You are on page 1of 31

AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

CERTIFICATE

Certified that :-
1. Proposal is techno economically viable
2. Length of 33 kv & 11 kv line I/C is Correctly Measured.
3. Proposal 33/11 kv Sub-station - DINARPURA ,SIKAR is at load
center.
4. 33 kv line is Proposed through shortest possible route.
5. Calculaton of various parameters have been checked and found.
correct.
6. system improvement is not possible bifergation

7. 33/11 kv S/S Jhigar chhoti all ready Proposed on 132 kv GSS


Kudan to be Shifted on 220 kv GSS Sikar

EXECUTIVE ENGINEER (O&M) ASSISTANT ENGINEER (O&M)


A.V.V.N.L. SIKAR A.V.V.N.L. PIPARALI
H.Q.SIKAR

SUPRENTENDING ENGINEER (SC)


A.V.V.N.L SIKAR

C/S

ZONAL CHIF ENGINEER (JJN-Z)


A.V.V.N.L. JHUNJHUNU
AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

PROPOSAL POWER FOR 33/11 S/S KV AT VILLAGE DINARPURA, SIKAR

Presently power supply to village Dolatpura , Katrathal , Dinarpura ,


Jhigar Chhoti , Gothra Bhukaran , Jerthi , Akawa is feeded by four nos. of 11K.V .
feeders which are very loaded and consumers are facing very low voltage and
conductor broken problem.

S.NO. 33/11Kv S/S 11kV feeder DTC(KVA) % VR


1 Jhigar chhoti Jhigar chhoti 2179 4.84
2 Dinarpura 2237 7.3
3 kudan Jherthi 3419 6.91
4 Gothara Bhukaran 2362 3.86

These localities are very rich agritulcure scope area. To reduce consumer's problem
and give better voltage profile to the agriculture consumers by diverting the load of
existing 11K.V.feeders on proposed 33/11K.V.S/S Dinarpura .
It requires 3.3 Km new 33Kv line and 5.7 Km (Includeing 1 Km conductor replace-
ment) 11 K.v. line proposed capacity of S/S is 3.15 MVA and proposed load is
4909 KVA.

Advantage of this sheme:-

1. The % VR of existing 11 K.v. feeders will be reduced from above 7 %to below
5 % as per enclosed annexure.

2. Total cost of the scheme is 79.74 lac & energy saving is 3.51 Lu

3. % return of this scheme is 12.14

4. The proposal S/S at Dinarpura will also help in further load grow of the area with
out further augmenation .

EXECUTIVE ENGINEER (O&M) ASSISTANT ENGINEER (O&M)


A.V.V.N.L. SIKAR A.V.V.N.L. PIPARALI
H.Q.SIKAR

JUNIOR ENGINEER (O&M)


A.V.V.N.L DADIYA
AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

Techinical Particulars of Proposed 33/11 kv Sub- Station

A CAPECITY 3.15 MVA


B PROPOSED LOAD 4909 KVA
C TYPE 4 BAY 4 OUT GOING
D PLACE DINARPURA

33KV LINE

1. PROPOSED LENGTH 2.8KM


2. NAEME OF 33 KV LINE 33 KV LINE DINARPURA FROM
132 KV GSS KUDAN

3. CIRCUIT SINGLE
4. SPACING DELTA
5. CONDUCTOR ACSR DOG
6. SUPPORT PCC POLE 9Mtr. LONG

11KV LINE

1. PROPOSED FEEDERS 4NOS


2. LENGTH 5.7 Km.
3. CITCUIT S/C
4. SPAN 70 Mtr.
5. SPACING DELTA
6. SUPPORT PCC POLE 8 Mtr LONG.

EXECUTIVE ENGINEER (O&M) ASSISTANT ENGINEER (O&M)


A.V.V.N.L. SIKAR A.V.V.N.L. PIPARALI
H.Q.SIKAR

JUNIOR ENGINEER (O&M)


A.V.V.N.L DADIYA
AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

Proposal for creation of 33/11 kv Sub- Station Dinarpura, sikar

ABSTRACT OF COST
1. COST OF 33/11 kv Sub- Station RS. 5370802
(1x3.15MVA power Transformer)

2. COST OF 33Kv LINE RS.815298


(2.8Km)

3. COST IF 11Kv line RS.1287824


(5.7 Km)

Total 7473924

COST OF CIVIL WORK RS.500000

Net expenditure for proposed 33/11 kv Sub- Station RS. 7973924

AE SAVING = 3.51 LU

COST BENEFIT= 2.758 x 3.51 x 100


. 79.74

.= 12.14 %

EXECUTIVE ENGINEER (O&M) ASSISTANT ENGINEER (O&M)


A.V.V.N.L. SIKAR A.V.V.N.L. PIPARALI
H.Q.SIKAR

JUNIOR ENGINEER (O&M)


A.V.V.N.L DADIYA
System parameters of proposed 33/11kv,1X 3.15 Mva S/S at Dinarpura Sikar

S.NO. NAME OF 33/11 KV S/S NAME OF FEEDER TEL LENGTH DTC % VR AEL AEF % EL % DL
OF LINE(KM) (KVA) LU LU
A Existing system Existing 11 kv
1.33/11 Kv S/S Kudan 11 Kv Jerthi 7.40 3419.00 6.91 2.88 71.88 4.00 11.12
11 Kv Gothra Bhukran 5.50 2362 3.86 0.97 49.66 1.95 5.40
2.33/11 Kv S/S Jhigar Chhoti 11 Kv Dinarpura 6.80 2237 7.3 2.26 47.03 4.81 13.36
11 Kv Jhigar Chhoti 6.40 2179 4.84 1.22 45.81 2.27 7.41
Total -A 10197.00 7.33
B Proposed System Proposed 11 Kv.

1. Proposed 33/11 Kv S/S Dnar 11 Kv Jerthi 7.5 1731 3.61 0.52 36.39 1.43 3.97
pura 11 Kv Gothra Bhukran 4.3 1146 1.37 0.16 24.09 0.68 1.89
11 Kv Dinarpura 2.6 971 0.71 0.07 20.41 0.33 20.93
11 Kv Katrathal 6.6 1061 2.28 0.26 22.31 1.15 3.2

Total -B 4909 1.01


C Remaining System Remaining 11 Kv
1.33/11 Kv S/S Kudan 11 Kv Jerthi 6 2444 5.06 1.49 51.38 2.90 8.07
11 Kv Gothra Bhukran 5.2 1216 2.38 0.32 25.57 1.26 3.5
2.33/11 Kv S/S Jhigar Chhoti 11 Kv Dinarpura 3.3 365 0.61 0.03 7.67 0.38 1.05
11 Kv Jhigar Chhoti 3.6 1263 1.7 0.3 26.55 1.10 3.08

Total -C 5288 2.14


D IF 33/11 KV S/S Jhigar Chhoti
From 132 kv S/S Kudan 1. Before (i) 4 3150 0.52 0.2 66.23 0.30 0.84
(ii) 10.5 56.5 2.43 1.71 118.79 1.43 3.99
Total -D -1 3206.5 1.91

2. After (i) 4 3150 0.52 0.2 66.23 0.30 0.84


(ii) 10.5 8800 3.4 3.45 185.01 1.86 5.1
Total -D-2 11950 3.65
F IF 33/11 KV S/S Jhigar Chhoti
From 220 kv S/S Sikar 1. Before (i) 8 8800 2.37 2.23 185.01 1.20 3.34
(ii)
Total -F -1 8800 2.23

2. After (i) 8 8800 2.37 2.23 185.01 1.20 3.34


(ii) 13.3 3150 1.72 0.67 66.23 1.01 2.82
Total -F-2 11950 2.9

AE Saving
1 IF 33/11 KV S/S Jhigar Chhoti
From 132 kv S/S Kudan .=(A+D1)-(B+C+D2) = 2.44

2 IF 33/11 KV S/S Jhigar Chhoti


From 220 kv S/S Sikar .=(A+F1)-(B+C+F2) = 3.51
AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

Load Position of Existing Proposed 33/11 kv Sub- Station Dinarpura, sikar

S.NO Name of 33/11 Kv S/S Capacity of Name of 11 Kv feeder Existing After proposed
power Trans. DTC(KVA) DTC(KVA)
1 Existing 33/11 Kv S/S 5.0 MVA 11 Kv Palthana 2029 2029
Kudan 11 Kv Thorasi 1692 1692
11 Kv Kudan 2301 2301
11 Kv Palari 1523 1523
11 Kv W/W 350 350
3.15 MVA 11 Kv Jerthi 3419 2444
11 Kv Jokhana 2124 2124
2.5 MVA 11 Kv Mailasi 1242 1242
11 Kv Gothra bhukran 2362 1216

2 Existing 33/11 Kv S/S 3.15 MVA 11 Kv Ola Ki Dhani 1556 1556


Jhigar chhoti 11 Kv Mailasi 1870 1870
11 Kv Dinarpura 2237 365
11 Kv P & T 180 180
2.5 MVA 11 Kv Akawa 2120 2120
11 Kv Jhigar chhoti 2179 1263

3 Proposed 33/11 Kv S/S 3.15 MVA 11 Kv Jerthi 1731


Dinarpura 11 Kv Gothra bhukran 1146
11 Kv Dinarpura 971
11 Kv Katrathal 1061

TOTAL 27184 27184

JUNIOR ENGINEER (O&M)


A.V.V.N.L DADIYA

EXECUTIVE ENGINEER (O&M) ASSISTANT ENGINEER (O&M)


A.V.V.N.L. SIKAR A.V.V.N.L. PIPARALI
H.Q.SIKAR
AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

Estimate for 1X 3.15 MVA, 33/11 KV S/S AT VILLAGE DINARPURA

S.NO Particulars Unit Qty. Rate Amount


1 PCC Pole 9 Mtr long Nos 8 1632.00 13056
2 PCC Pole 8 Mtr long Nos 14 956.35 13388.9
3 M.S. Chenal 100X50X6mm MT 0.5 25053.17 12526.585
4 M.S. Angle 65X65X6mm MT 0.25 28561.26 7140.315
5 M.S Flat 50X6 mm MT 1.5 17900.72 26851.08
6 11 Kv Disc Insulator (B& S) Nos 180 193.30 34794.00
7 11 Kv Disc H/W (B& S) Nos 60 310.21 18612.60
8 M.S. Nuts & Bolts All size MT 0.5 42560.00 21280.00
9 33/11 Kv 3.15MVA Power Trans Nos 1 1648633.00 1648633.00
10 25 KVA Dist Transformer Nos 1 27343.38 27343.38
11 33 KV Pin Insulator Nos 24 182.97 4391.28
12 33 KV Pin Nos 24 112.13 2691.12
13 11 KV Pin Insulator With Pin Nos 36 79.01 2844.36
14 33 KV S/S Structure Nos 1 145353.16 145353.16
15 33 KV G.O Switch with Pi Set 2 25000.00 50000.00
16 11 KV G.O Switch Set 6 5261.00 31566.00
17 33 KV Horns Gap Fuse Set 1 7850.18 7850.18
18 11 KV Horns Gap Fuse Set 5 1454.98 7274.90
19 33 KV LAS Nos 3 4446.37 13339.11
20 11 KV LAS Nos 15 3787.07 56806.05
21 12 KV Post Insulator Nos 105 217.40 22827.00
22 24 KV Post Insulator Nos 60 700.90 42054.00
23 M.S. Rod 20 mm DIA MT 0.2 26962.54 5392.51
24 P.G Clamp for Dog Conductor Nos 120 205.59 24670.80
25 Dog Conductor KM 0.5 37148.96 18574.48
26 12 KV Kiosk 630 Amp. VCB Nos 5 314233.74 1571168.70
27 Red Oxide LTR 15 22.00 330.00
28 All Pains LTR 20 29.00 580.00
29 Flood Light Set 5 1225.00 6125.00
30 11 KV CT/PT Set 100/5Amp. Nos 4 17691.73 70766.92
31 H T Tvm 4 Nos Nos 4 4035.19 16140.76
32 F eeder Metering Structure Nos 4 13500.00 54000.00
0
Total 3978372.188
Add 35 % over head Charges 1392430.27
G.Total 5370802.45
Say Rs. 5370802
AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

Estimate for 33 KV Line Standrad Cost for 1.0 km Line

S.NO Particulars Unit Qty. Rate Amount


1 PCC Pole 9 Mtr long Nos 16 1632.00 26112
2 33 kv Cross Aram with Top Hamp. Nos 15 828.28 12424.2
3 M.S. Chenal 100X50X6mm MT 0.1 25053.17 2505.317
4 M.S Flat 50X6 mm MT 0.5 17900.72 8950.36
5 11 Kv Disc Insulator (B& S) Nos 18 193.30 3479.40
6 11 Kv Disc H/W (B& S) Nos 6 310.21 1861.26
7 M.S. Nuts & Bolts All size MT 0.2 42560.00 8512.00
8 33 KV Pin Insulator with Pin Nos 48 295.10 14164.80
9 33 KV Line Dp Structure Nos 1 5061.53 5061.53
10 P.G Clamp for Dog Conductor Nos 12 205.59 2467.08
11 Dog Conductor KM 3.1 37148.96 115161.78
12 G.I Stay Set (3/4"x8") Set 10 531.95 5319.50
13 G.i.Wire (7/8 Swg) MT 0.1 36882.55 3688.26
14 G.I.Earthing wire(8 Swg.) MT 0.15 34500.00 5175.00
15 33 kv Stay Insulator Nos 10 13.00 130.00
16 Stay Clamp for 9 Mtr.Pol Nos 10 67.48 674.80

Total 215687.278
Add 35 % over head Charges 75490.55
G.Total 291177.83
Say Rs. 291178
AJMER VIDHUT VITRAN NIGAM LIMITED ,SIKAR

Estimate for Proposed 11 KV Line Standrad Cost for 1.0 km Line

S.NO Particulars Unit Qty. Rate Amount


1 PCC Pole 8 Mtr long Nos 16 956.35 15301.6
2 11 kv Cross Aram with Top Hamp. Nos 15 491.74 7376.1
3 M.S. Chenal 100X50X6mm MT 0.05 25053.17 1252.6585
4 M.S Flat 50X6 mm MT 0.01 17900.72 179.0072
5 11 Kv Disc Insulator (B& S) Nos 6 193.30 1159.80
6 11 Kv Disc H/W (B& S) Nos 6 310.21 1861.26
7 M.S. Nuts & Bolts All size MT 0.02 42560.00 851.20
8 11 KV Pin Insulator with Pin Nos 48 79.01 3792.48
9 11 KV Line Dp Structure Nos 1 3253.96 3253.96
10 P.G Clamp for Dog Conductor Nos 12 205.59 2467.08
11 Dog Conductor KM 3.1 37148.96 115161.78
12 G.I Stay Set (3/4"x8") Set 10 531.95 5319.50
13 G.i.Wire (7/8 Swg) MT 0.1 36882.55 3688.26
14 G.I.Earthing wire(8 Swg.) MT 0.15 34500.00 5175.00
15 11 kv Stay Insulator Nos 10 7.24 72.40
16 Stay Clamp for 8 Mtr.Pol Nos 10 44.61 446.10

Total 167358.1767
Add 35 % over head Charges 58575.36
G.Total 225933.54
Say Rs. 225934
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S - Kudan
Name of 11 Kv Feeder - Existing Jerthi
Feeder Code
Distance Load Kva Kva * Km kva2*Km
0.9 I
0 25 3419 3077.10 10520604.9
0.1 I
0 40 3394 339.40 1151923.6
0.1 I
0 65 3354 335.40 1124931.6
0.6 I
0 40 3289 1973.40 6490512.6
0.1 I
0 652 3249 324.90 1055600.1
0.1 I
0 103 2597 259.70 674440.9
0.3 I
0 40 2494 748.20 1866010.8
0.1 I
0 1479 2454 245.40 602211.6
0.7 I
0 125 975 682.50 665437.5
0.2 I
0 180 850 170.00 144500
0.1 I
0 40 670 67.00 44890
0.4 I
0 40 630 252.00 158760
0.2 I
0 40 590 118.00 69620
0.5 I
0 25 550 275.00 151250
0.8 I
0 126 525 420.00 220500
0.5 I
0 40 399 199.50 79600.5
0.2 I
0 166 359 71.80 25776.2
0.3 I
0 25 193 57.90 11174.7
0.1 I
0 40 168 16.80 2822.4
0.4 I
0 25 128 51.20 6553.6
0.4 I
0 63 103 41.20 4243.6
0.3 I
0 40 40 12.00 480
Total 3419.00 30430.00 9738.40 25071844.60
Total Line Length Km 7.40
Total DTC 3419.00
Percent VR 6.91
Annual Energy Losses Lu 2.88
A E F Lu 71.88
% EL 4.006
% DL 11.129
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S - Kudan
Name of 11 Kv Feeder - Existing Gothra bhukaran
Feeder Code
Distance Load Kva Kva * Km kva2*Km
0.4 I
0 100 2362 944.80 2231617.6
0.6 I
0 978 2262 1357.20 3069986.4
0.4 I
0 25 1284 513.60 659462.4
0.3 I
0 113 1259 377.70 475524.3
0.5 I
0 40 1146 573.00 656658
0.1 I
0 40 1106 110.60 122323.6
0.4 I
0 100 1066 426.40 454542.4
0.2 I
0 145 966 193.20 186631.2
0.2 I
0 100 821 164.20 134808.2
0.4 I
0 40 721 288.40 207936.4
0.2 I
0 40 681 136.20 92752.2
0.1 I
0 210 641 64.10 41088.1
0.2 I
0 105 431 86.20 37152.2
0.2 I
0 143 326 65.20 21255.2
0.5 I
0 103 183 91.50 16744.5
0.4 I
0 40 80 32.00 2560
0.4 I
0 40 40 16.00 640
Total 2362.00 15375.00 5440.30 8411682.70
Total Line Length Km 5.50
Total DTC 2362.00
Percent VR 3.86
Annual Energy Losses Lu 0.97
A E F Lu 49.66
% EL 1.946
% DL 5.405
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S - Jhigar Chhoti
Name of 11 Kv Feeder - Existing Dinarpura
Feeder Code
Distance Load Kva Kva * Km kva2*Km
1.2 I
0 80 2237 2684.40 6005002.8
0.4 I
0 25 2157 862.80 1861059.6
0.2 I
0 40 2132 426.40 909084.8
0.5 I
0 40 2092 1046.00 2188232
0.6 I
0 50 2052 1231.20 2526422.4
0.1 I
0 40 2002 200.20 400800.4
0.3 I
0 90 1962 588.60 1154833.2
0.4 I
0 165 1872 748.80 1401753.6
0.4 I
0 105 1707 682.80 1165539.6
0.5 I
0 573 1602 801.00 1283202
0.4 I
0 103 1029 411.60 423536.4
0.1 I
0 90 926 92.60 85747.6
0.2 I
0 80 836 167.20 139779.2
0.1 I
0 180 756 75.60 57153.6
0.2 I
0 208 576 115.20 66355.2
0.1 I
0 223 368 36.80 13542.4
0.5 I
0 40 145 72.50 10512.5
0.2 I
0 40 105 21.00 2205
0.2 I
0 40 65 13.00 845
0.2 I
0 25 25 5.00 125

Total 2237.00 24646.00 10282.70 19695732.30


Total Line Length Km 6.80
Total DTC 2237.00
Percent VR 7.30
Annual Energy Losses Lu 2.26
A E F Lu 47.03
% EL 4.810
% DL 13.362
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S - Jhigar Chhoti
Name of 11 Kv Feeder - Existing Jhigar Chhoti
Feeder Code
Distance Load Kva Kva * Km kva2*Km
1 I
0 193 2179 2179.00 4748041
0.5 I
0 25 1986 993.00 1972098
0.3 I
0 476 1961 588.30 1153656.3
0.1 I
0 336 1485 148.50 220522.5
0.4 I
0 40 1149 459.60 528080.4
0.3 I
0 88 1109 332.70 368964.3
0.7 I
0 80 1021 714.70 729708.7
0.3 I
0 25 941 282.30 265644.3
0.3 I
0 250 916 274.80 251716.8
0.3 I
0 40 666 199.80 133066.8
0.2 I
0 125 626 125.20 78375.2
0.4 I
0 25 501 200.40 100400.4
0.3 I
0 230 476 142.80 67972.8
0.4 I
0 126 246 98.40 24206.4
0.4 I
0 40 120 48.00 5760
0.2 I
0 40 80 16.00 1280
0.3 I
0 40 40 12.00 480
Total 2179 15502 6815.5 10649973.9

Total Line Length Km 6.40


Total DTC 2179.00
Percent VR 4.84
Annual Energy Losses Lu 1.22
A E F Lu 45.81
% EL 2.670
% DL 7.418
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Palsana
Name of 11 Kv Feeder- Mandha( R )
Feeder Code
Distance Load Kva Kva * Km kva2*Km
0.228 I
0 25 1120 255.36 286003.2
0.95 I
0 50 1095 1040.25 1139073.75
0.11 I
0 25 1045 114.95 120122.75
0.515 I
0 325 1020 525.30 535806
0.186 I
0 165 695 129.27 89842.65
0.532 I
0 25 530 281.96 149438.8
0.11 I
0 25 505 55.55 28052.75
0.1 I
0 100 480 48.00 23040
0.337 I
0 50 380 128.06 48662.8
0.279 I
0 100 330 92.07 30383.1
0.086 I
0 50 230 19.78 4549.4
0.667 I
0 25 180 120.06 21610.8
0.13 I
0 50 155 20.15 3123.25
0.147 I
0 25 105 15.44 1620.675
0.082 I
0 40 80 6.56 524.8
0.36 I
0 40 40 14.40 576

Total 1040.00 7870.00 2846.20 2481329.93


Total Line Length Km 4.82
Total DTC 1120.00
Percent VR 2.02
Annual Energy Losses Lu 0.29
A E F Lu 21.86
% EL 1.304
% DL 3.621
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Palsana
Name of 11 Kv Feeder- Chinkar
Feeder Code
Distance Load Kva Kva * Km kva2*Km
Dog 1.4 I
0 1090 4540 6356.00 28856240
0.234 I
0 25 3450 807.30 2785185
0.222 I
0 40 3425 760.35 2604198.75
0.269 I
0 90 3385 910.57 3082262.525
0.406 I
0 1380 3295 1337.77 4407952.15
0.351 I
0 75 1915 672.17 1287195.975
0.045 I
0 105 1840 82.80 152352
0.117 I
0 25 1735 203.00 352196.325
0.21 I
0 165 1710 359.10 614061
0.221 I
0 25 1545 341.45 527532.525
0.567 I
0 425 1520 861.84 1309996.8
0.284 I
0 40 1095 310.98 340523.1
0.041 I
0 25 1055 43.26 45634.025
0.263 I
0 100 1030 270.89 279016.7
0.345 I
0 40 930 320.85 298390.5
0.343 I
0 100 890 305.27 271690.3
0.947 I
0 155 790 748.13 591022.7
0.552 I
0 285 635 350.52 222580.2
0.057 I
0 25 350 19.95 6982.5
0.185 I
0 25 325 60.13 19540.625
0.233 I
0 75 300 69.90 20970
0.281 I
0 50 225 63.23 14225.625
0.089 I
0 50 175 15.58 2725.625
0.347 I
0 75 125 43.38 5421.875
0.273 I
0 25 50 13.65 682.5
0.219 I
0 25 25 5.48 136.875

Total 3450.00 31820.00 8977.50 19242476.20


For Dog. Total 1090.00 4540.00 6356.00 28856240.00
Weasel Dog. G.total
Total Line Length Km 7.10 1.40 8.50
Total DTC 1735.00
Percent VR 6.37 1.97 8.34
Annual Energy Losses Lu 2.21 1.00 3.21
A E F Lu 36.48
% EL 8.80
% DL 24.44
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Palsana
Name of 11 Kv Feeder- Chinkar (R )
Feeder Code
Distance Load Kva Kva * Km kva2*Km
Dog 1.634 I
0 25 1535 2508.19 3850071.65
0.222 I
0 40 1510 335.22 506182.2
0.269 I
0 90 1470 395.43 581282.1
0.406 I
0 25 1380 560.28 773186.4
0.104 I
0 105 1355 140.92 190946.6
0.41 I
0 190 1250 512.50 640625
0.109 I
0 40 1060 115.54 122472.4
0.515 I
0 75 1020 525.30 535806
0.306 I
0 25 945 289.17 273265.65
0.172 I
0 105 920 158.24 145580.8
0.262 I
0 380 815 213.53 174026.95
0.475 I
0 40 435 206.63 89881.875
0.519 I
0 50 395 205.01 80976.975
0.097 I
0 25 345 33.47 11545.425
0.415 I
0 40 320 132.80 42496
0.222 I
0 25 280 62.16 17404.8
0.129 I
0 90 255 32.90 8388.225
0.27 I
0 25 165 44.55 7350.75
0.334 I
0 50 140 46.76 6546.4
0.334 I
0 65 90 30.06 2705.4
0.506 I
0 25 25 12.65 316.25

Total 1510.00 14175.00 4053.10 4210986.20


For Dog. Total 25.00 1535.00 2508.19 3850071.65
Weasel Dog. G.total
Total Line Length Km 6.08 1.63 7.71
Total DTC 1020.00
Percent VR 2.88 0.78 3.66
Annual Energy Losses Lu 0.48 0.13 0.62
A E F Lu 21.44
% EL 2.88
% DL 7.99
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Palsana
Name of 11 Kv Feeder- Mandha( E )
Feeder Code
Distance Load Kva Kva * Km kva2*Km
0.228 I
0 25 3900 889.20 3467880
0.095 I
0 50 3875 368.13 1426484.375
0.11 I
0 25 3825 420.75 1609368.75
0.515 I
0 325 3800 1957.00 7436600
0.186 I
0 1520 3475 646.35 2246066.25
0.532 I
0 25 1955 1040.06 2033317.3
0.11 I
0 25 1930 212.30 409739
0.1 I
0 100 1905 190.50 362902.5
0.337 I
0 50 1805 608.29 1097954.425
0.279 I
0 800 1755 489.65 859326.975
0.288 I
0 40 955 275.04 262663.2
0.1 I
0 50 915 91.50 83722.5
0.146 I
0 25 865 126.29 109240.85
0.17 I
0 25 840 142.80 119952
0.22 I
0 75 815 179.30 146129.5
0.04 I
0 40 740 29.60 21904
0.046 I
0 25 700 32.20 22540
0.283 I
0 155 675 191.03 128941.875
0.1 I
0 25 520 52.00 27040
0.11 I
0 170 495 54.45 26952.75
0.285 I
0 100 325 92.63 30103.125
0.096 I
0 25 225 21.60 4860
0.095 I
0 25 200 19.00 3800
0.076 I
0 25 175 13.30 2327.5
0.12 I
0 25 150 18.00 2700
0.02 I
0 25 125 2.50 312.5
0.25 I
0 50 100 25.00 2500
0.148 I
0 25 50 7.40 370
0.375 I
0 25 25 9.38 234.375

Total 3900.00 37120.00 8205.22 21945933.75


Total Line Length Km 5.46
Total DTC 3900.00
Percent VR 5.83
Annual Energy Losses Lu 2.52
A E F Lu 81.99
% EL 3.074
% DL 8.540
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Chinkar
Name of 11 Kv Feeder- Sundarpura
Feeder Code
Distance Load Kva Kva * Km kva2*Km
1.2 I
0 25 890 1068.00 950520
0.196 I
0 25 865 169.54 146652.1
0.383 I
0 25 840 321.72 270244.8
0.271 I
0 25 815 220.87 180004.975
0.947 I
0 155 790 748.13 591022.7
0.552 I
0 285 635 350.52 222580.2
0.057 I
0 25 350 19.95 6982.5
0.185 I
0 25 325 60.13 19540.625
0.335 I
0 75 300 100.50 30150
0.281 I
0 50 225 63.23 14225.625
0.081 I
0 50 175 14.18 2480.625
0.347 I
0 75 125 43.38 5421.875
0.273 I
0 25 50 13.65 682.5
0.219 I
0 25 25 5.48 136.875

Total 890.00 6410.00 3199.25 2440645.40


Total Line Length Km 5.33
Total DTC 890.00
Percent VR 2.27
Annual Energy Losses Lu 0.28
A E F Lu 18.71
% EL 1.498
% DL 4.162
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Chinkar
Name of 11 Kv Feeder- Chinkar NEW
Feeder Code
Distance Load Kva Kva * Km kva2*Km
1.4 I
0 25 1150 1610.00 1851500
0.147 I
0 100 1125 165.38 186046.875
1.6 I
0 25 1025 1640.00 1681000
0.061 I
0 25 1000 61.00 61000
0.029 I
0 25 975 28.28 27568.125
0.064 I
0 65 950 60.80 57760
0.198 I
0 25 885 175.23 155078.55
0.246 I
0 205 860 211.56 181941.6
0.221 I
0 25 655 144.76 94814.525
0.567 I
0 385 630 357.21 225042.3
0.424 I
0 65 245 103.88 25450.6
0.069 I
0 50 180 12.42 2235.6
0.207 I
0 25 130 26.91 3498.3
0.274 I
0 40 105 28.77 3020.85
0.058 I
0 25 65 3.77 245.05
0.42 I
0 40 40 16.80 672

Total 1150.00 10020.00 4646.76 4556874.38


Total Line Length Km 5.99
Total DTC 1150.00
Percent VR 3.30
Annual Energy Losses Lu 0.52
A E F Lu 24.18
% EL 2.165
% DL 6.014
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Chinkar
Name of 11 Kv Feeder- Bassi
Feeder Code
Distance Load Kva Kva * Km kva2*Km
0.7 I
0 25 915 640.50 586057.5
0.162 I
0 25 890 144.18 128320.2
0.169 I
0 100 865 146.19 126450.025
0.236 I
0 165 765 180.54 138113.1
0.666 I
0 250 600 399.60 239760
0.281 I
0 50 350 98.35 34422.5
0.084 I
0 25 300 25.20 7560
0.165 I
0 25 275 45.38 12478.125
0.235 I
0 25 250 58.75 14687.5
0.088 I
0 25 225 19.80 4455
0.175 I
0 75 200 35.00 7000
0.224 I
0 50 125 28.00 3500
0.121 I
0 25 75 9.08 680.625
0.217 I 0
0 25 50 10.85 542.5
0.163 I 0.00 0
0 25 25 4.08 101.875

Total 915.00 5910.00 1845.48 1304128.95


Total Line Length Km 3.69
Total DTC 915.00
Percent VR 1.31
Annual Energy Losses Lu 0.15
A E F Lu 19.24
% EL 0.779
% DL 2.163
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Mandha
Name of 11 Kv Feeder- Gordhanpura
Feeder Code
Distance Load Kva Kva * Km kva2*Km
2 I
0 25 1355 2710.00 3672050
0.185 I
0 25 1330 246.05 327246.5
0.206 I
0 25 1305 268.83 350823.15
0.418 I
0 25 1280 535.04 684851.2
0.143 I
0 150 1255 179.47 225228.575
0.173 I
0 25 1105 191.17 211237.325
0.133 I
0 155 1080 143.64 155131.2
0.178 I
0 25 925 164.65 152301.25
0.325 I
0 325 900 292.50 263250
0.11 I
0 25 575 63.25 36368.75
0.376 I
0 25 550 206.80 113740
0.06 I
0 125 525 31.50 16537.5
0.445 I
0 75 400 178.00 71200
0.13 I 0
0 50 325 42.25 13731.25
0.189 I
0 150 275 51.98 14293.125
0.407 I
0 75 125 50.88 6359.375
0.224 I
0 25 50 11.20 560
0.15 I
0 25 25 3.75 93.75

Total 1355.00 13385.00 5370.94 6315002.95


Total Line Length Km 5.85
Total DTC 1355.00
Percent VR 3.81
Annual Energy Losses Lu 0.73
A E F Lu 28.49
% EL 2.546
% DL 7.073
Calculation of 11 kV Voltage Regulation and Annual Energy Losses
Name of 33/11 kv S/S -Mandha
Name of 11 Kv Feeder- Mandha NEW
Feeder Code
Distance Load Kva Kva * Km kva2*Km
0.254 I
0 25 1475 374.65 552608.75
0.371 I
0 25 1450 537.95 780027.5
0.8 I
0 25 1425 1140.00 1624500
0.439 I
0 105 1400 614.60 860440
0.118 I
0 40 1295 152.81 197888.95
0.621 I
0 325 1255 779.36 978090.525
0.11 I
0 25 930 102.30 95139
0.1 I
0 155 905 90.50 81902.5
0.283 I
0 25 750 212.25 159187.5
0.046 I
0 40 725 33.35 24178.75
0.04 I
0 75 685 27.40 18769
0.22 I
0 25 610 134.20 81862
0.17 I
0 25 585 99.45 58178.25
0.146 I 0
0 50 560 81.76 45785.6
0.1 I
0 40 510 51.00 26010
0.496 I
0 25 470 233.12 109566.4
0.197 I
0 25 445 87.67 39010.925
0.097 I
0 25 420 40.74 17110.8
0.198 I
0 50 395 78.21 30892.95
0.203 I
0 100 345 70.04 24162.075
0.053 I
0 50 245 12.99 3181.325
0.08 I
0 40 195 15.60 3042
0.092 I
0 25 155 14.26 2210.3
0.181 I
0 40 130 23.53 3058.9
0.157 I
0 25 90 14.13 1271.7
0.089 I
0 40 65 5.79 376.025
0.408 I
0 25 25 10.20 255

Total 1475.00 17540.00 5037.84 5818706.73


Total Line Length Km 6.07
Total DTC 1475.00
Percent VR 3.58
Annual Energy Losses Lu 0.67
A E F Lu 31.01
% EL 2.155
% DL 5.987
Calculation of 33 kV Voltage Regulation and Annual Energy Losses
(A)
Name of 220 kv S/S -Sikar
Name of 33 Kv Feeder - Kudan
Feeder Code
Distance Load Mva Mva* Km Mva2*Km
4 I
0 3.15 3.15 12.60 39.69

Total 3.15 3.15 12.60 39.69


Total Line Length Km 4.00
Percent VR 0.52
Annual Energy Losses Lu 0.20
A E F Lu 66.23
% EL 0.3056506849315
% DL 0.8490296803653
Calculation of 33 kV Voltage Regulation and Annual Energy Losses
(B)
Name of 220 kv S/S -Sikar
Name of 33 Kv Feeder - Kudan
Feeder Code
Distance Load Mva Mva* Km Mva2*Km
4 I
0 3.15 8.8 35.20 309.76
4 I
0 5.65 5.65 22.60 127.69
Total 8.80 14.45 57.80 437.45
Total Line Length Km 8.00
Percent VR 2.37
Annual Energy Losses Lu 2.23
A E F Lu 185.01
% EL 1.2058702392071
% DL 3.3496395533532
Calculation of 33 kV Voltage Regulation and Annual Energy Losses
(C)
Name of 132 kv S/S -Kudan
Name of 33 Kv Feeder - Proposed Dinarpura
Feeder Code
Distance Load Mva Mva* Km Mva2*Km
13.3 I
0 3.15 3.15 41.90 131.96925

Total 3.15 3.15 41.90 131.97


Total Line Length Km 13.30
Percent VR 1.72
Annual Energy Losses Lu 0.67
A E F Lu 66.23
% EL 1.0162885273973
% DL 2.8230236872146
Calculation of 33 kV Voltage Regulation and Annual Energy Losses
(D)
Name of 132 kv S/S -Kudan
Name of 33 Kv Feeder - Proposed Jhigar chhoti
Feeder Code
Distance Load Mva Mva* Km Mva2*Km
10.5 I
0 5.65 5.65 59.33 335.18625

Total 5.65 5.65 59.33 335.19


Total Line Length Km 10.50
Percent VR 2.43
Annual Energy Losses Lu 1.71
A E F Lu 118.79
% EL 1.4391053082192
% DL 3.9975147450533
Calculation of 33 kV Voltage Regulation and Annual Energy Losses
(E)
Name of 132 kv S/S -Kudan
Name of 33 Kv Feeder - Proposed Dinarpura
Feeder Code
Distance Load Mva Mva* Km Mva2*Km
7.5 I
0 3.15 8.8 66.00 580.8
3 I
0 5.65 5.65 16.95 95.7675
Total 8.80 14.45 82.95 676.57
Total Line Length Km 10.50
Percent VR 3.40
Annual Energy Losses Lu 3.45
A E F Lu 185.01
% EL 1.8650191177615
% DL 5.1806086604487

You might also like