0CZH9-02B
Replace 0CZH9-01B
General Description
Ventilation is a process by which one can exchange indoor air to outdoor air in order to improve the air quality
and to maintain environmental temperature conditions.
LG’s heat recovery ventilation system, , modulates the temperature and humidity of incoming fresh air to
match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cool-
ing or heating load placed on the air conditioning system to be reduced significantly. can be controlled
individually or integral with the air conditioning system.
provides efficiency, cost savings, superior performance, compact & light design, linear E.S.P control
ensuring vaious design of duct system and easy maintenance. Units are ideal for hotels, dormitories, restau-
rants, hospitals, retail establishments, theaters, schools, and office buildings.
A lot of information regarding the design & installation of this system is provided in this publication. The new
products series contains data on the same pattern. Please utilize all the information for conducting your busi-
ness efficiently. Make sure the specification, dimension or others technical data are same as provided in engi-
neering data book before you start the project.
LG Electronics Inc.
Air Conditioning Division
1
2
LG Airconditioners Product Data
Table of contents
Table of contents Page
3
1. Models List
[60Hz]
4
2. Model Number Nomenclature
L Z - H 0 8 0 2 B A 0
Development Sequence
Function
A : Basic
Model Type
B : Ceiling Concealed Type
Capacity
Ex) 080 -> 800 CMH 100 -> 1000 CMH
5
3. Features & Benefits
6
3. Features & Benefits
30˚C EA SA EA 25%
o 27˚C o
30 C 30 C Saving Energy
26˚C OA 26˚C
In order to ventilate the indoor air is When using the enthalpy heat
to open the window in summer. exchanger,it maintains the
While opening the window, the temperature and humidity of the
conditioned indoor air goes out. indoor and changes the polluted
Indoor air has to be cooling again. indoor air to the fresh outdoor air.
• Comparing to Enthalpy heat exchange ventilation with the window ventilation,Enthalpy heat exchange enables
to economize a electric bill.It also helps the environmental protection due to saving energy.
• The Enthalpy Heat Exchanger consists of Mechanism which is exchanged to the temperature heat
(temperatures)as well as the latent heat (moisture heat capacity).When it calculates at the electric heat
frequency quantity,it has an energy recovery effect above 3 times than the temperature heat.
7
3. Features & Benefits
EA(Exhaust Air)
OA(Outdoor Air)
SA(Supply Air)
RA(Return Air)
• Like appearing from the picture of the case only of the temperature heat exchange,the efficiency is high.
But when it calculates at enthalpy heat frequency quantity,it has a difference above 3 times.
Others LG
8
3. Features & Benefits
Deodorization Filter
(Option)
High performance Filter
2 4 6 8 10 12
9
3. Features & Benefits
Auto Operation :
- Automatically switches the ventilation mode (Total Heat Exchange Mode/Bypass Mode) according to the oper-
ating status of the air conditioner.
Damper
Damper
Exhaust Exhaust
Return air Return
air air air
Flexibility of Installation :
- Possibility of opposite installation of up and lower part
Case of the installation of 2 units, generally it is necessary to two maintenance spaces. If it is installed oppo-
site one unit of up and lower part, it is necessary to one maintencnce space.
(1500/2000 CMH models are not available.)
Maintenance
space
Installation of 2 units
Top Low
Opposite Installation of up and
Opposite installation of lower part of one unit
Low Top
up and lower part
10
3. Features & Benefits
88.2dB(A) 42.9dB(A)
Air Filter :
Collection Efficiency(%)
100
80
60
40
20
Polyethylene
0
0 10 20 30 40 50 60 70 80
Dust Feed(g)
- Air filter has sufficient effects with collection efficiency above 80%, which is 0.3µm sample particle smaller than
tobacco of smoke. It is even against floating particle from yellow sand.
- Few pressure loss in the static pressure plan.
- Excellent washing characteristic and durability.
250
External static pressure[pa]
200
150
100
50
0
600 700 800 900 1000 1100
3
Air Volume[m /h] Media : Poly propylene
Frame : Paper
11
3. Features & Benefits
LCD Wired Remote Control : (Accessory) EXTERNAL VENTILATOR OPERATION SUB FUNCTION
Linked Run Auto SHi Heater Preheat
Auto Hi
- It can control all the functions of the unit. You can Dual Remote
Central Run Heat XCH Auto Normal
Lo
Fan Speed
Defrost Humidify
ZONE
PLASMA e-SAVER fresh Delay Time Filter Time 1234
Timer Program set Sun Mon Tue Wed Thu Fri Sat
check and change operation mode, set timer & also On Off
Set no. Timer
Plasma
Set/Clr
Timer Cancel
fresh Auto
Plasma
Set/Clr
one Central Room. For Setting Temperature, Fan Sub Sub Sub Sub Sub Sub
speed and other sub functions, access the LCD 1 2 16 17 18 128
wired remote controller of each unit.
12
3. Features & Benefits
Ethernet
Remote
Controller
LGAP Central
Control System
Remote
Controller
13
4. Specifications
4.1 50Hz
Item Unit LZ-H0106BA0 LZ-H0156BA0 LZ-H0256BA0
Nominal Capacity CMH(CFM) 100(59) 150(88) 250(147)
Power Supply Ø,V,Hz 1, 220~240, 50 1, 220~240, 50 1, 220~240, 50
Step - S-HIGH / HIGH / LOW S-HIGH / HIGH / LOW S-HIGH / HIGH / LOW
Current SH/H/L Amps 0.32/0.3/0.28 0.36/0.36/0.35 0.55/0.5/0.34
Power Input SH/H/L W 68/60/50 83/80/78 130/115/80
Air Flow SH/H/L CMH(CFM) 100/100/90(59/59/53) 150/150/100(88/88/59) 250/250/180(147/147/106)
eco-V Mode
Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. : Refer to dimensional drawings.
*
14
4. Specifications
Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. : Refer to dimensional drawings.
*
15
4. Specifications
Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. : Refer to dimensional drawings.
*
16
4. Specifications
4.2 60Hz
Item Unit LZ-H0102BA0 LZ-H0152BA0 LZ-H0252BA0
Nominal Capacity CMH(CFM) 100(59) 150(88) 250(147)
Power Supply Ø,V,Hz 1, 220, 60 1, 220, 60 1, 220, 60
Step - S-HIGH / HIGH / LOW S-HIGH / HIGH / LOW S-HIGH / HIGH / LOW
Current SH/H/L Amps 0.45/0.41/0.39 0.5/0.48/0.42 0.65/0.60/0.36
Power Input SH/H/L W 76/64/60 100/95/77 140/130/80
Air Flow SH/H/L CMH(CFM) 100/100/70(59/59/41) 150/150/90(88/88/53) 250/250/150(147/147/88)
eco-V Mode
Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. : Refer to dimensional drawings.
*
17
4. Specifications
Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. : Refer to dimensional drawings.
*
18
4. Specifications
Notes:
1. eco-V mode : Total Heat Recovery Ventilation mode
2. : Refer to dimensional drawings.
*
19
5. Characteristic Curve
[Ventilation] [Efficiency]
150 90
Exchange efficiency[%]
Temperature exchanger efficiency
External static pressure[Pa]
(Sensible Efficiency) )
80
100
50 High
60
Low Enthalpy exchanger efficiency
(Total Efficiency Cooling)
0 50
0 50 100 150 0 20 40 60 80 100 120 140 160 180 200
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
150 90
Exchange efficiency[%]
80 (Sensible Efficiency)
100
Enthalpy exchanger efficiency
70 (Sensible Efficiency Heating)
High Super-High
50
Low 60
[Ventilation] [Efficiency]
90
200
Temperature exchanger efficiency
Exchange efficiency[%]
External static pressure[Pa]
(Sensible Efficiency)
80
150
Super-High
70 Enthalpy exchanger efficiency
100 (Sensible Efficiency Heating)
High
50 Low 60
20
5. Characteristic Curve
[Ventilation] [Efficiency]
90
200
Exchange efficiency[%]
External static pressure[Pa]
(Sensible Efficiency)
80
150
Super-High
50 Low 60
[Ventilation] [Efficiency]
300 100
200
80 Enthalpy exchanger efficiency
(Sensible Efficiency Heating)
150 Super-High
High 70
100
Enthalpy exchanger efficiency
60 (Total Efficiency Cooling)
50 Low
0 50
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
300 100
90
External static pressure[Pa]
(Sensible Efficiency)
200
80 Enthalpy exchanger efficiency
150 (Sensible Efficiency Heating)
70
100
Enthalpy exchanger efficiency
Super-High (Total Efficiency Cooling)
60
50
Low High
0 50
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400
Air Volume[m3/h] Air Volume[m3/h]
21
5. Characteristic Curve
[Ventilation] [Efficiency]
400 90
Tem
p
350 efficie erature
Exchange efficiency[%]
ncy exch
External static pressure[Pa]
a nge
300 80 Enth
alpy
exch
Super High ange
250 Enth efficie
alpy ncy(H
exch eatin
70 ange g)
200 efficie
High ncy(C
oolin
150 g)
Low 60
100
50
0 50
0 100 200 300 400 500 600 0 100 200 300 400 500 600 700
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
450 90
400 Tem
p
efficie erature
Exchange efficiency[%]
a nge
80 Enth
300 alpy
exch
ange
Super High Enth efficie
250 alpy ncy(H
exch eatin
70 ange g)
200 efficie
High ncy(C
oolin
150 g)
100 Low 60
50
0
50
0 100 200 300 400 500 0 100 200 300 400 500 600 700
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
400 90
350 Tem
p
efficie erature
Exchange efficiency[%]
ncy exch
External static pressure[Pa]
300 a nge
80 Enth
alpy
exch
250 ange
Super High Enth efficie
alpy ncy(H
exch eatin
200 70 ange g)
efficie
ncy(C
oolin
150 g)
High
100 60
Low
50
0 50
0 100 200 300 400 500 600 0 100 200 300 400 500 600 700
Air Volume[m3/h] Air Volume[m3/h]
22
5. Characteristic Curve
[Ventilation] [Efficiency]
400 90
350 Tem
p
efficie erature
Exchange efficiency[%]
ncy exch
External static pressure[Pa]
300 a nge
80 Enth
alpy
exch
250 Super High ange
Enth efficie
High alpy ncy(H
exch eatin
200 70 ange g)
efficie
ncy(C
150 Low oolin
g)
100 60
50
0 50
0 100 200 300 400 500 600 0 100 200 300 400 500 600 700
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
400 90
350 Tem
p
efficie erature
Exchange efficiency[%]
ncy exch
External static pressure[Pa]
300 a nge
Super High 80 Enth
alpy
exch
250 ange
High Enth efficie
alpy ncy(H
exch eatin
200 70 ange g)
efficie
ncy(C
Low oolin
150 g)
100 60
50
0 50
0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
700 90
Tem
p
600 efficie erature
Exchange efficiency[%]
ncy exch
External static pressure[Pa]
a nge
80 Enth
500 alpy
exch
Super High ange
High Enth efficie
400 alpy ncy(H
exch eatin
70 ange g)
efficie
300 Low ncy(C
oolin
g)
200
60
100
0 50
0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700
Air Volume[m3/h] Air Volume[m3/h]
23
5. Characteristic Curve
400 90
Tem
350 effic perature
Exchange efficiency[%]
ienc exch
y
External static pressure[Pa]
ange
300 80 Enth
alpy
exch
250 Enth ange
alpy efficie
Super High exch ncy(H
ange eatin
200 70 effic g)
ienc
y(Co
150 oling
Low High )
100 60
50
0 50
0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700
3
Air Volume[m /h] Air Volume[m3/h]
[ Ventilation] [Efficiency]
500 90
450 Tem
p
efficie erature
Exchange efficiency[%]
ncy exch
External static pressure[Pa]
400 a
80 nge
Enth
350 alpy
exch
ange
300 Enth efficie
alpy ncy(H
Super High exch eatin
250 70 ange g)
efficie
ncy(C
200 oolin
High g)
150
Low 60
100
50
0 50
0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
500 90
Tem
p
effic erature
En ienc exch
y
Exchange efficiency[%]
tha an ge
400 lpy
External static pressure[Pa]
80 exc
han
ge
Super High effi
300 En cie
tha ncy
lpy (He
70 exc atin
High ha g)
Low ng
200 ee
ffic
ien
cy(
Co
60 olin
100 g)
0 50
0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200
Air Volume[m3/h] Air Volume[m3/h]
24
5. Characteristic Curve
[Ventilation] [Efficiency]
500 90
Tem
effic peratur
ienc e ex
y cha
Exchange efficiency[%]
400 En nge
External static pressure[Pa]
tha
80 lpy
Super High exc
han
ge
effi
300 High cie
ncy
Low En (He
70 tha atin
lpy g)
exc
200 han
ge
effi
cie
ncy
60 (Co
100 olin
g)
0 50
0 200 400 600 800 1000 1200 1400 0 200 400 600 800 1000 1200 1400
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
500 90
Tem
effic peratu
ienc re e
y xcha
Exchange efficiency[%]
400 En nge
External static pressure[Pa]
tha
80 lpy
Super High exc
han
ge
effi
300 High cie
ncy
Low En (He
70 tha atin
lpy g)
exc
200 han
ge
effi
cie
ncy
60 (Co
100 olin
g)
0 50
0 200 400 600 800 1000 1200 1400 0 200 400 600 800 1000 1200 1400
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
500 90
Tem
effic peratu
Exchange efficiency[%]
ienc re e
400 y xch
External static pressure[Pa]
En a nge
80 tha
lpy
exc
ha
ng
300 ee
ffic
ien
Super High En cy(
??
70 tha He
lpy atin
e xch g)
200 ang
High?
ee
ffic
ien
60 cy(
Co
100 Low
?
olin
g)
0 50
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
Air Volume[m3/h] Air Volume[m3/h]
25
5. Characteristic Curve
[Ventilation] [Efficiency]
500 90
Tem
p
400 effic erature
External static pressure[Pa]
ienc exch
Exchange efficiency[%]
80 y ang
Ent e
Super High halp
y ex
300 cha
nge
effic
ienc
High 70 y(H
En eat
tha ing)
200 lpy
Low exc
han
g ee
ffic
60 ien
100 cy(
Co
olin
g)
0 50
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
Air Volume[m3/h] Air Volume[m3/h]
[Ventilation] [Efficiency]
500 90
Tem
effic peratur
Exchange efficiency[%]
ienc e ex
External static pressure[Pa]
400 y chan
80 ge
Ent
halp
Super High ye
xch
300 ang
ee
fficie
70 ncy
High En (He
tha atin
lpy g)
200 exc
han
Low ge
effi
60 cie
ncy
100 (Co
olin
g )
0 50
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
Air Volume[m3/h] Air Volume[m3/h]
26
6. Dimensional Drawings
A J
G
H
Suspension Fixture
Control Box
Blower for
supplying air
L
EA SA
Total Heat Exchanger
Air Filter
K
B
E
OA RA
D F
C
Unit: mm
Pitch of Suspension
Model Figure Nominal Duct Connection Flange Duct Pitch Weight
Fixture
Diameter
A B C D E F G H J K L (kg)
LZ-H0102BA0
LZ-H0106BA0
590 590 204 504 624.2 64 100 97.5 160 90 402 93 23
LZ-H0152BA0
LZ-H0156BA0
27
6. Dimensional Drawingss
A J
H
Maintenance Cover Control Box
Suspension Fixture
L
EA RA
OA SA
F
D C
Unit: mm
Pitch of Suspension
Model Figure Nominal Duct Connection Flange Duct Pitch Weight
Fixture
Diameter
A B C D E F G H J K L (kg)
LZ-H0252BA0
LZ-H0256BA0 640 596 320 568 636.2 55 150 140 160 70 430 84 24
28
6. Dimensional Drawings
EA RA
OA SA
50
Blower for
supplying air
150~250
Control Box
600
Suspension Fixture
Air Filter
Unit: mm
Pitch of Suspension
Model Figure Nominal Duct Connection Flange Duct Pitch Weight
Fixture
Diameter
A B C D E F G H J K L (kg)
LZ-H0356BA0
1013.6 988.2 271.6 938.8 1024.8 5.8 200 194 252 95.8 590 198 38
LZ-H0352BA0
LZ-H0506BA0
1013.6 988.2 271.6 938.8 1024.8 5.8 200 194 252 95.8 590 198 45
LZ-H0502BA0
29
6. Dimensional Drawings
EA RA
OA SA
50
Blower for
supplying air
150~250
Control Box
600
Suspension Fixture
Air Filter
Unit: mm
Pitch of Suspension
Model Figure Nominal Duct Connection Flange Duct Pitch Weight
Fixture
Diameter
A B C D E F G H J K L (kg)
LZ-H0356BA1
LZ-H0352BA1
1013.6 988.2 271.6 938.8 1024.8 5.8 200 194 252 95.8 590 198 35
LZ-H0506BA1
LZ-H0502BA1
30
6. Dimensional Drawings
RA
EA
SA
Blower for
OA supplying air
Longer than 600
Control Box
Total Heat Exchanger
Air Filter Maintenance Maintenance Cover
High Efficiency Filter space
Blower
Maintenance space
Suspension Fixture
Air Filter
Unit: mm
Pitch of Suspension
Model Figure Nominal Duct Connection Flange Duct Pitch Weight
Fixture
Diameter
LZ-H080*BA0 A B C D E F G H J K L (kg)
LZ-H100*BA0 1062 1140 365 987 1176 52 250 242 253 98 513 481 63
31
6. Dimensional Drawings
RA
O
EA
B
E
SA
N
OA
H2 A J
C
K
L
Unit: mm
Pitch of Suspension
Model Figure Duct Connection Flange Weight
Fixture
LZ-H150*BA0 A B C D E F G H J K L (kg)
LZ-H200*BA0 1312 1140 730 987 1176 52 242 253 98 340 350 138
32
7. Wiring Diagrams
33
7. Wiring Diagrams
34
7. Wiring Diagrams
35
7. Wiring Diagrams
36
8. External Static Pressure Settings
By setting a phase value of motor, you can control the air volume.
2. Select the Air volume mode which you want by pressing [ ] Timer
On Off
Set no. Timer
Program set Sun Mon Tue Wed Thu Fri Sat
button.
Phase value Cipher
3. Set up the phase value by pressing [ ] button until it Exhaust air
comes to the target value.
4. If you simultaneously press [timer, ] button for more than 3
seconds again, setting up completes.
You can set up the air volume at all air volume mode according to installation circumstances.
The phase value can range from 00 to 254. As the value is low, the air volume increases.
As making a shipment from the factory, the initial setting up value is “00”.
In case of model 'LZ-H1006BA0', it is recommended to set up the value from 0 to 100.
* For more information of setting up the phase value, refer to the external static pressure value table.
37
9. Installation
OA
(Fresh air outlet)
Inspection part
Control Box
New hood
(preventing penetration
of rain water)
Air return
system
EA
(Exaust air outlet)
OA Inspection
(Fresh air outlet) part SA RA
(Supply air) (Return air)
Air supply grille Air return grille
[Unit : mm]
A B C
LZ-H0102BA0
LZ-H0152BA0 504 624.2 100
LZ-H0106BA0
LZ-H0156BA0
38
9. Installation
OA
(Fresh air outlet)
Air return
system
EA Air return grille
(Exaust air outlet)
Inspection part
New hood
(preventing penetration
of rain water)
Air return
system
EA
(Exaust air outlet)
OA Inspection
(Fresh air outlet) part SA RA
(Supply air) (Return air)
Air supply grille Air return grille
[Unit : mm]
A B C
LZ-H0252BA0 568 636.2 150
LZ-H0256BA0
39
9. Installation
Ceiling suspension
bolts position
EA
(Exaust air outlet)
Inspection
part
450
( 600)
EA
(Exaust air outlet)
OA Inspection part
450( 600)
(Fresh air outlet) Air supply grille
Air return grille
Duct slope: More than 1/30(toward the wall) RA SA
Obtaining of right distance (Return air) (Supply air)
(preventing penetration of rain water)
[Unit : mm]
A B C
LZ-H050*BA0 938.8 1024.8 200
40
9. Installation
EA
(Exaust air outlet)
OA
(Fresh air outlet)
Y duct connecting
(user-supplied)
150~250
Min.600
Inspection
part
450
( 600)
Maintenance space
EA
(Exaust air outlet)
OA Inspection part
450( 600) Air return grille Air supply grille
(Fresh air outlet)
RA SA SA
(Return air) (Supply air) (Supply air)
Duct slope: More than 1/30(toward the wall)
Obtaining of right distance
(preventing penetration of rain water)
[Unit : mm]
A B C
LZ-H080*BA0 987 1176 250
LZ-H100*BA0 987 1176 250
41
9. Installation
EA
(Exaust air outlet)
C
OA
(Fresh air outlet)
Y duct connecting
(user-supplied)
150~2
Min.60
Inspection
port
450 Air supply grille
( 600) (user-supplied) Air supply grille
Air supply grille (user-supplied)
(user-supplied)
Maintenance space
Total Heat Exchanger
Air Filter
OA
(Fresh air outlet)
Inspection port
450 ( 600) Air return grille Air supply
RA SA RA SA SA SA grille
Duct slope : More than 1/30(toward the wall) (Supply air) (Return air) (Supply air) (Supply air)
Obtaining of right distance (Return air) (Supply air)
(preventing penetration of rain water)
[Unit : mm]
A B C
LZ-H150*BA0 987 1176 350
LZ-H200*BA0 987 1176 350
42
9. Installation
9.2 Installation
Installation of Main Body
Assembly of Washer, Nut
Ceiling Fixing Bolt
Tighten the commercial washer nut (more than 21mm for the outside (M10~12)
diameter of M10, to the commercial ceiling fixing bolt (M10) as shown
Nut
in the left figure.
Washer, Spring Lock
• For the ceiling fixing bolt, perform work less than 50mm under the Washer, Plain
ceil fixing bracket. Nut
Connection of Duct
1. After securely connect the duct with the duct connection
flange, wrap it with a commercial aluminium tape so that air Duct
cannot be leaked.
2. Adjust the duct from the ceiling so that no force is applied to
the main body of the ventilation system.
3. Always use two ducts at the outdoor with the heat insulating
material for prevention of dewing.
Taping
Duct
CAUTION:
• Check that there are no foreign materials (paper, vinyl, etc)
or cutoff powders in the duct before connecting the duct.
• Take care so that shock may not be applied to the damper
plate within the main body when performing the duct con-
nection work. Taping
• It is recommended to perform adiabatic treatment even to Heat Insulating Material
the duct pipe at the indoor side where ambient temperature Aluminium
is expected when the main body of the ventilation system
for cooling in summer.
• Take care so that work may not be performed as in the left
figure. Otherwise, it may cause reduction of air volume or Main Body
abnormal noise.
Duct to OA
43
9. Installation
2. After inserting the power cord into the bushing, fully insert it into the terminal
block for connection.
Bushing
Bushing
GN/YL BL BR
GND Power
Cord Clamp
44
10. LCD Wired Remote Control(AZLRAD)
3
10 4
Timer Cancel
fresh Auto
5
6
Program Week Holiday
2 Plasma
7
Set/Clr
11
Hour Min TIME RESET
9 12
Cover open status
45
20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355
Seoul 150-721, Korea
Phone: 3777-7969 Fax: 3777-5137/8
http://www.lge.com
http://biz.lgservice.com
Approvals:
EN ISO 9001
BS EN ISO 9001
ANSI/ASQC Q9001
P/No.: 3828A20428T KS A 9001
For continual product development, LG reserves the right to change specifications without notice
©LG Electronics INC. Printed in Korea. July/2005