Terminal test block

Terminal Test Block


A topmost requirement by Utilities is that • Dual marking system, one for
calibrating or replacing kwh meters identification of wiring (at connection
should be carried out without cutting the point) and another that helps
electrical energy supply, but also under identifying the kind of connection
full safety both for operators and (voltages and currents at their
equipment. respective phases).
A unit, linked between the current • New enclosure-like full cover fitted
transformers and the energy meters, is with two unloseable seal caps.
therefore required, which will enable the • The circuit opening and jumpering
operator to thoroughly and easily check operation is carried out by means of
the condition of the connections, namely the test plugs usually housed at the
that they are tight and reliable after a long outer side of the closing end walls.
frequent use, but mainly that they keep These plugs should be inserted in the
safe against the risk of electric shock. bottom sockets at the transformer side
Cewe Instrument can provide you with of each set of c.t. terminal blocks.
Terminal Test Block for your meters. We Contact between different potentials
offer one version for 3 currents/ 4 will thus be avoided.
voltages and one for 2 currents/3 • The test block assembly yields entire
voltages. The Test blocks are DIN rail protection against accidental hand
mounted and equipped with sealable a contact.
transparent cover.
• Energy Meter Test Blocks are
General features supplied fully assembled, in order to
meet the 100% quality requirement of
• Thickness of terminal block unit 12
the Quality Control Standard
mm., that makes easier standardised
Specification. Supply of loose
by the Utilities.
components could not be considered
• Disconnect operation by means of as under cover of such standard
slide link fitted with single unloseable specification because this latter
screw. This solution greatly increases contains the proper prescriptions for a
safety of operation as against existing correct assembly.
systems that require two tools for
operating the link.

2
Technical data
Technical specification
Size of test block unit
Rated voltage: 380V
Pollution degree: 3
Rated current: 5A
Rated cross-section: 10 mm²
AWG cross-section: 16..6
Insulating housing: Polyamide V0
Conductor bar: electrolytic copper
Finish of live parts: Electrolytic tin
plating.
Brass machined parts: > 58 % Cu
contents.
Material of test sockets: Cu.
Clamping units: Yellow chromate
passivated
hardened steel.
Disconnect device
designed to carry out
electrical insulation
function.
Transparent cover: UL std. V-0 grade
self-extinguishing

7E 10E
Total length mm (L) 150 192
Total height mm (A1) 76 76
Width mm (A2) 147 147
Weight kg 0.5 0.8

3
Components
1 GFS 35 din rail
2 BFRV10/D side fixing wall
3 RB-10 terminal block
4 RB-TE terminal block
5 RB-TM terminal block
6 CP2X12N jumper plug
7 ERB/10E/I enclosure cover
8 RMD Marking tags 10E/C(R,.N)

Tests
• Insulating strength 4x104MΩ
In addition to VDE certification tests, the • Heating of the jumper plugs (41A)
following laboratory tests have been • Incandescent wire 960 ºC (all plastic
successfully completed: parts)
• Tension fall under a 5A current • Composition of the conducting materials
• Heating with under a 50A current • Resistance to vibration
• Dielectric strength with a 6000V voltage • Resistance to humid environment
between potentials and 10000V to earth • Resistance of marking tags
• Short time current: 600A/1s

Name Description Article no.

Terminal Test Block Terminal Test Block 2 currents 3 voltages 379891006

Terminal Test Block Terminal Test Block 3 currents 4 voltages 379891007


A0190e-2

Cewe Instrument AB 4
Box 1006 y SE-611 29 Nyköping y SWEDEN
info@ceweinstrument.se y www.ceweinstrument.se