Track isolation Issue verification Report:-

Case-1

1. All track isolation, signal block, & Point block have been removed. As of now Except
T115B, T117B & T119B rest all are in drop condition (ref. pic a).

2. Verified in FRVD T115BISLS -SET &


T116BISLS- SET, Meanwhile normally
track isolation bit is set.

3. Applied track isolation in T118B-


T118BISLS –CLEAR, but could not reset
the isolation. In log it is observed that
T118BISLRSZ BIT is set but
L_T118BISLRSEN bit is not getting set.
Same checked on T119B &T120B
observation remains same.

Pic (a)

4. Simulated same scenario in T112B no any issue observed after resetting of isolation ,
T112BISLRSZ & T112BISLRSEN bit are getting set & isolation removed
5. As of now T118B, T119B & T120B are in isolation Condition.

Case-2 Uploaded logic after removing N_EMNP bit in T115BISLS & T116BISLS

1. After uploading logic in MlK B , MLK A & MLK B restarted.


2. Track isolation flashing indication appear on ATS at the same time we have verified into
FRVD no any track was Isolated in IXL.
3. Applied Isolation in T117B,T115B & T116B corresponding ISLS bit were set but Could not
reset the isolation .Restarted MLK then isolation removed ,as of now all tracks isolation
have been removed from all the tracks.
4. Restarted MLKA & MLK B & observed that no any track isolation indication appear on ATS
as well as IXL.

Case -3

1. As up to know it is observed after restarting of IXL no any Isolation applied & same confirmed in
IXL LOG.

2.Again Isolation Applied by me & tried to reset the isolation but could not happened so restarted
MLK B then corresponding track isolation flashing indication appeared & it is removed by simply
applying track isolation reset command only at that time no any acknowledgement tick mark were
appeared.

Conclusion:-

1. We have checked multiple times no any track isolation applied when MLK restarted. (In all the
condition whether track is drop or pickup)

2. Isolation applied only when we apply the isolation, in log it is confirmed that ISLRSZ bit is
getting SET after applying track isolation reset but ACKNOWLEDGEMENT bit (L_TXXXXISLRSEN) is
not getting set & on operator request stack (ATS ) Showing CLASS 1 COMMAND IS IN PROGRESS
FOR THIS DEVICE.Due to this track isolation reset is not functioning in T115B, T116B, T117B, T118B,
T119B & T120B.As per my understanding we will have to verify L_TXXXXISLRSEN path.