PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 1 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: Control cabinet C.T. Ratio: 3000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring OK Taps Tightened OK Type: 47D

Bearing Condition N/A Contacts Cleaned N/A Use: UV/PHASE SEQUENCE

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120 VAC


24VDC
Rust OK
CONTROL

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A N/A N/A N/A N/A TD-5=0.85 SEC.

As Found N/A N/A 90V/70% N/A N/A N/A 5.0 DEFINITE TIME

As Left N/A N/A 90V/70% N/A N/A N/A 5.0

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out “
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 92 V 61V X X
O.845SEC X
A Phase N/A 90V 63V 0.834SEC
B Phase N/A “ “ “
B Phase N/A ““ ““ ““
C Phase N/A
“ “ “
C Phase N/A
GRD N/A
GRD N/A FV NEG SEQ.TEST OK

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 2 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________
Circuit Identification: Control Cabinet C.T. Ratio: 3000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 47H

Bearing Condition N/A Contacts Cleaned N/A Use: U V/PHASE SEQ.

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120 VAC


Rust OK 24 VDC CNTRL.

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Ement A B C GRD Dial/Tap

Specified

As Found N/A 0.05SEC. 100V/90% N/A N/A N/A INST.

As Left N/A 0.05SEC. 100V/90% N/A N/A N/A INST.

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 103V 91.8V X X
0.32SEC. X
A Phase
B Phase
N/A
N/A
103V
103V
91.8V
91.8V 0.032SEC
0.32SEC.
B Phase
C Phase
N/A
N/A
103V
103V
91.8V
91.8V
0.032SEC
0.32SEC. PHASE SEQUENCE OK
C Phase N/A 103V 91.8V 0.32SEC
GRD N/A
GRD N/A FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 3 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: CONTROL CABINET C.T. Ratio: P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 81


Bearing Condition N/A Contacts Cleaned N/A Use: O/U FREQUENCY

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120V

Rust OK 24VDC C..P.

Remarks:
FIRST SETTING : 15-0-9-13 = 58HZ SECOND SETTING : 15-7-9-10 = 61HZ

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified

As Found N/A N/A 58HZ/61HZ 3 CYC.

As Left N/A N/A 58 HZ/61HZ 3 CYC.

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 58 HZ 61 HZ X X CYC
3.97 X 3.81 CYC.
A Phase N/A 58 HZ 61 HZ 3.97 CYC 3.81 CYC.
B Phase N/A 58 HZ 61 HZ 3.97 CYC 3.81 CYC.
B Phase N/A 58 HZ 61 HZ 3.97 CYC 3.81 CYC.
C Phase N/A 58 HZ 61 HZ 3.97 CYC 3.81 CYC.
C Phase
GRD N/A 58 HZ 61 HZ 3.97 CYC 3.81 CYC.

GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 4 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: CONTROL CABINET C.T. Ratio: 3000/5 P.T. Ratio:

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 46D

Bearing Condition N/A Contacts Cleaned N/A Use: CURRENT BALANCE

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 0.5 AMPS


Rust OK 24 VDC C.P

Remarks: PICK UP SETTING X RATED = OPERATIONAR AMPS


RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A

As Found N/A N/A 0.5 AMPS N/A N/A N/A 0.70 SEC.

As Left N/A N/A 0.5 AMPS N/A N/A N/A 0.70 SEC.

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 1 X 0.5 A =0.5A X X X0.70 SEC.
A Phase N/A 1 X 0.5 A =0.5A 0.70 SEC.
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 5 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: CONTROL CABINET C.T. Ratio: 3000/5 P.T. Ratio:

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 46D

Bearing Condition N/A Contacts Cleaned N/A Use: CURRENT BALANCE

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 0.5 A

Rust OK C.P. 24 VDC

Remarks:
PICK UP SETTING X RATED = OPERATING AMPS

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A


TEST OPERATIONS - AS FOUND - TIME IN SECONDS
As Found N/A N/A 0.90 A 1.5 SEC.
Inst. Element
As Left Time Element
N/A N/A Current/Voltage
0.90 A Current t / Voltage ICS AMPS
1.5 SEC.

P.U. Time
Zero Pick Drop Pick Drop
Set P.U. Tap 1 Tap 2 Up Out Up Out
Tap 1 Tap 2
X X X
TEST OPERATIONS- AS LEFT - TIME IN SECONDS
A Phase N/A 1.74 X 0.5=.87A 1.56 SEC. lnst. Element
Time Element Current/Voltage ICS AMPS
Current / Voltage
B Phase
Zero P.U. Time Pick Drop Pick
C Phase

GRD
Drop
P.U. Tap 1 Tap 2
Set Tap 1 Tap 2 UP Out Up Out
X X X

A Phase N/A 1.80 X .5 =.90 A 1.58 SEC.

B Phase

C Phase

GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 6 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: CONTROL CABINET C.T. Ratio: 4000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 32

Bearing Condition N/A Contacts Cleaned N/A Use: DIRECTIONAL

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120 VAC


Rust OK C.P. 24 VDC

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A

As Found N/A N/A 0.016

As Left N/A N/A 0.016

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 0.016 A 120 V X X X
A Phase N/A 0.16 A 120 V
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV
PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 7 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: CONTROL CABINET C.T. Ratio: 4000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 32

Bearing Condition N/A Contacts Cleaned N/A Use: DIRECTIONAL

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120 VAC

Rust OK C.P. 24 VDC

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A

As Found N/A N/A 0.016 A

As Left N/A N/A 0.016 A

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 0.016 A 120 V X X X
A Phase N/A 0.016A 12O V
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 8 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________
Circuit Identification: GEN.2 C.T. Ratio: 3000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 32R

Bearing Condition N/A Contacts Cleaned N/A Use: REVERSE POWER (40)

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120 VAC


Rust OK C.P. 24 VDC

Remarks:
FORMULA @ O DEG. = V X I X COS = 120V X 0.33A X 1= 39.6 WATS

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A

As Found N/A N/A 40 WATS 10 SEC.

As Left N/A N/A 40 WATS 10 SEC.

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 120 V 0.43 A X W 9.89
51.6 X SEC. X
A Phase N/A 120 V 0.33 A 39.6 W 10.01 SEC.
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 9 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: GEN 1 C.T. Ratio: 3000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 32 R


Bearing Condition N/A Contacts Cleaned N/A Use: REVERSE POWER (40)

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120VAC

Rust OK C.P. 24 VDC

Remarks:
FORMULA @ 0 DEG. = V X I X COS. = 120 X 0.33 X 1 = 39.6 WATS

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A

As Found N/A N/A 40 W 10 SEC.

As Left N/A N/A 40 W 10 SEC.

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2 10.08
A Phase N/A 120 V 0.50 A X W
60 X X
SEC.
A Phase N/A 120 V 0.33 A 39.6 W 10.01 SEC.
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 10 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: GEN. 2 C.T. Ratio: 3000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 32R

Bearing Condition N/A Contacts Cleaned N/A Use: REVERSE POWER

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120VAC


Rust OK C.P.24VDC

Remarks: FORMULA @ 0 DEG. V X I X COS. = 120V X 0.208A X 1 = 24.96W

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A

As Found N/A N/A 25 W 10 SEC.

As Left N/A N/A 25 W 10 SEC.

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 120V 0.32A X
38.4W X SEC. X
9.99
A Phase N/A 120V 0.208A 24.96W 10.01 SEC.
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 11 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: GEN 1 C.T. Ratio: 3000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 32R

Bearing Condition N/A Contacts Cleaned N/A Use: REVERSE POWER

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK 120 VAC


Rust OK C.P. 24 VDC

Remarks: FORMULA @ 0 DEG. V X I X COS. = 120V X 0.21A X 1 = 25.2W

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified N/A N/A TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
As Found N/A N/A 25 W 10 SEC.
Time Element Current/Voltage Current t / Voltage ICS AMPS
As Left N/A N/A 25 W 10 SEC.
P.U. Time
Zero Pick Drop Pick Drop
Set P.U. Tap 1 Tap 2 Up Out Up Out
Tap 1 Tap 2
X X X
10.08
A Phase N/A 120 V 0.30 A 36 W TEST OPERATIONS- AS LEFT - TIME IN SECONDS
SEC.
lnst. Element
B Phase Time Element Current/Voltage ICS AMPS
Current / Voltage
C Phase

GRD
P.U. Time
Zero Pick Drop Pick Drop
Set P.U. Tap 1 Tap 2 UP Out Up Out
Tap 1 Tap 2
X X X
A Phase N/A 120 V 0.21 A 25 W 9.98 SEC.

B Phase

C Phase

GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 12 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: CONTROL CABINET C.T. Ratio: 4000/5 P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK G lass Cleaned OK Device: ø/ Ground


Glass OK Case Cleaned OK

Foreign Material OK Relay Cleaned OK Mfr: ABB

Moisture OK Connection Tight N/A

Spiral Spring N/A Taps Tightened OK Type: 51I

Bearing Condition N/A Contacts Cleaned N/A Use: 50/51 (67)

Bearing End-Play N/A Insulation Resistance N/A Characteristics:

Disc Clearance N/A Trip Circuit OK O. C.


Rust OK C.P. 24 VDC

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified

As Found N/A 3.0 A 1.5 1.5 1.5 N/A 1.0

As Left N/A 3.0 A 1.5 1.5 1.5 N/A 1.0

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X 1.5
P.U. XTap
2.01 TapX2 3.0 UP Out Up Out
Tap 1 Tap 2
A Phase N/A 1.5 X 1.5
0.778 X 2.0
0.528 X 3.0
0.36 2.9 2.8 N/A N/A
A Phase
B Phase
N/A
N/A
1.5
1.5
0.778
0.781
0.528
0.538
0.360
0.3607 2.9
2.9 2.8
2.8 N/A
N/A N/A
N/A
B Phase
C Phase
N/A
N/A
1.5
1.5
0.7817
0.795
0.538
0.513
0.3607
0.3607 2.9
2.9 2.8
2.8 N/A
N/A N/A
N/A
C Phase
GRD
N/A
N/A
1.5 0.7980 0.5318 0.3607 2.9 2.8 N/A N/A
GRD N/A FV
PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 13 of: 13


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: CONTROL CABINET C.T. Ratio: N/A P.T. Ratio: 4/1

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket OK OK OK OK G lass Cleaned OK OK OK OK Device: ø/ Ground


Glass OK OK OK OK Case Cleaned OK OK OK OK

Foreign Material OK OK OK OK Relay Cleaned OK OK OK OK Mfr: ABB

Moisture OK OK OK OK Connection Tight N/A N/A N/A N/A

Spiral Spring N/A N/A N/A N/A Taps Tightened OK OK OK OK Type: 27/59

Bearing Condition N/A N/A N/A N/A Contacts Cleaned N/A N/A N/A N/A Use: OVER/UNDER VOLT. (67)

Bearing End-Play N/A N/A N/A N/A Insulation Resistance N/A N/A N/A N/A Characteristics:

Disc Clearance N/A N/A N/A N/A Trip Circuit OK OK OK OK 120 V AC

Rust OK OK OK OK C.P. 24 VDC

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified

As Found N/A N/A 140 / 90 140 / 90 140 / 90 85/30 1.0

As Left N/A N/A 140 /90 140 /90 140 /90 1.0

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage CURVE
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap
591 TapX2 27 UP Out Up Out
CURVE
Tap 1 Tap 2
A Phase N/A 141 90 X X0.11
59 X 1.0517
27 PHASE 59 SHORT DIF.
A Phase N/A 141 90 0.1100 1.0517
B Phase N/A 141 91 0.1082 1.0786 PHASE 27 MOD. DIF.
B Phase N/A 141 91 0.1082 1.0786 PHASE 59 SHORT DIF.
C Phase N/A 140 90 0.1086 1.0532 GRD. 59 MOD. DIF.
C Phase
GRD N/A
N/A 140
85 90
30 0.1086
0.9948 1.0532
1.0163 PHASE 27MOD
GRD 27 MOD.DIF.
DIF.

GRD N/A 85 30 0.9948 1.0163 FV GRD. 59 MOD. DIF.


GRD 27 MOD DIF.

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 1 of: 12


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear
____________________________________________________________________________________________________________________________________________

Circuit Identification: C.T. Ratio: P.T. Ratio:

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket G lass Cleaned Device: ø/ Ground


Glass Case Cleaned

Foreign Material Relay Cleaned Mfr:

Moisture Connection Tight

Spiral Spring Taps Tightened Type:

Bearing Condition Contacts Cleaned Use:

Bearing End-Play Insulation Resistance Characteristics:

Disc Clearance Trip Circuit


Rust

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified

As Found

As Left

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase X X X
A Phase
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV

PROTECTIVE RELAY TEST REPORT

Customer: American International Plaza Date : 01/27/2011 Sheet No. 1 of: 12


Address: Hato Rey, Puerto Rico Air Temp. 86 Submitted by : E.Pena
Owner User Date Last Inspection
Address Last Inspection Report No.
Equipment Location: Mezzanine Substation Relative Humidity
Owner Identification Paralleling Switchgear

____________________________________________________________________________________________________________________________________________

Circuit Identification: C.T. Ratio: P.T. Ratio:

VISUAL INSPECTION ROUTINE MAINTENANCE

A B C GRD A B C GRD

Cover Gasket G lass Cleaned Device: ø/ Ground


Glass Case Cleaned

Foreign Material Relay Cleaned Mfr:


Moisture Connection Tight

Spiral Spring Taps Tightened Type:

Bearing Condition Contacts Cleaned Use:

Bearing End-Play Insulation Resistance Characteristics:

Disc Clearance Trip Circuit

Rust

Remarks:

RELAY SETTINGS
Inst. Time
ICS
Element A B C GRD Dial/Tap

Specified

As Found

As Left

TEST OPERATIONS - AS FOUND - TIME IN SECONDS


Inst. Element
Time Element TEST OPERATIONS- Current
Current/Voltage AS LEFT - TIME IN SECONDS
t / Voltage ICS AMPS
lnst. Element
Time Element Current/Voltage ICS AMPS
P.U. Time Current / Voltage
Zero Pick Drop Pick Drop
Set P.U. P.U. Time1
Tap Tap 2 Up Out Up Out
Zero Tap 1 Tap 2 Pick Drop Pick Drop
Set
X
P.U. XTap 1 TapX2 UP Out Up Out
Tap 1 Tap 2
A Phase X X X
A Phase
B Phase
B Phase
C Phase
C Phase
GRD
GRD FV