Assembly- and service manual for

AC control unit KS 45

KONVEKTA part number: H11-004-478 Basic 1


and H11-005-472 Basic 2

ID#: 110044782AA
Konvekta AG
Am Nordbahnhof 5
34613 Schwalmstadt Germany

Tel. +49 ( 0 ) 66 91 / 76 – 0
Fax +49 ( 0 ) 66 91 / 76 - 200
 Info@konvekta.com
www.konvekta.com
110044782AA.doc

History of modification:

Index Date Remarks Depart. / Name


A00 06.09.2006 Document provides BKT3 P. Möller
A01 11.12.2006 Panel redesigned BKT3 P. Möller
A02 29.10.2007 Complete document revised BKT3 P. Möller
A03 03.04.2008 Complete document revised BKT3 P. Möller
A04 22.09.2009 Outside temperature display page 7 added BKT3 P. Möller
A05 18.02.2010 The KS45 to the function of p10 group management BKT3 P. Möller
expanded.
A06 01.06.2010 Possible error messages of KN400 inserted page BKT3 P. Möller
14
A07 05.07.2010 Extension of a basic KS45 by adding features to the BKT3 P. Möller
second basic

The high quality level of the KONVEKTA air conditioning units is guaranteed by continuous
development of the construction, equipment and accessories. This may result in differences
between the present maintenance instructions and your air conditioning unit. Please under-
stand that no claims can be forwarded regarding the instructions, the pictures and the de-
scriptions.

KONVEKTA AG Stand: 05.07.2010 Seite: 2/21


110044782AA.doc

Contents
Page:

1. General Description...........................................................................................................4
1.1. KS 45 Hardware...................................................................................................................4
1.2. KS 45 software.....................................................................................................................4

2. Function description .........................................................................................................5


2.1. Button assignment ...............................................................................................................5
2.2. Self test................................................................................................................................6
2.3. LED diagnostics of CANopen Systems ................................................................................7
2.4. External control KS45 ..........................................................................................................8
2.5. Storage of functions / values: ...............................................................................................9

3. Operation of the control via keyboard .............................................................................9


3.1. AUTO Function ....................................................................................................................9
3.2. Reheat function....................................................................................................................9
3.3. Manual ventilation ................................................................................................................9
3.4. Recirculated air flap ...........................................................................................................10
3.5. Display of outside temperature S5 .....................................................................................10
3.6. Up Arrow key S3 ................................................................................................................10
3.7. Down Arrow button S4 .......................................................................................................10
3.8. Accessing the software version..........................................................................................10
3.9. Accessing error ..................................................................................................................10
3.10. Setting group control: .......................................................................................................11

4. Control via external signals: ...........................................................................................11


4.1. Inputs / Outputs:.................................................................................................................13

5. Error handling..................................................................................................................13

6. Pin assignment Basic 1...................................................................................................14

7. Pin assignment Basic 2...................................................................................................15

8. Error messages ...............................................................................................................16

9. Dimensions ......................................................................................................................20

10. Notes ...............................................................................................................................21

KONVEKTA AG Stand: 05.07.2010 Seite: 3/21


110044782AA.doc

1. General Description

The KS45 is an operating unit for climate control KN400.


Due to its compact design of 96 x 48 mm, the device can be easily integrated in the dash-
board.
The driver will be painted with simple and clear operation of all functions of the optical cooling
relief of the passenger compartment.

1.1. KS 45 Hardware

• The control unit has dimensions of 96 x 48 x 80 mm.


• The operating software can download a program and a V24 engine transferred to the
control unit.
• The connection is made via two AMP Junior Timer (12 - and 18 pin) -.
• The CAN-BUS, we, the control unit connected to the controller KN400.

1.2. KS 45 software

The software of the KS45 is independent of the operating software of the KN400. The CAN
transmission protocol exchanges the commands and values with the KN400 network. Control
parameter and functions are stored in the KN400. The operating software for the KS45 can
be downloading via the program KSFlash and carry the V24 engine in the control over.

KONVEKTA AG Stand: 05.07.2010 Seite: 4/21


110044782AA.doc

2. Function description

2.1. Button assignment

S1 S5

S2 S6

S3 S4

Button S1 „AUTO“: Starts the automatic heating / cooling / ventilating


Button S2 „Reheat“: Reheat activated during XX minutes
Button S3 „Increase“: Increases the desired temperature
Increases the blower capacity
Button S4 „Decrease“: Decreases the desired temperature
Decreases the blower capacity
Button S5 „Evaporator blower“: Activates the manual blower capacity
Button S6 „recirculated air“: Activates the recirculated air flap

KONVEKTA AG Stand: 05.07.2010 Seite: 5/21


110044782AA.doc

2.2. Self test

When the power supply to the unit is interrupted the unit will carry out a self test after having
impressed voltage. Thereby all in- and outlets are being checked. In case parts of the air
conditioning unit (i.e. sensor) have to be exchanged, a self test has to be carried out to cali-
brate the unit.

Code Self test (S-Code):

- Lighting up of all symbols in the display:

8888

- Display of the unit type:

4500

- Display of the software version:

0004

- Display the selected group:

GU 0

The course of the self test is shown on the display: S01, S02 etc.

CAn11 (Group 1 Master)


Software: 2104
Config: 0001

Can12 (Group 1 Slave1)


Software: 2104
Config: 0001

CAn21 (Group 2 Master)


Software: 2104
Config: 0001

The version numbers can also be queried during the operation.

KONVEKTA AG Stand: 05.07.2010 Seite: 6/21


110044782AA.doc

2.3. LED diagnostics of CANopen Systems

Structure of the CANopen system bus (Controller Area Network):


Control CANopen
The control is a high-speed CANopen system, with 125 baud.
The CAN line required at the end of the line a terminating resistor of 60 ohms.
CAN High Voltage to GND approximately 2.6V Low Voltage CAN approximately 2.6V to GND

Blink the green LED on KN400rail Code:


There are two green LED for CAN diagnosis Presence:
- The left LED [in a code switch] gives information about the (climate - a CAN bus)
- The right LED [under coding 3] gives info on the (Control - 2 CANopen bus)

The following flash codes are defined in the KN400rail:


1 x flashing operation is not disturbed (connection to at least one node exists)
2 x flashing Master:
An expected node is not found
Slave:
Node is not configured yet waiting for command
Master or KS45rail (Virgin)
3 x flashing KS45rail or KN400rail perform self-test or valve
4 flashes no CAN connect to the node, or operating unit (connect lost)
5 flashes CAN hardware fault in the wiring
6 x Flashing emergency operation (emergency operation)

The following flash code is defined in the KS45rail:


Note: Flash code for the link KS45rail to the master!
1 x flashing operation is OK (to connect to master)
2 x flashing expected KN400 a master is not found
3 x flashing KS45rail or KN400rail perform self-test or valve
4 flashes CANopen connection to the master KN400rail lost (connect lost)

The nodes and be switched from the KS45rail KN400rail administered by Master on and log-
out.
Log In: When logging is the position, software version and configuration
for 5 seconds on the display.
Log Off: When Logout is ---- the position, as displayed and version number.

Control over the failure of the KS45rail CANopen:


In normal operation, the operating conditions over the control of the CANopen control
KS45rail to KN400rail Master will be transferred. Will also be transferred via hardware wiring
signal (enable control) to KN400rail. Only when the signal (release management) and
CANopen communication is available, the system work properly.

When KS45rail failure or interruption of the line are no CANopen Control signals to the mas-
ter KN400rail transferred and registered an error. By creating the signal (release manage-
ment) despite the lack of control switches CANopen connection from the KS45rail KN400rail
to the Master after about 5 minutes in the operating AUTO to ensure the operation. If the sig-
nal (release control turned off), is the KN400rail OFF.

KONVEKTA AG Stand: 05.07.2010 Seite: 7/21


110044782AA.doc

2.4. External control KS45

By an external switch to Digital signals are transmitted KS45rail to 24V.


The following operating modes can be set:

Software Basic 1
Control ON (keypad operation and direction of travel)
- Preheating / Preventilation 1
- Preheating / Preventilation 2
- Under voltage 1
- Under voltage 2
- AUTO
- Reheat (via AUTO button when active)
- ECO
- Tunnel (via button)

Software Basic 2
Control ON (keypad operation and direction of travel)
- Preheating / Preventilation 1
- 400V / 3Ph available
- More compressors can be started
- Reduced availability of power supply
- AUTO
- Reheat (via AUTO button when active)
- ECO
- Tunnel (via button)

The switching of the signals can also be done with a short "circuit break" because the state
delayed system to be passed. Note: The +24 volt power supply must go hand while switching
channels, however, be present.

The priority at the same time creates the signals is:

1) CAR
2) Under voltage 2
3) Under voltage 1
4) Preheating / Preventilation 2
5) Preheating / Preventilation 1

The external signals have priority over the keyboard!


About Digital Outputs 24V signal lamps can surveillance to the current operating altitude.
The following messages are possible:
- AUTO
- Reheat
- ECO
- Tunnel
- Preheating
- Under voltage
- Collective malfunction message

KONVEKTA AG Stand: 05.07.2010 Seite: 8/21


110044782AA.doc

2.5. Storage of functions / values:

After switching off the KS45 EEProm is stored in the following functions:

- Room set point adjustment


- Room Correction setting + / - 2 degrees
- AUTO
- Manual fan setting

3. Operation of the control via keyboard

To allow for operation via the keyboard must first release Enabled, then the average passen-
ger room temperature is displayed. If the release is not active blink the colon in Sekunden-
tackt.- A control (enable operation via keyboard and direction) Display:- Current actual tem-
perature averaged space The six films buttons can be set and the functions The shortcut can
be queried and version numbers Errors are called.

3.1. AUTO Function

The air conditioning control unit possesses an AUTO - function, which depending
on the temperature activates the cooling, ventilation or heating to regulate the
temperature in the vehicle.

Pressing the button S1 activates the AUTO - function.


The text >>AUTO<< appears on the display.

3.2. Reheat function

The air conditioning control unit possesses a reheat - function, which enables the
humid air to dry.

Pressing the button S2 activates the reheat - function.


The text >>Reheat<< appears on the display and the following actuators are
turned on:

– Compressor
– Condenser
– Evaporator blower automatic
– Recirculated air flap to recirculated air

By activating the compressor the air in the duct gets cold and the roof heating heats against
it.
After 20 min. the reheat – function will automatically be turned off.

3.3. Manual ventilation

The evaporator blower is controlled in AUTO –function, depending on the


temperature.
Through the button S5 the evaporator capacity can be determined manually.

KONVEKTA AG Stand: 05.07.2010 Seite: 9/21


110044782AA.doc

3.4. Recirculated air flap

The recirculated air flap is controlled in AUTO –function, depending on the temperature.
Through the button T6 the recirculated air flap can be determined manually, i.e. in case of tunnel pas-
sage.

3.5. Display of outside temperature S5

By pressing the button twice S5 the outside temperature is displayed on the dis-
play, again press back twice to room temperature.

3.6. Up Arrow key S3

Setting the Target temperature correction + /- 2 degrees in the passenger


compartment Adjust the air flow rate of the evaporator blowers. Maximum
heating (key 10sec. Press when AUTO active)

3.7. Down Arrow button S4

Setting the target temperature correction + / - 2 degrees in the passenger


compartment. Adjusting the air flow rate of the evaporator blowers. Maximum
cooling (key 10sec. AUTO press when active).

3.8. Accessing the software version

Simultaneously press the button S1 and S6 are the version number


of the KN400 and KS45rail queried. It appears on the display CAN1
then the software version, followed by the version parameter.
Displays the display example ---- Is the slave does not exist. By
pressing the S2 and S6, or after a waiting period of 10sec. the mode is switched back to the
basic display.

3.9. Accessing error

If the SERVICE icon appears on the screen is one or more error


messages. Simultaneously press the button S1 and S5, the error
memory is called. Appears on the display - - - - is no error entry.
Displays the display example 0200, it is an error available.

KONVEKTA AG Stand: 05.07.2010 Seite: 10/21


110044782AA.doc

If there are several mistakes that run automatically on the screen through. Note: There will be
max. 8 Error of KN400 retrieved.
An erase the error is only with the PC tool KSDiag possible.
By pressing the S2 and S6, or after a waiting period of 10sec. the mode is switched back to
the basic display.

3.10. Setting group control:

The initial setting is [size 0], so all controls for all 4 groups are simultaneously controlled. By
adjustment of the individual group with the control groups can be independently controlled
CANopen are connected.

By simultaneously pressing the button S1 and S3, if no approval or operating condition is


chosen is such a stand - [Size 0] appears on the display.

With the keys S3 + S4 can then group the required number will be selected.

Pressing the button S1 and S3, the mode with the [rSt] rely on the display and a self-test.

Display KS45rail KN400 Group


Gr 0 Group 1, Group 2, Group 3, Group 4
Gr 1 Group 1
Gr 2 Group 2
Gr 3 Group 3
Gr 4 Group 4

4. Control via external signals:

The following operating modes can be adjusted through external signals. A release by the
signal [A control] is not necessary. When there is no external signal, the colon blinks every
second.

Preheating / Preventilation 1 + 2 (optional)


Display:
- If current average room temperature
- Convector icon

Under voltage 1 + 2 (optional)


Display:
- If current average room temperature
- Convector icon blinks every second

KONVEKTA AG Stand: 05.07.2010 Seite: 11/21


110044782AA.doc

AUTO
Display:
- If current average room temperature
- AUTO symbol
- CLIMATE minutes when Stern. Use a compressor

Reheat (if AUTO active)


Display:
- If current average room temperature
- Reheat icon
- CLIMATE minutes when Stern. Use a compressor

ECO (CAR if active)


Display:
- If current average room temperature
- AUTO or reheat or convector icon
- CLIMATE minutes when Stern. Use a compressor
- ECO icon

Tunnel (CAR if active)


Display:
- If current average room temperature
- AUTO or reheat or convector icon
- CLIMATE minutes when Stern. Use a compressor
- FAN icon

Keys:
- S3 temperature correction +
- S4 temperature correction –
- S5 Manual fan setting
- S6 Tunnel
- S1 + S5 query the error code
- S2 + S6 querying the version number

Additional features:
- MAXIMUM heating
By long pressing S3 (about 10 sec when AUTO active)
Display: - 4 bars on the temperature indicator at the top ----

- MAXIMUM Cooling
By long pressing S4 (about 10 sec when AUTO active)
Display: 4 bars on the temperature gauge below ----

The following settings are permanently stored in even after the power is removed or re-
leased:

About External control:


Passenger compartment set temperature correction

KONVEKTA AG Stand: 05.07.2010 Seite: 12/21


110044782AA.doc

About [Control ON] keypad operation of KS45:


- Passenger compartment set temperature correction
- AUTO
- Reheat
- Ventilated
- Manual Blower

Display:

After switching on the power supply, the backlight is active. If there is up to no external power
supply signal is the cur-rent averaged temperature display.

4.1. Inputs / Outputs:

Digital inputs: The digital inputs, the switching states


different signals.
- External circuit

Analog Inputs: The analog inputs enter the following values:


- External potentiometer for set point adjustment

Digital outputs: About Digital outputs are different components in the


Vehicle switched. Semiconductor output DA1 to DA6 ever 200mA.
A power output of 3 amperes is available.
- External circuit

Analog outputs: The analog outputs to control the following components:


- Brushless Blowers 0-10V
- Recirculation valve actuating motor 0-10V

5. Error handling
Error handling via control unit KS45
The vehicle being turned off, the error storage can be called up by simultaneously pressing
the buttons S1 „AUTO“ and S5 „Evaporator blower“.
When the display remains dark there is no error registered.
In case the display indicates i.e. 0200 there is an error registered.

With the button T3 „increase“ the next error can be called up.

KONVEKTA AG Stand: 05.07.2010 Seite: 13/21


110044782AA.doc

6. Pin assignment Basic 1


KS45rail Plug X1:
12 Pin AMP

Plug Art Designation


X1 / 01 DA 01 Message AUTO
X1 / 02 DA 02 Message Reheat
X1 / 03 DA 03 Message ECO

X1 / 04 DA 04 Message Tunnel
X1 / 05 DA 05 Message Preheating
X1 / 06 DA 06 Collective fault message
X1 / 07 DA 07 Message Under voltage
X1 / 08 CAN LOW CANopen LOW control -Bus
X1 / 09 CAN HIGH CANopen HIGH control -Bus
X1 / 10 VCC24L 24V Supply
X1 / 11 VCC24 24V 24V Supply
X1 / 12 VCC24 GND GND 24

KS45rail Plug X2:


18 Pin AMP

Plug Art Designation


X2 / 01 DE 01 Control ON (using keyboard and direction)
X2 / 02 DE 02 AUTO
X2 / 03 DE 03 Reheat
X2 / 04 DE 04 ECO
X2 / 05 DE 05 Tunnel / SMOG
X2 / 06 GND intern NC
X2 / 07 AA 01 NC
X2 / 08 AA 02 NC
X2 / 09 AE 01 (DE 06) Preheating / Preventilation 1 (Temperature dependent)
X2 / 10 AE 02 (DE 07) Preheating / Preventilation 2 (Temperature dependent)
X2 / 11 AE 03 (DE 08) Under voltage 1
X2 / 12 AE 04 (DE 09) Under voltage 2
X2 / 13 AE 05 (0-5V) Correction specified nominal value + / - 2Grad about 10 K potenti-
ometer (option) or TA sensor
X2 / 14 GND VPOT Reference voltage (Option)
X2 / 15 + VPOT Reference voltage (Option)
X2 / 16 Diag. STXD PC – Interface ( V24Modul )
X2 / 17 Diag. SRXD PC – Interface ( V24Modul )
X2 / 18 GND NC

KONVEKTA AG Stand: 05.07.2010 Seite: 14/21


110044782AA.doc

7. Pin assignment Basic 2


KS45rail Plug X1:
12 Pin AMP

Plug Art Designation


X1 / 01 DA 01 Message AUTO
X1 / 02 DA 02 Message Reheat
X1 / 03 DA 03 Message ECO

X1 / 04 DA 04 Message Tunnel
X1 / 05 DA 05 Message Preheating
X1 / 06 DA 06 Collective fault message
X1 / 07 DA 07 Message Under voltage
X1 / 08 CAN LOW CANopen LOW control -Bus
X1 / 09 CAN HIGH CANopen HIGH control -Bus
X1 / 10 VCC24L 24V Supply
X1 / 11 VCC24 24V 24V Supply
X1 / 12 VCC24 GND GND 24

KS45rail Plug X2:


18 Pin AMP

Plug Art Designation


X2 / 01 DE 01 Control ON (using keyboard and direction)
X2 / 02 DE 02 AUTO
X2 / 03 DE 03 Reheat
X2 / 04 DE 04 ECO
X2 / 05 DE 05 Tunnel / SMOG
X2 / 06 GND intern NC
X2 / 07 AA 01 NC
X2 / 08 AA 02 NC
X2 / 09 AE 01 (DE 06) 400V 3Ph available
X2 / 10 AE 02 (DE 07) Compressor start enable
X2 / 11 AE 03 (DE 08) Power limitation
X2 / 12 AE 04 (DE 09) Preheating / Preventilation
X2 / 13 AE 05 (0-5V) Correction specified nominal value + / - 2Grad about 10 K potenti-
ometer (option) or TA sensor
X2 / 14 GND VPOT Reference voltage (Option)
X2 / 15 + VPOT Reference voltage (Option)
X2 / 16 Diag. STXD PC – Interface (V24Modul)
X2 / 17 Diag. SRXD PC – Interface (V24Modul)
X2 / 18 GND NC

KONVEKTA AG Stand: 05.07.2010 Seite: 15/21


110044782AA.doc

8. Error messages
Fühlerfehler: Fehler Nummer
Kurzschluss Außenfühler Short-circuit Outside sensor 01
Kabelbruch Außenfühler Cable breakdown Outside sensor 02
Kurzschluss Raumfühler 1 Short-circuit Room sensor 1 03
Kabelbruch Raumfühler 1 Cable breakdown Room sensor 2 04
Kurzschluss Konvektorfühler vorne 1 circuit Convector 1 sensor front 05
Kabelbruch Konvektorfühler vorne 1 breakdown Convector 1 sensor front 06
Kurzschluss Konvektorfühler hinten 1 circuit Convector 1 sensor rear 07
Kabelbruch Konvektorfühler hinten 1 breakdown Konvektor1 sensor rear 08
Kurzschluss Kanalfühler 1 circuit air duct sensor 1 09
Kabelbruch Kanalfühler 1 Cable breakdown air duct sensor 1 10
Kurzschluss Raumfühler 2 Short-circuit Room sensor 2 11
Kabelbruch Raumfühler 2 Cable breakdown Room sensor 2 12
Kurzschluss Konvektorfühler vorne 2 circuit Convector 2 sensor front 13
Kabelbruch Konvektorfühler vorne 2 breakdown Convector 2 sensor front 14
Kurzschluss Konvektorfühler hinten 2 circuit Convector 2 sensor rear 15
Kabelbruch Konvektorfühler hinten 2 breakdown Convector 2 sensor rear 16
Kurzschluss Kanalfühler 2 circuit air duct sensor 2 17
Kabelbruch Kanalfühler 2 Cable breakdown air duct sensor 2 18
Kurzschluss Vereisungsfühler 1 Short-circuit Eis sensor1 19
Kabelbruch Vereisungsfühler 1 Cable breakdown Eis sensor 1 20
Kurzschluss Vereisungsfühler 2 Short-circuit Eis sensor 2 21
Kabelbruch Vereisungsfühler 2 Cable breakdown Eis sensor 2 22
Kurzschluss Vereisungsfühler FB Short-circuit Frontbox Eis sensor 23
Kabelbruch Vereisungsfühler FB Cable breakdown Frontbox Eis sensor 24
Kurzschluss Wasserfühler Short-circuit water sensor 25
Kabelbruch Wasserfühler Cable breakdown water sensor 26
Kurzschluss Kondensatorfühler Short-circuit condenser sensor 27
Kabelbruch Kondensatorfühler Cable breakdown condenser sensor 28
Kurzschluss Frontboxfühler 1 Short-circuit Frontbox sensor 1 29
Kabelbruch Frontboxfühler 1 Cable breakdown Frontbox sensor 1 30
Kurzschluss Frontboxfühler 2 Short-circuit Frontbox sensor 2 31
Kabelbruch Frontboxfühler 2 Cable breakdown Frontbox sensor 2 32
Kurzschluss RES_33 Short-circuit RES sensor 33
Kabelbruch RES_34 Cable breakdown RES sensor 34

Rückmeldung Fehler: Fehler Nummer


Rückmeldung Verdichter 1 HD Feedback Compressor 1 HD 40
Rückmeldung Verdichter 1 ND Feedback Compressor 1 ND 41
Rückmeldung Verdichter 2 HD Feedback Compressor 2 HD 42
Rückmeldung Verdichter 2 ND Feedback Compressor 2 ND 43
Rückmeldung Standheizung Feedback Preheater 44
Rückmeldung Luftklappe 1 Feedback Circulation flap 1 45
Rückmeldung Luftklappe 2 Feedback Circulation flap 2 46
Rückmeldung Abtauthermostat 1 Feedback Eis switch 1 47
Rückmeldung Abtauthermostat 2 Feedback Eis switch 2 48
Rückmeldung Motorschutz Verdichter Feedback Engine protection 49
Rückmeldung Warnung Vereisung 1 Feedback warning Eis 1 50
Rückmeldung Warnung Vereisung 2 Feedback warning Eis 2 51
Rückmeldung Dach Heizung 1 Feedback Top heater 1 52
Rückmeldung Dach Heizung 2 Feedback Top heater 2 53
Rückmeldung Dach Heizung 3 Feedback Top heater 3 54
Rückmeldung res Feedback RES 55
Rückmeldung Sicherung 1 Feedback Fuse 56
Rückmeldung Elektronisches Relais Feedback electronic Relays 57
Rückmeldung Diagnose Verdampfergebläse Feedback Evaporator blower 58
Rückmeldung Diagnose Verflüssiger Feedback Condenser blower 59

KONVEKTA AG Stand: 05.07.2010 Seite: 16/21


110044782AA.doc

Poti Rückmeldung Fehler: Fehler Nummer


Fehler Poti Luftklappe 1 Poti Circulation flap 1 60
Fehler Poti Luftklappe 2 Poti Circulation flap 2 61
Fehler Poti Luftklappe Frontbox Poti Circulation flap Frontbox 1 62
Fehler Poti Dachventil 1 Poti Roof heating valve 1 63
Fehler Poti Konvektorventil 1 Poti Convector heating valve 1 64
Fehler Poti Frontboxventil Poti Frontbox heating valve 1 65
Fehler Poti Dachventil 2 Poti Roof heating valve 2 66
Fehler Poti Konvektorventil 2 Poti Convector heating valve 2 67
Fehler Poti Luftklappe 1 Frontbox Poti Air flap Frontbox 1 68
Fehler Poti Luftklappe 2 Frontbox Poti Air flap Frontbox 2 69
Fehler Poti Luftklappe 3 Frontbox Poti Air flap Frontbox 3 70
Fehler Poti Luftklappe 3 Poti Circulation flap 3 71
Fehler Poti Luftklappe 4 Poti Circulation flap 4 72
Fehler Poti RES_73 Poti RES 73
Fehler Poti RES_74 Poti RES 74
Fehler Poti RES_75 Poti RES 75
Fehler Poti RES_76 Poti RES 76
Fehler Poti RES_77 Poti RES 77
Fehler Poti RES_78 Poti RES 78
Fehler Poti RES_79 Poti RES 79

Sonstige Eingänge / Fehler: Fehler Nummer


Fehler Drucktransmitter ND error Pressure transmitter ND 90
Fehler Drucktransmitter HD error Pressure transmitter HD 91
Störung Generator error Generator 92

Digitale Ausgänge: Fehler Nummer


Kurzschluss DA Verdampfer Stufe 1 (Freigabe DZM) Short-circuit DA Evaporator blower step 1 100
Kurzschluss DA Verdampfer Stufe 2 Short-circuit DA Evaporator blower step 2 101
Kurzschluss DA Verdampfer Stufe 3 Short-circuit DA Evaporator blower step3 102
Kurzschluss DA Verdichter 1 Short-circuit DA Compressor 1 103
Kurzschluss DA Verdichter 2 Short-circuit DA Compressor 2 104
Kurzschluss DA Kondensator 1 Short-circuit DA Condenser 1 105
Kurzschluss DA Kondensator 2 Short-circuit DA Condenser 2 106
Kurzschluss DA Zusatzheizung Short-circuit DA Preheater 107
Kurzschluss DA Wasserpumpe Short-circuit DA Water pump 108
Kurzschluss DA Luftklappe Klima 1/A Short-circuit DA Circulation flap 1/A 109
Kurzschluss DA Luftklappe Klima 1/B Short-circuit DA Circulation flap 1/B 110
Kurzschluss DA Luftklappe Klima 2/A Short-circuit DA Circulation flap 2/A 111
Kurzschluss DA Luftklappe Klima 2/B Short-circuit DA Circulation flap 2/B 112
Kurzschluss DA Wasserventil Dach 1/A Short-circuit DA Roof heating valve 1/A 113
Kurzschluss DA Wasserventil Dach 1/B Short-circuit DA Roof heating valve 1/B 114
Kurzschluss DA Wasserventil Dach 2/A Short-circuit DA Roof heating valve 2/A 115
Kurzschluss DA Wasserventil Dach 2/B Short-circuit DA Roof heating valve 2/B 116
Kurzschluss DA Wasserventil Konvektor 1/A Short-circuit DA Convector heating valve 1/A 117
Kurzschluss DA Wasserventil Konvektor 1/B Short-circuit DA Convector heating valve 1/B 118
Kurzschluss DA Wasserventil Konvektor 2/A Short-circuit DA Convector heating valve 2/A 119
Kurzschluss DA Wasserventil Konvektor 2/B Short-circuit DA Convector heating valve 2/B 120
Kurzschluss DA Wasserventil Frontbox A Short-circuit DA Frontboxr heating valve A 121
Kurzschluss DA Wasserventil Frontbox B Short-circuit DA Frontboxr heating valve B 122
Kurzschluss DA Luftklappe Frontbox A Short-circuit DA Circulation flap Frontbox A 123
Kurzschluss DA Luftklappe Frontbox B Short-circuit DA Circulation flap Frontbox B 124
Kurzschluss DA Luftklappe Frontbox 1/A Short-circuit DA Air flap Frontbox 1/A 125
Kurzschluss DA Luftklappe Frontbox 1/B Short-circuit DA Air flap Frontbox 1/B 126
Kurzschluss DA Luftklappe Frontbox 2/A Short-circuit DA Air flap Frontbox 2/A 127
Kurzschluss DA Luftklappe Frontbox 2/B Short-circuit DA Air flap Frontbox 2/B 128
Kurzschluss DA Luftklappe Frontbox 3/A Short-circuit DA Air flap Frontbox 3/A 129
Kurzschluss DA Luftklappe Frontbox 3/B Short-circuit DA Air flap Frontbox 3/B 130

KONVEKTA AG Stand: 05.07.2010 Seite: 17/21


110044782AA.doc

Kurzschluss DA Frontboxgebläse Stufe1(Freigabe DZM) Short-circuit DA Evaporator blower Frontbox step 1131
Kurzschluss DA Frontboxgebläse Stufe 2 Short-circuit DA Evaporator blower Frontbox step 2132
Kurzschluss DA Frontboxgebläse Stufe 3 Short-circuit DA Evaporator blower Frontbox step 3133
Kurzschluss DA Frontboxklima Short-circuit DA Frontbox climate 134
Kurzschluss DA Klima AN Short-circuit DA climate ON 135
Kurzschluss DA Umluft / Umluft 1 Short-circuit DA Circulation inside air 1 136
Kurzschluss DA Umluft / Mischluft 1 Short-circuit DA Circulation mix air 1 137
Kurzschluss DA Umluft / Frischluft 1 Short-circuit DA Circulation fresh air 1 138
Kurzschluss DA Umluft / Umluft 2 Short-circuit DA Circulation inside air 2 139
Kurzschluss DA Umluft / Mischluft 2 Short-circuit DA Circulation mix air 2 140
Kurzschluss DA Umluft / Frischluft 2 Short-circuit DA Circulation fresh air 2 141
Kurzschluss DA DA_142 Short-circuit DA RES 142
Kurzschluss DA Flüssigkeitsventil 1 Short-circuit DA liquid valve 1 143
Kurzschluss DA Flüssigkeitsventil 2 Short-circuit DA liquid valve 2 144
Kurzschluss DA Unterstuhlgebläse 1 Stufe 1 Short-circuit DA unterchair blower1 step 1 145
Kurzschluss DA Unterstuhlgebläse 1 Stufe 2 Short-circuit DA unterchair blower1 step 2 146
Kurzschluss DA Unterstuhlgebläse 2 Stufe 1 Short-circuit DA unterchair blower2 step 1 147
Kurzschluss DA Unterstuhlgebläse 2 Stufe 2 Short-circuit DA unterchair blower2 step 2 148
Kurzschluss DA Wasserpumpe Dach Short-circuit DA water pump Roof 149
Kurzschluss DA Frontbox Heizung Stufe 1 Short-circuit DA Frontbox heater step 1 150
Kurzschluss DA Frontbox Heizung Stufe 2 Short-circuit DA Frontbox heater step 2 151
Kurzschluss DA Frontbox Luftverteilung Scheibe Short-circuit DA Frontbox Air flap window 152
Kurzschluss DA Frontbox Luftverteilung Fahrer Short-circuit DA Frontbox Air flap driver 153
Kurzschluss DA Frontbox Luftverteilung Fuß Short-circuit DA Frontbox Air flap feat 154
Kurzschluss DA Frontbox Kondensator Short-circuit DA Frontbox Condenser 155
Kurzschluss DA Frontbox Verdichter Short-circuit DA Frontbox Compressor 156
Kurzschluss DA Luftklappe Klima 3/A Short-circuit DA Circulation flap 3/A 157
Kurzschluss DA Luftklappe Klima 3/B Short-circuit DA Circulation flap 3/B 158
Kurzschluss DA Luftklappe Klima 4/A Short-circuit DA Circulation flap 4/A 159
Kurzschluss DA Luftklappe Klima 4/B Short-circuit DA Circulation flap 4/B 160
Kurzschluss DA Ölsumpfheizung Short-circuit DA Oil heater 161
Kurzschluss DA Dachheizung Stufe 1 Short-circuit DA Roof heater step 1 162
Kurzschluss DA Dachheizung Stufe 2 Short-circuit DA Roof heater step 2 163
Kurzschluss DA Heizleistung Gesamtfahrzeug Short-circuit DA heater vehicles 164
Kurzschluss DA Heizleistung Dach Short-circuit DA heater Roof 165
Kurzschluss DA Konvektor Short-circuit DA heater Convector 166
Kurzschluss DA Unterstuhlheizer 1 Short-circuit DA heater unterchair 1 167
Kurzschluss DA Unterstuhlheizer 2 Short-circuit DA heater unterchair 1 168
Kurzschluss DA Generator Short-circuit DA Generator 169

Systemfehler: Fehler Nummer


Klima CAN Fehler Verbindung Slave 1 Klima CAN error connection Slave 1 200
Klima CAN Fehler Verbindung Slave 2 Klima CAN error connection Slave 2 201
Klima CAN Fehler Verbindung Slave 3 Klima CAN error connection Slave 3 202

Klima CAN Knoten Doppelt Klima CAN Node double 208


Klima CAN Unerwarteter Knoten Angemeldet Klima CAN Node unexpected 209

Klima CAN Fehler Master Klima CAN error Master 210


Klima CAN Fehler Slave 1 Klima CAN error Slave 1 211
Klima CAN Fehler Slave 2 Klima CAN error Slave 2 212
Klima CAN Fehler Slave 3 Klima CAN error Slave 3 213

Fehler NV- Ram/Batteriestatus RAM error 220

Signal CAN open Fehler Verbindung Master zum Bedieneinheit Signal CAN open connection Master control panel 222
Signal CAN open Fehler Verbindung Slave 1 zum Bedieneinheit Signal CAN open connection Slave 1 control panel 223
Signal CAN open Fehler Verbindung Slave 2 zum Bedieneinheit Signal CAN open connection Slave 2 control panel 224
Signal CAN open Fehler Verbindung Slave 3 zum Bedieneinheit Signal CAN open connection Slave 3 control panel 225

KONVEKTA AG Stand: 05.07.2010 Seite: 18/21


110044782AA.doc

Klima CAN Fehler Verbindung SUP1 Klima CAN error connection SUP 1 231
Klima CAN Fehler Verbindung SUP2 Klima CAN error connection SUP 2 232
Klima CAN Fehler Verbindung SUP3 Klima CAN error connection SUP 3 233
Klima CAN Fehler Verbindung SUP4 Klima CAN error connection SUP 4 234
Klima CAN Fehler SUP1 Klima CAN error SUP 1 235
Klima CAN Fehler SUP2 Klima CAN error SUP 2 236
Klima CAN Fehler SUP3 Klima CAN error SUP 3 237
Klima CAN Fehler SUP4 Klima CAN error SUP 4 238

Klima CAN Time out Klima CAN time out 250

KONVEKTA AG Stand: 05.07.2010 Seite: 19/21


110044782AA.doc

9. Dimensions

KONVEKTA AG Stand: 05.07.2010 Seite: 20/21


110044782AA.doc

10. Notes

KONVEKTA AG Stand: 05.07.2010 Seite: 21/21