FOSTER WHEELER USA CORPORATION


PAGE 1 OF 5
SINCRUDOS DE ORIENTE REQUISITION DATE
CLIENT CONTRACT 13-04561
SINCOR
JOSE REFINERY
SITE ITEM NO. 4561-1745-E 07/19/1999
ANZOÁTEGUI VENEZUELA
MATERIAL C1 08/03/99 C4
OR DRY TYPE TRANSFORMERS C2 08/25/99 C5
SERVICE C3 C6

TABLE OF CONTENTS

I. SCOPE AND REQUIREMENTS 2

II. ITEM LIST 3

III. APPLICABLE JOB SPECIFICATIONS AND DRAWINGS 3

IV. CORRESPONDENCE 4

V. IDENTIFICATION 4

VI. ATTACHMENTS 5

SINCOR REV DATE 08/25/99


DOCUMENT NO:
C2 APP’D
BY: A. HENRIQUEZ P.O. NO. VENDOR:
REQUISITION
FOSTER WHEELER USA CORPORATION
PAGE 2 OF 5
CHANGE No.C2 DATE 08/25/1999 REQUISITION NO. 4561-1745-E
I. SCOPE AND REQUIREMENTS

This bulk material requisition covers the minimum requirements for


design, fabrication, supply and delivery on site of dry type power
transformers up to 1500 kVA as follows:

I.a) DRY TYPE POWER TRANSFORMER, EPOXY ENCAPSULATED, Shall meet the
following requirements:

 60 kVA; 460/208-120 VAC.

 ENCLOSURE IP31 MINIMUM FOR INDOOR USE.

 PRIMARY TAPS WITH FULL CAPACITY 5% ABOVE AND BELOW RATED


VOLTAGE IN 2.5% STEPS.

 SOUND LEVEL SHALL NOT EXCEED 50 Db.

 INSULATION MATERIALS FOR 220 ºC MINIMUM AS INDICATED IN JOB


SPEC. 4478-72A24.

 TRANSFORMER WILL HAVE A ELECTROSTATIC SHIELD.

 FLOOR MOUNTED WITH ROLLERS.

Remaining requirements and characteristics as indicated in the


attached specifications.

I.b) DRY TYPE POWER TRANSFORMER, EPOXY ENCAPSULATED, Shall meet the
following requirements:

 3 kVA; 480/120 VAC., 1 PHASE

 ENCLOSURE IP31 MINIMUM FOR INDOOR USE.

 PRIMARY TAPS WITH FULL CAPACITY 5% ABOVE AND BELOW RATED


VOLTAGE IN 2.5% STEPS.

 SOUND LEVEL SHALL NOT EXCEED 40 Db.

 INSULATION MATERIALS FOR 185 ºC MINIMUM

 WALL MOUNTED.

Remaining requirements and characteristics as indicated in the


attached Specifications.
REQUISITION
FOSTER WHEELER USA CORPORATION
PAGE 3 OF 5
CHANGE No.C2 DATE 08/25/1999 REQUISITION NO. 4561-1745-E
II. ITEM LIST

ITEM
DESCRIPTION QUANTITY

SS3-TR-460/208-120-2-SP Dry type epoxy encapsulated 1


transformer for indoor use, 60 kVA,
460/208-120V, 3Phase. Shall be
manufactured by AGECELEC.

SS3-TR-460/240-120-1-RTU/LP Dry type epoxy encapsulated 1


transformer for indoor use, 3 kVA,
460/120V, 1 Phase shall be
manufactured by AGECELEC.

III. APPLICABLE JOB SPECIFICATIONS AND DRAWINGS

JOB SPEC DESCRIPTION REV

4478-72A24 Dry type power transformers up to B-0


1500 kVA.

1020-13-00-1602-ET-018 General notes specification and B-0


vendor documents for electrical
equipment.

4478-97A1 Preparation and packaging of material 0


for shipment.

DRAWING DESCRIPTION REV

ES025 208/120V Small Power Distribution 1


Panel
Sheets A to D, 1 to 8.

4561-2-74-30-504 Power Distribution Panel Single Line 1


Diagram.
REQUISITION
FOSTER WHEELER USA CORPORATION
PAGE 4 OF 5
CHANGE No.C2 DATE 08/25/1999 REQUISITION NO. 4561-1745-E
IV. CORRESPONDENCE

A.All correspondence and drawing transmittals shall be via express


mail unless otherwise approved by OFW.

B.All correspondence shall be submitted in triplicate.

C.Correspondence concerning COMMERCIAL MATTERS (pricing, terms,


shipment information, etc.) shall be directed as specified on the
Purchase Order.

D.Correspondence concerning TECHNICAL MATTERS (drawings,


engineering data, etc.) shall be directed to:

OTEPI CONSULTORES, S.A.


Zona Rental Universidad Metropolitana,
Edificio 1, Terrazas del Avila,
Caracas 1070, Venezuela
Attention: A. Henríquez
Telephone N° (02) 2042196
E-mail address: ahenriquez@otepi.com.ve

V. IDENTIFICATION

All drawings, details, summary sheets, packing lists, shipping


documents and invoices shall be identified by the following
information. Shipments may be rejected unless this information is
included:

Plant Name Delayed Coking Unit


Item Number
Contract No. 13-004561
Requisition No. 4561-1745-E
P.O. No.
For
SINCOR Coker Project
Jose, Venezuela
REQUISITION
FOSTER WHEELER USA CORPORATION
PAGE 5 OF 5
CHANGE No.C2 DATE 08/25/1999 REQUISITION NO. 4561-1745-E
VI. ATTACHMENTS

You might also like