NOTIFIED BODY No. 1293
CERTIFICATE OF CONSTANCY OF PERFORMANCE
No. 1293 - CPR - 0545
In compliance with Regulation (EU) No 305/2011 of the European Parliament and of the Council
of 9 March 2011 (the Construction products Regulation or CPR), this certificate applies to the
construction product
Conventional fire alarm manual call point SensoMAG MCP50
For specifications see Annex to this certificate
laced on the market under the name or trade mark of
Teletek Electronics JSC
14A Srebarna Str., 1407 Sofia, Bulgaria
and produced in the manufacturing plant
Teletek Electronics JSC
14A Srebarna Str., 1407 Sofia, Bulgaria
This certificate attests that all provisions conceming the assessment and verification of constancy of
performance described in Annex ZA of the standards.
EN 54-11:2001
EN 54-11:2001/A1:2005
under system 1 for the performance set out in this certificate are applied and that the factory
production control conducted by the manufacturer is assessed to ensure the
constancy of performance of the construction product.
This certficate was first issued on April 11", 2017 and will remain valid as long as neither the
harmonised standard, the construction product, the AVCP methods nor the manufacturing conditions
in the plant are modified significantly, unless suspended or withdrawn by the notified product
certification body.
i y
N Nova Dubnica, April 11”, 2017 wf Hudak
5 Geena Director NB
x EVPU a, Trontianska 18, SK 01851 Nove Dubnice, Slovak Republic, wor evmu.sk
< Page 112. Foo asta RevAnnex to Certificate No. 1293 - CPR — 0545 from April 11", 2017
Technical Specifications
SensoMAG MCPSO is 4 manual call point, designed to work with conventional fie panels In stay-by mode, the
reseltable (flexible) cal point element isin a middle position. The call point is powered off and the LED is off
\When pressed on the resettabe element is moving down and a color stip is shown on atts upperside. The call
point is powered on and the LED is on-this is a “Fire alarm” condition. The resetting of the flexible element back
In stay.by mode Is done with the special Key tool-fx the long side ofthe tool at the call point bottom side and
push Up unt flexible element moves up in middle poston(a click is hear).
Products parameters:
Operating voltage: 9-30vDe
"Nominal operating voltage: AVC
Current consumption in alarm state: 2amA/ISV, 38mA24V, 48MAOV_
‘Operating temperature: 10 = 40°C
Relative humidity 93% @ +40°C
Material (plastic), colour: ABS, red
Degree of protestion: 1Pao.
Dimensions: ‘90x56x90mm
Weight: 150g
Essential characteritics ‘Test specification | Harmonised technical
specifications
Nominal activation conditions 432,444.74, | EN54-11:2001
Sensitivity and Performance under | 47.4=N/A,5.2,5.3 | EN 54-11:2001/A1:2005
fire conditions Z
(Operational reliability 42434,45, [EN64-11-2001
46,472,473, | EN 54-11:2001/A1:2005
4.75, 4.8N/A,
54,55
Durabilty of operational reliabilly. 01.5.7, 58=NIA\59 | EN54-11:2001
temperature resistance EN 54-11:2001/41:2005
‘Durability of operational reliably: _|cl 514t05.17 EN 4-11-2001
vibration resistance, EN 54-11:2001/41:2005
Durabilty of operational reliably: | l.5.10, 5.11=N/A, | EN54-11-2001
humidity resistance 5.12, 5.192N/A__| EN 54-11.2001/A1:2005
‘Durabilty of operational reliably. ol. 5.11=N/A, 5.13. EN54-11.2001
corrosion resistance EN 84-11:2001/A1.2005,
‘Durability of operational reliabiliy, |i. 5.6, 5.18 EN 54-11-2001
electrical stability EN 54-11:2001/A1:2005,
Nova Dubnica, April 11", 2017 M
EVPO ass, Tentianska 19, SK 018 §1 Nova Dubice, Slovak Republic, nnw.ovou.sh
Page 2/2, Foo 426-13 Rev