Professional Documents
Culture Documents
The Warranty on your SCHULZ compressor will only be effective following the
receipt of the warranty registration form completed by a SCHULZ certified
technician.
See Warranty Registration Form (Page 126)
! IMPORTANT
This Instruction Manual contains important use, installation, maintenance and
safety information and should always be available to the machinery operator. To
prevent personal injuries or material damage to your rotary screw air compressor,
always familiarize yourself with the contents of this manual before operating or
maintaining your equipment.
! IMPORTANT
Use only SCHULZ original parts for your rotary screw air compressor
maintenance. These are available through your SCHULZ Authorized Service
Center. See table 36 (page 121).
INSTRUCTION MANUAL
SCREW AIR COMPRESSOR
SRP 3200 SRP 3200 SS
ELECTRONIC
INDEX
Introduction EN-69
ENGLISH
INTRODUCTION
Instruction Manual
COMPRESSOR INSPECTION
Immediately inspect your compressor for both obvious and unseen freight damage. Report this to the
freight company immediately! Repair any freight damage before operating the air compressor.
USE
SCHULZ air compressors are designed for the compression of atmospheric air only and within the pressure
parameters indicated in the SCHULZ literature.
EN-69
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
SAFETY
In addition to these instructions, the local regulations in your country may impose additional requirements
that must be observed.
- extremely hot parts, energized electrical components, compressed air parts and moving parts;
- turns on or off automatically relative to system pressure or actuation of the thermal protection
elements;
- may cause mechanical or electrical interference in nearby equipment;
- installation must be protected from access by unauthorized persons, children or animals;
- operate and maintain this equipment with appropriate supervision and appropriate use of
personal protective equipment;
- unit must be installed and operated in well ventilated areas with protection from elements;
2. Never attempt to exceed the maximum operating pressure indicated on the compressor.
3. Do not attempt maintenance before disconnecting the electrical power supply.
4. Do not adjust the safety valve. It is permanently adjusted at the factory.
5. Do not attempt to repair or air/oil tank. Certification and operation tank may be adversely affected.
Consult your SCHULZ Authorized Service Center.
6. Never run the air/oil tank above the maximum pressure indicated in its identification tag.
7. The end user must have a new inspection in the air/oil tank carried out after 5 years from the
manufacturing date shown in its identification tag, or when a mechanical or chemical problem,
which may jeopardize its resistance, occurs. This inspection must be made and approved by an
authorized engineer (skilled professional), according to local technical norms. The subsequent
inspections shall be determined by the authorized engineer. We recommend the replacement of
the tank for a new one every ten years, or according to the authorized engineer.
8. Air compressing is a heat generating process. Surfaces and parts are subject to high
temperatures, therefore, to avoid burns, be careful when handling them.
9. Do not use the compressed air from this equipment for breathing air. It contain carbon
monoxide or other harmful substances. If used for such purpose, special filters after the
compressor must be installed. Consult your SCHULZ Authorized Service Center for further
information.
10. Before connecting the compressor re-fastening of the electrical conection.
11. Keep the refrigeration air inlet always 15 clean, to prevent the propeller from sucking remains (Figure 2,
page 73).
12. Never use solvent to clean the compressor's internal/external parts. Use neutral detergent.
13. Never activate the safety valve if the compressor is operating/pressurized, to
avoid burns.
14. Avoid the accumulation of solvents, paints or other chemicals that can cause explosion risks, or compressor
damage.
15. Do not carry out maintenance jobs with the compressor on. For safety reasons, press the emergency
button 5 (Figure 23, page 92) located in the instrument panel.
16. If the equipment shows any irregularities, stop its operation immediately and get in touch with the nearest
SCHULZ Authorized Service Center.
EN-70
SAFETY
Blow down
TECHNICAL DATA
220V - 380V - 440V / 60Hz
cfm 945
DISPLACEMENT
m³/min 26.7
hp 200
kW 150
220/380
Voltage (V) 380/660
MAIN MOTOR 440/760
RPM 3,580
SRP 3200 Y/
Start mode
soft
SRP 3200 SS starter (SS)
hp 5
kW 3.7
FAN’S MOTOR
220/380/
Voltage (V)
440
RPM 900
2 1
3
16
18 - 4
5
7
22
17
9
SCALE 25.400
14 4 - 18
8
11
13
15 19
20
21
10
12
FIGURE 2
SCALE 25.400
EN-73
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
INSTALLATION
1. LOCATION:
Install the compressor in a covered, well ventilated area, free from dust gases, toxic gases, humidity or
any other sources of contamination. The presence of contaminants in the air (dust, fibers, etc.) may
cause premature obstruction to the air filter and the air/oil after-cooler (please see chapter on Preventive
Maintenance, page 119, item 5.1. Chemical gases may pass through the air inlet filter and contaminate
the oil, causing lubricating problems and diminished air quality. The maximum recommended working
ambient temperature is 40 ºC (104 ºF). Should temperature be higher, exhaust fans or must be provided
in order to bring ambient temperature to its required level. The lower the temperature, the better the
compressor's working conditions. The installation of a hot air duct from the compressor's cooling air
outlet may be installed. Care should be taken to insure that NO AIR FLOW RESTRICTION is created.
Connection to the compressor cabinet must also be accomplished in such a manner as to insure the
ease of maintenance. (Consult your SCHULZ Authorized Service Center for assistance and
recommendations).
Do not install the compressor in chemically insalubrious areas.
ATTENTION
2. DIMENSION AND POSITION IN THE COMPRESSOR (See Figures 3, [4 and 5, page 76])
Place compressor a minimum distance (See Figure 5, page 75) from any wall or obstacle to facilitate
adequate air flow and ease of maintenance.
POWER SUPPLY
1,460/57.5
1,890/74.4
1,200/47.2
2,840/111.8
3,120/122.8
2,7
40
/10
7.8
.7
0/56
1,44
FIGURE 3
ATTENTION Operating conditions and demands on the machine may dictate a modification of the
maintenance intercal(s). Maintenance intervals must be reduced to 50% in high
demand situations or contaminated environments. Consult with your SCHULZ
Authorized Service Center for additional information as failure to follow these
recommendations may cause damage to the compressor and void the Warranty.
EN-74
INSTALLATION
3. FOUNDATION/PACKAGING:
Install the compressor by removing the transportation accessory (base) and place it on a level concrete
floor, considering the compressor's weight (according to Table 1 Technical Data, page 72). Draining is
necessary (oil separation container or a separate container) to remove the condensed water. It's neither
necessary to install vibration absorbers nor to fasten the chassis on the floor.
4. ELECTRICAL CONNECTION
Before connecting electrical power supply it is recommended that internal electrical connections be
checked for security following shipping. Consult a licensed electrician to evaluate power supply and
install appropriate electrical connections for your air compressor.
Your compressor must be installed in accordance with federal state and local electrical
ATTENTION codes.
Wiring must be sized appropriately to accommodate in-rush current and distance to power supply (See
Table 2, page 84).
The electric supply system must be protected with NH fuses. Y start - retarded fuse and soft starter -
extra-fast fuse, installed next to the compressor (see Table 1, page 72).
Always check if the transformer's capacity can stand the compressor's power. If a
ATTENTION separate transformer is not available, check whether the energy supply and main
circuit breakers can stand a voltage load increase.
The electrical power supply should not have a voltage variation greater than ± 10%.
The voltage drop caused by the motor's start up should not exceed 10%.
The frame of the compressor should be grounded appropriately.
The Compressor's Electrical Panel has a terminal block (X2) for the incorporation of a remote start switch.
The motors are equipped with a protection relay (PTC), installed in the coil.
The electric diagrams are shown in Figures 6 to 12 (pages 77 to 83), with the connection diagrams, and
guidelines + diagrams A and B for the installation of capacitors on page 85.
Terminal block (X0) power supply: supplies compressor according to nominal voltage indicated in the
start switch cabinet
Terminal Block (X2) command supply: command supply must be apart from power supply.
Command voltage for all models is 220Vac.
EN-75
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
INSTALLATION
1
/8.
207
121/4.7
33.3/1.3
23.9/0.94
.5
5/7
90.
Ø1
Ø 228.6/9.0
(8x)Ø
19.05
/3/4”
Ø 116.9/4.6
Ø 134.9/5.3
303
/11
.9
FIGURE 4
3,000/118.1
.0
/59
00
1,500/59.0 1,5
.3
/39
00
1,0 SCALE 25.400
1,500/59
.0
FIGURE 5
EN-76
FAN’S MOTOR MAIN MOTOR REF. DESCRIPTION
K1 THREE-PHASE SUPPLY CONTACTOR
K2 DELTA START CONTACTOR
K3 STAR START CONTACTOR
K4 FAN'S MOTOR CONTACTOR
SUPPLY KP1 COMPRESSOR'S MOTOR PROTECTION RELAY (PTC)
3~50/60Hz M1 COMPRESSOR'S MOTOR
R S T
MULTI-WIRE DIAGRAM
M2 FAN'S MOTOR
X0
15 X0 THREE-PHASE SUPPLY’S TERMINAL BLOCKS
KFF X2 COMMAND TERMINAL BLOCKS
INSTALLATION
K4 K1 K2 K3
78/E7 78/E4 78/E5 78/E4
2 4 6 2 4 6 2 4 6 2 4 6
FIGURE 6 - MULTI-WIRE DIAGRAM - DELTA STAR START SWITCH - 220V - 380V - 440V
200hp
M1
3 4
M 2 M 5
M2 5hp
3~ 1 3~ 6
X4:PTC
TK 78/B4 78/E2
X4:PTC
EN-77
EN-78
EMERGENCY OVERLOAD OVERLOAD LACK OF PHASE LOAD/UNLOAD REMOTE PRESSURE TEMPERATURE
DOOR’S SENSOR MAIN MOTOR FAN’S MOTOR START/STOP LOCAL SENSOR SENSOR
21 22
78/D2
31 32
FUNCTIONAL DIAGRAM
B1
INSTALLATION
X3 14 X3 8
15
X3 10 X3 12
KFF
SW1 95 77/B2
16 X2 3 X2 5
P T
KP1 TK
67
78/B3 96 77/F1 X2 4 X2 6
SW2 K4 X3 9 X3 11
78/E6
68
X3 13 X3 7
SCREW AIR COMPRESSOR
X01: 1 2 3 4 5 6 7 8 9 X02: 1 2 3 6
X09:
X2: 1 X3: 1 T1 X3: 2 1 1
H1 X1 2
F1-4A F2-2A F3-2A
X03: 3
220Vca
4
X2 X3 X3 2
ELECTRONIC INTERFACE
H2 X2
2 3 220-24V 4
SERIAL
X08: 1 2 3 4 5 6 7 8 9 10 X06: 1 2
78/A3
13
K1
21 21 78/E4
14
K2 K3 X3 5 X3 15 16
77/F4
77/E6
78/E5 78/E4
22 22
X4 1 2
R.A.
FIGURE 7 - FUNCTIONAL DIAGRAM - DELTA STAR START SWITCH - 220V - 380V - 440V
A2 T2 A1 A1 A1 A1 A1
KP1 K1 K3 K2 Y2 K4
A1 T1 A2 A2 A2 A2 A2
X3 6
PHASE
NEUTRAL
ONN CLOSED SWITCH 21 22 21 22 78/D5 21 22 78/D4
OFF OPEN SWITCH
ON/OFF
LOAD/UNLOAD
SRP 3200 - FUNCTIONAL DIAGRAM
REMOTE/LOCAL
SRP 3200 SRP 3200 SS
1 2 3 4 5 6 7 8
LAYOUT
T1
INSTALLATION
X3 X2
PE
KP1 KFF
K4
X4
C R
ACRYLIC
PROTECTION
E
PE
FRONTAL VIEW
EN-79
EN-80
MAIN MOTOR FAN’S MOTOR
REF. DESCRIPTION
A1 SOFT STARTER
K4 POWER CONTACTOR
M1 COMPRESSOR’S MOTOR
M2 FAN’S MOTOR
X2, X3,
SUPPLY TERMINAL
X4
MULTI-WIRE DIAGRAM
3~50/60Hz
F1, F2,
L1 L2 L3 FUSE DISCONNECTOR
F3
INSTALLATION
F1 4A FUSE
REMARK: THE PROTECTION FUSES ARE THE F2, F3 2A FUSE
CUSTOMER’S RESPONSIBILITY AND MUST T1 220-24V CONTROL TRANSFORMER
BE EXTRA-FAST. KP1 220V THERMISTOR RELAY 1NA + 1NF AUXILIARY CONTACTOR
SW1,
DOOR’S END OF STROKE
SW2
SCREW AIR COMPRESSOR
A1
R S T
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFF
FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
FF FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF
1 3 5
I
P K4
0
RESET
82/C5 2 4 6
INTERFACE
MAN x EQUIPMENT
U V W
FIGURE 9 - MULTI-WIRE DIAGRAM - SOFT STARTER START SWITCH - 220V - 380V - 440V
R S T
R S T
X4
M
M1 3 M
PTC 81/D2 M2 t
3 81/B4
PTC
5 hp
200 hp
FAN MOTOR
MAIN MOTOR
21 22
81/D4
31 32
FUNCTIONAL DIAGRAM
B1
INSTALLATION
X3 15 X3 X2 X2
14 8 3 5 X3 10 X3 12
A1
82/C6
SW1 14 16 K1
82/C2 P T
SW2 15
KP1
X3 81/D2 X3 X2 X2 X3
13 7 4 6 9 X3 11
18 16
81/D2
X01: 1 2 3 4 5 6 7 8 9 X02: 1 2 3 6
X09:
1 1 2 X03:
T1 1
H1 X1 1
{F1} {F2} {F3}
2
220Vca
ELECTRONIC INTERFACE
X2 X3 X3 3
H2 X2
2 3 220-24V 4 2 SERIAL 4
25VA 1 2 3 4 5 6 7 8 9 10 1 2
X08: X06:
81/A3 82/B1
13
K4 X3 15 16 17
82/B6
14
82/E2
80/E4
80/E4
81/B2
X3 6
82/E2 A1
A1 S1 A2
KP1
A2 S2 X3 5 X2
TERMINAL 1 2 3 4 5 6
FIGURE 10 - FUNCTIONAL DIAGRAM - SOFT STARTER START SWITCH- 220V - 380V - 440V
82/B1 N°
RPW-220-PTC
PHASE
NEUTRAL
220Vca
REMOTE CLOSED SWITCH
LOCAL OPEN SWITCH
ON/OFF
LOAD/UNLOAD
REMOTE/LOCAL
EN-81
EN-82
1 2 3 4 5 6 7 8
A
COMMAND DIAGRAM
INSTALLATION
81/D6
81/E6
R. A.
SCREW AIR COMPRESSOR
A1
81/B2 K4
A2
81/B4
81/B4
C
4
0
A1
X1: 1 2 3 X7: 1 2 X2: 10 11 12 13 14 15 16
SSW
D ELECTRIC BOX FAN
X2: 1 2 3 4 5
81/D4
FIGURE 11 - COMMAND DIAGRAM - SOFT STARTER START SWITCH - 220V - 380V - 440V
81/D4
LAYOUT
A
INSTALLATION
X3
B PE
K4
KP1
A1
C
X2 T1
X4 GROUNDING BAR
EN-83
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
INSTALLATION
Example: Motor’s current 35A (220V) - 35 mm² cable section maximun distance found 266 meters.
WAYS TO INSTALL
WALLS POLES
EN-84
INSTALLATION
5. INSTALLATION OF CAPACITORS
Power Factor Correction
A rational and economic way to obtain the necessary reactive energy for your compressor's proper
operation is the installation of capacitors next to it.
The capacitors installation, however, must be preceded by operational measures that reduce the reactive
energy necessity, as the switching off of motors or other idle inductive loads.
The advantage of the power factor correction is a meaningful voltage improvement.
CARES DURING INSTALLATION OF CAPACITORS
Installation location:
- Avoid sun exposure or installation near high temperature equipment;
- Do not block cabinets' air inlet and outlet;
- Locations must be protected against suspended solid and liquid materials (dust, oil, etc);
- Avoid capacitor installations next to the ceiling (heat);
- Avoid capacitor installations next to non linear loads.
Protection Against Short Circuits
Fuses: Design fuses according to equation: In x 1,65
NOTE: "In" capacitor's plate datum
Use the commercial value of immediately superior retarded type fuse.
Conductors: Use conductors over-designed in 1,43 times the capacitor's nominal current and take into
consideration other criteria such as: the way to install, ambient temperature, etc..
REMARKS: For diagram A connection (Y ) adjust the new current that will go through the relay.
NOTES: The installation of capacitors to correct the power factor shall be made by a certified
professional.
See in Diagram A's and B’s Figures 13 and 14, the proper way to connect capacitors during the
installation of your compressor.
L1 L2 L3
X0 R S T
1 3 5 1 3 5 1 3 5
K1 K2 K3
2 4 6 2 4 6 2 4 6
R S T
1 3 5
1 3 5 1 3 5
KX A1 K4
2 4 6 2 4 6 2 4 6
1 6 F4 F5 F6 U V W
2 M 4
3 3~ 5
FOR CONNECT KX
CONSULT THE NEAREST
TECHNICAL ASSISTANCE
F4 F5 F6
M M2
M
M1
3~ 3~
MAIN MOTOR FAN MOTOR
C1
INSTALLATION
6. AIR DISTRIBUTION
The manufacturer supplies the compressor with a flange (Figure 4, page 76) in the air outlet for the
network. To maximize air delivery to point(s) of use, air distribution piping diameter should be no smaller
than the air outlet diameter.
Do not use air line filters or regulators whose ports are smaller than the air piping diameter. In smaller
systems it is recommended that an air tank (condensed separator) be installed. It should have a
minimum storage capacity that is equal to or greater than 1/5th of the capacity (in gallons per minute or
liters) of the compressor.
Installing a tank in this manner will significantly reduce the interval of the demand fluctuations within the
control system of the compressor.
If SRP 3200 and SRP 3200 SS compressor is properly sized for a facility, the installation of a tank isn't
necessary. However, a good compressed air network design always includes the installation of a tank in
order to cushion control fluctuations caused by erratic air consumption, gather condensed water and to
maintain an adequate air supply during consumption peaks.
We recommend that the installation, at the compressor's outlet, include an auxiliary air outlet with a hose
and nozzle to clean the cooler and other tasks which may require the use of local compressed air.
For more information and guidance in the design of your air distribution system, please consult your
SCHULZ Authorized Service Center.
IMPORTANT
To maintain compressed air quality, do not locate condensed separator, filters or refrigerated dryers in vicinity
of cooling air exhaust stream. (See Figure 15).
8 1 2
www.schulz.com.br
A EMERGÊNCIA
Network
4
PRESSÃO DIFERENCIAL PRESSÃO DIFERENCIAL
DO FILTRO DE ÓLEO DO SEPARADOR
6 7
INSPEÇÃO E MANUTENÇÃO
SEMANAL
SRP 3200
A
Até 27 PSID - Normal Acima de 27 PSID - Providencie a troca
7 1
3 Verifique a temperatura da descarga
Temperatura máxima admitida de 110º C
6
PERIÓDICA
COM O COMPRESSOR DESENERGIZADO
MÁQUINA AUTOMÁTICA
Não efetue manutenção com o equipamento energizado sob risco de acidentes pessoais.
Com as portas abertas este compressor desliga no modo EMERGÊNCIA.
Em caso de dúvidas, consulte o Manual de Instruções ou a Assistência Técnica Autorizada.
005.1920-0
200 hp
5
Electronic
FIGURE 15 - COMPRESSOR’S TYPICAL INSTALLATION WITH ATTACHMENTS FOR COMPRESSED AIR TREATMENT.
Note: Installation expenses and accesories are the customer’s responsability.
If the installation is not made, the service valve and even the compressor will be compromised.
If a piston compressor is connected to the network, it must be separated from the screw compressor by
a pressure vase, unless the network volume between them is big enough.
Connect a water drain hose from the compressor´s water separator to an oil separating well or a
separate container.
We recommend the installation of a bypass (service unit), at the compressed air discharge, with a hose
and blowing nozzle to clean the cooler's core and to perform other services that require local
compressed air.
2
1 - Compressor with air cooler (inside the cabin) 4
2 - Network's water separator
3 - Air supply downpipe
5
4 - Water drain
3 3
5 - Removal of compressor's condensed: to the oil 6
separator container or to a separate container
6 - Service valve
Special installation cares: (for installations without a drier and special filters):
- tube's inclination toward water separators 2 of at least 1:200
- connection of air supply pipes 3 to the main tube's upper side
- provide pipes with water separators 5
- provide water separators for the network 2 with automatic drains and valves
If you are going to equip the compressed air network with treatment devices (such as dryers and special
filters), get in touch with the nearest Schulz Authorized Service Center or export@schulz.com.br.
STORAGE AND
STORAGE AND TRANSPORTATION
TRANSPORTATION
1 - Place a steel beam (of about 1.8m or 70.8 inches ) between the lifting cables.
2 - Place 2 steel beams (of about 2m or 78.7 inches) under the compressor.
EN-87
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
INSTALLATION
FIGURE 17- LIFTING THE COMPRESSOR FIGURE 18- MOVING IT WITH A FORKLIFT
The forklift's forks must be placed under the compressor, according to the direction shown in Figure 18.
WORKING PRINCIPLES
1. AIR END
The main parts of a air end are:
Unit's body 1.
Two screw rotors, 2 and 3, operating on ball bearings on body 1, a discharge flange 4 and a ball bearing cover
6.
The driving shaft is retained by a seal 5.
2. AIR FLOW
When turning on the motor, power is transmitted to the axle of the air end by the electrical motor.
The rotation of the screws creates a vacuum and the air production cycle begins when suction occurs.
The [atmospheric] air flows through filter (item 1) and enters the air end (item 3) [radially] through the
hole located in the inlet control valve (item 2). Air compression [axial] is accomplished as air is forced
between the flutes of the screws (rotors) and the air end housing. Air is then forced through the
discharge port.
12
P1
8
SFS2069-M10X1.25-1
A 6
7 14
P R
P R
4
2
5
9 S1
3
11
10
13
During this start sequence, the air end is lubricated by residual oil. (See Oil Flow description, page 90).
Air suction happens through a small passage area orifice and it does not require the motor's full power to
start (it starts empty), but it allows the fast pressurization of the air/oil tank (item 4) causing, by the action
of the pressure differential, the circulation of lubricant oil (item 5) to the air end.
The compressed air flows inside the separator element [item 6 (6 parts)] dragging with it a small quantity
of oil that, because of the restriction caused by the filtering mesh, loses speed and “falls” at the bottom of
the air/oil separator receiver's second stage (item 7).
At the discharge of the compressing unit, the inlet air, mixed with lubricant oil, is introduced tangentially
and at high velocity into the tank. Here it the centrifugal force separated the [denser] oil from the air. Due
to its density, the oil settles to the bottom of the tank.
WORKING PRINCIPLES
In a few seconds after the start the internal pressure of the tank rises to 3.4 bar to 4.1 bar (50 to 60 psig),
the motor is operating at its' nominal rotation and the air can be introduced and compressed at full
capacity with the inlet control valve (item 2) completely open.
With the inlet control valve totally open and the air being compressed at full capacity, the pressure in the
tank rises rapidly and overcomes the spring tension which maintains closure of the minimum pressure
check valve (item 8) and the air passes through the after-cooler and into the compressed air network.
The minimum pressure valve has the following functions:
A. Operates as a check valve, preventing system air from re-entering the compressor when the
compressor is off or modulated;
B. Maintains minimum pressure of about 3.4 bar (50 psig) to ensure adequate lubrication;
C. Maintains minimum oil pressure to prevent inappropriate oil consumption rate.
3. OIL FLOW
There is a residual quantity of oil present in the air end. This residual oil provides lubrication for the first
few seconds. Once the compressor starts and pressure of around 2.0 bar (30 psig) is achieved in the
separator (item 4), positive pressure on the surface of the oil in the tank (item 4) forces oil into the air end
thereby insuring lubrication.
During the first few minutes of operation the oil will not be heated to its' ideal working temperature (60 to
70ºC or 140 to 158º F). In order to rapidly achieve the desired temperature, the oil circuit has a
thermostatic valve (item 10) with two circulation routes.
Below 80ºC or 176º F, the oil flows into the compressing unit through an oil by-pass (item 11). The
thermostatic valve prevents oil flow through the oil cooler.
The oil warms up quickly from the heat of compression and very quickly reaches the ideal operating
temperature.
At 80ºC or 176ºF the thermal element expands, displacing the piston inside the valve that progressively
opens the oil by-pass and allows oil flow through the oil cooler (item 12).
In addition to rapid warming of the oil the thermostatic valve prevents oil cooling to temperatures below 80ºC
or 176ºF. By regulating oil flow through the cooler and the by-pass, the valve ensures that all of the oil
injected into the air end is at the ideal working temperature. This reduces the condensation of water vapor in
the separator and tank which maintains the quality of the oil and reduces air system contamination.
The oil from the two circulation routes (cooler and by-pass) mixes and is filtered (item 13) before being
injected into the air end.
The oil deposited at the bottom of the separator element is continuously evacuated back to the inlet side
of the air end through the oil return pipe (item 14).
4. COMPRESSOR´S CONTROL HOSES (see Figure 22, page 91)
A. Hose oil return line from air - only separator;
B. Separator element’s restriction indicating hose (input);
C. Solenoid valve’s supply hose and separator element’s (output);
D. Network’s supply hose (pressure sensor);
E. Oil filter’s restriction indicating hose (input);
F. Oil filter’s restriction indicating hose (output);
G. Relief valve’s control hose;
H. Admission valve’s control hose;
I. Pilot valve’s hose of the admission valve’s control;
J. Relief valve’s return hose;
K. Separator element’s restriction (output).
EN-90
WORKING PRINCIPLES
H C
J
I Hot air outlet
P1
D SFS2069-M10X1.25-1
4 G
Network
air outlet
3 A
C A
P R
K
3
P R
B A
5
M2 1
S1
S1 - temperature sensor
F
P1 - pressure sensor
M1 M1 - restriction oil filter pressure gauge
E
M2 - separator differential pressure gauge
SYSTEM CONTROL
Compressor SRP 3200’s and SRP 3200 SS’s Electronic Interface is programmed to carry out controls
according to the nominal pressure shown on the product's identification plate.
CAPTIONS
Remark: P2 and P3 parameters do not have operation function for these compressors.
EN-91
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
SYSTEM CONTROL
2. With the relief valve open, the depressurization of tank (item 5) will start up to the volume aspirated by the
admission valve's by-pass, balancing the air volume drained by the relief valve, thus equalizing the receiver's
pressure between 3,1 and 4,1 bar (45 to 60 psig), necessary to guarantee the system's lubrication, and
reducing power in 50% while in this mode.
3. In this control's phase, the compressor will not produce air to the network. If there is consumption in this
moment, pressure may drop in the system, causing the Electronic Interface to energize the solenoid valve
and the compressor will start compressing again. If the system's pressure remains above P1 for a period of
time longer than the adjusted, the compressor will switch off automatically (see unload time adjustment,
page 101, Table 12).
INSTRUMENT PANEL
EN-92
Electronic Interface
INDEX
Introduction EN-95
Electronic Interface EN-95
Displays EN-95
Keys EN-96
Leds EN-96
Menus and Their Functions EN-97
Navigating Through Menus EN-97
Parameter Change EN-98
Menu’s Features EN-98
Software’s Additional Features EN-109
Structure of Menu EN-109
Electronic Interface Connections EN-112
Digital Input EN-112
Analog Input EN-112
Output Relays EN-113
Electronic Output EN-113
RS 485 Communication EN-113
Electronic Interface Supply EN-113
ELECTRONIC INTERFACE
Electronic Interface
1. Introduction
The purpose of the Electronic Interface is to provide users with the main information about the compressor's
control, to monitor measured magnitude, to protect several compressor's components and to provide
maintenance information. Existing parameters in the Electronic Interface may be changed, according to the
compressor's real use need, in a simple and safe way.
Before making any changes in the Electronic Interface's parameters, read all the manual. Should
! there be any doubt, please get in touch with the nearest Schulz Authorized Service Center.
2. Electronic Interface
In its front panel, the Interface has three displays with lighting (A, B and C), 8 keys and 4 leds, according to the
Figure below:
Leds
0
bar C
A psi B 0
F
Displays
Keys
FIGURE 24
2.1 Displays
Each display presents a specific function, according to the table below:
TABLE 3
EN-95
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
ELECTRONIC INTERFACE
2.2 Keys
Each key has a specific function, according to table below:
KEYS FUNCTIONS
Return (Selects previous parameters in menus and sub-menus).
TABLE 4
2.3 Leds
Each led has a specific function, according to table below:
LED MEANINGS
bar When pressure unit is shown in bar.
psi When pressure unit is shown in psi.
0
C When temperature unit is shown in Celsius degrees.
0
F When temperature unit is shown in Fahrenheit degrees.
TABLE 5
IMPORTANT
The description should in the Interface display, indicated the messages and parameters of the screw
air compressor.
EN-96
ELECTRONIC INTERFACE
Software
Start menu Occurrences Hours Controls General menu
version
Configuration Parameters
Regulating Parameters
Monitoring Parameters
Maintenance Parameters
Digital input
Diagnosis Parameters
test
Analog input
Parameters
test
Analog
setting Parameters
Analog
Parameters
configuration
FIGURE 25
EN-97
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
ELECTRONIC INTERFACE
STATUS MEANINGS
Ready to start Compressor is ready to be turned on.
Standby Compressor will turn on immediately after the minimum "wait" time is over
(set in the monitoring menu).
Starting Compressor has received a start control and is starting.
Partial load Compressor is working at partial load.
Full load Compressor is working at full load.
Unloaded Compressor is working unloaded.
Stopping Compressor has received a stop control and is stopping. In this status, the
compressor starts to unload, pressure begins to decrease and the starting
switch is turned off, as soon as the "Stop" time is over (set in the monitoring
menu).
Wait Compressor is off and can only be turned on again when this time is over.
Remote mode Remote modeCompressor is enabled to work remotely, that is, at distance.
TABLE 6
EN-98
ELECTRONIC INTERFACE
- Protections
PROTECTIONS MEANINGS
Over pressure Switching off due to over pressure.
Over temperature Switching off due to over temperature.
Over Temp. alarm Over temperature alarm.
Inverted phase Compressor's power input phases are inverted, that is, the
(optional) compressing unit rotation is inverted.
Lack of phase Switching off of three-phase supply or lack of phase.
Compressor's motor Compressor's motor overload.
Fan's motor Fan's motor overload.
Emergency Emergency button pressed.
Temp. sensor Problems in temperature sensor or in this signal's reading.
Pressure sensor Problems in pressure sensor or in this signal's reading.
TABLE 7
- Maintenance jobs:
JOBS MEANINGS
Change air filter Time to change air filter.
Change oil filter Time to change oil filter
Check separator Change separator element.
Change oil Time to change oil.
TABLE 8
Remarks: The time to change the oil filter, change the oil and check the separator is directly related to the
hours the compressor has remained on, whereas the time to change the air filter is directly related to the
hours the compressor has worked at full load.
If the hours to carry out maintenance jobs are set similarly for the oil change, oil filter change and separator
element change, the following maintenance job sequence will appear in the starting menu: change oil filter,
change oil and check separator.
To reset maintenance warnings when they appear on the starting screen, you should first update the number
of hours in the Maintenance Menu and press the reset key, in the starting menu, right after it.
In the starting menu, it is also possible to read two temperature measurements, if their respective sensors
are connected. To carry out such reading, press key.
TEMPERATURE
READINGS MEANINGS
MEASUREMENTS
0
T1 Ex: 35 C Shows measured temperature.
0 0
132 C / 269 F No sensor is connected.
0
T2 Ex: 58 C Shows measured temperature.
0 0
132 C / 269 F No sensor is connected.
TABLE 9
EN-99
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
ELECTRONIC INTERFACE
3.3.2 Occurrence menu
The Electronic Interface can memorize the last ten occurrences related to the protection actuations and
maintenance job warnings.
OCCURRENCES MEANINGS
Occurrence nr. 1 Shows occurrence nr. 1
Occurrence nr. 2 Shows occurrence nr. 2
Occurrence nr. 3 Shows occurrence nr. 3
Occurrence nr. 4 Shows occurrence nr. 4
Occurrence nr. 5 Shows occurrence nr. 5
Occurrence nr. 6 Shows occurrence nr. 6
Occurrence nr. 7 Shows occurrence nr. 7
Occurrence nr. 8 Shows occurrence nr. 8
Occurrence nr. 9 Shows occurrence nr. 9
Occurrence nr. 10 Shows occurrence nr. 10
TABLE 10
To accurately know the day and hour when the occurrence happened, select the desired occurrence and
keep key pressed.
PARAMETERS MEANINGS
On Hours the compressor remained on.
Full load Hours the compressor remained at full load.
Partial load No applicable to this version.
Air filter Hours missing to change air filter.
Oil filter Hours missing to change oil filter.
Separator Hours missing to change air/oil separator element.
Change oil Hours missing to change oil.
TABLE 11
Example A
In order to check how many hours are missing for the oil change, do as follows:
Starting menu Current hour, weekday, month and compressor's status will be available in this menu.
Press key.
Press key.
Hours on menu The number of hours the compressor remained on will be shown.
Press key.
Full load The number of hours the compressor remained at full load will be shown (NA).
Press key.
Partial load The number of hours the compressor remained at partial load will be shown.
Air filter The number of hours missing for air filter change will be shown.
Press key.
Oil filter The number of hours missing for oil filter change will be shown.
Press key.
Separator The number of hours missing to check the separator element will be shown.
Press key.
Oil change The number of hours missing for oil change will be shown.
P3 No applicable. P2 P4
P2 No applicable. P1 P3
P1 Pressure minimum level for full load operation. 2,0 bar P2
29 PSI
Unload / off It means the time the compressor will remain unloaded before 0 min 20 min
switching off.
Press. Setting Automatic weekly program of pressure levels, current hour and date.
TABLE 12
EN-101
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
ELECTRONIC INTERFACE
Example B
To change P1 load pressure level, do as follows:
Starting menu Current hour, weekday, month and compressor's status are available in this menu.
Press key.
Press key.
Hours on menu The number of hours the compressor remains on will be shown here.
Press key.
AUT control menu The compressor's control mode will be shown here.
Press key.
Press key.
Press key.
Press key.
Press key.
P1 P1 parameter's value will stop flashing and the change is consequently confirmed.
EN-102
ELECTRONIC INTERFACE
Time/
Load Parameter Mon 06: 30 am 7.0bar
Time/
Mon 05: 30 pm [OFF]
Load Parameter
FIGURE 26
TABLE 13
Remarks:
- It is possible to turn off the compressor locally when start / stop mode is remote;
- It is possible to turn off the compressor at distance when start / stop mode is local.
EN-103
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
ELECTRONIC INTERFACE
Starting menu Current hour, weekday, month and compressor's status are available in this menu.
Press key
Press key
Hours on menu The number of hours the compressor remains on will be shown here.
Press key
AUT control menu The compressor's control mode will be shown here.
Press key
Press key
Press key
Press key
Press key
Press key
Air filter The hours missing to change air filter can be set here.
Press key
"001 Code" The word "code" along with numbers 001 will be shown.
ELECTRONIC INTERFACE
Press key
Air filter The desired value to change air filter will appear.
Air filter The Air Filter parameter's value will stop flashing and the
change is consequently confirmed.
Remark: To return to starting menu, press reset key
3.3.10 Diagnosis Menu
Diagnoses that allow testing the Electronic Interface's different inputs and outputs are available in this menu.
Attention: The Electronic Interface's relays will be activated during the test!
This test can only be carried out with compressor OFF.
EN-106
ELECTRONIC INTERFACE
PARAMETERS FUNCTIONS
Ana. Input 1 The available voltage at analog input 1 is shown on display
Ana. Input 2 The available voltage at analog input 2 is shown on display
Ana. Input 3 The available voltage at analog input 3 is shown on display
Ana. Input 4 The available voltage at analog input 4 is shown on display
TABLE 20
Remark: Value 023 will be shown on the display when the analog input is set for KTY10 sensor and it is not
connected to the Electronic Interface.
PARAMETER FUNCTION
Display test All digits of all displays and leds are on at the same time during this test.
TABLE 21
PARAMETER FUNCTION
Key test When the key is pressed, its respective function is shown on the alphanumeric
display (UP / DOWN / SUB / ADD / ENT / RST / OFF / ON).
Three seconds after checking all keys, the startingl menu will be shown.
TABLE 22
ELECTRONIC INTERFACE
Remark: Should there be any change as to sensor type, check jumpers position as shown below:
2 4 2 4 2 4 2 4
Jumpers
1 3 1 3 1 3 1 3
2 4 2 4 2 4 2 4
1 3 1 3 1 3 1 3
Do not change the analog inputs existing configuration, both in settings and
jumpers shown above, without consulting the nearest Schulz Authorized Service
Center!
ELECTRONIC INTERFACE
General Configuration
Menu Automatic re-turn on
Start / Stop or Load /Remote unload
Compressor No.
Pressure unit
Temperature unit
Language
Regulation
Minimum value
Cte P
Cte I
Monitoring
Operation maximum pressure
Unload maximum pressure
Maximum temperature to switch off
Temperature to alarm
Number of starts/hour
Time of start
Time of commutation
Time to activate solenoid valves
Minimum time unloaded
Stop time
Wait time
Standard adjustment
Enable Date&Hour
Hour Adjustment
Compressor on hours
Full load hours
Partial load hours (NA)
EN-110
ELECTRONIC INTERFACE
Maintenance
Remaining hours to change air filter.
Remaining hours to change oil filter.
Remaining hours to check separator change.
Remaining hours to change oil.
Diagnoses
Digital input test Digital input 1
Digital input 2
Up to digital input 8
Input Configuration
Analog calibration Pressure signal offset
Pressure signal range
Main temperature
Temperature 1 T1
Temperature 2 T2
TABLE 27
EN-111
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
ELECTRONIC INTERFACE
DIGITAL
X01- FUNCTIONS ACTION
INPUT
1 / C+ Digital input supply
= 20Vdc
Input 1 2 / C1 Emergency stop Switching off
Input 2 3 / C2 Compressor's motor overload (note 1) Switching off
Input 3 4 / C3 Fan's motor overload Switching off
Input 4 5 / C4 Inverted phase (optional) Switching off
Input 5 6 / C5 Lack of phase (note 2) Switching off
Input 6 7 / C6 Start/Stop Load/Unload (remote)
Input 7 8 / C7 Remote Mode
Input 8 9 / C8 Not used
TABLE 28
Note 1 - If this failure occurs in the SRP 3200 SS version, please check its status.
Note 2 - Not used in the SRP 3200 SS version.
Start/Stop Local & Load/Unload Local
- Configuration menu:
Ext = On/Off or Load/unload
- Digital Input:
X01-8 = Deactivated.
Start/Stop Local & Load/Unload Remote
- Configuration Menu:
Ext = Load/Unload
- Digital Inputs:
X01-8 = Activated X01-7 determines Load/unload
Start/Stop Remote & Load/Unload Local
- Configuration menu:
Ext = On/Off
- Digital Inputs:
X01-8 = Activated X01-7 determines Start/Stop
ANALOG
X02- FUNCTIONS SIGNAL
INPUT
1 / A+ From 4 to 20mA analog input supply
= 20Vdc
Input 1 2 / A1 Pressure measurement 4-20mA
Input 2 3 / A2 Main temperature measurement (KTY10) Resistance
Input 3 4 / A3 Temperature measurement (KTY10) T1 Resistance
Input 4 5 / A4 Temperature measurement (KTY10) T2 Resistance
6 / A- Ground temperature sensors
TABLE 29
EN-112
ELECTRONIC INTERFACE
IMPORTANT
Refer to Troubleshooting, page 122 as well.
EN-113
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
CONTROL MODE
The Electronic Interface is programmed in the factory to operate automatically, that is: the compressor's
motor will be switched off when the time the compressor remains unloaded is higher than the programmed
time, automatically returning if pressure is lower than P4 value.
The compressor runs at full load getting unloaded as soon as the maximum work pressure is reached.
The P4 unloaded time is adjusted in the factory through the Electronic Interface.
If during this adjusted time there is no consumption to cause a pressure drop, the compressor will switch off,
returning to operate when pressure is lower than parameter P4 adjusted in the Electronic Interface.
The motor can have up to 4 starts per hour, what is not economically viable.
START UP
After all the compressor is installed and connected as per the customers requirements, the compressor
must be started in the presence of a representative of the nearest SCHULZ Authorized Service Center. This
technician will validate the Warranty as required by SCHULZ and will guide the customer on starting
procedures, and provide owner/operator training in the compressor's operation and preventive
maintenance. The compressor's warranty will be validated and the warranty period initiated only a) upon
production of the service report provided by SCHULZ Authorized Service Center during the first start
procedure - one copy of which will remain with the customer and b) the filling in of the Technical Delivery
Log (page 129) which will be sent to the factory by the technician. Instructions contained in item "A" of the
Warranty Terms (page 126), under General Warranty Conditions, must be followed.
START PROCEDURE
SRP 3200’s and SRP 3200 SS’s series compressor is tested in the factory
and supplied with mineral lubricant oil ISO 46.
Before the compressor's initial start, check the re-fasten the
connections of the hydraulic circuit hoses and of the electric
contacts.
1. FIRST START PROCEDURE:
1.1. Open the cabinet's front right door (facing the panel) and check the oil
level, wich must be at the maximum level of the oil level sight (item 1, Figure
35, page 119);
1.2. If the ambient temperature is different from (Table 34, page 118)
specifications, change to screw compressor lubricant oil ISO 32.
1.3. The lack of phase relay LED must be on (showing the three phases in
the compressor’s supply circuit), located in the start switch;
1.4. The Electronic Interface’s display must show the message: “READY to START”. FIGURE 28
1.5. Close the air outlet valve and the doors*;
1.6. Remove the filter(s) and open the admission valve manually. Pour appoximately 1-2 liters (0.94-1.88
QT) of oil, if the compressor has not been used for mode than a month.
1.7. Check Rotation by quickly pressing the Start Key (green) to switch on the compressor and
immediately pressing the emergency stop (red) button, switching the compressor off and observing the
direction of rotation. It must be in the direction indicated by the arrow located in the air end casting
(Figure 28). The rotation of the cooling fan must be checked as well. The correct air flow is toward the
cooler.
Notes: If the rotation is incorrect, disconnect input power from the compressor and interchange two (2)
wires at the disconnect. To reverse fan direction, interchange two (2) wires at contactor K4. Repeat
procedure 1.7.
Unlock the emergency button and press the reset key in the Electronic Interface to cancel message
“EMERGENCY” on the display, which will later show item 1.4's characteristics.
1.8. After making sure that the rotation direction is correct, close the side door and press the Start Key
(green) to run the compressor again, keeping the valve closed until the compressor reaches its
maximum pressure and starts to unload P4. Slowly open the valve and your rotary screw air compressor
is now ready to supply compressed air to the network.
EN-114
START PROCEDURE
IMPORTANT
1- In the start, the motor must not work for more than three seconds (3) with the inverted rotation.
Item “1.7” is accomplished quickly and will be easily observed. In case of problems during the start-
up, consult the Troubleshooting Tips Chapter, page 122.
2- In emergencies, press the emergency button 5 (Figure 23, page 92) that will switch off the
compressor.
3- The emergency button must only be used when the compressor needs to be stopped immediately.
Its use under normal conditions will cause failure in the equipment. This is not covered by the
warranty.
4- In normal operations, use the Stop Key (red) on the instrument panel, where a timed unload will
occur before the compressor stops.
5- * This compressor is equipped with safety sensors at the doors (SW1 and SW2). When opened,
they switch the compressor OFF.
STOP PROCEDURE
1. STOP
1.1. The compressor is programmed to stop, this is regulated in the Electronic Interface.
1.2. Press the Stop Key (red) in the instrument panel [manual stop].
2. EMERGENCY STOP
2.1 The compressor stops when the emergency button is pushed.
2.2 To turn on the compressor again, turn the emergency button clockwise to unlock it. Then, turn the
compressor on in the usual way. An emergency stop is shown in the record of electronic failures. Press
the Reset button before turning the compressor on again.
ADJUST OF MODULATING
1. PILOT VALVE
The pilot valve PS2 is located in the control valve.
1- Open the locking nut (A) of the pilot valve PS2 and tighten the adjusting screw (B) several turns, making
the number of turns. The pilot valve is now out of operation and the pressure range can be adjust.
2- Start the compressor and open the air line to consumption that does not exceed the compressor's output.
3- Adjust the upper and the lower pressure limit, see the manual page 104, Table 15, for the Electronic Interface.
4- Open the pilot valve by the same amount of turns as you tightened it, and tighten the locking nut (A).
5- Start the compressor and check that the intake valve starts closing when the pressure rises above the set
lower limit. As the pressure reaches the set upper limit, the intake valve should still be slightly open. This is
easy to notice as the final closing (last 10 mm or 3/8”) takes place very quickly when the compressor unloads.
6- If the intake valve closes too early, tighten the screw (B) to raise the pressure.
7- If the intake valve does not close steplessly, open the screw (B) to lower the pressure. B
A
Note: When unloading or stopping, the compressor's pneumatic cylinder must
close the intake valve completely.
FIGURE 29
EN-115
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
PREVENTIVE MAINTENANCE
Dispose of the used separator element (6 parts) according to current local norms. Allow
the compressor to cool down before starting the maintenance job.
3.3.1 Removal
1- See Before maintenance procedures.
2- Remove the connector at the top of the output valve. Through the connector opening, fasten a
screw (M8 x 70) to the output valve piston as shown in the Figure 31 page 117. This is to prevent
the valve from coming apart when it is removed.
3- Remove the output valve.
4- Remove the separator element support bolts.
5- Remove the separator elements.
EN-116
PREVENTIVE MAINTENANCE
MANTENIMIENTO PREVENTIVO
3.3.2 Installing
1- Clean the tank sealing surfaces and the output valve.
2- Clean the orifice in the oil return pipe.
3- Clean the oil return pipe screen filter (inside the tank) e.g. by blowing pressurized air through the
connector. Clean the tank as necessary. Check that the conical sleeves in the tank are clean and that
they have no sharp edges.
4- Lubricate the O-rings and install them to the groove in the lower end of the separator element. Install
the new elements in place by hand (See Figures 32 and 33). Check the condition of the separator
element side bold washers. Replace as necessary. Install the side bolts, checking that the notch in the
end of the element is at the screw.
5- Install an output valve sealing kit.
6- Check the condition of the output valve plate sealing and replace is as necessary.
7- Install the valve assembly in place.
8- Tighten the mounting screws evenly.
9- Remove the screw that was installed when dismantling, and install the control pressure connector.
10- Change the setting in the Electronic Interface system to corresponded with the new separator
(recommendation: 6,000 h).
The manitenance procedures are for normal operation conditions. Anticipate the inspections
if the compressor is operating in environments where the working conditions are severe and
the atmosphere contains pollutants. This measure will prevent your compressor from failing,
and will avoid low quality compressed air and the Warranty's cancellation.
CORRECT CORRECT
INCORRECT INCORRECT
EN-117
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
PREVENTIVE MAINTENANCE
Allow the compressor to cool down before starting the job. Dispose of the used filter
according to current local norms.
4.1.1 See page 116, Before maintenance procedures.
4.1.2 Drain the filter housing of oil by opening the drain screw.
4.1.3 Remove the filter housing cover and take out the old filter.
4.1.4 Clean the filter housing.
4.1.5 Install a new filter. Grease the mating surface of the filter.
4.1.6 Install a new O’ring to the filter housing cover and mount the cover into place.
4.1.7 Update the Electronic Interface's control system so that there is correspondence with the new filter
element (recommendation: 1,000h)
Remark: The first change is carried out at 300h of operation.
ISO 46
1 Máx.
Mín.
1. Oil level sight
2. Oil fill in plug
3 3. Oil drain valve
FIGURE 34
OIL FILTER
FIGURE 35
5. QUARTERLY
Clean the cooler.
A clogged cooler increases the compressor's temperature and may cause the compressor to
stop.
5.1 To externally clean the cooler (Figure 36) use compressed air from ouside into its circuit.
For a more complete cleaning, brush its internal surface.
FIGURE 36
EN-119
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
PREVENTIVE MAINTENANCE
IMPORTANT The first element oil filter change must be carried out with 300 operating hours
with subsequent changes every 1,000 hours (on the Electronic units, this
interval is indicated on the display).
11. SERVICE LOG (schedule)
Following any maintenance to your equipment, always fill in the Service Log on page 127.
NOTES:
Do not clean and reuse filter elements if the number of accumulated operating hours exeeds the
prescribed maintenance interval (as indicated either on the Electronic Interface display or in this
Manual.)
EN-120
PREVENTIVE MAINTENANCE
DAILLY WEEKLY EVERY 1,000 h EVERY 3,000 h EVERY 6,000 h ANNUALLY WHEN
PROCEDURE REQUIRED
CHECK FAILURE INDICATING LIGHTS
CHECK OIL LEVEL (1)
CHANGE OIL (80 LITERS/84.8 QT)
REPLACE OIL FILTER ELEMENT
REPLACE AIR/OIL SEPARATOR ELEMENT (6 PARTS) (6)
CHECK SEPARATOR ELEMENT RESTRICTION (3)
CHECK OIL FILTER RESTRICTION (4)
REPLACE AIR FILTER
CLEAN COOLER EXTERNALLY (5)
CHECK OIL LEAKAGE
CHECK SAFETY VALVE
CLEANING OF THE SRP 3200 SS ELECTRIC
BOX FILTER
CHECK HOSES' CONDITION
FASTEN CONNECTIONS AND SCREWS (5)
CHECK AND FASTEN THE ELECTRIC SWITCH
CONNECTIONS
CLEAN COMPRESSOR
CHECK MOTOR'S BEARINGS (ACCORDING
TO ITS INSTRUCTION MANUAL)
TABLE 35
Routine maintenance can be performed by the end user, but any additional maintenance should be carried
out by a representative of the nearest SCHULZ Authorized Service Center.
Operating conditions and demands on the machine may dictate a modification of the maintenance
intercal(s). Maintenance intervals must be reduced to 50% in high demand situations or contaminated
environments. Consult with your SCHULZ Authorized Service Center for additional information as failure to
follow these recommendations may cause damage to the compressor and void the Warranty.
IMPORTANT
(1) Check the oil level when the compressor is not running (wait until the air and the oil are separated and that the
bubbles (foam) are eliminated, in order to get an accurate oil level checking).
(2) The first time at 300 hours.
(3) Pressure difference on separator element.
(4) Pressure difference on oil filter.
(5) Quarterly.
(6) Change Every 6,000 Hours (1 year) whichever occurs first.
MAINTENANCE PARTS
In order to maintain your warranty and maximize serviceability, your Schulz compressor needs routine
maintenance (as outlined in the Preventive Maintenance chapter).
The following table shows the parts and code of the maintenance materials that should be purchased from
your SCHULZ Authorized Service Center.
Code Denomination
- Lubricant mineral oil
007.0179-0 Air filter (2 parts)
85062259 Oil filter element
007.0162-0 Air/oil separator element (6 parts)
007.0176-0 Filter box fan’s (2 parts) - SRP 3200 SS
TABLE 36
EN-121
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
FIGURE 38
OIL CONSUMPTION
Oil consumption may be increased due to any of the following conditions:
1.Excess temperature during operation. If temperature is consistently above 90 ºC or 194 ºF, reduce the
normal oil change interval to 500 hours. (or 50% of recommended life expectancy);
2. If air/oil separator elements are clogged;
3. If there is varnish formation: it affects cooling and oil separation. Varnish formation (oil oxidation) can be
seen, in metal levels, as a brown varnish/lacquer layer.
Note: We suggest not to change the oil type because there might be contamination caused
by chemical incompatibility, decreasing the oil's lifetime and causing lubrication problems.
CORRECTIVE MAINTENANCE
In order to guarantee the product's SAFETY and RELIABILITY, repairs, maintenance and
adjustments must be carried out with original parts by your nearest SCHULZ AUTHORIZED
SERVICE CENTER.
TROUBLESHOOTING TIPS
Listed below are a number of malfunctions/difficulties that may be encountered which may cause the
compressor to operate incorrectly or to stop operating completely.
Many simple procedures, designed to solve problems, are offered to the operator through the Electronic
Interface display. These are valid corrective measures that can be attempted without the need for
specialized technical assistance.
However, should the problem persist after having tried the established corrective actions, please contact the
nearest SCHULZ Authorized Service Center.
EN-122
TROUBLESHOOTING TIPS
Air/oil separator element clogged. Change air/oil separator element and the oil
(see Table 34, page 118).
SRP 3200 SS Soft Starter is not ready Identify cause and consult Instruction Manual.
Compressor switches off to start.
and doesn't re-start even High temperature. Check oil level and fill as needed
with low network pressure. (Compressor may be supplied with (see Table 34, page 118).
temperature sensor that will inform
the Electronic Interface of problem). Check fan (propeller) for breakage.
Replace if necessary.
EN-123
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
TROUBLESHOOTING TIPS
Power loss in the command. Look for the cause according to diagram.
Fan motor coil burnt. Check if fan (propeller) is not broken.
Compressor lost output Air filter clogged. Check the air filter condition, replace if
suddenly. necessary (Figure 37 page 120).
Pressure in the air
network is very low. System pressure gauge hose is Connect hose or replace it.
disconnected or leaking
Note: (Look for air leakage noise).
Before taking any action Solenoid valve coil burnt or with
on the following discrepancy, Call technical assistance.
orifice clogged .
read the "remarks" at the
end of this chapter and on Hose feeding solenoid valve is torn
or disconnected. Reconect or repair hose.
the Electronic Interface
display. Air leakage in some of the
compressor's ducts. Repair leakage.
Air consumption much lower than Switch off some parallel compressor
compressor's production capacity. or install larger tank.
Compressor with very Discharge valve closed. Open the valve slowly.
fast load/unload cycles. (in this case, pressure in the network
is very low).
High load loss near compressor. Eliminate load loss.
Excess oil in tank Remove excess oil .
Oil by pass to system. Compressor's oil foaming. Load and unload cycle is fast.
Separator element compromised. Replace separator element.
EN-124
TROUBLESHOOTING TIPS
Compressor operating too much Check your air network consumption pattern.
Too much water in above the system capacity. If the problem is not solved, call technical
air/oil receiver. assistance.
REMARKS
If there is a pressure drop or a low pressure condition in the air network, monitor the compressor
operation for the following:
Before assuming a compressor malfunction, slowly close the discharge valve until closed and
observe the length of time required to pressurize the compressor and monitor the motor's electrical
consumption.
If the compressor pressurizes normally, and the pressure shown on the display of the compressor's
Electronic Interface is high and yet the system in the facility remains low when the valve is opened,
there is a in all likelihood a blockage in the system. (i.e. a freezing problem with the refrigerated dryer
of a clogged filter) significant air loss in the air network.
If the pressure in the compressor drops immediately with the opening of the valve and the
compressor cannot maintain pressure then there is either a significant air loss in the network (i.e.
stuck solenoid valve in regenerative dryer or faulty float drain in filter) or demand has increased due
to a recent equipment installation. In this case, the necessary air demand is higher than production.
If the compressor is compressing air at full load and the electrical consumption is within normal
limits, the problem may not be the compressor itself.
In any case, if a situation is not resolved through the use of the troubleshooting guide, consult your
SCHULZ Authorized Service Center.
EN-125
SCREW AIR COMPRESSOR SRP 3200 SRP 3200 SS
WARRANTY TERMS
Schulz S.A., within the limits of these terms, does grant this product's first buyer/end user a warranty against any material
or manufacturing defect in the air end for a period of 2 (two) years from date of purchase invoice (or warranty registration
by SCHULZ Authorized Service Center) if and only if the with the following conditions are met:
A. The 1,000 (one thousand) hour period for lubricant oil change is respected (air end).
B. Only approved lubricoolant and original SCHULZ repair/maintenance parts are used.
C. The compressor is not operated without air filter or with such a damaged one that effective filtration is lost, or with
the air/oil separator element showing restriction on the panel in excess of recommended maintenance interval.(air
end).
D. The remaining components of the compressor are warranted against manufacturing defects for a period of 1 (one)
year (Including the legal warranty period first 90 [ninety] days), from date of original purchase or warranty registration
by SCHULZ Authorized Service Center.
GENERAL WARRANTY CONDITIONS
A. This warranty shall only be considered valid if the start-up is performed and registered by your SCHULZ Authorized
Service Centers and the presentation, to SCHULZ S.A. of the Technical Service Report and the Technical Delivery Log.
B. SCHULZ assumes no liability for lost production due to equipment malfunction.
C. No warranty service will be performed without the original purchase documentation.
D. Wearing parts, such as the ones below, which are naturally worn out by regular use and that are affected by the
installation and the way the product is used are excluded from this warranty: air filter, oil filter, valves, hoses, bearings,
oil seal, oil level sight, valves, belt, electric components, electronic sensors, air end coupling, electric motor fan,
sensors at the doors, electronic interface, separators elements and lubricant oil. Schulz S.A. will only assume
responsibility for the servicing expenses of the above mentioned parts after evaluation by Schulz S.A. factory personnel
and the identification of manufacturing defects.
E. This warranty will not apply to cleaning and installation services, roller bearings re-lubrication, adjustments requested
by customer, change of lubricant oil and filters, nor to any damage caused to the product's external parts or damage in
general due to incorrect use, neglect, modifications, external agents, use of improper attachments, inappropriate sizing
for the application, shipping or delivery damage, physical modification (not authorized by SCHULZ S.A.), use not in
accordance with this instruction manual, inadequate electrical conductors, wrong voltage electrical connections or
installation in a system subject to excessive voltage fluctuations.
F. Schulz S.A. warrants the electric motor and the electric switch to the extent that these items are warranted by their
manufacturers. Said manufacturers and SCHULZ S.A. reserve the right to subject failed components to the
manufacturers' evaluation. Defects resulting from installation errors are not covered by this warranty.
G. The warranty of the Electronic Interface and sensors shall only apply if they have not been violated. The warranty will
not cover parameter modifications of the Electronic Interface when performed by unauthorized persons. Therefore,
compressor failures, stops, damage or production losses resulting from such procedures are not the responsibility of
SCHULZ S.A. or the component manufacturer.
H. The input voltage to the compressor must be maintained within a variation of ± 10% (Electronic Interface).
I. Schulz S.A. warrants that parts availability will be maintained (at SCHULZ AUTHORIZED SERVICE CENTER) for a
period not less than 5 (five) years from the last date of manufacture of a specific compressor model.
WARRANTY TERMINATION
This warranty will be considered void in the following situations:
A. At the end of its warranty period.
B. When the product is delivered for servicing to unauthorized shops.
C. When signs of modification are noted.
D. When maintenance has not been performed to SCHULZ standards or repair parts used are not SCHULZ original
parts.
WARNINGS
A. This compressor is supplied according to the customer's technical specifications at the time of ordering. It has
specific displacement, pressure and voltage characteristics that cannot be changed, modified or altered in any way.
B. Lubrication of your rotary screw air compressor is fundamental. Maintenance of proper lubricoolant levels is
paramount and has been discussed numerous times in this manual.
C. Expenses related to the servicing of the compressor which are judged to be outside the warranty parameters are the
customer's responsibility.
D. Dealers, representatives or Schulz Authorized Service Centers are not authorized to change these terms or to
assume responsibilities on behalf of SCHULZ S.A..
E. Figures are intended to show component flow and orientation only and are not intended to be a specification
drawing. Specification figures are available upon request from SCHULZ S.A. only.
F. The SCHULZ technician will provide service on a first come first served basis.
G.This SCHULZ product is supplied with tracking control of its components.
EN-126
Note: Schulz S.A. reserves the right to make changes to these warranty policies without prior notice.
SERVICE LOG
The purpose of this card is to provide a centralized location for the documentation of all service and
maintenance performed on your compressor.
Careful maintenance of this record will help you to track equipment maintenance intervals and expenses, as
well as schedule routine maintenance.
To facilitate accuracy and expedience when requesting services or materials, please have your
compressor's model number, serial number and the service log available.
______/______/______
Optional equipment
NOTES
EN-127
EN-128
Services:
Working Ambient Compressor’s (Oil change, filter element
Date temperature change, re-fastening of Remark Signature
hours temperature
electrical connections, etc.)
SERVICE LOG
SCREW AIR COMPRESSOR
SRP 3200 SRP 3200 SS
TECHNICAL DELIVERY LOG
PRODUCT
Compressor model Series nº Air end model Pressure (bar) Voltage
SRP Series nº
DATE SCHULZ AUTHORIZED SERVICE CENTER
DISTRIBUTOR/DEALER
Name
Address
COSTUMER
Name
Address
INSTALLATION
With air treatment unit Brand Model
YES NO
With additional tank Capacity (liters) Housed with cover
YES NO Nº Serie YES NO
It has
Pre-filter Post-filter Adsorbent filter Automatic drain Others
COMMAND TYPE
FIRST START
Electronic network 2
Cable section mm or AWG
Adequate Inadequate
Only neutral
It has grounding YES NO Input cable distance m or inch
Check
Owner/Responsible Technician
EN-130
025.0508-0
JULIO/JULY/04
P E Ç A S R I G I N A I S
INFORMACIÓN TÉCNICA
R u a D o n a Fr a n c i s c a , 6 9 0 1
TECHNICAL INFORMATION
Fo n e ( 5 5 ) ( 4 7 ) 4 5 1 60 0 0 Fa x ( 5 5 ) ( 4 7 ) 4 5 1 6 0 5 5
export@schulz.com.br CEP 89219 000 JOINVILLE SC BRASIL
schulz@schulz.com.br
w w w. s c h u l z . c o m . b r