You are on page 1of 2

2013 SPD APPLICATION GUIDE

Large Service 2500 - 4000A


TO LOAD

NON
DISCONNECT MODULAR
NON SWITCHES HCS 100kA
MODULAR MODULAR MODULAR
HBS 600kA HAS 200kA
HDS 150kA
TRANSFORMER
PROCESS NON
60A 60A 30A CONTROL MODULAR
PANEL HCS 100kA ELEVATOR

EMERGENCY POWER /
MAIN SWITCHBOARD DISTRIBUTION BOARD / PANEL SENSITIVE PANELS DOWNSTREAM / OUTDOOR LOADS
2,500A - 4,000A 1,200A - 2,000A 400A - 800A

Medium Service 1200 - 2000A Small Service <800A


TO LOAD

NON
MODULAR
MODULAR NON HCS 100kA
HAS 200kA MODULAR NON
HDS 150kA * MODULAR
HDS 150kA

60A DOWNSTREAM /
30A SENSITIVE LOADS
30A

MAIN DISTRIBUTION SUB DISTRIBUTION MAIN DISTRIBUTION


BOARD / PANEL BOARD / BRANCH PANEL BOARD / PANEL
1,200A - 2,000A 400A - 800A ≤ 800A

Specialty Service Outdoor / Miscellaneous

AUTOMATIC OTHER APPLICATIONS


TRANSFER SWITCH • Compressors/Air Handler
GENERATOR • Chillers
HAS 200kA • Rooftop HVAC
NON
MODULAR • Pump Control Panel
SPS50A 50kA • Outdoor Equipment & Lighting
MODULAR
WITH DISC • Wind Turbine
INTEGRAL • PV Inverter (AC & DC)
UTILITY DISCONNECT • Security System
• Elevator Control Panel
HAS 200kA MAIN DISTRIBUTION
• Process Controller
BOARD / PANEL
EMERGENCY SERVICE (6 MAIN CIRCUIT • Lighting Control Panel
BREAKERS) (Typical Application)

Modular - Serviceable and replaceable subassembly componentry.

31 Loyang Crescent Singapore 509013


Tel: (+65) 6214 1830 Fax: (+65) 6214 1831
Email: ENQUIRY@Hitachi-CFP.com
Website: www.Hitachi-CFP.com
SURGE PROTECTION DEVICES
UL 1449 Third Edition Listed

SPS HBS Series


2500A - 4000A
• 400 - 1000kA per phase
• Type 1 SPD, 200kA SCCR
• 20kA In (for UL 96A), ALL Mode, EMI/RFI Filtering
• Recommend: 16 mm2 (#6 AWG), 60A OCPD / Circuit Breaker
• Standard: Disconnect Switch
• Optional: Surge Counter

SPS HAS Series


1200A - 2000A
• 300 - 500kA per phase
• Type 1 SPD, 200kA SCCR
• 20kA In (for UL 96A), ALL Mode, EMI/RFI Filtering
• Recommend: 16 mm2 (#6 AWG), 60A OCPD / Circuit Breaker
• Optional: Disconnect Switch, Surge Counter

SPS HDS Series


400A - 800A • 100 - 200kA per phase
• Type 1 SPD, 200kA SCCR
• 20kA In (for UL 96A), ALL Mode, EMI/RFI Filtering
• Recommend: 10mm2 (#8 AWG), 40A OCPD / Circuit Breaker

SPS HCS Series • 100kA per phase


200A - 400A • Type 1 SPD, 200kA SCCR
• 20kA In (for UL 96A), ALL Mode
• Included: 914.4mm (3 feet) of 6mm2 (#10 AWG)
• Recommend: 30A OCPD / Circuit Breaker

SPS50A Series • 50kA per phase


< 200A • Type 1 SPD, 200kA SCCR
• 20kA In (for UL 96A), L-N Mode
• Included: 6mm2 (#10 AWG)
• Recommend: 30A OCPD / Circuit Breaker
• Optional: N-G & L-G

31 Loyang Crescent Singapore 509013


Tel: (+65) 6214 1830 Fax: (+65) 6214 1831
Email: ENQUIRY@Hitachi-CFP.com
Website: www.Hitachi-CFP.com

You might also like