NOTES:

1. PV MODULES ARE WIRED IN DAISY CHAIN


CONFIGURATION.

2. PV STRINGS (2 MPPT USED PER INVERTER):


INVERTER 1 : 1st STRING - 10 PANELS
2nd STRING - 11 PANELS
INVERTER 2 : 1st STRING - 10 PANELS
2nd STRING - 11 PANELS
LEG-SRAINV1
REFERENCE FILES:
1. WGLS-LEG_SRA_TR_001
2. SOLAREDGE SE5000H DATA SHEET
LEG-SRAINV2 TO INVERTER
1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 1.1.6 1.1.7 1.1.8 1.1.9 1.1.10 1.1.11 1.2.1 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 1.2.7 1.2.8 1.2.9 1.2.10 LIQUID TIGHT FLEXIBLE
CONDUIT 32mmØ
8000

2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 2.1.7 2.1.8 2.1.9 2.1.10 2.1.11 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 2.2.8 2.2.9 2.2.10

- PV LOCATION

KEYPLAN
SCALE: NTS

CONDUIT LAYOUT PRC NO. PRC VALIDITY DATE

SCALE: NTS PTR NO. PTR DATE ISSUED

PROFESSIONAL ELECTRICAL ENGINEER PTR PLACE ISSUED TIN NO.

DATE

BUILDING OWNER PLACE

1 FOR CONSTRUCTION K. BAYOT 03.12.2019

A FOR INFORMATION K. BAYOT 02.07.2019

REV: DESCRIPTION: BY: DATE:


PV MODULE
STATUS:
(UNDERSIDE) FOR CONSTRUCTION
CONCRETE SLAB C-CLAMP UNISTRUT CLAMP
NAIL (CONCRETE NAIL HOT DIP GALVANIZED
EXTENSION CABLE NAIL FOR FLAT BAR CONDUIT FOR CONC. BEAM/SLAB) STEEL
DC CABLE 6mm2 WOOD FLOORING
BOLT AND NUT
HILTI BOND DIOCESE OF LEGAZPI
WOOD NAILER LIQUID TIGHT FLEXIBLE ST. RAPHAEL THE ARCHANGEL PARISH - CONVENT 1
OR SLAB METAL CONDUIT LEGAZPI CITY, ALBAY, 4500
CONDUIT (UV/OUTDOOR RATED) PHILIPPINES
CONDUIT
COUPLING
°

NEGATIVE PV CABLE POSITIVE PV CABLE


90

UNISTRUT CHANNEL
CONDUIT HOT DIP GALVANIZED
CONDUIT CONDUIT STEEL, LENGTH: 200mm
CLAMP ELBOW
CONDUIT
30 30 30 ALL DC CABLES SHOULD NOT TOUCH WeGen ENERGY PHILIPPINES
CONDUIT THE ROOF SURFACE. A UNISTRUT CHANNEL UNIT 2802D/2803A WEST TOWER, PSE CENTER
EXCHANGE RD., ORTIGAS CENTER
IF PV MODULE ORIENTATION DOES NOT ALLOW CLAMP STAND WILL BE INSTALLED EVERY 1.5m - 2m OF PASIG CITY, PHILIPPINES 1605
DIRECT CABLE CONNECTION TO THE NEXT PV THE CONDUIT RUN.
MODULE, AN MC4 EXTENSION CABLE SHALL BE
USED OR WHENEVER APPLICABLE. PROJECT:
11.97kWp PV PROJECT
LEGAZPI - ST. RAPHAEL THE ARCHANGEL
PARISH - CONVENT 1
TITLE:

CONDUIT & WIRING LAYOUT


TYPICAL MC4 EXTENSION CABLE TYPICAL CONDUIT INSTALLATION DETAIL "A"
SCALE AT A3: DATE: DRAWN: CHECKED:
SCALE: NTS SCALE: NTS SCALE: NTS N/A 02.07.2019 K. BAYOT RMC
PROJ. CODE: DRAWING NO: SHEET:
1
LEG LEG-SRA-EE-LAY-002-1 REV:
1