Voltage, Frequency Prime Standby Engine Make & Model: Perkin® 404D-22G
400V, 50 Hz 20.0 kVA / 16.0 kW 22.0 kVA / 17.6 kW Alternator manufactured for
Leroy Somer
FG Wilson by:
480V, 60 Hz 22.5 kVA / 18.0 kW 25.0 kVA / 20.0 kW
Alternator Model: LL1114M
Ratings at 0.8 power factor. Control Panel: DCP-10
Please refer to the output ratings technical data section for Base Frame: Heavy Duty Fabricated Steel
specific generator set outputs per voltage. Circuit Breaker Type: 3 Pole MCB
Frequency: 50 Hz 60 Hz
Engine Speed: RPM 1500 1800
Prime Rating
These ratings are applicable for supplying continuous electrical power Fuel Tank Capacity:
(at variable load) in lieu of commercially purchased power. There is no 66 (17.4)
limitation to the annual hours of operation and this model can supply 10%
Fuel Consumption:
overload power for 1 hour in 12 hours.
(100% Load) - Prime 5.3 (1.4) 5.8 (1.5)
Standby Rating
These ratings are applicable for supplying continuous electrical power (at - Standby 5.9 (1.6) 6.5 (1.7)
variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).
Available Options
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m FG Wilson offer a range of optional features to tailor our generating
(328 ft) A.S.L. 30% relative humidity. sets to meet your power needs. Options include:
Fuel consumption data at full load with diesel fuel with specific gravity of
0.85 and conforming to BS2869: 1998, Class A2.
A wide range of Sound Attenuated Enclosures
A variety of generating set control panels
Additional alarms and shutdowns
1500 (59.1) 620 (24.4) 1115 (43.9) 447 (985) 454 (1001)
Dry = With Lube Oil Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22.
Generating set pictured may include optional accessories.
Engine Technical Data Air Systems 50 Hz 60 Hz
Bore / Stroke: mm (in) 84.0 (3.3)/100.0 (3.9) - Prime 1.5 (51) 1.7 (61)
Naturally Aspirated - Standby 1.5 (51) 1.7 (61)
Induction:
Max. Combustion Air Intate
Restriction: kPa (in H2O) 3.0 (12.0) 3.0 (12.0)
Cooling Method: Water
Governing Type: Mechanical
Governing Class: ISO 8528
Compression Ratio: 23.3:1
Cooling System 50 Hz 60 Hz
Displacement: l (cu. in) 2.2 (135.2)
Cooling System Capacity: l (US gal) 6.5 (1.7) 6.5 (1.7)
Moment of Inertia: kg m² (lb/in²) 2.72 (9308)
Water Pump Type: Centrifugal
Engine Electrical System:
Heat Rejected to Water & Lube Oil:
- Voltage / Ground 12/Negative
kW (Btu/min) - Prime 17.0 (967) 19.9 (1132)
- Battery Charger Amps 65
- Standby 19.6 (1115) 22.2 (1262)
Weight: kg (lb) - Dry 242 (534)
Heat Radiation to Room: Heat radiated from engine and alternator
- Wet 251 (554) kW (Btu/min) - Prime 5.7 (324) 6.3 (358)
- Standby 7.1 (404) 7.4 (421)
Performance 50 Hz 60 Hz Radiator Cooling Airflow: m³/min (cfm) 33.0 (1165) 41.4 (1462)
External Restriction to
Engine Speed: rpm 1500 1800 125 (0.5) 125 (0.5)
Cooling Airflow: Pa (in H2O)
Gross Engine Power: kW (hp)
Designed to operate in ambient conditions up to 50°C (122°F).
- Prime 18.7 (25.0) 22.0 (30.0) Contact your local FG Wilson Dealer for power ratings at specific site conditions.
- Standby 743.0 (107.8) 731.0 (106.0) Oil Filter Type: Spin-On, Full Flow
Total Oil Capacity: l (US gal) 10.6 (2.8)
Oil Pan: l (US gal) 8.9 (2.4)
Oil Type: API CH4 15W-40
Standby Load Load Load Load Exhaust Gas Flow: m³/min (cfm)
50 Hz 5.9 (1.6) 4.3 (1.1) 3.1 (0.8) - Prime 3.6 (129) 4.3 (153)
60 Hz 6.5 (1.7) 4.9 (1.3) 3.6 (1.0) - Standby 3.9 (139) 4.8 (168)
(Based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Exhaust Gas Temperature: °C (°F)
Class A2)
- Prime 445 (833) 440 (824)
- Standby 505 (941) 510 (950)
Alternator Physical Data Alternator Operating Data
Alternator
50 Hz 60 Hz
Performance Data:
220/127V
Motor Starting
55 52 48 52
Capability* kVA
Short Circuit
- - - -
Capacity %
Output Ratings
Voltage Technical
Technical Data 50Data
Hz 50 Hz Output
VoltageRatings Technical
Technical Data 60Data
Hz 60 Hz
Voltage Prime: Standby: Voltage Prime: Standby:
kVA kW kVA kW kVA kW kVA kW
415/240V 20.0 16.0 22.0 17.6
400/230V 20.0 16.0 22.0 17.6 220/127V 22.5 18.0 25.0 20.0
Documentation