ID#: 110044782AA
Konvekta AG
Am Nordbahnhof 5
34613 Schwalmstadt Germany
Tel. +49 ( 0 ) 66 91 / 76 – 0
Fax +49 ( 0 ) 66 91 / 76 - 200
Info@konvekta.com
www.konvekta.com
110044782AA.doc
History of modification:
The high quality level of the KONVEKTA air conditioning units is guaranteed by continuous
development of the construction, equipment and accessories. This may result in differences
between the present maintenance instructions and your air conditioning unit. Please under-
stand that no claims can be forwarded regarding the instructions, the pictures and the de-
scriptions.
Contents
Page:
1. General Description...........................................................................................................4
1.1. KS 45 Hardware...................................................................................................................4
1.2. KS 45 software.....................................................................................................................4
5. Error handling..................................................................................................................13
9. Dimensions ......................................................................................................................20
1. General Description
1.1. KS 45 Hardware
1.2. KS 45 software
The software of the KS45 is independent of the operating software of the KN400. The CAN
transmission protocol exchanges the commands and values with the KN400 network. Control
parameter and functions are stored in the KN400. The operating software for the KS45 can
be downloading via the program KSFlash and carry the V24 engine in the control over.
2. Function description
S1 S5
S2 S6
S3 S4
When the power supply to the unit is interrupted the unit will carry out a self test after having
impressed voltage. Thereby all in- and outlets are being checked. In case parts of the air
conditioning unit (i.e. sensor) have to be exchanged, a self test has to be carried out to cali-
brate the unit.
8888
4500
0004
GU 0
The course of the self test is shown on the display: S01, S02 etc.
The nodes and be switched from the KS45rail KN400rail administered by Master on and log-
out.
Log In: When logging is the position, software version and configuration
for 5 seconds on the display.
Log Off: When Logout is ---- the position, as displayed and version number.
When KS45rail failure or interruption of the line are no CANopen Control signals to the mas-
ter KN400rail transferred and registered an error. By creating the signal (release manage-
ment) despite the lack of control switches CANopen connection from the KS45rail KN400rail
to the Master after about 5 minutes in the operating AUTO to ensure the operation. If the sig-
nal (release control turned off), is the KN400rail OFF.
Software Basic 1
Control ON (keypad operation and direction of travel)
- Preheating / Preventilation 1
- Preheating / Preventilation 2
- Under voltage 1
- Under voltage 2
- AUTO
- Reheat (via AUTO button when active)
- ECO
- Tunnel (via button)
Software Basic 2
Control ON (keypad operation and direction of travel)
- Preheating / Preventilation 1
- 400V / 3Ph available
- More compressors can be started
- Reduced availability of power supply
- AUTO
- Reheat (via AUTO button when active)
- ECO
- Tunnel (via button)
The switching of the signals can also be done with a short "circuit break" because the state
delayed system to be passed. Note: The +24 volt power supply must go hand while switching
channels, however, be present.
1) CAR
2) Under voltage 2
3) Under voltage 1
4) Preheating / Preventilation 2
5) Preheating / Preventilation 1
After switching off the KS45 EEProm is stored in the following functions:
To allow for operation via the keyboard must first release Enabled, then the average passen-
ger room temperature is displayed. If the release is not active blink the colon in Sekunden-
tackt.- A control (enable operation via keyboard and direction) Display:- Current actual tem-
perature averaged space The six films buttons can be set and the functions The shortcut can
be queried and version numbers Errors are called.
The air conditioning control unit possesses an AUTO - function, which depending
on the temperature activates the cooling, ventilation or heating to regulate the
temperature in the vehicle.
The air conditioning control unit possesses a reheat - function, which enables the
humid air to dry.
– Compressor
– Condenser
– Evaporator blower automatic
– Recirculated air flap to recirculated air
By activating the compressor the air in the duct gets cold and the roof heating heats against
it.
After 20 min. the reheat – function will automatically be turned off.
The recirculated air flap is controlled in AUTO –function, depending on the temperature.
Through the button T6 the recirculated air flap can be determined manually, i.e. in case of tunnel pas-
sage.
By pressing the button twice S5 the outside temperature is displayed on the dis-
play, again press back twice to room temperature.
If there are several mistakes that run automatically on the screen through. Note: There will be
max. 8 Error of KN400 retrieved.
An erase the error is only with the PC tool KSDiag possible.
By pressing the S2 and S6, or after a waiting period of 10sec. the mode is switched back to
the basic display.
The initial setting is [size 0], so all controls for all 4 groups are simultaneously controlled. By
adjustment of the individual group with the control groups can be independently controlled
CANopen are connected.
With the keys S3 + S4 can then group the required number will be selected.
Pressing the button S1 and S3, the mode with the [rSt] rely on the display and a self-test.
The following operating modes can be adjusted through external signals. A release by the
signal [A control] is not necessary. When there is no external signal, the colon blinks every
second.
AUTO
Display:
- If current average room temperature
- AUTO symbol
- CLIMATE minutes when Stern. Use a compressor
Keys:
- S3 temperature correction +
- S4 temperature correction –
- S5 Manual fan setting
- S6 Tunnel
- S1 + S5 query the error code
- S2 + S6 querying the version number
Additional features:
- MAXIMUM heating
By long pressing S3 (about 10 sec when AUTO active)
Display: - 4 bars on the temperature indicator at the top ----
- MAXIMUM Cooling
By long pressing S4 (about 10 sec when AUTO active)
Display: 4 bars on the temperature gauge below ----
The following settings are permanently stored in even after the power is removed or re-
leased:
Display:
After switching on the power supply, the backlight is active. If there is up to no external power
supply signal is the cur-rent averaged temperature display.
5. Error handling
Error handling via control unit KS45
The vehicle being turned off, the error storage can be called up by simultaneously pressing
the buttons S1 „AUTO“ and S5 „Evaporator blower“.
When the display remains dark there is no error registered.
In case the display indicates i.e. 0200 there is an error registered.
With the button T3 „increase“ the next error can be called up.
X1 / 04 DA 04 Message Tunnel
X1 / 05 DA 05 Message Preheating
X1 / 06 DA 06 Collective fault message
X1 / 07 DA 07 Message Under voltage
X1 / 08 CAN LOW CANopen LOW control -Bus
X1 / 09 CAN HIGH CANopen HIGH control -Bus
X1 / 10 VCC24L 24V Supply
X1 / 11 VCC24 24V 24V Supply
X1 / 12 VCC24 GND GND 24
X1 / 04 DA 04 Message Tunnel
X1 / 05 DA 05 Message Preheating
X1 / 06 DA 06 Collective fault message
X1 / 07 DA 07 Message Under voltage
X1 / 08 CAN LOW CANopen LOW control -Bus
X1 / 09 CAN HIGH CANopen HIGH control -Bus
X1 / 10 VCC24L 24V Supply
X1 / 11 VCC24 24V 24V Supply
X1 / 12 VCC24 GND GND 24
8. Error messages
Fühlerfehler: Fehler Nummer
Kurzschluss Außenfühler Short-circuit Outside sensor 01
Kabelbruch Außenfühler Cable breakdown Outside sensor 02
Kurzschluss Raumfühler 1 Short-circuit Room sensor 1 03
Kabelbruch Raumfühler 1 Cable breakdown Room sensor 2 04
Kurzschluss Konvektorfühler vorne 1 circuit Convector 1 sensor front 05
Kabelbruch Konvektorfühler vorne 1 breakdown Convector 1 sensor front 06
Kurzschluss Konvektorfühler hinten 1 circuit Convector 1 sensor rear 07
Kabelbruch Konvektorfühler hinten 1 breakdown Konvektor1 sensor rear 08
Kurzschluss Kanalfühler 1 circuit air duct sensor 1 09
Kabelbruch Kanalfühler 1 Cable breakdown air duct sensor 1 10
Kurzschluss Raumfühler 2 Short-circuit Room sensor 2 11
Kabelbruch Raumfühler 2 Cable breakdown Room sensor 2 12
Kurzschluss Konvektorfühler vorne 2 circuit Convector 2 sensor front 13
Kabelbruch Konvektorfühler vorne 2 breakdown Convector 2 sensor front 14
Kurzschluss Konvektorfühler hinten 2 circuit Convector 2 sensor rear 15
Kabelbruch Konvektorfühler hinten 2 breakdown Convector 2 sensor rear 16
Kurzschluss Kanalfühler 2 circuit air duct sensor 2 17
Kabelbruch Kanalfühler 2 Cable breakdown air duct sensor 2 18
Kurzschluss Vereisungsfühler 1 Short-circuit Eis sensor1 19
Kabelbruch Vereisungsfühler 1 Cable breakdown Eis sensor 1 20
Kurzschluss Vereisungsfühler 2 Short-circuit Eis sensor 2 21
Kabelbruch Vereisungsfühler 2 Cable breakdown Eis sensor 2 22
Kurzschluss Vereisungsfühler FB Short-circuit Frontbox Eis sensor 23
Kabelbruch Vereisungsfühler FB Cable breakdown Frontbox Eis sensor 24
Kurzschluss Wasserfühler Short-circuit water sensor 25
Kabelbruch Wasserfühler Cable breakdown water sensor 26
Kurzschluss Kondensatorfühler Short-circuit condenser sensor 27
Kabelbruch Kondensatorfühler Cable breakdown condenser sensor 28
Kurzschluss Frontboxfühler 1 Short-circuit Frontbox sensor 1 29
Kabelbruch Frontboxfühler 1 Cable breakdown Frontbox sensor 1 30
Kurzschluss Frontboxfühler 2 Short-circuit Frontbox sensor 2 31
Kabelbruch Frontboxfühler 2 Cable breakdown Frontbox sensor 2 32
Kurzschluss RES_33 Short-circuit RES sensor 33
Kabelbruch RES_34 Cable breakdown RES sensor 34
Kurzschluss DA Frontboxgebläse Stufe1(Freigabe DZM) Short-circuit DA Evaporator blower Frontbox step 1131
Kurzschluss DA Frontboxgebläse Stufe 2 Short-circuit DA Evaporator blower Frontbox step 2132
Kurzschluss DA Frontboxgebläse Stufe 3 Short-circuit DA Evaporator blower Frontbox step 3133
Kurzschluss DA Frontboxklima Short-circuit DA Frontbox climate 134
Kurzschluss DA Klima AN Short-circuit DA climate ON 135
Kurzschluss DA Umluft / Umluft 1 Short-circuit DA Circulation inside air 1 136
Kurzschluss DA Umluft / Mischluft 1 Short-circuit DA Circulation mix air 1 137
Kurzschluss DA Umluft / Frischluft 1 Short-circuit DA Circulation fresh air 1 138
Kurzschluss DA Umluft / Umluft 2 Short-circuit DA Circulation inside air 2 139
Kurzschluss DA Umluft / Mischluft 2 Short-circuit DA Circulation mix air 2 140
Kurzschluss DA Umluft / Frischluft 2 Short-circuit DA Circulation fresh air 2 141
Kurzschluss DA DA_142 Short-circuit DA RES 142
Kurzschluss DA Flüssigkeitsventil 1 Short-circuit DA liquid valve 1 143
Kurzschluss DA Flüssigkeitsventil 2 Short-circuit DA liquid valve 2 144
Kurzschluss DA Unterstuhlgebläse 1 Stufe 1 Short-circuit DA unterchair blower1 step 1 145
Kurzschluss DA Unterstuhlgebläse 1 Stufe 2 Short-circuit DA unterchair blower1 step 2 146
Kurzschluss DA Unterstuhlgebläse 2 Stufe 1 Short-circuit DA unterchair blower2 step 1 147
Kurzschluss DA Unterstuhlgebläse 2 Stufe 2 Short-circuit DA unterchair blower2 step 2 148
Kurzschluss DA Wasserpumpe Dach Short-circuit DA water pump Roof 149
Kurzschluss DA Frontbox Heizung Stufe 1 Short-circuit DA Frontbox heater step 1 150
Kurzschluss DA Frontbox Heizung Stufe 2 Short-circuit DA Frontbox heater step 2 151
Kurzschluss DA Frontbox Luftverteilung Scheibe Short-circuit DA Frontbox Air flap window 152
Kurzschluss DA Frontbox Luftverteilung Fahrer Short-circuit DA Frontbox Air flap driver 153
Kurzschluss DA Frontbox Luftverteilung Fuß Short-circuit DA Frontbox Air flap feat 154
Kurzschluss DA Frontbox Kondensator Short-circuit DA Frontbox Condenser 155
Kurzschluss DA Frontbox Verdichter Short-circuit DA Frontbox Compressor 156
Kurzschluss DA Luftklappe Klima 3/A Short-circuit DA Circulation flap 3/A 157
Kurzschluss DA Luftklappe Klima 3/B Short-circuit DA Circulation flap 3/B 158
Kurzschluss DA Luftklappe Klima 4/A Short-circuit DA Circulation flap 4/A 159
Kurzschluss DA Luftklappe Klima 4/B Short-circuit DA Circulation flap 4/B 160
Kurzschluss DA Ölsumpfheizung Short-circuit DA Oil heater 161
Kurzschluss DA Dachheizung Stufe 1 Short-circuit DA Roof heater step 1 162
Kurzschluss DA Dachheizung Stufe 2 Short-circuit DA Roof heater step 2 163
Kurzschluss DA Heizleistung Gesamtfahrzeug Short-circuit DA heater vehicles 164
Kurzschluss DA Heizleistung Dach Short-circuit DA heater Roof 165
Kurzschluss DA Konvektor Short-circuit DA heater Convector 166
Kurzschluss DA Unterstuhlheizer 1 Short-circuit DA heater unterchair 1 167
Kurzschluss DA Unterstuhlheizer 2 Short-circuit DA heater unterchair 1 168
Kurzschluss DA Generator Short-circuit DA Generator 169
Signal CAN open Fehler Verbindung Master zum Bedieneinheit Signal CAN open connection Master control panel 222
Signal CAN open Fehler Verbindung Slave 1 zum Bedieneinheit Signal CAN open connection Slave 1 control panel 223
Signal CAN open Fehler Verbindung Slave 2 zum Bedieneinheit Signal CAN open connection Slave 2 control panel 224
Signal CAN open Fehler Verbindung Slave 3 zum Bedieneinheit Signal CAN open connection Slave 3 control panel 225
Klima CAN Fehler Verbindung SUP1 Klima CAN error connection SUP 1 231
Klima CAN Fehler Verbindung SUP2 Klima CAN error connection SUP 2 232
Klima CAN Fehler Verbindung SUP3 Klima CAN error connection SUP 3 233
Klima CAN Fehler Verbindung SUP4 Klima CAN error connection SUP 4 234
Klima CAN Fehler SUP1 Klima CAN error SUP 1 235
Klima CAN Fehler SUP2 Klima CAN error SUP 2 236
Klima CAN Fehler SUP3 Klima CAN error SUP 3 237
Klima CAN Fehler SUP4 Klima CAN error SUP 4 238
9. Dimensions