsible for
telecommunication for power transmission and distribution and also defines a telegram structure
FT1.2 (IEC60870-5-1) is a data format used for protocols like IEC60870-5-101 or -103
13. Siemens serial Hub
Restricted © Siemens AG 2013 All rights reserved. 7XV5655
F02_Page 254 Siemens Power Academy TD
Defining COM Port
RS485 termination
RS485 termination on or off*
On / Off S1
On / Off
*an RS485 bus has to be terminated at both of the ends of the line to avoid reflections.
SICAM PAS
14. Connection of a
Field Device with IEC 60870-5-103
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Our desired configuration
PAS Server
SIPROTEC
Serial Hub
7XV5655
Mini Bay Unit
6MB525
The serial hub is already pre-configured and provides a new COM-Port at your
PC
These addresses are sent from the device, these names are for further processing in PAS
14. Connection to a field
Restricted © Siemens AG 2013 All rights reserved. device via IEC 103
F02_Page 267 Siemens Power Academy TD
Defining message designations
Commands
Some general
device parameters
have to be entered
manually,
e.g. device name
and address
To import a device it is
necessary to have such a
Device File (from DIGSI).
ID Description
ID Description
50 Single indication
1 Single switch command, pulse
51 Transient message (fleeting point)
2 Double switch command, pulse
52 Double indication
3 Digital Setpoint, 8 bits
53 Tap position indication
4 Analogue setpoint, normalized
54 Bit pattern 8 bits
5 Digital Setpoint, 16 bits
55 Bit pattern 16 bits
6 Digital Setpoint, 32 bits
56 Bit pattern 32 bits
7 (Special command)
57 Bit pattern 24 bits
8 Single switch command, continuous
58 Metering value (counter)
9 Double switch command, continuous
59 Measured value
10 Metered value freeze command (restore)
60 Short time message (special single indication)
11 Switching authority command
61 Absolute time message with value
12 Digital output (1 bit) --> CR
62 Measured value, floating point
13 Task controlled output (1bit) --> CR
63 Single indication with value
14 State acquisition
70 Tap position indication (BCD)
15 Analogue Setpoint, floating point
71 Tap position indication (1 out of 6 bits)
16 Tap changer command
72 Tap position indication (1 out of 14 bits)
17 Analogue S etpoint, fixed point
73 Tap position indication (1 out of 22 bits)
18 Flag setting command
74
14. Connection to a field
Tap position indication (1 out of 30 bits)
Restricted © Siemens AG 2013 All rights reserved. device via IEC 103
F02_Page 279 Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
15. SICAM PAS CFC Logic Function
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Inserting „Automation“ Components
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 281 Siemens Power Academy TD
1. Example: OR Grouping
•As soon as one Alarm raises, the Resultant Alarm also raises.
•If all Alarms have cleared, the Resultant Alarm also clears.
SICAM PAS
Alarm 1
Alarm 2
RTU OR Resultant Alarm
Control Center
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Information Information
to SoftPLC from SoftPLC
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 282 Siemens Power Academy TD
Routing messages to SoftPLC
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 283 Siemens Power Academy TD
Information from SoftPLC...
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 284 Siemens Power Academy TD
Template PLC Master Device – Duplicating
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 285 Siemens Power Academy TD
Renaming duplicated message
As information name
has to be unique, we
have to rename the
new message.
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 286 Siemens Power Academy TD
Information from SoftPLC
In Mapping we now find the new message, and again we route it to SoftPLC also.
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 287 Siemens Power Academy TD
Opening SoftPLC Desktop
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 288 Siemens Power Academy TD
SoftPLC Desktop
Offline files
Window to edit file content
Function Blocks
and Variables
Compiler messages
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 289 Siemens Power Academy TD
Creating a CFC file
Editors
1.
4.
3.
2. Enter file name
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 290 Siemens Power Academy TD
Choosing a CFC block from the catalog
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 291 Siemens Power Academy TD
Inserting a CFC block
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 292 Siemens Power Academy TD
Inserting Variable into interconnection column
M=Master
S=Slave
G=Group
2. Select a Variable
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 293 Siemens Power Academy TD
Connecting block input and Variable
Shift-
click
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 294 Siemens Power Academy TD
Connecting Group Alarm Message to the output
Resultant Alarm
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 295 Siemens Power Academy TD
Compilation
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 296 Siemens Power Academy TD
Feature Enabler – Enable Automation
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 297 Siemens Power Academy TD
UI-Operation – Update system/view
and start automation
We have to start
all the automation
tree
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 298 Siemens Power Academy TD
Testing the Logic Function
The ValueViewer is the most simple way to watch the Resultant Message
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 299 Siemens Power Academy TD
CFC Examples
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 300 Siemens Power Academy TD
2. Grouping with a Boolean OR
Resultant Alarm
Alarm 2
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 301 Siemens Power Academy TD
3. Grouping with a “PAS_GROUPI”-Function Block
We usually rename
the group, e.g. to the
name of the resultant
message.
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 302 Siemens Power Academy TD
3. Grouping with a “PAS_GROUPI”-Function Block
2nd step is to assign the desired alarms to the new “Group” which appears as a new
column.
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 303 Siemens Power Academy TD
3. Grouping with a “PAS_GROUPI”-Function Block
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 304 Siemens Power Academy TD
3. Grouping with a “PAS_GROUPI”-Function Block
4th step is link the “Group” to the block input, and finally the resultant alarm
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 305 Siemens Power Academy TD
4. Interlocking
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 306 Siemens Power Academy TD
4. Interlocking
Q8 CB Command
Q1
Bus Bar Disconnnector Q1
Circuit Breaker Q0
Line Disconnector Q9
Earth Switch Q8
Q9
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 307 Siemens Power Academy TD
4. Interlocking
Note:
Testing interlocking always requires a positive (command executes) as
well as a negative (command does not execute) test !
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 308 Siemens Power Academy TD
4. Interlocking
On initiation of this command, the PAS system checks whether the Automation component was
actively running. If not, the command was locked (and cannot bypass the automation) for security
reasons.
Note:
Any command with interlocking should be ticked here!
Commands without COMMCP block must not be ticked!
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 309 Siemens Power Academy TD
5. Command Derivation
Out
CB “Off”
ION SEND Command
Output Comm
Alarm 1 INDIC
19 Cause
14 ValType
0 BOValue
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 310 Siemens Power Academy TD
6. Converting a Counter Differential Value to
a Counter Final Value
Counter Differential Value = After every restore the value is set to “0”
Counter Final Value = The value is accumulated after every restore.
Counter
Counter Final Value
Differential
Value
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 311 Siemens Power Academy TD
Diagnostic
•Run Sequence
•Online mode
•Watch list
•CDA – Control Data Analyzer
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 312 Siemens Power Academy TD
Run Sequence
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 313 Siemens Power Academy TD
Online Mode
The online values appear in blue colour at the inputs and outputs of all the blocks
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 314 Siemens Power Academy TD
Watchlist
Current value
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 315 Siemens Power Academy TD
CDA (Control Data Analyzer)
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 316 Siemens Power Academy TD
CDA – Necessary settings
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 317 Siemens Power Academy TD
CDA – Mapping an output to CDA
Currently Raised
Raised Cleared
Restricted © Siemens AG 2013 All rights reserved. 15. CFC logic functions
F02_Page 318 Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
16. IEC61850 Communication
Standard for Substations
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
International Standard
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 320 Siemens Power Academy TD
IEC 61850 - Speed
IEC 103
The protocol IEC 103 typically supports data rates of 9600 bit per second.
In contrast to IEC 103, IEC 61850 works nowadays with Fast Ethernet (100 megabits per
second). This is about 10.000 times faster than IEC 103.
If required the data rate can be expanded to up to 10 gigabits per second.
IEC 61850
IEC 61850
The communication standard IEC 61850 strictly separates data and services of the required
communication technology. That is, if there are new and faster ways of data transmission you
just need to change the “vehicle”, data and services keep equal.
IEC 61850
Interoperability
the ability of two or more IEDs from the same vendor, or from different vendors, to
exchange information and to use it for execution of customized functions
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 324 Siemens Power Academy TD
IEC 61850 - Interoperability
A big advantage of IEC 61850 is the standardization of services, description language and
interfaces.
That means, each vendor of IEC 61850 compatible devices has to develop according to the IEC
61850 standard. Therefore it is generally possible that devices of different vendors can talk to
each other in the same network without changing the protocol.
In order to configure IEC 61850 compatible devices all vendors have to use the same
configuration language SCL.
SCL:
Substation Configuration Language is based on XML
XML:
eXtended Markup Language is based on HTML
XML is a neutral format for data exchange. Mostly used in documentation.
More and more XML is used for configuration and data exchange of automation applications.
• XML is not a programming language ! ! !
• XML is not a database ! ! !
HTML:
HyperText Markup Language is a text based language for structuring of contents like texts,
pictures and hyper links in documents. HTML documents are the basis of the World Wide Web
and can be depicted by webbrowsers. Along with the real text HTML contains additional
information in terms of meta data. These meta data give information about the author, the
language or the colour of the text.
Markup
<contact>
Element Name
<name> Element Value
Start Tag <firstname>Dieter </firstname>
<familyname>Hochmuth </familyname>
</name>
<company>Siemens IC</company>
End Tag <phone Type=„Office“>267</phone>
<phone Type=„Fax“>100</phone>
</contact>
Attribute Name Attribute Value
Corporate
Network TCP/IP
There are several description files within IEC 61850
HMI
SCADA – WAN
standard.
The next slides explain the most common description
files:
• ICD file
• CID file
• SCD file
• SSD file
Corporate The ICD file describes the IED in general. The ICD file is like a template of an IED.
Network TCP/IP
Corporate The SSD file describes the pure configuration of the substation (without
Network TCP/IP description of the IED).
HMI
SCADA – WAN
-Q1 -Q8
-Q0 630A
-Q1 -Q8
M
L1,L2,L3
-T5
L1,L2,L3
L1,L2,L3
600-300/LA
15VA SP20
L1,L2,L3
600-300/LA
15VA SP20
-F6
-F6
Corporate The CID file describes the already configured IED. That is, substation
Network TCP/IP configuration + ICD
HMI 0 <?xml version="1.0" encoding="UTF-8"?>
SCADA – WAN 1 <SCL xmlns="http://www.iec.ch/61850/2003/SCL" xmlns:xsi="http://www.w3.org/2001/XMLSch
2
3 <Private type="Siemens-SclLib-Version">V02.11.01</Private>
4 <Private type="Siemens-SclLib-EditTime">19.11.2012 11:28:39</Private>
5 <Private type="Siemens-CRC">1434020772</Private>
6 <Header id="IED_1" version="1" revision="19" toolID="IEC61850 System Configurator, Version:
7 <Text>CID-File for device: IED_1</Text>
8 <History>
9 <Hitem version="1" revision="19" when="Monday, November 19, 2012 11:28:39 AM"
who="Licenced User: E D SE TRAINING 10 </History>
11 </Header>
12 <Substation name="Shoaibah 3">
13 <VoltageLevel name="Voltage level1">
-Q1 -Q8 14 <Bay name="Field1"/>
15 </VoltageLevel>
M
16 </Substation>
-Q0 630A 17 <Communication>
18 <Private type="Siemens-AppId-Correction_Fully">true</Private>
M
19 <SubNetwork name="Subnet1" type="8-MMS">
20 <Text/>
21 <Private type="Siemens-Start-Address">172.16.0.1</Private>
22 <Private type="Siemens-Default-Subnet-Mask">255.255.255.0</Private>
23 <Private type="Siemens-Application">GOOSE
-T5 application1||0001||PriorityLow||10|2000|000|4</Private>
L1,L2,L3 24 <BitRate unit="b/s" multiplier="M">100</BitRate>
25 <ConnectedAP iedName="IED_1" apName="P1">
26 <Private type="Siemens-Application-GSEControl">GOOSE
application1|CTRL|Control_DataSet1</Private>
L1,L2,L3 27 <Address>
600-300/LA 28 <P type="IP" xsi:type="tP_IP">192.168.245.12</P>
15VA SP20
29 <P type="IP-SUBNET" xsi:type="tP_IP-SUBNET">255.255.255.0</P>
-F6
Corporate The SCD file describes the entire substation configuration with all IEDs. That is,
Network TCP/IP SCD file is the merger of all CID files.
HMI
SCADA – WAN
M M M M
M M M M
Corporate
Network TCP/IP
HMI
SCADA – WAN
ICD CID
ICD CID
File
File
File File
IED Configured
Capability IED
Description SCD Description
File
Substation
Configuration
SSD Description
File
System
Specification
Description
61850 Client
Time synchronization
Control
Select before Operate (SBO) with
extended safety all commands to high
voltage devices
Direct Control with normal safety all
other commands
Information Report
all information in monitoring direction to
PAS
GOOSE
Inter device communication
interlocking, blocking etc.
File Transfer
61850 Server 61850 Server 61850 Server Alarm lists, Event lists
Transmission of fault records
Time Synchronisation
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 334 Siemens Power Academy TD
Updating ICD - Files
IED 1 All devices in the network need to know each other. In order to obtain this
status each *.icd file of each device needs to be updated in a central
database.
Afterwards the updated *.icd files can be downloaded to the devices.
Vendor A
Database
Ethernet with Engineering-Engineering- Engineering- Ethernet with
data data data
IEC 61850 IEC 61850
IED 2 IED 3
Vendor B Vendor C
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 335 Siemens Power Academy TD
IEC 61850 – creating PAS configuration data
5 The system configurator merges all *.icd files to one *.scd file.
Clients
• Client communicates
with several servers
• Server
supports connection
at the same time to
several clients
Servers
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 337 Siemens Power Academy TD
Publisher Subscriber Architecture
Multicast
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 338 Siemens Power Academy TD
Concept of a Logical Node
configuration
data
input output
data data
Basic Function
(e.g. Protection)
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 339 Siemens Power Academy TD
Logical Nodes
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 340 Siemens Power Academy TD
Data Objects – approx. 350 classes are specified
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 341 Siemens Power Academy TD
Standardizing Communication with Logical Nodes
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 342 Siemens Power Academy TD
Example
Measurement Unit
IED3 IED2
TCTR XCBR
Circuit Breaker
T1 Q0
IED - Intelligent Electronic Device (every device with a communication interface)
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 343 Siemens Power Academy TD
Addressing to control a circuit breaker
IED1/CBCSWI1.Pos.ctlVal
Ethernet based
Ethernet components from
RuggedCom recommend -
www.ruggedcom.com TP
34>(3xNo.of Switches)+No.of
IEDs) 16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 345 Siemens Power Academy TD
Configurations – Optical Ring with SIPROTECs
Substation communication
Transmission of fault records
Download and upload of settings
IED configuration
MACH1000 series
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 349 Siemens Power Academy TD
FO Cables and Distances
http://www.ruggedcom.com
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 350 Siemens Power Academy TD
Ethernet Master clocks
Meinberg LANTIME/GPS
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 351 Siemens Power Academy TD
Engineering
IED file
(*.icd)
Update
Device specific
Device library parameter set
Export
System
configuration
Station file
Download
data (*.scd)
Import
Standardized file
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 352 Siemens Power Academy TD
Diagnosis Tool Networkview
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 353 Siemens Power Academy TD
Diagnosis Tool IEC-Browser
16. IEC61850 –
Restricted © Siemens AG 2013 All rights reserved. Communication Standard
F02_Page 354 Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
17. Configuring IEC 61850 IEDs
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Process of Engineering
System configurator
System
Device files ICD in DIGSI: Export
configuration-
• IP-Addresses
data (*.scd)
IED file • GOOSE mapping
Configuring
(*.icd)
Update
Device library Device specific CID Import
parameter set
Download
System configurator
System
Device files
in DIGSI: Export
configuration-
• IP-Addresses
data (*.scd)
IED file • GOOSE mapping
Configuring
(*.icd)
Update
Device library Device specific Import
parameter set
Download
Mandatory data
in LD PROT/ e.g.
System interface LN RREC
IEC61850
S=specified data are always
X=extended data entered in SCD
User specific
data
SIPROTEC data in LD CTRL /
(Siemens-specific) in LD LN GGIOs
CTRL / LN GGIOs
System configurator
SICAM PAS
18. SNMP Simple Network
Management Protocol
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Network control via SNMP
SICAM PAS allows to manage and control system components supporting SNMP
(Simple Network Management Protocol), e.g. SIPROTEC relays, Switches or SICAM
PAS Station Units.
The SNMP protocol is based on UDP/IP (User Datagram Protocol/ Internet Protocol).
The idea of SNMP is to monitor and control networks and their components
(i.e. switches, routers, etc). This ought to work fast but with low bandwidth.
There should be transmitted no text (e.g. „PowerSupplyPrimary“), just numbers (e.g. „6“).
On sender side is a translation table which converts text to numbers and on receiver side
from numbers to text.
SNMP Manager SNMP Agent SNMP Agent
This table „Text – Number“ is called The number in the MIB is called OID
MIB (Management Information Base) (Object Identifier)
18. SNMP Simple Network
Restricted © Siemens AG 2013 All rights reserved. Management Protocol
F02_Page 373 Siemens Power Academy TD
What is a MIB (Management Information Base)?
• Is there a way to give the numbers a structure? So, the assignment „Number – Text“ is much faster ?
• Is it possible to cover really ALL information of ALL vendors in this table?
The answers are: „Yes“ and „Actually yes“
Here we had to enter the IP address of Here we have to enter the access code
the manager (PAS computer), only if we for the SNMP agent
had more than one IP address.
Device Description for the electrical EN 100 module just contains the 2 port failure
messages
18. SNMP Simple Network
Restricted © Siemens AG 2013 All rights reserved. Management Protocol
F02_Page 378 Siemens Power Academy TD
Configuration – Insert Device
SNMP Manager
Channel 1 faulty
Channel 2 faulty
el 1
el 2
n
n
Chan
Chan
SNMP Agent
SICAM PAS
Cu
FO
SICAM
PAS CC
Switch 1 Switch 2
100 Mbit/s
FO Ethernetring
SIPROTEC 1
Switch 3
Especially for switches with many ports, a grouping of all port related messages is
desired. This can easily be done in SICAM PAS without using CFC logic.
FO-Port 1 faulty
FO-Port 2 faulty Redundancy fault
Cu-Port 3 faulty
Cu-Port 4 faulty
Cu-Port 5 faulty
Cu-Port 6 faulty Port fault
Cu-Port 7 faulty
Cu-Port 8 faulty
Cu
FO
For each device to monitor (Switches or EN100) we can assign lists Port fault and/or
Redundancy fault.
In Mapping we now can assign each single message to the existing lists
SICAM PAS
19. HMI-Interface and Topology
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Creating an HMI Interface
Do not mix up
with Remote
Control Centers !
A *.PXD file will be created, which later has to be imported into PAS CC.
All the HMI mapped messages appear with their names and their internal addresses.
SICAM PAS PQS / YL7J002004 / IEC 60870-101 Master / Interface / miniRTU / Buffer overflow
SICAM_PAS_PQS\YB
NQ079932\IEC60870-
101Master\Interface\
RTU\Disconnector Q9
Training City
Sw 20kV
itch
g ear
rela
ted Feeder 12
n am
es
Disconnector Q9
The topological name will replace the technological name for the use in the HMI system
19. HMI interface and
Restricted © Siemens AG 2013 All rights reserved. Topology
F02_Page 405 Siemens Power Academy TD
At the very beginning all information is located in the top level
1. We create a new 2. Select the top level again, and activate the filter
“Station” called to display just the RTU messages
SSTN Training RTU to
group all RTU related
messages
Now just move the selected items into the desired level (drag & drop)
The RTU messages now have disappeared from the top level
Here we can replace the previous (technological) names by the new (topological) names.
SICAM PAS
20. Introduction to SICAM SCC
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
What is SICAM SCC?
TeleControlCenter
SICAM SCC visualizes and archives
the process data of SICAM PAS. SICAM SCC
SICAM SCC allows to control your (SCC= Substation Control Center)
substation (command execution)
Switching devices
Automatic creation of
scripts
IndustrialX-Controls
The central point for provisioning settings in SCC is the WinCC Explorer.
• Graphics Designer
• Alarm Logging
• Tag Logging
• Text Library
• User Administrator
After defining a new station in the project the following steps takes
place
Import / Update of SICAM PAS – Data
o Import of SICAM PAS variables into the tag management
o Import of SICAM PAS
messages into the alarm
logging
o Import of SICAM PAS
measured and metered
values into the tag logging
o Generation of the SICAM
specific structure variables
and the required internal
variables
and furthermore
Filter for Event List
Dialogue to control the Switching Authority
Control buttons for Bay- and Telecontrol Blocking
Off On Int
Note: Entering the first tag, automatically also enters the related command
tag.
Restricted © Siemens AG 2013 All rights reserved. 20. Introduction to SCC
F02_Page 423 Siemens Power Academy TD
Switchgear Objects - Colour
The switching devices are controlled in two steps with IndustrialX Controls
1st operation step: Selection of the switching direction
2nd operation step: Initiation of switching execution
If a connected device supports „Select before Operate“, this two-step
operation can be combined with this characteristic.
Further characteristics
Event List
Displays all information exept
analog and metered values
Alarm List
Display urgent alarms or
warnings, the operator has to
react to
The original absolute time stamp created directly in IED or in IED-connection are
recorded in the alarm logging
In the event lists are recorded besides the time stamp and the status of the indication
also further additional information like cause, source, status information, …
The display of values in SICAM PAS CC-Alarm logging includes besides the ON/OFF
also
Intermediate position (double indications)
Bit pattern
Text values
The text values can be parameterized specifically, e.g. higher/lower.
Up to 8 different text groups can be created.
Command indications are recorded additionally to the process indication
The logic of the acknowledgement can be selected in the alarm lists,
it can be acknowledged
Raised
Cleared
Raised and Cleared
The entry of the raised status be kept in the alarm list until the reception of the clear status
Restricted © Siemens AG 2013 All rights reserved. 20. Introduction to SCC
and
F02_Page 429 eventually the acknowledge of the cleared status. Siemens Power Academy TD
Connection States
GI finished
Communication Failure
SICAM Valpro is the program for evaluation of measurement and counter archives
Display of measured and Time
metered values as a graph interval
or table
Original
values
SIMATIC WinCC
15 min
Tag logging archive Maximum
1h
values
1d
15 min
Average
1h
values
SICAM 1d
archived Valpro 15 min
original values Minimum
1h
values
1d
Power factors
(Current/Voltage)
15 min
Cumulative-/
Difference values 1h
(Counters) 1d
The graphical display of measurement curves is using the same graphic module
as in the Comtrade Viewer and SIGRA 4 program
Following functions are
supported:
Activating / Deactivating
Zooming
Optimize the display in X- and Y-
direction
Hide / Unhide diagrams
Hide / Unhide curves
Select visible time frame
Configure curve settings
Configure diagram settings
Change legend of Diagrams
The displayed area can be adjusted for optimized navigation (and print out)
in minute, hour, day, month, year
SICAM PAS
21. SCC Software Setup
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Components
License Manager
WinCC Runtime
WinCC Configuration
WinCC OPC-Server
WinCC Smarttools
These two icons on the desktop indicate that WinCC and the
associated License Manager were installed.
SICAM PAS
22. Starting a SCC Project
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Authorization
PAS CC and WinCC require some licences for configuration as well as for the
runtime system.
These licences are provided together with the PAS CC packet in form of software
keys on memory sticks.
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 472 Siemens Power Academy TD
Starting the License Manager
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 473 Siemens Power Academy TD
Automation License Manager
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 474 Siemens Power Academy TD
Starting WinCC
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 475 Siemens Power Academy TD
Creating a Project
Single HMI
PC
Server
Client 1 Client 32
Server 1 Server 6
Client 1 Client 32
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 476 Siemens Power Academy TD
Name and path
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 477 Siemens Power Academy TD
The WinCC Explorer
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 478 Siemens Power Academy TD
Setting active design
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 479 Siemens Power Academy TD
Computer properties
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 480 Siemens Power Academy TD
Tasks to be started with the Runtime
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 481 Siemens Power Academy TD
Language and Key Disabling
To disable key
commbinations for the
operator during runtime
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 482 Siemens Power Academy TD
Graphics Runtime
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 483 Siemens Power Academy TD
The Communication Driver
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 484 Siemens Power Academy TD
Starting the SICAM PAS Wizard
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 485 Siemens Power Academy TD
SICAM PAS Wizard – Station name
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 486 Siemens Power Academy TD
SICAM PAS Wizard – Choosing PAS export data
Choose path
Choose file
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 487 Siemens Power Academy TD
SICAM PAS Wizard
No need to change
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 488 Siemens Power Academy TD
SICAM PAS Wizard - Initialisations
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 489 Siemens Power Academy TD
SICAM PAS Wizard - finished
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 490 Siemens Power Academy TD
IP Address of SICAM PAS computer
IP address of the
connected PAS system,
not PAS CC !
If both are on the same
computer, you may keep
0.0.0.0
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 491 Siemens Power Academy TD
Imported Tags
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 492 Siemens Power Academy TD
Data structure (monitoring direction)
Value………… indicates the current state, i.e. raised, cleared, on, off, open, close or any numerical value
for a metered or measured value
Cause……….. indicates, why a message was processed, i.e. spontaneous, general interrogation, cyclic
transmission, feedback, command termination...
Alarm………… only used for certain PCC projects; can be ignored for PAS
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 493 Siemens Power Academy TD
Data structure (control direction)
Value……………… indicates the control value, e.g. open, close, raise, lower,...
Cause…………….. indicates, why a message was processed, i.e., feedback, command termination...
AddCause………. indicates e.g. interlocking, switching current check, control authority violation...
Restricted © Siemens AG 2013 All rights reserved. 22. Starting a SCC project
F02_Page 494 Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
23. Graphics Designer
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Graphics Designer in the WinCC Explorer
Library
Object palette
with standard
Colour palette objects like line,
circle, square,
text…
Zoom function
Style palette for
line styles, line
weight, line
end…
WinCC Wizards
Construction
layers
Samples:
Global Library
SIMATIC-graphical
objects
Project-Library
SICAM-graphical objects
Switchgear devices
The main difference between these 2 libraries is, that the SICAM-Library basically
contains energy technical objects. These are often dynamised, I.e. assigned to any
processing logic. The configurer just has to assign the necessary tags.
SICAM-Objects are prepared for the SICAM PAS Data structure.
Double click the object - and browse for the status message of your breaker
The switchgear object needs to be assigned to the structure tag. This is why the
single components (Value, Validity, Cause…) are not shown here.
Restricted © Siemens AG 2013 All rights reserved. 23. Graphics Designer
F02_Page 501 Siemens Power Academy TD
Assigning tags
Tag for
acknowledging
blinking is always
the same
„QuitBlinking“
Selecting the measurd value tag provides (different to switchgear objects) all components of the
data structure. For the full functionality we have to assign the desired tag with the extension
“Counter” (!).
The object internally also evaluates the tags “Value” and “Validity”.
Note: the default “MesuredValue.Counter” is not a valid tag name. It has to be replaced by the
desired measured value tag from your Tag Management!
If device faulty
When overflow (e.g. more than 24mA)
If communication between PAS and PASCC fails
The values for Upper and Lower Limits are related to the displayed values, i.e. they depend on the
scaling.
If no limits have to be displayed, we have to enter values which practically cannot be reached.
Displaying a voltage of 20kV, the Upper Limit 1 can be set to e.g. 100kV, the Upper Limit 2 to
110kV, the Lower Limit 1 to (minus) -100kV, the Lower Limit 2 to -110kV.
*) The divider is the 2. possibility of scaling in WinCC. The usual scaling is to be done in the Tag
Management (see next page).
In „Miscellaneous“ we find the attribute „Display“, which can display or hide the text with
a Yes or No.
With a right hand mouse click you can choose „Dynamic dialog“
From all the components we have to choose *.Value, which carries the process value
SICAM PAS
24. Bay and Telecontrol Blocking
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Function of Bay- and Telecontrol Blocking
Offline display
Just another
symbol with the
same functions
SICAM PAS
25. Compatibility Key
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Compatibility Key between PAS and PAS CC
PAS CC reads the current compatibility key (via an external tag) and compares it with the
imported one. If keys differ, PAS CC stops Runtime.
When PAS and WinCC communicate, PAS sends the current PAS Compatibility Key to
WinCC (via an external tag) and WinCC compares it with the imported key.
If the compared keys were different, WinCC would pop up a message box to shut
down the Runtime.
It is automatically
displayed to overlay
the current diagram.
SICAM PAS
26. Switching Authority
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Definition of Switching Authority
Because of security reasons it is usually not allowed, that 2 operators have control
access to a substation at the same time
The Switching authority is the right of one operator (one Control station), to
control the substation via the control system, i.e. to execute commands.
At the same time this right was cancelled for all other operators.
2 1 1
3 2
4
5 3
Remote Local
Every control interface has a parameter called „Switching Authority Group Assignment“
The one we are defining, is the light-coloured line, while all ohter
interfaces are dark-coloured.
You can assign only your interface in the light line.
In „Mapping“ we find a message „AuthorityValue“ (Type SAC) which is our Switching Authority.
We tick it for Alarm Logging (Event List) as well as for Tag Management (Picture).
As it was not yet set, the value is still 0, which means neither LOCAL nor REMOTE, but
„everyone allowed to control“
= 8 Local 3
= 4 Local 2
= 2 Local 1
=
=
=
=
=
1.48.576 Remote 5
524.288 Remote 4
262.144 Remote 3
131.072 Remote 2
65.536 Remote 1
In PAS CC we now can find the new tag to control and to display.
= AuthorityValue
Checkbox
(for up to 3 PAS CC and up to 5 Remote Control Centers)
An operation from the Remote Control Center should be just the opposite.
SICAM PAS
27. WinCC User Administrator
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Task of the User Administrator
With the User Administrator we can define rights for each user.
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 546 Siemens Power Academy TD
User Administrator
Here we can
define user-
groups and
single users,
with certain
rights
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 547 Siemens Power Academy TD
Login-Function via key combination (option 1)
Press a key
combination,
then assign
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 548 Siemens Power Academy TD
Login via Button (option 2)
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 549 Siemens Power Academy TD
Login via button
*) If multiple monitors are used, the number defines on which of the monitors the login menu has to appear
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 550 Siemens Power Academy TD
Login Popup menu in Runtime mode
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 551 Siemens Power Academy TD
How to request a right e.g. for a switch
1st example:
A circuit breaker is only to be controlled by operators with rigth level 3 (process
controlling)
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 552 Siemens Power Academy TD
Entering the requested right
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 553 Siemens Power Academy TD
If operator does not have the requested right…
If the operator tries to operate an object he was not allowed, the system denies.
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 554 Siemens Power Academy TD
How to request a right e.g. for a button
2nd example:
A button is only to be controlled by operators with rigth level 10
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 555 Siemens Power Academy TD
User Administrator – Defining level of rights
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 556 Siemens Power Academy TD
Entering the requested right
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 557 Siemens Power Academy TD
If operator does not have the requested right…
If the operator tries to operate an object he was not allowed, the system denies.
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 558 Siemens Power Academy TD
Displaying the current operator
27. WinCC
Restricted © Siemens AG 2013 All rights reserved. Administrator
F02_Page 559 Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
28. Alarm Logging
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Use of Alarm Logging
Value current state, i.e. raised, cleared, on, off, open, close....
Location control source, i.e. local, remote, automatic, DIGSI local...
Cause cause of transmission
Status (Validity) chatter blocking. bay blocking, telecontrol blocking, overflow, not topical...
Additional Cause e.g. interlocking, control authority violation,...
ID number PASCC internal identification number
Supplementary Info (Additional Information)relative time (protection)
T.st.=Time status i.e. valid time, invalid time, synchronized, DST or normal time
SICAM Flag no meaning
The Wizard automatically assigns 2 (of 6) SICAM Message Classes to all imported messages.
All Single Points get the class „SICAM Message“,
all Double Points and Transients get „SICAM Message DI/TR/FB“.
Necessary for
Event List!
Segment 1
from to
yyyymmddhhmm
SICAM PAS
29. Redundancy
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Definition
IED IED
IED IED IED IED
Process Process Process Process
Sub-devices
If enabled system redundancy and interface redundancy, there are 4 functional equal
communication channels between PAS/PQS systems and sub-device. Each system is
connected with the sub-device via 2 interfaces.
Secondary Full Server Primary Full Server Secondary Full Server
Primary Full Server
Primary Secondary
sub-device Sub-device
Control
Center …with Full Redundancy
The system in standby mode detects the outage of the process leading system by
missing responds on requests. In this case the standby system automatically takes over,
and switches to leading mode.
On outage of the process leading Full Server, the Standby-Full Server takes over and
together all DIPs also switch over to the secondary system.
On outage of a DIP, only this one switches over. All not affected computers remain in
their current redundancy state.
The leading computer remains as active, even though the previously leading computer
would operate again. Primary Full Server Secondary Full Server
The manual system switchover always is computer specific, i.e. the redundancy state of
Full Servers and DIPs can change independently.
On a manual system switchover, all processes from the process leading computer will
switch over to the secondary machine.
Leading system
Standby system
With System and Interface redundancy, we now see the status of all 4 interfaces.
IED
RTU
Communication between
SICAM PAS 101 HMI PAS 1 101 HMI PAS 2
Slave prim. sec.
RTU and PAS 1 disturbed.
All undisturbed drivers in
Base Base PAS 1 remain active.
T101 Master driver in
Master
61850 101 61850 101
secondary system (PAS 2)
takes over communication
with RTU.
IED
RTU
Redundancy Scenario 2
Control Center HMI
SICAM
PAS CC
SoftPLC or another ‚Base‘
component of primary system
(PAS 1) fails.
101 HMI 101 HMI
Undisturbed drivers in
SICAM PAS PAS 1 PAS 2
Slave prim. sec. primary system remain
active.
Base Base
Base ‚Base‘ with all it‘s
components will be activated
Master
61850 101 61850 101
in secondary system (PAS 2).
V6 Protocols
IED IED
Connection of
Control Center HMI - doubled IEDs for same process
SICAM
PAS CC
objects
or
- one IED connected with two
independent interfaces.
SICAM PAS
“System Redundancy”
SICAM PAS PAS 1 PAS 2 +
prim. sec.
“Interface Redundancy”
„ONE process image“ „ONE process image“
Master
IED IED
IED
Control Center CC can establish two independent links to the redundant substation.
CC receives all information in monitoring direction but is only
allowed to send commands via one channel.
In case that CC keeps just one channel active and changes the
communication channel due to lost communication or for other reasons,
the SICAM PAS ensures that…
IEC60870-5-101
T101
Standby driver receives telegrams, but does not send
any telegram. Offline telegram buffer keeps latest
Modem messages internally.
Splitter
DNP
standby driver does not receive
telegrams, but Offline telegram buffer
PAS 1 PAS 2 keeps latest messages internally.
prim. sec.
Serial Hub
Ethernet TCP/IP
PAS 1 PAS 2
prim. sec.
Base Base
Router Router The Control Center can activate (STARTDT) the other
communication link independent of the redundancy
Ethernet TCP/IP
status of the substation.
Also in the case, that the link to PAS
PAS 1 PAS 2 2 will be activated, the command
prim. sec.
reporting in the substation HMI
Base Base (SICAM PAS CC) will be processed
correctly and completely.
S S
S S
Redundant systems exchange process and system data among each other during
operation. Therefore they use a network adapter.
In order to minimize the risk of redundancy failures due to a network cable problem, we
strongly recommend the use of a teaming adapter for communication among the two
systems.
System redundancy only works when all SICAM PAS computers are in the same
domain with the same user logged in.
You have to define, which network adapter is to be used as a System Adapter (network
adapter connected to the redundant system).
After SICAM PAS SW installation and reboot, the installation program detects, if more
than 1 network adapter was available. Subsequently the tool MediaSenseCheck
automatically opens.
Here just enter the IP address of the system adapters of both Full Servers and all DIPs
(and not IP addresses of any other network adapters).
Open properties of
My Network Places
on the Desktop Open properties of
LAN Connection Open properties of Internet
Protocol
29. SICAM PAS
Restricted © Siemens AG 2013 All rights reserved. redundancy
F02_Page 613 Siemens Power Academy TD
Modifying the HOSTS file – Proceeding
Now, after Notepad disappeared, press the open key in the window, which is now on
top. This automatically copies the content of the Hosts file into the LMHosts file!
Select Advanced and Advanced Settings in the window Network Connections, which
is still open.
As final test send a PING with name resolution from and to all involved computers.
Name of Partner N
system can be Booting stops
resolved?
Partner system
J Does Compkey N Booting stops
already
match?
running?
N J
Systems synchronises
Runtime
system active
SICAM PAS
30. Station Unit
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Overview
VGA Adapter
(Maximum resolution:
2048 x 1536 pixels 16M
colors @ 75Hz refresh
rate)
1 x Serial Port
Shock-proof Design
Recommendation:
Regular checks with this tool every two
month, after a life time of more than three
years monthly
Prevent Restart - After enabling/disabling of the FBWF for a certain volume a reboot of the
device is needed. This command is used to suppress this restart.
FBWF Tray - Starts the Icon in tray in the Windows Status Bar. The tray is used to be
Display started automatically.
Restricted © Siemens AG 2013 All rights reserved. 30. Station Unit
F02_Page 648 Siemens Power Academy TD
Software – Routing Tool
Scope of delivery
Setup for Installation on top of SICAM PAS V6.00
Service Information for installation and configuration of this driver
Pre-defined device descriptions for PSCM and Digital I/O Board
SICAM PAS V7.00 and higher have this driver installed by default
Features
support of potential-free binary output contacts of the Power Supply Control Module (PSCM)
support of binary contacts on Digital I/O board
•output contacts can be configured for use as
- Single Command
- Double Command
- Bit String Command
•Input Contacts can be configured for use as
- Single Point Information
- Double Point Information
- Bit String Information
Power Supply Switch-Over
•Double Command can be configured in order support switching between redundant power
supplies
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Or der Num be r : 6 M D 9 1 - 0 -
Ve r sion V ersi on 2.20 2 2 0
Pr im ar y Pow e r Supply: DC 24 – 60 A
A C / DC 110 – 23 0V B
Se c ondar y Pow e r Supply: DC 24 – 60 V A
A C / DC 110 – 23 0V B
No se cond ary po w er su pply C
CPU Type : CPU Mod ule w i th Sing le Co re CPU
( Ce leron M 4 40, 1 .8 6GHz), 2 x 4 GB CF, 2 GB RAM, Ima ge SU V 2.2 0, Bac ku p DV D 0
CPU Mod ule w i th Dual Core CPU
( Co re Du o T250 0, 2 GHz), 2 x 4 GB CF, 2 GB RAM, Imag e SU V2 .20 , Backup DVD 1
CPU Mod ule w i th Dual Core CPU w ith RAID system
( Intel Co re 2 Du o L750 0, 1.6GHz ), 2 x 2 GB CF, 4 GB RAM, Imag e SU V2.20, Backup
DV D, incl. RA ID c ontrolle r a nd RAID Sy stem Lev el 1 i ncl. 1 00 GByte disks 2
I/O Boar ds : Non e 0
One Digital I/O Modu le (32 bin ary con ta cts) 1
Tw o Digital I/O Modu le (64 bin ary co nta cts) 2
PC I - Adapte r : Without PCI – A dapter A
With PCI – Ad apter B
COM Por t Expande r: Without COM Port Exp ande r A
8 p orts, inc l. Oc to pus Cabl e B
Guar ante e Exte nsion: Stand ard 2 yea r g uara ntee 0
Guara ntee for 3rd y ear 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Order Number 6 M D 9 9 - A 0 - 0 A A 0 Order Number 6 M D 9 9 - A 0 - 0 A A 0
| | | | | | | | | |
| | | | | | | | | |
Version: 6 7 8 | | Version: 6 7 8 | |
Version V2.20 2 2 0 | | Version V2.20 2 2 0 | |
Power Supply: 10 11 I/O Module 10 11
DC 24-60V A 0 Digital I/O Module (32 contacts) F 0
AC / DC 110-230V A 1 Carrier Board for I/O Modules F 1
Power Supply Control Module A 8 44-pin D-Sub Connector with cable (2 meters)
CPU 10 11 and pigtail F 2
CPU Module with Single Core CPU 44-pin D-Sub Connector with cable (10 meters)
(Celeron® M 440, 1.86GHz), 2 x 4GB CF, 2GB RAM, and pigtail F 3
Image SU V2 20, Recovery DVD Set B 0 Miscelaneus 10 11
CPU Module with Dual Core CPU Front Cover G 0
(Core Duo T2500, 2GHz), 2 x 4GB CF, 2GB RAM, System Rack without modules and power supplies G 1
Image SU V2 20, Recovery DVD Set B 1 USB DVD Drive G 2
CPU Module with Dual Core CPU for Raid System Upgrade 10 11
(Intel Core 2 Duo L7500 1.6GHz),
Upgrade Kit for SICAM Station V2.00 / V2.10
2 x 4GB CF, 4GB RAM, Image SU V2 20,
Recovery DVD Set, incl. Raid Controller consists of
B 2 - 2 x 4GB CF cards,
Data Storage 10 11 - 1 x Recovery DVD Set incl.Upgrade License for
4GB Compact Flash Card C 0 Windows Embedded Standard (COA Sticker) H 1
100 GB Harddisk for Raid System only C 1 Software 10 11
PCI-Adapter 10 11 Recovery DVD Set (without MS License) S 1
PCI-Adapter D 0
Front Plate replacement for PCI Bridge D 1
Com Port Expander 10 11
8 Ports, incl. Octopus Cable E 0
Octopus Cable E 1
DC – AC converter is required to power the SICAM PAS uses SIEMENS IPC with a DC
PC from the station battery Power Supply
No redundant power supply Redundant power supply, switchover without
reboot
Standard PCs have reduced temperature SICAM PAS uses IPC with higher
range temperature range 0°to 55°C
environment temperature w/o fan (with no
PCI cards)
Standard PCs are leading users to "play" SICAM Station Unit has no floppy & CD Rom
with the systems drive.
SICAM Station Unit runs Windows XP Embedded
(WXPE) OS, i.e. the OS is especially tailored for the
SA application no games, multimedia etc.
Restricted © Siemens AG 2013 All rights reserved. 30. Station Unit
It657
F02_Page is very difficult to get spare parts due to SICAM PAS Station Unit guarantees up
Siemens Power to 10TD
Academy
Siemens Power Academy TD
SICAM PAS
31. Project Configurations
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
IEC 61850 Ethernet Medium: FO Ring
Router
Control Centre
Converter
Diagnosis
Field 1 ... n
Switchgear
Router
Control Centre
Diagnosis
16 Interfaces RJ45
(CAT 5-Standard)
Field 1 ... n
Switchgear
Router
Control Centre
Diagnosis Switch
Field 1 ... n
Switchgear
Router
Control Centre
Switch
Diagnosis
62,5µ or 50µ , 1300nm
Field 1 ... n
Switchgear
Router
Control Centre
Switch Switch
Diagnosis
62,5µ or 50µ , 1300nm
Field 1 ... n
Switchgear
Switch
Diagnosis
Switch 62,5µ or 50µ , 1300nm
Switch Switch
Field 1 ... n
Switchgear
Diagnosis Switch
62,5µ or 50µ , 1300nm
Switch
100 MBit - Ethernet-network
IEC61850 FO-ring
with ring management
Switch
Switch
Which
complexity is
still wise?
Feld 1 ... n
Switchgear
Ethernet TCP/IP
Switchgear
General station
indications
Station Bus Ethernet TCP/IP with IEC61850 Station Bus Ethernet TCP/IP with IEC61850 Station Bus Ethernet TCP/IP with IEC61850
Schaltanlage
Switchgear- -Section
Abschnitt
I I Schaltanlage
Switchgear –-Section
Abschnitt
II II Schaltanlage
Switchgear – Section
Abschnitt
- I and
I und
II II
Main protection and control Main protection and control Backup-protection
10km
SICAM PAS CC
Local HMI
Station bus Ethernet with IEC61850 Station bus Ethernet with IEC61850 Station bus Ethernet with IEC61850
Control Centre
SICAM PAS
138 / 13.8kV
Load shedding - function
SICAM PAS
32. Normalization
Modification of values
Scaling of measurements and counter values
Inverting single or double point indications
Adaptation of transformer tap position indications
For measurements
the input type and
conversion type are
important!
Assign Normalization
For indications
Input type Digital,
Conversion type
Conversion
SICAM PAS
33. System Variables
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
System Variables
Communication failed
(often used to log in event/alarm list)
Value
1 _Opr
0
2 _ComFault
1
2 _OprReady
1
Time
GI
Note:
Telecontrol Blocking is
not specifically indicated
in the Value Viewer
Regular GI
Overall
Process
Image
Overall Interface
Process specific image
Image
SICAM PAS
34. OPC Communication with COM /
DCOM
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
What is OPC ?
OPC
stands for OLE (Object Linking and Embedding) for Process Control
is the automation industry‘s version of OLE
provides an open, flexible, plug-and-play software standard for software
interoperability in the automation industry
specific to the automation industry and its' unique needs for data
communication (alarming, historical data access and trending, batch
and more)
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 700 Siemens Power Academy TD
What is OPC ?
OPC
is based on OLE, COM (component object model) and DCOM
(distributed component object model) technologies
consists of a standard set of interfaces, properties and
methods for use in process- control and manufacturing
automation application
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 701 Siemens Power Academy TD
Why is OPC ?
Openness
System-wide operation between automation products of different manufacturers
Data are only acquired once from field level right up to operational control level
Access to MS-Office under Windows
Ease of Use
Same user interface for different components
Performance
C++ interface
Efficient data access through volume operations
Requirement-oriented client-server communication
Connectability
Can be reached by any computer in the LAN/WAN (via COM/DCOM)
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 702 Siemens Power Academy TD
How does OPC work ?
OPC Client
OPC Initiates OPC communications
Client Read/write requests
OPC
OPC Communications based on
COM/DCOM
Data: single or in groups
OPC OPC Server
Server
Executes client requests
Cyclically/change-driven
Makes own data available
Network
Network
PAS CC From any To any client
server
HMI system
Routing
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 704 Siemens Power Academy TD
OPC Server & Client: Configuring a common account
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 705 Siemens Power Academy TD
OPC Server & Client: Configuring a common account
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 706 Siemens Power Academy TD
OPC Server & Client: Default Properties for DCOM
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 707 Siemens Power Academy TD
OPC Server & Client: Default Properties for DCOM
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 708 Siemens Power Academy TD
OPC Server & Client: COM Security
Permissions have to be
configured in all the 4 buttons
see following pages
3 1
4
2
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 709 Siemens Power Academy TD
OPC Server & Client: Access Permissions, Default
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 710 Siemens Power Academy TD
OPC Server & Client: Default
1 2
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 711 Siemens Power Academy TD
OPC Server & Client: Default
3 3
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 712 Siemens Power Academy TD
OPC Server & Client: Limits
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 713 Siemens Power Academy TD
OPC Server & Client: Assigning new Administrator
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 714 Siemens Power Academy TD
OPC Server & Client: Assigning new Administrator
Open OpcEnum properties, select Identidy tab and enter again the desired account
and password.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 715 Siemens Power Academy TD
OPC Server & Client: Assigning new Administrator
Open Security tab and assign the new account once more to „configuratuion
permissions“
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 716 Siemens Power Academy TD
OPC Server & Client: for local accounts
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 717 Siemens Power Academy TD
OPC Server & Client: for local accounts
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 718 Siemens Power Academy TD
OPC Server
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 719 Siemens Power Academy TD
OPC Server: Feature Enabler without Password
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 720 Siemens Power Academy TD
OPC Server: Assigning new Administrator
Open the properties of the SIEMENS SICAM PAS OPC DA Server, Open Identidy tab
and assign the new account once more.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 721 Siemens Power Academy TD
OPC Server: UI-Configuration
Has to be entered
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 722 Siemens Power Academy TD
OPC Server: Mapping
Enable
information,
which has to be
routed to any
OPC client
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 723 Siemens Power Academy TD
OPC Server: UI-Operation
Update System.
Start the OPC Server (remains in „Pending Up“)
Data is now ready for being polled by a client.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 724 Siemens Power Academy TD
OPC Client
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 725 Siemens Power Academy TD
OPC Client: Feature Enabler with Password
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 726 Siemens Power Academy TD
SSR: Assigning new Administrator
Now select the Services, open the properties of the PAS OPC Client, Open LogOn tab
and assign the new account once more.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 727 Siemens Power Academy TD
SSR: Assigning new Administrator
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 728 Siemens Power Academy TD
OPC Client
Enter OPC
Client and
interface.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 729 Siemens Power Academy TD
OPC Client: Selecting an OPC server
Select the Computer Name parameter and hit the browser button to browse for an
OPC Server computer.
Note: The red parameter field is not yet to be configured.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 730 Siemens Power Academy TD
OPC Client: Selecting an OPC server
Open the Local Network, select the desired computer name, and mark the
OPCServer.SICAM_PAS_DA
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 731 Siemens Power Academy TD
OPC Client: Selecting an OPC server
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 732 Siemens Power Academy TD
OPC Client: Entering a device
Now enter a device. The device represents the physical device to communicate with.
Browse for the desired variables in Value Selection Box
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 733 Siemens Power Academy TD
OPC Client: Variables supplied by the server
While browsing for the desired variables, the OPC-Server already is in RUN
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 734 Siemens Power Academy TD
OPC Client: Templates
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 735 Siemens Power Academy TD
OPC Client: Correct protocol information types
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 736 Siemens Power Academy TD
OPC Client: Mapping
With the USE information is made available for all the routing, e.g. to PAS CC
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 737 Siemens Power Academy TD
OPC Client: UI-Operation
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 738 Siemens Power Academy TD
Known (Windows-)problems
Under Windows XP SP2 you may have problems with access rights between server
and client. Then please follow these instructions:
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 739 Siemens Power Academy TD
OPC Client: overwriting limits
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 740 Siemens Power Academy TD
OPC Client: Security options - DCOM
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 741 Siemens Power Academy TD
DCOM Machine Access Restrictions
These settings disable the buttons “Edit Limits” in the computer properties on page 11.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 742 Siemens Power Academy TD
DCOM Machine Launch Restrictions
A Restart is
recommended after these
settings.
These settings disable the buttons “Edit Limits” in the computer properties on page 11.
Restricted © Siemens AG 2013 All rights reserved. 34. OPC with COM/DCOM
F02_Page 743 Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
35. OPC-XML-Server
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Basics
OPC XML-DA Server is a protocol for SICAM PAS. Microsoft IIS-Server is used as Web-
Server for OPC XML-DA.
This allows data exchange of SICAM PAS with any OPC XML-DA Client.
OPC XML-DA Server and OPC XML-DA Client are installed on different PCs, the
communication runs on TCP/IP.
The open communication provides data exchange with other Systems, which are based
on Microsoft Windows, but also on other operating systems, e.g. LINUX.
OPC XML-DA Server supports the exchange of structured information (process data) via
Internet using XML (EXtensible Markup Language).
The OPC XML-DA Client can set protocol parameters through the OPC XML-DA Server
and can read and write all values, which in SICAM PAS UI have been mapped to OPC
XML-DA.
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 745 Siemens Power Academy TD
Difference to previous OPC
„normales“
PreviousOPC
OPCDA
DA OPC XML-DA
Windows
or other
Control Center
Windows OPC XML-DA Client
Operating System
OPC DA Client
LAN LAN,WAN /
Internet
SICAM PAS
SICAM PAS
IIS Microsoft
OPC DA Webserver
Server
OPC XML-DA
Server
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 746 Siemens Power Academy TD
Overview of OPC data flow (Example)
PAS
IIS
Computer
Server Client Computer
Softing
OPC Server LAN
LANor
or OPC Client
WAN
WAN
RTU Network
Network
IEC101 slave Routing
IEC101 master
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 747 Siemens Power Academy TD
Pre-Conditions
Windows IIS (Internet Information Server) from Version 5.1 forward is to be installed on
your PAS computer (Attention with CAT-Clients, contact your IT Service!)
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 748 Siemens Power Academy TD
Creating OPC XML-DA Server in PAS
o Ready
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 749 Siemens Power Academy TD
Starting OPC XML-DA Server in Runtime
Update System
and start OPC
branch
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 750 Siemens Power Academy TD
Softing Demo Client
Just started
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 751 Siemens Power Academy TD
Softing Demo Client – Establishing connection
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 752 Siemens Power Academy TD
Softing Demo Client – Successful connection
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 753 Siemens Power Academy TD
Softing Demo Client – Provided Data
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 754 Siemens Power Academy TD
Softing Demo Client – Displaying Details
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 755 Siemens Power Academy TD
Softing Demo Client – Visualised Data Points
Data points of
the selected
group
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 756 Siemens Power Academy TD
Softing Demo Client – Watching Data
The tab „DA Items“ now shows all related values online
Restricted © Siemens AG 2013 All rights reserved. 35. OPC XML Server
F02_Page 757 Siemens Power Academy TD
Siemens Power Academy TD
SICAM PAS
36. SICAM PAS Automation
with the programming language ST
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Overview
No recursion !
Example
Example
Example
FB:
Syntax of a declaration:
Example
PROG:
In SICAM PAS there is a special global program for interfacing variables. This
program does not include source code -> global data file „pasglob.poe“
Function blocks are able to access global variables of their program via
VAR_EXTERNAL
better with input/output variables
Example:
TYPE
State : BYTE:=4;
END_TYPE
Operand1
Expression1 Operator
Statement Keyword Operand2
Expression2
ST-Programm
Statement
; Blank command
Priority
Syntax:
Designator := Expression
Example:
Trigger := TRUE;
a := 4 / 2 + 1;
b := FunctionA(4);
FB-Call (Example):
Declaration Program
VAR
FB_TEST : PAS_SASS; FB_TEST(EN:=TRUE);
END_VAR b:=FB_TEST.MARKER;
RETURN (Example)
RETURN;
Syntax:
Example:
Syntax:
CASE Print OF
Print value: Command block;
ELSE Command block;
END_CASE;
Example:
CASE value1 OF
1: RETURN;
2: flag:=TRUE;
ELSE flag:=FALSE;
END_CASE;
Syntax:
Example:
FOR i:=5 to 1 BY -1 DO
value[i]:= i;
END_FOR;
Syntax:
WHILE Print DO
Command block;
END_WHILE;
Example:
WHILE flag=TRUE DO
wert:=wert-1;
if wert<5 THEN flag:=FALSE;
END_IF;
END_WHILE;
Syntax:
REPEAT
Command block;
UNTIL Print
END_REPEAT;
Example:
REPEAT
value:=wert+1;
UNTIL value>5
END_REPEAT;
(* Comment *)
Example:
(* This is a comment *)
SICAM PAS
37. ST Lab
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
How can I write my own Function Block?
My new file
Here we have to write the code
External Variables
LOGIC:
110 or
101 or
011
THEN OUT=1, otherwise 0
Create Indication,Enable = 1, Cause = spontaneous, Indictype= SP, Signal_1 receives current value
from the boolean variable OUT, Change to trigger the block, Send to execute during startup!
OUT_IND is the resultant variable and gets the result from CRI-output INDIC
SICAM PAS
38. SICAM PAS User Administration
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Administrating Users
Users Administration
The Administrator can assign a user to a predefined user group (level of rights)
Logging in the first time into User Administration, the system requests the default
Login:
User: Administrator
Password: Admin
SICAM PAS
39. Server-DIP Configuration
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Full Server – DIP Configuration
IEC T101
Up to 6 DIPs
Corporate
Up to 350 Bay devices
Control Center Network TCP/IP
Up to 20.000 data points
Full Server
DIP No.1 DIP No.2
Station Bus
Browser button
In our configuration, we will cut the RTU application from Full Server and
paste it to the DIP (check COM port)
After having updated the system and connecting communication cable now to the
other computer, the RTU is now running at the DIP
SICAM PAS
40. Group Indicator in Alarm Logging
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
What is that for ?
If new messages appear in the Alarm List, the system has to inform the operator about.
Open properties
Value = 128 64 32 16 8 4 2 1
7 6 5 4 3 2 1 0
Acknowledge-Bit State-Bit
1. Display or hide
2. Display static or blinking
3. Display in red or green
Red
Grey
Next page
Invisible
Must be dynamic next page
Red
Green
SICAM PAS
41. Sound output with WinCC Horn
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
WinCC Horn
The sound can be acknowledged, either with acknowledgement of the message in the
Alarm List, or by a separate button.
Set the value of o binary variable – with the name Horn – to the value of 0
…when sounding
As the Horn tag is a binary tag, it corresponds with the values for the attribute Display, i.e. Yes and No refer to 1 and 0 (or True and False)
SICAM PAS
42. Topological coloring
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Why Topological Colouring?
Ex.
Red = under voltage
Green= de-energized
Here we get
preconfigured objects
supporting dynamic
colouring
Usually we do not
have do change
anything here.
Just having chosen
the type „with
measurement“, we
have to define the
switching point and
hysteresis
Here we have to
assign the respective
tags.
*.Validity and
*.Value
SICAM PAS
43. Diagnostic tools
Restricted © Siemens AG 2013 All rights reserved. siemens.com/poweracademy
Diagnostic - tools for PAS V7
Windows Services
Process Explorer
Event Viewer
SSRTestUI
Portmon
MediaSenseCheck
Shows all available network adapters. The desired PAS-network adapter has to be added to the