Storm Trapper® H.E. (High Energy) Low Voltage
Distribution Class MOV Surge Arrester 235-16
GENERAL
Cooper Power Systems Storm
Trapper H.E. (High Energy), low volt-
age distribution class surge arresters
are designed to provide surge pro-
tection at distribution transformer
secondary bushings, service
entrance locations, and any other
electrical apparatus connected to a
secondary voltage source.
The Storm Trapper H.E. is the
industry's first low voltage distribution
class arrester and has successfully
passed all design tests for light duty
distribution class arresters per
ANSI/IEEE C62.11.
Years of research by Cooper
Power Systems in low voltage sec-
ondary circuits concluded that the
types and magnitudes of surges that Figure 1.
can exist in these circuits are more Storm Trapper H. E., external mount.
severe than previously thought. The
Storm Trapper H.E. arrester, born out
of this research, was designed to
reliably handle the stresses found in
these low voltage circuits. The
research further noted that transformer
failure rates can be significantly
reduced by adding surge protection
to transformer secondary bushings.
Field experiments in some of the
most severe lightning areas of the
United States has shown that trans-
former failure rates can be reduced
to far below 0.1% by applying Storm
Trapper H.E. arresters to transformer
secondaries.
FEATURES
The Storm Trapper H.E. family of
arresters incorporates the highest
energy handling Metal Oxide Varistors
(MOV's) when compared to other
arresters promoted for similar appli-
cations. This superior energy han- Figure 2. Figure 3.
dling ability assures long service life Storm Trapper H.E., metal enclosed. Storm Trapper H.E., internal mount.
even in the most severe service con-
ditions. Storm Trapper H.E. arresters
were designed with a full 40 kA surge DESIGNS energized source come with black
withstand capability, four times the The Storm Trapper H.E. is available wire insulation while the ground lead
level of traditional secondary arresters. in three design configurations: exter- has white insulation. The length of the
The durable MOV's used in the nal mount, metal enclosed, and inter- line and ground leads play an impor-
Storm Trapper H.E. are manufac- nal mount. All external mount and tant role in the protective ability of the
tured by Cooper Power Systems at metal enclosed Storm Trapper H.E.'s arrester. The longer the leads are,
our ISO-9001 certified plant in Olean, are UL® and CSA® listed for safety. the higher the voltage let through to
New York. This allows constant QA Standard line and ground leads on the protected equipment. Thus to
monitoring to assure that only the the external mount and metal improve the equipment protection, it
highest quality high energy MOV's enclosed designs are 18 inch, #10 is strongly recommended that all line
get selected for use in Storm Trapper AWG stranded copper. The line and ground leads be kept to the
H.E. arresters. leads that are connected to the minimum required length.
LOW VOLTAGE
Ensures high pressure
continuous contact.
IDENTIFICATION
INFORMATION
Provides convenient refer-
ence for arrester type and SEALING COMPOUND
UL
Figure 4.
Cutaway Illustration of external mount Storm Trapper H.E. arrester without mounting bracket (two pole model illustrated).
2
235-16
2.20''
.187" (56 mm) 1.83''
(4.7mm) (46 mm)
DIA. HOLES
(4 PLACES) 1.37'' 1.20''
(35 mm) (30 mm)
.53''
(13 mm)
.56 x 2.50
(14 x 64 mm)
(SLOT)
4.75''
(121 mm)
4.14''
(105 mm)
.96''
(24 mm)
Figure 5.
Dimensional information for external mount Storm Trapper H.E. arrester (shown with optional mounting bracket).
*Based on a current impulse that results in a discharge voltage cresting in 0.5 µs.
TABLE 3
TABLE 2 Performance Test Characteristics*
Insulation Withstand Voltages
Description Characteristics
Arrester Rating 1.2/50 Impulse 1 min Dry 10 sec Wet
(V rms) (kV crest) (kV rms) (kV rms) High-current, 2 discharges of 40 kA crest, 4/10 µs current wave
Short-duration
All 10 6 6 Low-current, 20 surges of 75 A-2000 microsecond duration
Ratings Long-duration
Duty Cycle 22 operations of 5 kA crest, 8/20 µs current wave
3
Storm Trapper® H. E. Low Voltage
Distribution Class MOV Surge Arrester
2.56''
2.48'' (65 mm)
(63 mm)
1.37" 1.96''
(35 mm) (50 mm)
STAINLESS
AIR STEEL
BOX
FULLY
POTTED EXTERNAL
MOUNT STORM
TRAPPER H.E.
4.75'' 4.25''
(121 mm) (108 mm)
Storm Trapper® H.E.
FAILURE
INDICATOR
WINDOW
FRONT VIEW SIDE VIEW
Figure 6.
Dimensional information for metal enclosed Storm Trapper H.E. arrester (shown with optional mounting bracket).
2.67''
(68 mm)
1.50''
(38 mm)
.56''
(14 mm)
.51''
1.65'' (13 mm)
5.12'' (42 mm)
(130 mm) .88''
(22 mm)
4
235-16
TEMPORARY
OVERVOLTAGE (TOV)
CAPABILITY
The ability of the Storm Trapper H.E.
to withstand 60 Hz temporary over-
voltage conditions is graphically
shown in Figure 8.The graph shows
for a given voltage magnitude (on a
per unit of MCOV basis), the time an
arrester can survive a TOV condition
without going into thermal runaway.
1.6
1.5
1.4
PER UNIT OF MCOV
1.3
1.2
1.1
TIME (Seconds)
Figure 8.
Temporary Overvoltage Capability.
ORDERING INFORMATION
To order a Cooper Power Systems TABLE 4
Storm Trapper H.E. arrester, Internal Mount Storm Trapper H.E. Arrester Selection
determine the arrester Maximum Catalog Number
Continuous Operating Voltage Storm
Trapper H.E. Voltage With Without
(MCOV) rating for the intended appli- Arrester Rating MCOV Number Terminal Terminal
cation and specify the appropriate Type (V rms) (V rms) of Poles Lugs Lugs
catalog number from Table 4 or 5.
Contact the Cooper Power Systems
Internal Mount 480 400 2 ASZH480U200* ASZH480U202**
sales engineer in your location for
more information.
* 10 inch leads
** 24 inch leads
5
Storm Trapper® H. E. Low Voltage
Distribution Class MOV Surge Arrester
A B C
INDUSTRIES
COOPER
MCOV
RATED
ASZ4C1
DISTRIBUTION SURGE ARRESTER
PRIMARY
CIRCUIT
PANEL
METER
Figure 9.
Location categories in low-voltage circuits.