Professional Documents
Culture Documents
Installation Sheets
DOCUMENT HISTORY
Date Revision Reason for change
27APR00 1.0 Initial release
30AUG01 2.0 Add GFD, MODCOM, and 3-NSHM(1) installation sheets.
01NOV01 3.0 Add 24DC12, 3-SAC, ATCK, CRC, CRCRL, CRCSND, KPDISP,
SIGA-MD, and SIGA-SEC installation sheets.
11DEC01 4.0 Correct titles in Content to match installation sheet titles
23MAR05 5.0 Revised to match current set of installation sheets
Content
Introduction
Other documents
In addition to documents in the EST3 library, you may find the
following documents useful.
Signature Series Intelligent Smoke and Heat Detectors
Applications Bulletin (P/N 270145): This manual provides
Wiring diagrams
Connection to 12 Vdc powered devices
The 24DC12 module provides two basic functions. First, it
reduces a 24 Vdc input to 12 Vdc for a Grade A local burglar
alarm bell or a 12 Vdc security/access device such as dual + To 12 Vdc
NAC input - security device
tech motion detectors or a stacked photoelectric beam.
Second, it ground isolates the system initiating device circuit From +
from the outer enclosure of the Grade A local burglar alarm 24 Vdc -
[1] C
bell, which is usually connected to earth ground.
EOLR
- + NO
The 24DC12 is also listed for fire applications such as
powering 12 Vdc accessory devices, relays, etc. NC
16 15 14 13 12 11 10 9
The 24DC12 provides up to one amp of 12 Vdc to security
devices. 24DC12 OPTIONAL: Loop
connection if security
device is not ground
8 7 6 5 4 3 2 1
Specifications isolated.
Bell: 1
Power input
Tamper switches: 1 alarm housing - inner and outer To tamper initiating
+
housing 24 Vdc IN
-
EOLR device circuit
Access control: Models 339-E1, 681-B1, 875-E1 - 24 Vdc OUT (IDC8/4 input,
[1] SIGA-SEC2)
manufactured by Edwards or equivalent manufacturer + to next device
LOOP1
S
H
A A
LOOP1
N/C B B
LOOP1
N/C
12 AWG (1.5 sq mm) maximum
Line interface module 18 AWG (0.75 sq mm) minimum
Termination: Removable plug-in terminal strip on module
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing
OUTPUT MODULE
Circuit configuration
Class B (Style 4)
Class A (Style 6)
Circuit capacity: 99 addressable analog sensors and 99
addressable analog modules
Circuit resistance: 50 W, max.
Circuit capacitance: 0.5 mF, max.
Standby current: 175 mA (includes full loop of devices)
Controller module
Alarm current: 205 mA (includes full loop of devices)
Isolators: Maximum of 6 isolators. Maximum of 25 devices
between isolators.
Installation instructions
The Addressable Analog Driver Controller (AADC) module 1. Connect the LIM card to CIRCUIT 1 on the backside of the
provides one Class A or Class B loop. The loop can contain up rail module assembly. See Figure 1.
to 99 addressable analog sensors and 99 addressable analog
modules. 2. If a control/display module is required, install it at this time.
Refer to the instructions provided with the control/display
The module requires one space on the rail chassis and is module.
secured to the rail assembly using snap rivet fasteners. The
module features a hinged front panel for mounting displays or 3. Install the module on the rail.
a blank protective faceplate.
4. Before connecting the field wiring, test the field wiring for
All field wiring connections to the AADC are made via plug-in opens or shorts.
connectors that permit termination of field wiring without the
When a circuit checks out properly, connect it to the
module being installed in the enclosure. The plug-in
appropriate terminals as shown in Figure 2. Polarity is
connectors and snap rivet mounting also facilitate rapid
indicated for normal monitoring of the circuit's electrical
troubleshooting without the use of tools.
integrity.
Warnings
This product contains components that are sensitive to static
electricity. Failure to follow proper handling procedures may
result in equipment damage.
Rail modules may not be plugged into the rail chassis
assembly while voltages are present on the rail. Failure to de-
energize the panel before plugging in the rail module may
result in equipment damage.
CIRCUIT 1
Wiring diagram
B B S A A N/C B B N/C
H
LOOP1 LOOP1 LOOP1
Circuit 1
3-AADC1
Notes
1. All wiring supervised and power-limited
[2] Shield, if used, must be continuous and
free from earth ground
EARTH GROUND
NETWORK B
NETWORK A
the cabinet as well as processing the data received from
the network for display. The 3-ANNCPU1 contains 1MB
24 VDC
SPARE
of RAM.
24 VDC
An internal calendar and clock with leap year function 4 Ferrite Clamp
provides date/time event stamping and initiates timed (supplied)
events. The controller automatically identifies and 1 2 3 4 5 6 7 8 9 10
RX TX RX TX RX TX RX TX
3. 24 VDC available from Primary
or Booster Power supply.
network over a Class A or B RS-485 network data 4. Install ferrite clamp around
circuit. The controller functions as the local bus master 24VDC power wiring, close to
and supervises all bus traffic between modules in the the enclosure wall.
5. Make sure daughter board
cabinet. connections are secure and
were not loosened during
The 3-ANNCPU1 module requires two spaces at the left- shipment.
most position of the enclosure. The controller is secured
to the inner door by two retainer brackets. All field wiring
connections to the 3-ANNCPU1 module are made via a
plug-in connector, permitting termination of field wiring
without the equipment installed in the enclosure. All
external connections are power- limited and transient 3-ANNCPU1
protected. The plug-in connector facilitates rapid remove
and replace troubleshooting without the use of tools.
Note: 3-CPU Boot and Application Code must be
version 1.33 or greater. J5
SPECIFICATIONS
RX1
Space Required 2 spaces in enclosure TX1
RX2
Display (optional) 3-LCD Display mounts on front TX2
RX3
TX3
Message Capacity
Message Queue 500 Events per queue
Event History Log 1,000 to 1,700 Events, depending
on event type To 3-LCD
J1
Network Com Port
RS-485 Isolated, Class B or Class A
Max. length 5,000 ft (1,524 m)
between any three panels
Max.Resistance 90 !
Max.Capacitance 0.3 "F
Wiring type 1 twisted pair, 18 AWG
2
(0.75 mm ) min.
2
12 AWG (2.5 mm ) max.
INSTALLATION SHEET:
Power Requirements
Voltage 24 Vdc 3-ANNCPU1
Standby Current 171 mA @ 24 Vdc Annunciator Controller Module
Alarm Current 195 mA @ 24 Vdc INSTALLATION SHEET P/N: 387464 FILE NAME: 387464.CDR
REVISION LEVEL: 1.0 APPROVED BY: SM
Termination Plug-in terminal strip
DATE: 05/05/98 CREATED BY: GS
Operating Environment GS BUILDING SYSTEMS CORPORATION
Temperature 32 °F to 120 °F (0 °C to 49°C) A UNIT OF GENERAL SIGNAL
TX RX TX RX TX RX TX RX
RX TX RX TX RX TX RX TX
3-ANNCPU1
J3 J2 J3 J2 J3 J2 J3 J2 P3
To install in 3-EVPWRA:
1. Remove one module retainer bracket and loosen the other (see figure below).
2. Connect cable assembly 360136 (supplied with 3-EVPWRA) to J5 on the 3-ANNCPU1.
3. Remove the 4 locking tabs on the 3-ANNCPU1.
4. Place the 3-ANNCPU1 between the module retainer brackets.
5. Tighten module retainer brackets on both ends.
6. Connect cable assembly 360136 to 3-EVPWR connector J6.
7. Connect cable assembly 46050-1878 (supplied with 3-EVPWRA) from P3 on the 3-ANNCPU1 to P1 on the 3-EVPWR.
J5 3-ANNCPU1
TB1
10 B-
360136
9 B+
8 A-
7 A+
5 GND
4 +24V
3 GND
2 +24V
1 EGND
P3
3-EVPWRA
24V + - + -
J6
J5
P1 J2
A IN
46050-1878
3-ANNCPU3
Annunciator Controller Module
Wiring diagram
The 3-ANNCPU3 Annunciator Controller Module is the control
element for all the LCD and LED/Switch displays in an
enclosure. The 3-ANNCPU3 processes all control information To 24 Vdc
from switches on the displays installed within the cabinet as back box power supply
well as processing the data received from the network for
display.
An internal calendar and clock with leap year function provides
date-time event stamping and initiates timed events. The
controller automatically identifies and supervises all modules
installed in the annunciator, and has an integral watchdog to
identify both hardware and software faults.
The 3-ANNCPU3 communicates with other 3-ANNCPUs and
3-CPUs on the network over a Class A or B RS-485 network
data circuit. The controller functions as the local bus master E + G + G A A B B
SPARE
RX TX RX TX RX TX RX TX
3-ANNCPU3
J3 J2 J3 J2 J3 J2 J3 J2 P3
To install in a 3-EVPWRA:
1. Remove one module retainer bracket and loosen the other (see figure below).
2. Connect cable assembly 360136 (supplied with 3-EVPWRA) to J5 on the 3-ANNCPU3.
3. Remove the 4 locking tabs on the 3-ANNCPU3.
4. Place the 3-ANNCPU3 between the module retainer brackets.
5. Tighten the module retainer brackets on both ends.
6. Connect cable assembly 360136 to 3-EVPWR connector J6.
7. Connect cable assembly 46050-1878 (supplied with 3-EVPWRA) from P3 on the 3-ANNCPU3 to P1 on the 3-EVPWR.
J5
360136
P3
3-EVPWRA
J6
J5
P1
46050-1878
INSTALLATION
1. Fill out and install a label in each LED/Switch display 1
(step 1.) 2
2. Mount the display on the 3-ANNSM module (step 2.)
RX TX
TX RX
RX TX
TX RX
RX TX
TX RX
RX TX
connector J1 on the display to connector J1 on the 3-ANNSM 3-ANNSM 3-ANNSM 3-ANNSM 3-ANNCPU
module (step 3.) 3
J3 J2 J3 J2 J3 J2 J3 J2 P3
4
4. Install the module in the inner door of the enclosure
(Figure 2.)
Installation
1Insert
ID label 1S
NOT FL
2 Mount
Display 5
RT
H
1S
SO T FL
1S
UT
EA T FL
ST
H
6
Figure 2
1S
W T FL
ES
T
2N
D
NO F
RT L
2N
SO F
2N
D
UT L
H
H
Installing the 3-ANNSM on the Inner Door
EA D F
2N
W DF
ST L
ES L
1. Install the lower module retainer bracket (5) on the inner
T
3R
NOD F
RT L
H
door (6) using the nuts (2) provided. Do not tighten the
3R
SO D F
3R
UT L
H nuts at this time.
EA D F
ST L
3R
W DF
ES L
Control or
indicator Functional description
Page level Indicates paging volume. When paging, speak
meter at a level that causes the far right LED to only
3-ASU flicker occasionally.
Ready to Green LED flashes during pre-announcement
Page LED tone, then is on steady when the system is
ready to page
All Call Green LED on indicates the ASU is in the All
switch/LED Call mode. Pressing the All Call switch directs
the page to all areas of the facility. To exit the
All Call mode, press the switch a second time
or press the All Call Minus, EVAC, or Alert
switches.
All Call Minus Green LED on indicates the ASU is in the All
switch/LED Call Minus mode. Pressing the All Call Minus
switch directs the page to the areas of the
facility, which have not been automatically
3-ASU/4 selected to receive the EVAC or Alert
tone/message. To exit the All Call Minus
The Audio Source Units (ASU) are shipped unassembled and mode, press the switch a second time or press
consist of a chassis assembly, a controller board, and a cover the All Call, EVAC, or Alert switches.
assembly. The chassis assembly provides the mounting
supports for the controller board and cover assembly. Phone Page Green LED on indicates the ASU is in the
switch/LED Phone Page mode. Pressing the Phone Page
The 3-ASU has a filler plate that mounts on the cabinet inner switch replaces the paging microphone (item
door to prevent access to the electronics. 2) with the firefighter’s telephone system.
Individuals in remote areas of the facility can
The 3-ASU/4 has a chassis assembly that provides a four-slot then issue a page via the firefighter’s
rail for installing rail modules. telephone system. All phone paging is under
the direct control of the ASU operator. Press
Specifications the switch a second time to disconnect the
Phone Page mode.
Cabinet installation: One chassis space
Rack dimensions: 12.0 x 19.0 x 5.25 inches EVAC Green LED on indicates the ASU is in the
(30.48 x 48.26 x 13.34 cm) switch/LED EVAC mode. Pressing the EVAC switch
Operating current: 45 mA directs the page to areas of the facility, which
Options: 3-ASUMX/nn Memory (nn = minutes of messages) are automatically receiving the evacuation
Audio channels: 8 simultaneous tone/message. To exit the EVAC mode, press
Audio inputs the switch a second time or press the All Call,
Local microphone (isolated and supervised) All Call Minus, or Alert switches.
Remote microphone (isolated and supervised)
Firefighter's telephone (isolated and supervised) Alert Green LED on indicates the ASU is in the
One aux signal source (isolated and supervised) switch/LED Alert mode. Pressing the Alert switch directs
Prerecorded message storage the page to areas of the facility, which are
2 minutes standard (expandable to 100 minutes) automatically receiving the Alert
Auxiliary input tone/message. To exit the Alert mode, press
Input impedance: 1 kW the switch a second time or press the All Call,
Input level: 0.1 Vrms to 1.0 Vrms All Call Minus, or EVAC switches.
Frequency response: 100 Hz to 4 kHz
RCIC
J3
Secure chassis to
backbox studs with RCIC
#8-32x locknut here
RCIC
3-CHASS
ASU RCIC
Ribbon cable
P/N 250195-01 Cover
assembly
Threaded
J4 mounting
stud #8 x 32 locknut
3-CHASS
Notes
1 2 3 4 5 6 7 8 9 10 11 12 13 14 1. All wiring is supervised and
power-limited
[2]Connect to TB2 Audio A OUT
+/- on the CPU when
AUDIO DATA TELEPHONE PAGE REMOTE MIC AUX installed in non-network
PRIMARY SECONDARY OUT KEY AUDIO applications
J2 J3 J4
From previous CHAS-7 J10 AOUT BIN
AIN CIN
J6
AOUT DIN From previous CHAS-7 J11 DOUT
RCIC
COUT DOUT
J8 J9
To next CHAS-7 J8 CIN
P/N 250190
P/N 250191
P/N 250192
From previous CHAS-7 J10 COUT From previous CHAS-7 J11 BOUT
J2 J3 J4
From previous CHAS-7 J10 AOUT BIN
AIN CIN
J6
AOUT DIN From previous CHAS-7 J11 DOUT
J5 J7
BOUT
Top rail
RCIC
COUT DOUT
J8 J9
Bottom rail
P/N 250190
P/N 250191
P/N 250192
Installation instructions 4. Connect the first ribbon cable (P/N 250195-00) from J1 on
the Rail Chassis Interface Card (RCIC) to J2 on the FTCU.
WARNING: Disconnect power to cabinets before installing or Connect the second ribbon cable from J1 on the FTCU to
removing components. Failure to do so may result in serious J2 on the ASU.
injury or loss of life.
Cover
J3 assembly
J3
Threaded
mounting
stud #8 x 32 locknut
3-CHASS
[1] [1] [2] [2]
Detail diagram
Notes
[1] Mounting stud for the ASU cover assembly
[2] Mounting stud for the FTCU cover assembly
J2 J3 J4
From previous CHAS-7 J11 BOUT
From previous CHAS-7 J10 AOUT BIN
AIN CIN
J6
AOUT DIN From previous CHAS-7 J11 DOUT
J8 J9 P/N 250191
To next CHAS-7 J8 CIN
To next CHAS-7 J9 DIN
P/N 250192
Notes
1 2 3 4 5 6 7 8 9 10 11 12 13 14 1. All wiring is supervised and
power-limited
[2]Connect to TB2 Audio A OUT
+/- on the CPU when
AUDIO DATA TELEPHONE PAGE REMOTE MIC AUX installed in non-network
PRIMARY SECONDARY OUT KEY AUDIO applications
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 4 3 21 [2]
CHANNEL 2 CHANNEL 1
TROUBLE TROUBLE URSM
TB1 1 2 3 4 5 6
A A B B Not used
+ - + - TB1
RISER
7 8 9 10
_ 11 12 13 14
_
FTCU + +
Local Cabinet TELEPHONE TELEPHONE
[3] CHANNEL 2 CHANNEL 1
24 Vdc +
_
Red
Black
Listed primary or auxiliary power supply
Notes
[1] Set Single Input Signal Modules to personality code 6
[2] Set Single Input Modules to personality code 3
[3] UL/ULC listed 47 kW EOL
[4] Class B (Style Y), twisted-shielded wires
5. All shields shall be continuous and insulated from ground, except at the originating panel
6. All wiring is power-limited
The 3-ATPINT Interface card is a 25 VRMS and 70 VRMS Input Voltage 25 VRMS or 70 VRMS
adapter for the ATP Amplifier Terminal Panel. The 3- Number of Circuits 2
ATPINT is required when using a distributed (high Supervisory Isolation DC Blocking Capacitor
voltage) output of an audio amplifier as the audio source
for the ATP.
SPECIFICATIONS
The 3-ATPINT is designed for use with audio source
amplifiers which use 24 VDC output circuit supervision
NOTES
with EOL resistor. Multiple 3-ATPINT cards can be
connected to a common source amplifier using Class B or 1. Use a SIGA-CT1 or SIGA-CT2 (P-code 3) to monitor the
Class A supervision, as provided by the sourcing amplifier. URSM at the end of the audio risers.
INSTALLATION INSTRUCTIONS
1 Remove the old cover plate and retaining clips on the 3-ATPINT
left side of the ATP (4 screws).
3 Mount the 3-ATPINT board (4) on the four short PREAMP 1 IN OUT RISER OUT PRE-AMP
70V 25V
spacers (5) and secure with four long spacers (3).
1 P1
4 Install the new cover plate (2) on the long spacers with PREAMP 2
screws and washers (1) provided. 70V 25V
1 P2
IN OUT RISER OUT PRE-AMP
1 PRE-AMP 2
2
3 + - S + - S + - S
4
5
INSTALLATION SHEET:
6
3-ATPINT ATP Interface
INSTALLATION SHEET P/N: 387284 FILE NAME: 387284.CDR
REVISION LEVEL: 2.0 APPROVED BY: D. Becker
Bottom View
DATE: 04/06/99 CREATED BY: D. Miner
EDWARDS SYSTEMS TECHNOLOGY, INC.
G FAX 941-753-1806
A UNIT OF GENERAL SIGNALS
SARASOTA, FL: 941-739-4300
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
EDWARDS
INTERNATIONAL,
SYSTEMS TECHNOLOGY CANADA: 905-270-1711 FAX 905-270-9553
WIRING
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
To TB1 on Audio Amplifier To TB1 on Audio Amplifier To TB1 on Audio Amplifier To TB1 on Audio Amplifier
TB1
To TB2 on Audio Amplifier To TB2 on Audio Amplifier To TB2 on Audio Amplifier To TB2 on Audio Amplifier
10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
Shield, Shield,
if used if used
Audio Riser
Output
UL/ULC Listed 15K! EOL
ON LAST ATP ONLY
(For Class B circuits Only) From Power
Amp Output
To Power
Amp Audio
Input
2 3 2 3
Do Not Use
+ - S + - S + - S + -S + -S + - TB4
AMPLIFIER TERMINAL PANEL (ATP) P/N 240068 TB1 IN OUT OUT IN OUT BATT. 120VAC H
+ - S + - S + - S PREAMP #1 PWR AMP #1 OUT 60HZ
WARNING 10A MAX.
N
PRE-AMP 1 AMP #1 FOR CONTINUED PROTECTION G
AGAINST THE RISK OF FIRE, 3AB-20A
PREAMP 1 IN OUT RISER OUT PRE-AMP REPLACE ONLY WITH SAME
70V 25V
1 P1
TB3 + - TYPE 8 RATING FUSE.
FUSE
Removable Cover
PREAMP 2
POWERPANELACTIVITY
120 VAC OUT TB5
70V 25V
FAIL TRBL BATT. IN
IN OUT RISER OUT PRE-AMP
1 P2
AMP #2 24 VDC
WARNING PRE-AMP 2
40AH MAX.
IMPROPER
+ -
CONNECTION
S + -
OF TERMINALS
S + - S
WILL RESULT IN A FAILURE OF POWER SUPPLY TB2 IN
PREAMP #2
OUT OUT
PWR AMP #2
IN OUT
BATT.
OUT
+
+ - S + - S + - S + -S + -S + -
[3AMPCON1.CDR]
Input #2 wired identical to Input #1 Do Not Use
Wiring Notes
1. Circuit polarity shown in supervisory condition.
2. Supervised circuit when URSM is used.
3. Power limited circuit.
4. Back up amplifier size must equal the wattage of the largest
amplifier to be backed up.
5. Set J1 & J2 to match source amplifier output voltage.
JUMPER SETTINGS 6. Refer to Audio Manual, P/N 270219 for additional ATP and
P1 = 1/2, Pre-Amp #1 Input 70 VRMS power amplifier installation information.
P1 = 2/3, Pre-Amp #1 Input 25 VRMS 7. Additional ATPs may be connected to the same audio source by
P2 = 1/2, Pre-Amp #2 Input 70 VRMS connecting the ATP pre-amp output to the pre-amp input of the
P2 = 2/3, Pre-Amp #2 Input 25 VRMS next ATP.
3-BATBKT
INSTALLATION SHEET:
INSTALLATION
Side View
Front View 3-BTSEN
RCC7R, RCC14R or
RCC21R Enclosure
12Volts 3-BATS
12Volts
12Volts
12Volts
non-power limited.
3-BATS
Battery Shelf
WARNINGS
INSTALLATION NOTE
WIRING
Common battery for multiple power supplies Batteries can deliver high currents. Remove all jewelry before
working on these circuits.
To Booster
INSTALLATION INSTRUCTIONS
To Primary
The battery cabinet must be installed in the same room as the fire
alarm panel and wiring run in conduit.
Side View
Enclosure
COVER 3-BTSEN
Black Red
12Volts 12Volts
Black Red
12Volts 12Volts
Notes:
1. Supervised, not power limited.
2. To get twice the distance between the panel and the 3-
BTSEN, use one pair of wires for each power supply in the INSTALLATION SHEET
panel. Refer to the following table for wire distances.
1 8.84 ft. 14 ft. 22.4 ft. 35.4 ft. DATE: 13FEB01 CREATED BY: D. Miner
(2.7 M) (4.27 M) (6.83 M) (10.79 M)
EDWARDS SYSTEMS TECHNOLOGY, INC.
2 4.42 ft. 7 ft. 11.2 ft. 17.7 ft. SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
(1.35 M) (2.13 M) (3.41 M) (5.4 M) OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
3-BTSEN-E
Battery Distribution Bus
To booster(s)
To primary
and booster
Installation instructions
The battery cabinet must be installed in the same room as the Black Red
fire alarm panel and wiring run in conduit.
+ +
12 volts 12 volts
Side view
Enclosure
Notes
Cover 3-BTSEN-E
1. Supervised and nonpower-limited
2. For maximum distances from the battery cabinet and
power supplies, each power supply must have its own pair
of wires from the battery cabinet. Refer to the table below.
SPECIFICATIONS
3-CAB7B Dimensions (H x W x D)
Rough-In (See note 1) 23.2 in x 24.0 in x 3.86 in
(58.98 cm x 60.9 cm x 9.8 cm)
Finished
Surface Mounted 25.5 in x 27.34 in x 5.5 in
(64.77 cm x 69.4 cm x 14.0 cm)
Semi-Flush Mounted 25.5 in x 27.34 in x1.65 in
(64.77 cm x 69.4 cm x 4.19 cm)
3-CAB14B Dimensions (H x W x D)
Rough-In (See note 1) 35.5 in x 24.0 in x 3.86 in
(90.17 cm x 60.9 cm x 9.8 cm)
Finished
Surface Mounted 37.75 in x 27.34 in x 5.5 in
(95.89 cm x 69.4 cm x 14.0 cm)
Semi-Flush Mounted 37.75 in x 27.34 in x 1.65 in
(95.89 cm x 69.4 cm x 4.19 cm)
3-CAB21B Dimensions (H x W x D)
Rough-In (See note 1) 47.75 in x 24.0 in x 3.86 in
(121.29 cm x 60.9 cm x 9.80 cm)
Finished
Surface Mounted 50.0 in x 27.34 in x 5.5 in
(127.0 cm x 69.4 cm x 14.0 cm)
Semi-Flush Mounted 50.0 in x 27.34 in x 1.65 in
(127.0 cm x 69.4 cm x 4.19 cm)
Note:
1) Add 1/4" to height and width to allow for knockouts when
framing in backbox for semi-flush mounting.
Equipment Capacity
3-CAB7B
Chassis 1 chassis assembly
Batteries 3-CAB21B shown
Model 6V8A 4 max.
Model 12V10A 2 max.
Model 12V17A 2 max.
3-CAB14B
Chassis 2 chassis assemblies
Batteries
Model 6V8A 4 max.
Model 12V10A 2 max.
Model 12V17A 2 max. INSTALLATION SHEET:
3-CAB21B
Chassis 3 chassis assemblies
Batteries 3-CAB Series Equipment
Model 6V8A
Model 12V10A
4 max.
2 max.
Enclosure Backboxes
Model 12V17A 2 max.
INSTALLATION SHEET P/N: 387557 FILE NAME: 387557.CDR
REVISION LEVEL: 1.0 APPROVED BY: K. Patterson
DATE: 24MAY99 CREATED BY: G. Sutton
POWER LIMITED
Wire
Right Front
Nonpower-limited
wiring area under
rail assembly
NON-POWER LIMITED
Left Rear
pins.
2. Attach the hinge stop to the outer door assembly.
3. Attach a grounding strap from the outer door ground Back box
strap stud on the back box to the outer door. right flange
3-CAB14DR Red door w/window for CAB21B back boxes 6411 Parkland Drive 625 6th Street East
GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
CORPORATION
USA Canada N4K 5P8
CABINET INSTALLATION DIMENSIONS
Inner Door Assembly
Connect grounding strap
(P/N 260077) to inner door
CENTER
CHASSIS
BOTTOM
CHASSIS
BATTERY AREA
DO NOT INSTALL CONDUIT
Mount inner door on
inner hinge pins.
A
F
D A
Retaining
Clip See details on
other side
E
B
B E
C F
OUTER DOOR
1.3 in
(3.3 cm)
SPECIFICATIONS
Dimensions (HWD) BATTERY AREA
DO NOT INSTALL CONDUIT
3-CAB5B Back Box
Rough-In 22.37 in x 14.0 in x 3.86 in
(56.82 cm x 35.56 cm x 9.80 cm)
NOTE: Add 1/4" to height and width to
allow for knockouts when framing in
backbox for semi-flush mounting.
MODEL DEFINITIONS
Finished
Surface Mounted 24.25 in x 16.4 in x 5.5 in
3-CAB5 Cabinet with Door, Gray
(61.60 cm x 16.4 cm x 14.0 cm)
3-CAB5R Cabinet with Door, Red
Semi-Flush Mounted 24.25 in x 16.4 in x 1.65 in
(61.60 cm x 16.4 cm x 4.19 cm)
Capacity
Modules Five module spaces 3-CAB5 / 3-CAB5-R
Battery Two 10 AH @ 12 VDC
Finish
3-CAB5 Gray textured enamel
3-CAB5R Red textured enamel
CABINET INSTALLATION
1. Mount the backbox at the required location. A
dedicated 120 VAC (for systems using model 3-PPS/M
power supplies), or 230 VAC (for systems using model
3-PPS/M-230 power supplies) 50/60 Hz circuit is
required for each cabinet. Install all conduit and pull all
wiring into the backbox before proceeding to the next
step.
2. Install the outer door at this time. INSTALLATION SHEET:
3. Install the 3-TAMP5 Tamper Switch, if used. 3-CAB5
4. Install the equipment chassis. After all chassis 3-CAB5R
assemblies have been installed, mount the inner door
on the inside hinge pins. INSTALLATION SHEET P/N: 270487 FILE NAME: 270487.CDR
5. Connect the ground strap between the stud on the REVISION LEVEL: 2.0 APPROVED BY: K. Patterson
inner door and the backbox, using the hardware DATE: 12/17/98 REVISED BY: D. Miner
provided.
6. Install the ground strap between the stud on the A UNIT OF GENERAL SIGNAL
GS GS BUILDING SYSTEMS CORPORATION
exterior door and the stud on the backbox. GS BUILDING SYSTEMS 6411 Parkland Drive 625 6th Street East
CORPORATION Sarasota, FL 34243 Owen Sound, ON, Canada
INSTALLATION INSTRUCTIONS
These instructions are for right-hand swing open
operation of the outer door. For left-hand swing open Outer door assembly
operation, attach the enclosure hardware to the opposite
side. Hinge
pins.
2. Attach the hinge stop to the outer door assembly.
3. Attach a grounding strap from the outer door ground Back box
strap stud on the back box to the outer door. right flange
3-CAB21DR-E Red door w/window for CAB21B back boxes 6411 Parkland Drive 625 6th Street East
GS BUILDING SYSTEMS Sarasota, FL 34243 Owen Sound, Ontario
CORPORATION
USA Canada N4K 5P8
CABINET INSTALLATION DIMENSIONS
Inner Door Assembly
Connect grounding strap
(P/N 260077) to inner door
CENTER
CHASSIS
BOTTOM
CHASSIS
BATTERY AREA
DO NOT INSTALL CONDUIT
Mount inner door on
inner hinge pins.
A
F
D A
Gasket
Retaining
Clip See details on
other side
E
B
Plexiglass B E
C F
INSTALLATION
Mount the chassis assembly on the six #6-32 studs at the rear of the
cabinet. Secure the chassis to the cabinet with the washers and nuts
provided. An 11/32" nut driver simplifies chassis installation.
If a primary or booster power supply is used with this chassis, mount the
heat sink on the four threaded stand-offs under the rails, then secure the
PC board to the four threaded stand-offs.
J11
J10
J9
J8
J11
J10
J11
J10
J9
J8
J11 [3CHAS7.CDR]
J10
INSTALLATION SHEET:
[3RAILCN1.CDR]
J10 COUT J11 DOUT
3-CHAS7
Installation instructions are continued on following
two pages. Seven Local Rail Module Chassis
J10
J11
2. Connect a top rail data cable (6 pin ribbon cable connector) to
connector J11 BOUT on the top rail of chassis #1. Route the cable
down to chassis #2 and connect to J9 BIN on the chassis #2 top rail.
Top Rail 3. Connect a bottom rail power cable (4 pin connector) to connector J10
COUT on the bottom rail of chassis #1. Route the cable down to
chassis #2 and connect to J8 CIN on the chassis #2 bottom rail.
Bottom Rail Top Rail Power Cable 4. Connect a bottom rail data cable (6 pin ribbon cable connector) to
P/N 250191 connector J11 DOUT on the bottom rail of chassis #1. Route the cable
J9 Top Rail Data Cable down to chassis #2 and connect to J9 DIN on the chassis #2 bottom
J8
rail.
J11
P/N 250190
J10
5. Repeat this process between chassis #2 and chassis #3.
Bottom Rail Power Cable NOTE: The chassis containing the 3-CPU1 Central Processor can only
P/N 250192 have chassis power and data connections made to connectors J10
Bottom Rail Data Cable AOUT and J11 BOUT on the top rail and J10 COUT and J11 DOUT on the
P/N 250190 bottom rail. The chassis containing the 3-CPU can never have
Chassis #2 connections coming into connectors J8 AIN, J9 BIN, J8 CIN or J9 DIN.
J9
J8
J11
J10
Top Rail
Bottom Rail
J9
J8
J11
J10
J9
Bottom Rail Power Cable
J8
P/N 250192
Bottom Rail Data Cable
J11
J10
P/N 250190
Top Rail
Bottom Rail
J9
J8
J11
J10
[3RAILCN2.CDR]
The figure to the left shows an Audio Source Unit (ASU) and two 3-
Chassis #1 CHAS7 chassis in a common cabinet. The ASU unit is connected to the
two rails using a Rail Chassis Interface Card. The Rail Chassis Interface
Card is mounted below the rails in the 1/2 footprint IRC-3 module space
of the ASU unit chassis.
J9
J8
J11 2 In this example, the ASU can be either the top or middle chassis.
Connect the power and data cables as follows:
J10
1. Connect the top rail power cable (3 pin connector) to connector J10
Top Rail 1
AOUT on the top rail of chassis #1. Route the cable down to the Rail
Chassis Interface Card and connect to J28 AIN.
2. Connect the top rail data cable (4 pin connector) to connector J11
Bottom Rail COUT on the top on bottom rail of chassis #1. Route the cable down to
the Rail Chassis Interface Card and connect to J4 BIN.
J9
J8
J11 4 3. Connect the bottom rail power cable (4 pin connector) to connector
J10
J10 COUT on the bottom rail of chassis #1. Route the cable down to
the Rail Chassis Interface Card and connect to J3 CIN.
3 4. Connect the bottom rail data cable (6 pin ribbon cable connector) to
connector J11 DOUT on the bottom rail of chassis #1. Route the cable
down to the Rail Chassis Interface Card and connect to J6 DIN.
Chassis #2
1 5. Connect a top rail power data cable to connector J5 AOUT on upper
left side of the Rail Chassis Interface Card. Route the cable up to
J9 2 connector J8 AIN on the top rail of chassis #2.
J8
J10
J11
6. Connect a top rail data cable to connector J7 BOUT on the upper right
side of the Rail Chassis Interface Card. Route the cable up to
2 connector J9 BIN on the top rail of chassis #2.
Top Rail 1 J2 J3 J4
7. Connect a bottom rail power cable to connector J8 COUT on the left
BIN
AIN CIN
AOUT
J6
DIN
center of the Rail Chassis Interface Card. Route the cable up to
J5 J7 connector J8 CIN on the bottom rail of chassis #2.
Bottom Rail 3 BOUT
J11
Source Unit
J10
Rail
Chassis
Interface
4 Card
J9
J8
TB1
INSTALLATION
1. Install the 3-LCD display module (if
required).
• Remove the blank front panels from the
support brackets on the 3-CPU1. Primary power
• Connect the ribbon cable on the 3-LCD supply Primary power
to J1 on the 3-CPU1. The colored edge supply monitor
is pin 1.
• Connect the ground cable on the 3-LCD
to the 2-pin header on the 3-CPU1. The N C N N C N
-
N N C N
TB1
[AUDIORISER1.CDR]
From
AUDIO DATA PRIMARY
on 3-ASU
Figure-4: Typical Class B network audio riser wiring (requires a 3-RS485A or 3-RS485B card)
From
[AUDIORISER2.CDR]
AUDIO DATA PRIMARY
connections on 3-ASU
Figure-5: Typical Class A network audio riser wiring (requires a 3-RS485A card)
To COM terminal on
listed equipment
To RxD terminal on
listed equipment
To TxD terminal on
listed equipment
TR OUBLE
N
O
N
O
C
ALAR M
N
-
A
N
C
N
O
SUP
C N
C
Type: Isolated, Class B
Connector: RJ-11
Common control relays: 3 Form C relays rated at 30 Vdc @ 1A
TB1
Installation instructions
1. Install any 3-CPU3 option cards required. Refer to the
respective installation sheets for the option card being
The 3-CPU3 Central Processor Module is the control element installed.
for all rail modules and control/display modules installed within 2. Slide the 3-CPU3 into the first two rail slots on the rail
an enclosure. The 3-CPU3 processes all information from chassis assembly. Be careful to align the option cards into
modules installed within the cabinet as well as data received the card guides.
from other panels over the network data riser.
3. Gently push the 3-CPU3 until it is firmly seated into the rail
Note: 3-CPU3 is a replacement for the 3-CPU1 and 3-CPU. connectors.
The 3-CPU3 has an internal calendar/clock with leap year 4. Secure the module to the rail by pushing the top and
function provides date/time event stamping and initiates timed bottom snap rivet fasteners until they lock in place.
events. The 3-CPU3 automatically identifies and supervises all 5. Connect the field wiring.
modules installed on the rail chassis and has an integral
watchdog to identify both hardware and software faults. The
module has Form-C common alarm, trouble, and supervisory Primary power
supply Primary power
relay contacts that operate whenever any alarm, supervisory, supply monitor
or fault condition is detected in the network.
The 3-CPU3 communicates with other 3-CPUs on the network
over an RS-485 or fiber optic network data circuit. Class A or B N
O
C
TROUBLE
N
C
N
O
C
ALARM
N
-
A
N
C
N
O
SUP
C N
C
wiring configuration can be used for the network data circuit TB1
From
AUDIO DATA PRIMARY
on 3-ASU
Figure 5: Typical Class B network audio riser wiring (requires a 3-RS485A or 3-RS485B card)
From
AUDIO DATA PRIMARY
connections on 3-ASU
Figure 6: Typical Class A network audio riser wiring (requires a 3-RS485A card)
TB2
R C R C
R T T O R T T O
X X S M X X S M
1 1 1 1 2 2 2 2
N C N N C N N N C N
C O O A C O C
TROUBLE ALARM SUP
TB1
3-CPU3
To COM terminal on
listed equipment
To RxD terminal on
Figure 7: Common relay wiring listed equipment
To TxD terminal on
listed equipment
WARNINGS 3-FIB/3-FIBA
This product contains components which are sensitive to static
electricity. Failure to follow proper handling procedures to
prevent damage from electrostatic discharge may result in
equipment failure. P6 NORM TEST P8
P1 JP1 P3
NOTES 3-FIB/A Interface Card
P5 P7
To test the fiber optic connection, place JP1 in the TEST position.
The 3-FIB/3-FIBA will transmit a constant signal which can be 3-FIB/3-FIBA
used for fiber optic budget measurements and troubleshooting. Fiber Optic Communications
Return JP1 to the NORM position when testing is finished.
Interface Module
INSTALLATION SHEET P/N: 387333 FILE NAME: 387333.CDR
REVISION LEVEL: 2.0 APPROVED BY: D. Munn
DATE: 29JAN99 CREATED BY: G. Sutton
Figure 1 5
Figure 2
6 J1
3-FIB/A
4 Electronics Card
7
J2
4
2 5
3-FIB/A P6 P8
J2 JP1
3-FIB/A
P1 P3
TB1 JP1
A OUT NET P1 P3 A OUT AUDIO
J2 3-FIB/A Interface Card
3
B IN NET P5 P7 B IN AUDIO
6 (3-FIB/A only)
8 B OUT AUDIO
4 B OUT NET P2 P4
3FIB3.CDR TB1 (3-FIB/A only)
P2
P5
P1
P6
5 3-FIB/A
4
Component Interface Card
Sides
J2
3
3-CPU1
NORM
side view
JP1
TEST
5
P4
P7
P3
P8
J1
8
Figure 3
3-CHAS7 - Front View Side View CAB5
5
8
P2
P5
P1
P6
DS5
DS4
DS8
DS7
J8
J9 3-MPFIB
J10
J11
Mounting 3-FIB/A
Bracket Ingerface
3-PPS(/230) Interface
Card
Card
3-PPS(/230) Footprint
JP1
DS6
DS3
DS2
DS1
J9
J8
P8
P3
P4
P7
J9
J8
J11
J10
J11
J10
[3fibmtg1.CDR]
1 2
P1 P3
P1 P3
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
P5 P7
P5 P7
P2 P4
P2 P4
Fiber Optic
Fiber Optic Network Data Riser
Network Data Riser Fiber Optic
Audio Data Riser
3-CPU1 with 3-FIB
or 3-CPU1 with 3-FIB/A
3-CPU1 with 3-FIBA P6 P8
P6 P8
P1 P3
P1 P3
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 P5 P7
P5 P7
P2 P4
P2 P4
P1 P3 P1 P3
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 P5 P7
P5 P7
P2 P4 P2 P4
P1 P3 P1 P3
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
P5 P7 P5 P7
P2 P4 P2 P4
From 3-ASU Primary Audio Data From 3-ASU Primary Audio Data
Figure-4A: 3-FIB(/A) Class B Network and Audio Figure-4B: 3-CPU1 Class A Network and Audio
Fiber Optic Connections Fiber Optic Connections
3-CPU1 with 3-FIB/A
P6 P8
To next panel
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
P1 P3
3-CPU1 module
P5 P7
P2 P4
P6 P8
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Fiber Optic P1 P3
P2 P4
P1 P3 Fiber Optic
P5 P7
Audio Data Riser
P2 P4
Fiber Optic P1 P3
P2 P4
P1 P3
Maintain physical separation or
P5 P7
2 hour fire rating
P2 P4
Copper Wire 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 P1 P3
Copper Wire
Network Data Riser P2 P4
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
3-CPU1
3-CPU1
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
From 3-ASU
From previous panel Primary Audio
3-CPU1 module Data
NORMAL
B AUDIO J2 A AUDIO Circuit length: 5,000 ft (1,524 m) max. between any three
TX RX TX RX
panels
Circuit resistance: 90 W, max.
Circuit capacitance: 0.03 mF, max.
Wire type: Twisted Pair, 18 AWG (0.75 sq mm) min.
Copper wired audio data circuit
Circuit length: 5,000 ft (1,524 m) max. between any three
panels
Circuit resistance: 90 W, max.
Circuit capacitance: 0.09 mF, max (includes shield
capacitance, if required)
U3 U2
The 3-FIBMB is powered by the panel supply, but it includes • All wiring is power-limited
input terminals for a secondary power source. This permits • The 3-FIBMB does not support annunciator panels
communication to continue through the module, even with the
panel power disconnected. In the event a panel needs to be • Unconditional eye safe laser IEC 825/CDRH Class 1
powered down for service, a 24 V battery source can be compliant
connected to the module to maintain network and audio
communications during servicing. See “Notes,” below.
TEST
NORMAL
B AUDIO J2 A AUDIO
3. Route the ribbon cable under the rail to the far right of the TX RX
chassis. TX RX
RX TX RX TX
B DATA A DATA
Ribbon
TEST
NORMAL
cable
B AUDIO J2 A AUDIO
J2
TX RX TX RX
J9
J8
J2
J11
J10
3-PPS(/230) 3-FIBMB
J1 footprint
Electronics
card
Figure 3: Mounting the bracket and the 3-FIBMB
Fiber testing
To test the fiber-optic connection, put jumper J2 ( located on
CPU side Fiber-optic the 3-FIBMB board) in the TEST position. The 3-FIBMB then
view Interface module
transmits a constant signal that can be used for fiber-optic
budget measurement and troubleshooting. Return J2 to the
Figure 1: Connecting the ribbon cable and adaptor card NORMAL position when testing is finished.
A data
A AUDIO
audio
A DATA
TX
The following wiring diagrams can be used with single mode or
RX
A
Network AUDIO AUDIO AUDIO AUDIO
RX TX
RX
TX
OUT IN A IN A OUT B IN B OUT
A A B B
multimode fiber. If using single mode use the SMXLO or + - + - + - + - + - + -
B data
B AUDIO
TX RX
B DATA
audio
TX
RX
SMXHI transceivers. If using multimode use the MMXVR
B
RX TX
RX
TX
transceivers.
Fiber-optic network Fiber-optic audio
data riser data riser
CPU with 3-FIBMB RX
audio
A A UDIO
A DATA
RX
CPU with 3-FIBMB
A
TX TX RX
A data
Network AUDIO AUDIO AUDIO AUDIO
audio
A AUDIO
TX
A DATA
TX
RX
OUT IN A IN A OUT B IN B OUT
A
A A B B Network AUDIO AUDIO AUDIO AUDIO
RX TX
RX
+ - + - + - + -
TX
+ - + - OUT IN A IN A OUT B IN B OUT
B data
TX
B AUDIO
B DATA
A A B B
TX
+ - + - + - + - + - + -
RX
B data
TX RX
B AUDIO
audio
B DATA
RX
TX
RX
B
RX TX
RX
TX
CPU with 3-FIBMB TX RX CPU with 3-FIBMB
A data
TX RX
audio
A A UDIO
A data
A AUDIO
A DATA
audio
TX
RX
A DATA
TX
RX
A
A
Network AUDIO AUDIO AUDIO AUDIO
Network AUDIO AUDIO AUDIO AUDIO RX TX RX TX
RX
TX
RX
TX
OUT IN A IN A OUT B IN B OUT OUT IN A IN A OUT B IN B OUT
A A B B A A B B
+ - + - + - + - + - + -
+ - + - + - + - + - + -
B data
B AUDIO
TX
B data
B AUDIO
TX RX
B DATA
B DATA
audio
TX
TX
RX
B
RX RX TX
RX
RX
TX
Fiber-optic Fiber-optic Maintain physical separation
network data riser audio data riser or two-hour fire rating
A AUDIO
audio
TX RX
A DATA
A data
TX
RX
audio
A AUDIO
A DATA
TX
RX
A
A
Network AUDIO AUDIO AUDIO AUDIO RX TX
RX
TX
RX
TX
OUT IN A IN A OUT B IN B OUT A A B B
A A B B + - + - + - + - + - + -
+ - + - + - + - + - + -
B AUDIO
B DATA
B data
TX RX
B AUDIO
audio
B DATA
TX
RX
B
RX TX
RX
TX
From 3-ASU primary audio data
From 3-ASU primary audio data
Class B network and audio fiber-optic connections Class A network and audio fiber-optic connections
RX
RX
audio
A AUDIO
A
Network
A DATA
AUDIO AUDIO AUDIO AUDIO
RX
TX
A
AUDIO AUDIO AUDIO AUDIO
TX
TX
A A B B OUT IN A IN A OUT B IN B OUT
+ - + - + - + - + - + - A A B B
+ - + - + - + - + - + -
B data
TX
B AUDIO
B DATA
B data
TX RX
B AUDIO
audio
TX
B DATA
TX
RX
B
RX
RX
RX TX
RX
TX
Fiber-optic Copper wire network Fiber-optic
To next panel network data riser network data riser
data riser
A data
TX RX
audio
A data
A AUDIO
audio
A AUDIO
A DATA
TX
RX
A DATA
TX
RX
A
A
RX
RX TX
TX
OUT IN A IN A OUT B IN B OUT
RX
TX
B AUDIO
audio
B DATA
B data
TX
B AUDIO
TX
B DATA
RX
B
TX
RX TX
RX
TX
RX
RX
Fiber-optic
Fiber-optic audio data riser
audio data riser
CPU with 3-FIBMB TX RX
A data
audio
A AUDIO
RX
TX RX
A data
RX TX
A DATA
TX
RX
RX
TX
+ - + -
TX
TX RX
B AUDIO
audio
B DATA
- + - + - + - + -
TX
RX
+ - +
B
B AUDIO
RX TX
B DATA
RX
TX
A AUDIO
audio
A DATA
TX
RX
TX
A A B B
+ - + - + - + - + - + -
CPU
B AUDIO
RX
audio
B DATA
RX
CPU
From previous panel Network AUDIO AUDIO AUDIO AUDIO
OUT IN A IN A OUT B IN B OUT
A A B B
+ - + - + - + - + - + -
audio
A data
A AUDIO
A DATA
RX
TX
A
Network AUDIO AUDIO AUDIO AUDIO
RX TX
RX
TX
OUT IN A IN A OUT B IN B OUT
A A B B
+ - + - + - + - + - + -
B AUDIO
TX B data
B DATA
TX
RX RX
+
RX TX RX TX
B DATA A DATA
TB1
–
TEST
NORMAL
CPU with 3-FIBMB
B AUDIO A AUDIO
U2
J2
TX RX
A data
A AU DIO
audio
TX RX TX RX
A DATA
RX
TX
TX
+ - + - + - + - + - + -
U3
TX RX
B data
B AUDIO
B DATA
audio
TX
RX
TX
RX
RX
TX
U2
TX RX
A data
A AUDIO
audio
A DATA
TX
RX
RX
TX
+ - + -
U3
TX
B data
B AUDIO
B DATA
TX
RX
U2
audio
RX
RX
X
TX transceiver TX transceiver
TX
TX
Data and audio circuit for Class B using single mode and
multimode fiber
A AUDIO
audio
A DATA
TX
RX
RX TX
TX
B AUDIO
B DATA
audio
TX
RX
B
RX
RX TX
TX
Multimode transceivers
Data and audio circuit for Class A using single mode and
multimode fiber
SPECIFICATIONS
Installation 1LRM space on the rail
chassis
Module Configuration 8 Initiating Device Circuits, 4 of
which are convertible to 3-IDC8/4
Notification Appliance Circuits
Initiating Device Circuit (IDC)
Wiring Configuration Class B (Style B)
Detector Voltage 16.23 to 25.4 Vdc, Max. ripple TB1
400 mV
Short Circuit Current 75.9mA Max.
Circuit Resistance 50Ω Max. RX TX
JP1 JP2
1 1
Power 60 W @ 25 Vrms
100 W @ 70 Vrms
EOL Resistor 15 KΩ
INSTALLATION SHEET:
Maximum Wire Size 12 AWG (2.5 mm2 ) 3-IDC8/4
Termination Removable plug-in terminal Traditional Zone I/O Module
strips on module
Current Requirements (does not include LED/Switch module on NAC) INSTALLATION SHEET P/N: 270492 FILE NAME: 270492.CDR
Standby 50 mA @ 24 Vdc
REVISION LEVEL: 2.0 APPROVED BY: D. Becker
Alarm 330 mA @ 24 Vdc
Operating Environment DATE: 12/17/98 CREATED BY: D. Miner
Temperature 32°F (0°C) to 120°F (49°C)
EDWARDS SYSTEMS TECHNOLOGY, INC.
Humidity 93% RH, non-condensing SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
WIRING
1 4
UL/ULC Listed
2 3 4.7KΩ EOL
- - - - - -
+ + + + + + UL/ULC Listed
15KΩ EOL
IDC/NAC #2
IDC #4
1 2 3 4 5 6 7 8 9 10
JUMPER SETUP
To TB1 on Module
Circuits Signal Source
External via Terminals Internal 24 VDC
(3.5A max. per NAC pair)
IDC/NAC 1/2 JP1 to 1 & 2 JP1 to 2 & 3
TB1 JP2 to 1 & 2 JP2 to 2 & 3
Wiring Notes
1 1 1. For maximum wire resistance, refer to the appendix.
2 2
3 3
JP3 JP4
2. Maximum #12 AWG (2.5 mm2) wire; minimum #18 AWG (0.75
mm2).
3. Shields (if used) must be continuous and free from Earth Ground.
TB2 4. IDC/NACs 1 & 2 share the same input source. Set both JP1 & JP2
to 1/2 for the external source (TB1-9 & 10). Set JP1 & JP2 to 2/3 for
the internal 24 VDC source. NOTE: There is a 3.5 amp total limit for
both NAC1 and NAC2. External sources must be power limited.
5. IDC/NACs 5 & 6 share the same input source. Set both JP3 & JP4
10 9 8 7 6 5 4 3 2 1 to 2/3 for the external source (TB2-1 & 2). Set JP3 & JP4 to 1/2 for
the internal 24 VDC source. NOTE: There is a 3.5 amp total limit
for both NAC5 and NAC6. External sources must be power limited.
IDC/NAC #6
Product description Panel Silence: Yellow LED, integrated with Panel Silence
switch
Drill: Yellow LED, integrated with Drill switch
Alarm: Red LED
Power Test CPU
Fail
Gnd
Fault
Disable
Supervisory: Yellow LED
Reset Alarm
Silence
Panel
Silence Drill Trouble: Yellow LED
Monitor: Yellow LED
Operator controls
Reset switch
Alarm Silence switch
Panel Silence switch
Drill switch
Alarm queue switch
Alarm Supvr Trouble Monitor
Supervisory queue switch
Previous Trouble queue switch
1 2 3
Monitor queue switch
Message
Next
7 8 9
10-digit keypad with Enter and Delete keys
Details
Command
0 Menus
Details switch
Command Menus switch
Operating environment
The 3-LCD Display provides the operator interface for the Temperature: 32 to 120 °F (0 to 49 °C)
system. The 3-LCD mounts on the CPU panel support Humidity: 93% RH, noncondensing at 32 °C
brackets and is connected to the module with a ribbon cable.
Only one 3-LCD Display is required to provide point of control Installation instructions
for an entire network. Additional displays may be added to any 1. Remove the blank front panels from the support brackets
CPU module located throughout the network, providing an on the CPU.
additional point of control and/or annunciation.
2. Connect the ribbon cable on the 3-LCD to J1 on the CPU.
The display provides a 64- by 128-pixel, back-lit liquid crystal The colored edge is pin 1.
display for displaying text. LEDs are provided for: power, test,
CPU fail, ground fault, and disable indication. Switches with 3. Connect the ground cable on the 3-LCD to the 2-pin
integral LED feedback are provided for reset, alarm silence, header on the CPU. The 2-pin header is located just
panel silence, and drill functions. Message queue selection above the Network B terminals on TB2.
switches with integral LEDs are provided for the alarm,
4. Snap the 3-LCD onto the left mounting brackets provided
supervisory, trouble, and monitor message queues. Next and
on the CPU.
Previous Message switches scroll through the selected
message queue. The Details switch provides additional
information for the currently selected queue. The Command
Menus switch displays the main menu. The display includes a
10-digit numeric keypad with Enter and Delete keys. N
O
C N
C
N
O
C N
-
N
C
N
O
C N
C
A
Specifications
TROUBLE ALARM SUP
TB1
Installation:
Plugs into connector J1 on CPU module.
Mounts on the front of the CPU module.
Compatible CPU models: 3-CPU, 3-CPU1, 3-CPU3
Power requirements
Ribbon cable
Connected to Standby current Alarm current J1
Alarm Panel
Silence switch
Reset Silence Silence Drill
Specifications N C N N N C N
N C N -
Installation:
O C O A C O C
TR OU BLE ALAR M SU P
TB1
40 characters
Indicators
Power: Green LED
Test: Yellow LED 3-LCDXL CPU
CPU Fail: Yellow LED
INSTALLATION
TX RX
TX RX
J1
[3LDSM.CDR]
DC VOLTS
O 24
INSTALLATION SHEET:
3-LDSM
LED Display Support Local Rail Module
INSTALLATION SHEET P/N: 270485 FILE NAME: 270485.CDR
REVISION LEVEL: 2.0 APPROVED BY: D. Becker
DATE: 06/14/99 REVISED BY: D. Miner
EDWARDS SYSTEMS TECHNOLOGY, INC.
SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
3-MODCOM, 3-MODCOMP
Modem Communicator
3-MODCOMP
All 3-MODCOM specifications apply, plus the following.
Pager interface communication protocol
TAP: Telelocator Alphanumeric Protocol for pagers
J1
Installation instructions
1. Install a display faceplate in the recess on the front of the
P3
module if needed. Refer to the Control/LED Displays
installation sheet P/N 270493 for more information.
2. Mount the MODCOM in one space on the rail chassis.
The Modem Communicator (MODCOM) is designed with 3. Connect phone lines to Line 1 and Line 2 as indicated on
modem and dialer capabilities. The MODCOM is used for the wiring diagram on this sheet.
downloading information from remote sites.
The MODCOM is designed with dialer communication WARNINGS
capabilities. It sends alarm, supervisory, and trouble
information to a remote site using one or two telephone lines 1. Remove AC and battery power before installing or
(two per NFPA 72). This information can be reported in dual or removing option modules.
split format for sending to any desired receiver.
2. Components in this system are static sensitive. Discharge
The MODCOMP is designed with pager interface static buildup on your body before handling.
communication capabilities. Information is sent to remote sites
like the MODCOM, but can also be sent to individual 3. The MODCOM does not place calls or monitor the panel
or phone line during the programming process.
predefined pagers.
4. When programming emergency numbers and/or making
Multiple MODCOMs can be used in a cabinet and in a network
environment. Every 24 hours, the MODCOM performs an test calls to emergency numbers:
automatic test call to verify communications between the fire a. Remain on the line and briefly explain to the
alarm panel and the Central Monitoring Station (CMS). dispatcher the reason for the call.
b. Perform such activities in the off-peak hours, such as
Specifications early morning or late evenings.
All MODCOMs 5. It is up to the installer to verify DACT/receiver compatibility
Input power: 60 mA (supervisory), 95 mA (active) at least once per year.
Mounting: One expansion slot
Phone line: One/two loop start line on public switched
telephone network, pulse, or DTMF dialing. (Party, ground
start, and PBX lines are not acceptable.)
Wall connector: Standard RJ31X or RJ38X phone jack
Line supervision
Trouble when: On-hook line voltage < 10 V
Off-hook current < 10 mA
Telco compliance: Communications Canada CS-03,
FCC/CFR 47 Part 68
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 0 to 93% RH (noncondensing)
FCC registration number: EDWUSA-47115-AL-E
SURGE
PROTECTOR RING
(RED)
TIP
YELLOW
4 5 (GREEN)
3 6 TO PHONE LINE #2
RJ31X
8 PIN MODULAR (WIRED SAME AS
2 7 CONNECTOR FOR PHONE LINE #1)
BLACK
1 8 PHONE LINE #1
PREMISES 4 5 RJ31X
3 6
PHONES 8 PIN MODULAR
CONNECTOR FOR
2 7 PHONE LINE #2
1 8
NO T-TAPS
PERMITTED
[1] FERRITE
CLAMPS
[3]
Notes
7 FT [2]
[1] Connect J20 and J21 to RJ31X or RJ38X (2.13 M)
(CA31A or CA38A in Canada) telephone
jacks installed by an authorized telephone J20 J21
J 11
J10
MPFIB
Mounting NSHM
J8
J9
Bracket (rear view)
J 11
J10
Ribbon J1
cable
J2
Interface
CAB5 Installation Adapter
Half footprint
mounting space
3-PPS(/230)
MPFIB
Mounting
J8
J9
Bracket
Step 5: Mount (snap) the NSHM to the MPFIB mounting
J 11
J10
bracket
Note: The ribbon cable must be connected before completing
this step.
Step 2: Mount the Interface Adapter to the CPU
Mounting
Snap rivet bracket
J2 J2
J2 CPUx
Interface Snap rivet
Adapter
Connected to Ribbon
Interface Adapter cable
Step 3: Set the jumper on the NSHM Step 6: Set up the modem
DIP switch SW1 and SW2 must be set up prior to installation.
The following tables show the proper switch positions.
+ -
NSHM
Rear view
JP1 1 ON
Network 12 2 SW1 SW2
B Side 3 3 4-wire mode
JP1 12 34 5 67 8
NSHM
TB1
+ -
JP1
Network 12
3
B Side
Modem 2
(if used)
Ditek
GFD
Network [1]
[3]
A Side [2]
Ribbon NSHM1
Cable
CPU
Note: No wiring
permitted to Network Network CPU Network
B IN connection. B Side Up to 6 miles A Side
TB2 (see Specifications) Note: No wiring
Network permitted to Network NSHM1
OUT IN Ribbon
A A B B A OUT connection. Cable
+ - + -
TB2
Network
OUT IN
A A B B
+ - + - Network
Ditek
From previous panel controller B Side
[1]
TB2-NETWORK IN B+/B- [2]
Ditek
GFD
[1] Network
[3]
[2] A Side
Ribbon
NSHM1
CPU Cable
Ditek Ditek
GFD GFD
[1] [1]
[3] [3]
[2] [2]
Network
A Side
Ribbon
NSHM1
CPU Cable CPU
Network
Network A Side
Note: No wiring A Side Note: No wiring
permitted to Network CPU permitted to Network
B IN connection. Network Single Node A OUT connection.
Ribbon
NSHM1
Ribbon Cable
B Side Cable
NSHM2
TB2 TB2
Network Network
OUT IN OUT IN
A A B B A A B B
+ - + - + - + -
TB2 Network
Network Network
OUT IN B Side
A A B B B Side
Ditek + - + -
[1]
[2]
To next panel controller From previous panel controller
TB2-NETWORK IN B+/B- TB2-NETWORK IN A+/A-
Up to 6 miles Ditek
(see Specifications) [1] Up to 6 miles
[2] (see Specifications)
To alternate
24 Vdc power
supply
TB1
+ -
JP1
1
2
3
TX RX
Open 1/2
Installation instructions
1. Set the jumpers as required.
2. Install a display or blank faceplate on the front of the
module.
The 3-OPS Off Premises Signaling module provides three 3. Mount the 3-OPS module in one space on the rail chassis.
independent reverse polarity circuits for transmitting alarm, 4. Install the provided snap rivet fasteners.
supervisory, and trouble signals to compatible receivers.
Reversing a circuit's polarity indicates an active alarm 5. Connect all wiring using the wiring diagram on this sheet.
condition; loss of circuit continuity indicates circuit trouble. As
an alternate to three independent circuits, the reverse polarity Wiring diagrams
alarm circuit may be configured to transmit panel trouble by
removing circuit continuity, when using a compatible single Note: When wiring the module field wiring plug, the scalloped
circuit reverse polarity receiver. A supervised local energy edge must face down and terminal clamp screws face up. The
master box trip circuit is also provided to activate a 14.5 W pins are numbered right to left.
master box trip coil. A configurable NO/NC trouble contact is
provided on the module.
The 3-OPS module requires one connection on the rail chassis
and is secured to the assembly using snap rivet fasteners. All
field wiring connections to the 3-OPS module are made via
plug-in connectors, permitting termination of field wiring without
having the module installed in the enclosure. The plug-in
connectors and snap rivet mounting also facilitate rapid
remove-and-replace troubleshooting without the use of tools. Three reverse polarity circuit configuration
The module features a hinged front panel for mounting
displays or a blank protective faceplate. To TB1 on Off Premises
Signal Module
Specifications
Installation: 1 space on the rail chassis Trouble relay is
Circuit configuration terminals 1 and 2
Reverse polarity: 3 independent reverse polarity circuits
for alarm, supervisory, and trouble notification [10] [3] [4] [5] [6] [7]
Local energy: 14.5 W coil Dedicated line to
Maximum wire size: 12 AWG (2.5 sq mm) reverse polarity
Trouble relay: NO or NC configuration rated 24 Vdc @ 1 A alarm receiver
Termination: Removable plug-in termination strips on module
[3] [4] [5] [6] [7]
Open circuit voltage: 24 Vdc, nominal
Dedicated line to
Short circuit current: 7 mA max. reverse polarity
Current requirements (does not include LED/Switch module) trouble receiver
Standby current: 53 mA @ 24 Vdc
Alarm current: 147 mA @ 24 Vdc [3] [4] [5] [6] [7]
Operating environment Dedicated line to
Temperature: 32 to 120 °F (0 to 49 °C) reverse polarity
Humidity: 93% RH, noncondensing at 32 °C supervisory receiver
[10]
Municipal circuit
SPECIFICATIONS
RCC7R Cabinet
RCC14R Cabinet
C
BACKBOX
1.25 in 1.25 in 1.25 in
G (3.18 cm) (3.18 cm) (3.18 cm)
5.5 in 5.5 in 5.5 in
H (13.97 cm) (13.97 cm) (13.97 cm)
[3RCC21A2.CDR]
Non-power limited
Wire
POWER LIMITED wiring area under
Right Front
rail assembly
NON-POWER LIMITED
Left Rear
Left Side View
Battery Battery
PRODUCT DIAGRAM
SPECIFICATIONS
RCC7R-E Cabinet
RCC14R-E Cabinet
N
J RCC7R-E RCC14R-E RCC21R-E
I
M 23.36 in 35.61 in 47.75 in
A (59.3 cm) (90.4 cm) (121.29 cm)
TOP VIEW
H
1.25 in 1.25 in 1.25 in
B (3.18 cm) (3.18 cm) (3.18 cm)
ALL KNOCKOUTS 14.1 in 14.1 in 14.1 in
FOR 3/4" CONDUIT C (35.8 cm) (35.8 cm) (35.8 cm)
OUTER DOOR (1.9 cm)
GROUND
F
E 23.25 in 35.47 in 47.72 in
STRAP D (59.1 cm) (90.1 cm) (121.21 cm)
4.37 in 4.37 in 4.37 in
E (11.1 cm) (11.1 cm) (11.1 cm)
5.5 in 5.5 in 5.5 in
F (13.97 cm) (13.97 cm) (13.97 cm)
C
BACKBOX
1.25 in 1.25 in 1.25 in
G (3.18 cm) (3.18 cm) (3.18 cm)
5.5 in 5.5 in 5.5 in
H (13.97 cm) (13.97 cm) (13.97 cm)
[3RCC21A2.CDR]
Operating Environment
Temperature 32 - 120 °F (0 - 49 °C)
Humidity 93% non-condensing
WARNINGS 3-REMICA
1. This product contains components which are
sensitive to static electricity. Failure to follow proper
handling procedures to prevent damage from LOCAL PAGE ACTIVE
REMOTE PAGE BUSY
failure.
2. Ensure the 24VDC riser is deenergized before
making cable connections.
JUMPER SETTINGS
Jumper JP1 and JP2:
Position A: Selects ac supervision when connecting
the audio output to 3-ASU.
Position B: Selects dc supervision when connecting
the audio output to 3-REMICA.
FRONT SIDE
INSTALLATION INSTRUCTIONS
INSTALLATION SHEET:
1. Remove the top module retainer bracket on the inner
door of the remote annunciator enclosure.
2. Loosen the bottom module retainer bracket.
3. Insert the bottom of the 3-REMICA into the bottom 3-REMICA Remote Microphone
module retainer bracket next to the annunciator panel
controller.
4. Tilt the 3-REMICA forward until the top touches the INSTALLATION SHEET P/N: 387466 FILE NAME: 387466.CDR
inner door. REVISION LEVEL: 2.0 APPROVED BY: D. Munn
5. Tighten the bottom module retainer bracket.
DATE: 19JAN00 CREATED BY: M. Rimes
6. Secure the top module retainer bracket to the inner
door. EDWARDS SYSTEMS TECHNOLOGY, INC.
SARASOTA, FL: 941-739-4300 FAX 941-753-1806
7. Connect the cable assembly from P3 on the CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
annunciator panel controller to P4 on the 3-REMICA. OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
FIELD WIRING
AUDIO IN
From Remote Microphone
From secondary See Note 2
24VDC riser KEY IN
From primary NC
24VDC riser C To trouble relay
NO interface circuit
TB1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
JP2
Place jumper to position A when B
audio output is connected to an JP1
Audio Source Unit input. A
B Place jumper to position A when
audio output is connected to an
JP2 A Audio Source Unit input.
Place jumper to position B when B
audio output is connected to the JP1
Remote Microphone input. A
B Place jumper to position B when
audio output is connected to the
A Remote Microphone input.
Notes:
1. Power-limited and supervised.
2. Terminate KEY IN input with 1.8 k! EOL resistor
when not used.
47 k! EOL
3-REMICA
TB1-19
TB1-20
8 7
INSTALLATION INSTRUCTIONS
PAGING
1. On the 3-REMIC circuit card assembly, configure JP1 and JP2 LOCAL
PAGE
ACTIVE
assembly using four #6-32 X 1/2 pan head screws. See below.
3. Connect field wiring to 3-REMIC circuit card.
3-REMIC Assembly
4. Connect the ribbon cable on the page control housing assembly
to J1 on the 3-REMIC circuit card.
5. Position the page control housing on the threaded studs and
secure using the four washers and nuts provided.
J11
J10
J11
J10
To remote microphone
TB1-AUDIO INPUT terminals
4
To remote microphone
TB1-KEY INPUT terminals
2
Notes:
1. All wiring supervised and power-limited.
+ + E AUDIO KEY AUDIO KEY AUDIO KEY NC C NO 2 Terminate KEY input terminals with 1.8 k! EOL
2 G 2 G G resistor when not used.
4 N 4 N N OUTPUT INPUT 2 INPUT 1 TROUBLE
V D V D D
3 Shield required when audio riser shares conduit
TB1 with telephone riser.
Remote microphone
4 Connect to audio source unit TB1-REMOTE MIC AUDIO
and -REMOTE MIC KEY input terminals when last remote
microphone unit in chain.
JP2
Place jumper to position A when B
audio output is connected to an JP1
Audio Source Unit input. A
A B Place jumper to position B when
JP2 audio output is connected to the
Remote Microphone input.
Place jumper to position B when B
audio output is connected to the JP1
Remote Microphone input. A
A B Place jumper to position A when
audio output is connected to an
Audio Source Unit input.
47 k! EOL
3-REMICP
TB1-19
TB1-20
8 7
Grounding
strap
Outer door
The remote annunciator cabinet door assembly consists of an inner 3-RLCM/D, 3-6ANN/D, and 3-10ANN/D
door and an outer door. The outer door has a viewing window and is
secured in the closed position with a key lock. The inner door provides Remote Annunciator
mounting space for the panel electronics and is secured in the closed
position with a captive screw.
Cabinet Doors
The line of remote annunciator cabinet door assemblies include:
INSTALLATION SHEET P/N: 387310 FILE NAME: 387310.CDR
Model Description
REVISION LEVEL: 2.0 APPROVED BY: K. Patterson
3-RLCM/D Grey door with window for the 3-LCDANN semi-flush
and surface mount cabinets DATE: 06DEC99 CREATED BY: G. Sutton
3-6ANN/D Grey door with window for the 6-ANN semi-flush
and surface mount cabinets EDWARDS SYSTEMS TECHNOLOGY, INC.
SARASOTA, FL: 941-739-4300 FAX 941-753-1806
3-10ANN/D Grey door with window for the 10-ANN semi-flush CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
and surface mount cabinets OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
INSTALLATION INSTRUCTIONS
Outer door
Inner door
Grounding
strap
Outer door
The remote annunciator cabinet door assembly consists of an inner 3-RLCM/D-E, 3-6ANN/D-E, and 3-10ANN/D-E
door and an outer door. The outer door has a viewing window and is
secured in the closed position with a turn knob lock. The inner door
Remote Annunciator
provides mounting space for the panel electronics and is secured in the Cabinet Doors
closed position with a captive screw.
The line of remote annunciator cabinet door assemblies include:
INSTALLATION SHEET P/N: 387553 FILE NAME: 387553.CDR
Model Description
REVISION LEVEL: 1.0 APPROVED BY: K. Patterson
3-RLCM/D-E Grey door with window for the 3-LCDANN-E semi-
flush and surface mount cabinets DATE: 06DEC99 CREATED BY: G. Sutton
3-6ANN/D-E Grey door with window for the 3-6ANN-E semi-flush
and surface mount cabinets EDWARDS SYSTEMS TECHNOLOGY, INC.
SARASOTA, FL: 941-739-4300 FAX 941-753-1806
3-10ANN/D-E Grey door with window for the 3-10ANN-E semi-flush CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
and surface mount cabinets OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
INSTALLATION INSTRUCTIONS
Outer door
Inner door
J3 J2
Circuit capacitance: 0.3 mF, max.
Network audio circuit
Circuit configuration: Class A (3-RS485A only), Class B
(3-RS485A and 3-RS485B)
Isolation: Audio AIN and Audio BIN isolated, Audio AOUT
and Audio BOUT not isolated
Wire type: Twisted pair (6 twists per foot min.),
18 AWG (0.75 sq mm) min.
Circuit length: 5,000 ft (1,524 m) between any 3 panels CPU
Circuit resistance: 90 W, max. rear view
Circuit capacitance: 0.09 mF, max.
Wiring diagrams
Class A wiring
3-SAC
SAC bus SAC bus TB2
A A B B Ferrite
+ +
clamps
[4]
4 1
[1] [2]
The 3-SAC is a high-speed module used to support Card
Reader Controller modules and Keypad Display modules. The [3] Keypad
3-SAC is capable of Class A and Class B configuration and CRC Display CRC
occupies one rail module space.
The 3-SAC module can support a maximum of 62 CRCs or
KPDISPs. Events are passed to the 3-SAC module, then
passed to the 3-CPU1 for alarm processing.
Class B wiring
Specifications
3-SAC
Mounting: One expansion slot SAC bus SAC bus TB2
Device support A A B B
+ + Ferrite
Class A: 30 devices
clamps
Class B: 62 devices (31 per loop)
Wire size: 14 to 22 AWG (1.5 to 0.25 sq mm) 4 1 [4]
SAC bus wiring 120 ! EOL
Type: unshielded, twisted pair, > 6 twists per foot resistors
Maximum run from 3-SAC: 4,000 ft (1,220 m) @ 25 pF/ft [1] [2]
Maximum total capacitance: 0.1 !F
Maximum total resistance: 52 " Keypad
[3] CRC Display CRC
Maximum voltage: 10 Vdc
Maximum current: 250 mA
Current requirements (does not include LED/Switch module) [1] [2]
Standby/Alarm: 40 mA @ 24 Vdc
Operating environment Keypad
CRC Display CRC
Temperature: 32 °F (0 °C) to 120 °F (49 °C)
Humidity: 93% RH, noncondensing
WARNINGS Notes
[1] Refer to device installation sheets for proper wiring.
1. Remove AC and battery power before installing or [2] Maximum of 30 devices for Class A, 62 devices
removing option modules. (31 per loop) for Class B.
2. Components in this system are static sensitive. Discharge [3] Security Access Control Bus.
static buildup on your body before handling. [4] Install the provided ferrite clamps as shown. The clamps
must be mounted on the lines as they exit the cabinet.
5. Up to 4,000 ft @ 25 pF/ft (1,220 m). All wiring is power-
limited and supervised.
47 kΩ EOL
(Yellow-Violet-Orange)
To initiating device
INSTALLATION INSTRUCTIONS circuit +/- inputs
3-TAMP
3-TAMP5
3-TAMPRCC
#8 lock washer
(2 places) INSTALLATION SHEET P/N: 387422 FILE NAME: 387422.CDR
REVISION LEVEL: 2.0 APPROVED BY: B. Shivers
#8-32 nut
(2 places) DATE: 17NOV99 CREATED BY: G. Sutton
Figure-1: Tamper switches mount to the top or side of their respective EDWARDS SYSTEMS TECHNOLOGY, INC.
cabinets and are secured using hardware provided in the hardware SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
kit. This figure shows the installation of a 3-TAMP. OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
PRODUCT DESCRIPTION SPECIFICATIONS
The model 3-ZA20A/B and 3-ZA40A/B audio amplifiers demultiplex the 8 Installation: 1 rail chassis slot position
multiplexed audio signals on the network audio riser. Under command of Frequency Response: 400 Hz to 4 kHz at -3 dB
the network, 1 of the 8 available signals is distributed over the speaker Harmonic Distortion: < 7%
circuit. Command and control signals for the amplifier are sent and Audio Circuit:
received via the network data riser in response to network programming. Wiring Configuration
3-ZA20B/40B Class B (Style Y)
Amplifers are in 20- and 40-Watt, Class A and Class B versions.
Supervised, power-limited 25 Vrms or 70 Vrms outputs are available on 3-ZA20A/40A Class A (Style Z) or Class B (Style Y)
both versions. Amplifiers use a Class D switch mode design to provide EOL Resistor 15 k! (internal on 3-ZA20A/40A)
better than 80% efficiency. Each amplifier's output is directly wired to a Outputs:
single speaker zone. 3-ZA20A/20B 20 watts @ 25 Vrms or 70 Vrms
3-ZA40A/40B 40 watts @ 25 Vrms or 70 Vrms
Each amplifier has a 1 kHz temporal (3-3-3) tone generator for use as an Current Rating
evacuation signal in the event of a fault with the network audio circuit. A Standby 35 mA (all models)
standby amplifier may be configured for automatic replacement of any Alarm 1.25 A (3-ZA20A/20B)
online amplifier configuration, in the event of an online amplifier failure.
2.30 A (3-ZA40A/40B)
The standby amplifier must be the same wattage as the largest amplifier
within the enclosure. The amplifiers draw power from the primary and 24 Vdc NAC Circuit:
booster power supplies which must be sized according to the enclosure Wiring Configuration
electrical load. 3-ZA20B/40B Class B (Style Y)
3-ZA20A/40A Class A (Style Z) or Class B (Style Y)
Each amplifier is also provided with an independently controlled Voltage 24 Vdc nominal
supervised, power limited 24 VDC Notification Appliance Circuit (NAC) Current 3.5 A
rated at 3.5 A. This facilitates the addition of visual notification appliances EOL Resistor 15 k! (internal on 3-ZA20A/40A)
to audio notification circuits.
Termination Removable plug-in terminal strips
2
Each amplifier requires one LRM space on the rail chassis and is secured Maximum Wire Size 12 AWG (2.5 mm )
to the assembly using snap rivet fasteners. All field wiring connections to Backup Tone 1 kHz temporal (3-3-3)
the amplifier module are made via plug-in connectors, permitting Operating Environment
termination of field wiring without the module installed in the enclosure.
Temperature 32 - 120 °F (0 - 49 °C)
Humidity 93% RH, non-condensing
WARNINGS
1. This product contains components that are sensitive to static
electricity. Failure to follow proper handling procedures may cause 3-ZA20A/B, 3-ZA40A/B
equipment failure.
2. Rail modules should not be plugged into the rail chassis assembly
while 24 Vdc is present on the rail. Failure to remove 24 Vdc may UNUSED UNUSED UNUSED
TB1
24VDC
NAC/B
+ -
UNUSED
Audio power
damage the equipment. module
subassembly
3. Operating the amplifier at an output greater than that required by
the speaker may overdrive the speaker circuit and result in damage Audio amp 25Vrms 70Vrms
Configuration
to the equipment. transformer jumper
subassembly
J4
J3
JP2
1
jumpers
TB2
BACK-UP NAC/A NAC/B
- + - + S - + S - +
2. Set jumpers JP1 and JP2 on the audio power module subassembly
for 25 or 70 Vrms, depending on the input required by the audio
circuit speakers. Front view Rear view
JP1 JP2
25 Vrms 2 to 3 2 to 3 INSTALLATION SHEET:
70 Vrms 1 to 2 1 to 2
3. Set the jumper on the audio amp transformer subassembly for 25 or
3-ZA20A, 3-ZA20B, 3-ZA40A, 3-ZA40B
70 Vrms, depending on the input required by the audio circuit Zoned Audio Amplifiers
speakers.
4. Slide the amplifier module into the required rail chassis slot
position.
INSTALLATION SHEET P/N: 387463 FILE NAME: 387463.CDR
5. Gently push the zone amplifier module into the connectors to
ensure good contact. REVISION LEVEL: 2.0 APPROVED BY: E. Onstine
6. Secure the zone amplifier module to the rail by pushing in the top DATE: 05FEB00 CREATED BY: G. Sutton
and bottom snap rivet fasteners.
EDWARDS SYSTEMS TECHNOLOGY, INC.
7. Connect the field wiring. SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
Note: The gain control pot may be adjusted later for desired output OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
level. Fully CCW is maximum gain and fully CW is minimum gain. INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
FIELD WIRING
Notes:
4 5
UL/ULC
LISTED
S S
EOL
2
Class A (Style Z)
UL/ULC
LISTED
EOL
Class A (Style Z)
TB1
3-ZAxx
Backup amplifier First amplifier on circuit Second amplifier on circuit Last amplifier on circuit
Notes:
1. All wiring supervised and power-limited.
2. Backup amplifier must be rated greater than or equal to the
other amplifiers to which it is connected and be installed in
the same enclosure.
3. Backup amplifier wiring must be rated greater than or equal to
field wiring used on amplifiers connected to the backup amplifier.
3-ZAxx 3-ZAxx
TB2 TB2
Warning: 3-ZAxx amplifiers must
BACK-UP NAC/A NAC/B BACK-UP NAC/A NAC/B
be configured for 25 Vrms output.
S S S S
Class A only
TB1
CH1 Out
SIGA-AAxx
UL/ULC listed 15 k! EOL CH1 In
for Class B circuits only
Class A only
CH2 Out
Notes TB3
1. Configure the 3-ZAxx audio amplifiers for 25 Vrms. UL/ULC listed 15 k! EOL CH2 In
2. A maximum of 16 SIGA-AAxx audio amplifiers may for Class B circuits only
be connected to the output of a single 3-ZAxx audio
amplifier. From Signature controller
or
3. Shield required when the audio riser wiring shares previous Signature device
the same conduit as the telephone riser.
To next
Signature device
Gain control
Adjusting the amplifier output levels JP2
You must adjust the output level of all zoned amplifier Mounting
brackets
Mounting
brackets
Notes
1. This product should only be installed in a CHAS7
containing a primary or booster power supply. 3-ZA90 Zoned Audio Amplifier
2. Do not use the gain control pot to adjust output level
except when calibrating the amplifier as described in the
Installation and Service Manual. Doing so can damage the INSTALLATION SHEET P/N: 387516 FILE NAME: 387516.CDR
amplifier.
REVISION LEVEL: 5.0 APPROVED BY: R. Miller
3. When using Signature Series CC1 or CC2 modules to DATE: 23AUG04 CREATED BY: M. Rimes
switch amplifier output branch circuits, a maximum of 10
modules may be connected to the output of an amplifier. EDWARDS SYSTEMS TECHNOLOGY, INC.
SARASOTA, FL: 941-739-4300 FAX 941-753-1806
CHESHIRE, CT: 203-699-3000 FAX 203-699-3075
OWEN SOUND, CANADA: 519-376-2430 FAX 519-376-7258
INTERNATIONAL, CANADA: 905-270-1711 FAX 905-270-9553
FIELD WIRING
Notes
Zone Audio Amplifier [1] All wiring supervised and power-limited.
[2] Install listed 15 kΩ EOL resistor on last device only when wired as
Class B (Style Y) riser.
TB1
BACK-UP NAC/A NAC/B [3] Polarity of signal circuit shown in supervisory state.
- + - + S - + S - + [4] Shield required when audio riser shares same conduit as telephone
riser.
[5] Electrical supervision requires wire runs to be broken at each
device. Do not loop signal wires around device terminals.
[4] [6]
[6] Twisted pair not required when audio circuit riser shares conduit
exclusively with 24 Vdc NAC riser.
Class B (Style Y)
UL/ULC
S S LISTED
EOL
[2]
Class A (Style Z)
Mounting Mounting
brackets brackets 25 Vrms
JP1 70 Vrms
Ribbon cable Ribbon cable
connector for left connector for right
control/display control/display
module module JP2: Selects the amplifier output voltage configuration to report
to the panel controller
Gain control
Mounting Mounting
25 Vrms
brackets brackets
JP2 70 Vrms
BACK-UP NAC/A NAC/B
- + - + - + - +
Note: JP1 and JP2 must be set for the same output voltage.
The 3-ZA95 Zoned Audio Amplifier module is a key component
in an emergency communication system that consists of Installation instructions
audible notification appliances (speakers only). The 3-ZA95
provides the following: To install the amplifier:
TB1
BACK-UP NAC/A NAC/B
- + - + S - + S - +
[4] [6]
Class B (Style Y)
UL/ULC
S S listed
EOL
[2]
Class A (Style Z)
Notes
1. All wiring is supervised and power-limited
2. Install a listed 15 k EOL resistor on the last device only when wired as a Class B (Style Y) riser
3. Polarity of signal circuit is shown in the supervisory state
4. Shield required when audio riser shares the same conduit as the telephone riser
5. Electrical supervision requires wire runs to be broken at each device. Do not loop signal wires around device terminals.
6. Twisted pair is not required when the audio circuit riser shares the conduit exclusively with the 24 Vdc NAC riser
Notes
1. All wiring is supervised and power-limited
2. Backup amplifier must be rated greater than or equal to the other amplifiers to which it is connected and must be installed in
the same enclosure
3. Backup amplifier wiring must be rated greater than or equal to the field wiring used on amplifiers connected to the backup
amplifier
10ANN/B(-S)
2-CPU
The following models identify the same wallbox:
Model Mounting
10ANN/B Surface Optional module
10ANN/B-S Semi-flush
Semi-flush
3
14.48 in (36.78 cm) 2
6
3
2.75 in (6.99 cm)
13.19 in 12.1 in
(33.5 cm) (30.7 cm)
Detail
1 Ground Strap
2
2 Wallbox 3 1
3 Ground Lug 3
4 Typical Knockout 6
Surface mount 4
5 Earth Ground Wire 5
16.1 in (40.9 cm) 6 Outer Door
INSTALLATION SHEET:
10ANN/B(-S)
Semi-flush
23.86 in (60.60 cm)
Surface mount
2 in 1 in 2 in
2 in 2 in
2 in 2 in
Specifications
Size: 23.65 x 25.85 x 3.86 in (60.07 x 65.66 x 9.80 cm)
Material: 14 gauge steel Remove unused knockout
Finish: Red textured enamel and insert knockout plug.
Key locks: 4
Screws:
10-32 x 1 in machine screws: 4
10-32 x 2 in machine screws: 10
Compatible with 3-RCC7R cabinet only
Installation instructions
1. Disconnect all power before installing.
2. Remove the existing door from the cabinet. Figure 2: Knockout plug
3. Place the ATCK cover over the cabinet and lock the
four key locks. The key locks hold the cover in place. Warnings
4. Use the ATCK cover as a template to mark screw Disconnect all power before installing or drilling holes.
holes on all sides of the cabinet (fourteen holes). When drilling holes into the cabinet, make sure not to
(Newer cabinets include the screw holes.) drill into any existing wires or hardware.
5. Remove the cover and drill all marked holes with a
1/4-inch drill bit.
6. Remove any unused knockouts and insert knockout
plugs. (See Figure 2.)
Enclosure Enclosure
Module Module
NC NO
Bell Code output relay normally-open Daughter board Main board
JP1
Bell Code output relay normally-closed
NC NO
Temporal output relay normally-open
JP2 TB1-1 through TB1-12 TB1-1 through TB1-7
Temporal output relay normally-closed
Round selection
ON S1-3 Description
ON 4 rounds
1 2 3 4 5 6 7 8
OFF 6 rounds
Parity settings
ON S1-6 Description
OFF Even parity
1 2 3 4 5 6 7 8
ON No parity
Installation instructions
1. Fill out the identification label and insert it between the front
membrane and the circuit board.
Display
Installation
Label
3-24R 3-12SG 3-12/S1GY 3-6/3S1G2Y
3-24Y 3-12SR 3-12/S1RY 3-6/3S1GYR
3-24G 3-12SY 3-12/S2Y
3-12RY
SPECIFICATIONS
Read Distance Option D Buffered Direct Connect Keypad
Over all Operating Limits, minimum (@12 Vdc): 5.0 inches (12.7 Operating Voltage Range (+dc): 10 Vdc -26 Vdc
cm) Input Voltage (Maximum Data 0/1 Lines): 14 Vdc
Non-Metallic Mounting, typical (@12 Vdc): 8.0 inches (20.3 cm) Input Voltage (Maximum Interface Lines): 14 Vdc
Mounted on Metal, typical (@12 Vdc): 5.5 inches (14 cm) Operating Parameters
Environmental Characteristics Excitation Frequency: 125 KHz
Operating Temperature Range: -30oC to 65oC (-22oF to 150oF) Duty Cycle (alternate power level rate): 20% @ 60mS period
Storage Temperature Range: -40oC to 85oC (-40oF to 185oF) Read and Report Speed (26 bit Wiegand Card): 175mS
Operating Humidity Range: 5% to 95% non-condensing Maximum Cable Distance to CRC: 500 feet (152 meters)
Operating Vibration Limit: .04 g2/Hz 20-2000Hz LED Type: Bi-colored Red/Green
Operating Shock Limit: 30 g, 11mS, Half Sine LED Operation (CRC control of red/green): <.5 V on LED control
Weight: 11.3 oz (310 gms) line
Dimensions: 5. inches (12.7 cm) x 5. inches (12.7 cm) x 1 inch Beeper Operation (CRC control): <.5 V on beeper line
(2.54 cm) LED Control (default): internal/single
Power Requirements Beeper Control (default): Beeper enabled
Power supply: Linear type recommended Wiegand Data Pulse Widths (default): 40uS
Operating Voltage Range (+dc): 10 Vdc -28.5 Vdc Wiegand Data Interval (default): 2mS
Maximum Average Current 12 V: 90 mA
Transient Protection (all terminals): UL 294
Reverse Voltage Protection: YES
Input Voltage (maximum data-0/1 lines): 28.5 Vdc
Input Voltage (maximum interface lines): 28.5 Vdc
WIRING CONNECTIONS
+DC Ground Data0 Data1 Shield Green Red Beeper Hold Tamper Tamper
Ground LED LED Not Used Common Select
Red Black Green White Drain Orange Brown Yellow Blue --- ---
P1
TB1 123
1 - DC + TM
2 - GND
3 - DATA "0"
4 - DATA "1"
5 - DATA RTN 3.28" (8.33cm)
If no electrical box
7/64 (.109) inch
6 - Green LED
diameter hole 7 - Red LED 5.00" (12.7cm)
8 - Beeper
9 - Hold
10 - COM
11 - Tamper
TAMPER SW
1 - n/o SW1
3 - n/c P2
TM
5.00" (12.7cm)
1.00" (2.54cm)
Power Requirements
Operating Voltage Range (+dc): 5.1 Vdc -16.0 Vdc
Absolute Maximum (+dc non-operating): 18.0 Vdc
Maximum Average Current 12 V: 50 mA
Transient Protection (all terminals): 8,000 V
Reverse Voltage Protection
Input Voltage (maximum data-0/1 lines): 16.0 Vdc
Input Voltage (maximum interface lines): 16.0 Vdc
Operating Parameters
Excitation Frequency: 125 KHz
1.00"
Duty Cycle (alternate power level rate): 20% @ 60mS period
Read and Report Speed (26 bit Wiegand Card): 175mS
Maximum Cable Distance to CRC: 500 feet (152 meters) INSTALLATION SHEET
LED Type: Bi-colored Red/Green
LED Operation (CRC control of red/green): <.5 V on LED control
line CR-5365
Beeper Operation (CRC control): <.5 V on beeper line Proximity Reader
LED Control (default): internal/single
Beeper Control (default): Beeper enabled INSTALLATION SHEET P/N: 3100110 FILE NAME: 3100110.CDR
Wiegand Data Pulse Widths (default): 40uS REVISION LEVEL: 2.0 APPROVED BY: R. Tucker
Wiegand Data Interval (default): 2mS DATE: 18JUL00 CREATED BY: S. Hawes
WIRING CONNECTIONS
+DC Ground Data0 Data1 Shield Green Red Beeper Hold Card
Ground LED LED Not Used Present
Red Black Green White Drain Orange Brown Yellow Blue Violet
WIRING CONNECTIONS
+DC Ground Data0/ Data1/ Shield Green Red Beeper Hold Card
Data Clock Ground LED LED Not Used Present
Red Black Green White Drain Orange Brown Yellow Blue Not Used
BEEPER (YELLOW)
RED LED (BROWN)
GROUND (BLACK)
5-12 VDC (RED)
HOLD (BLUE)
3.0" (7.62cm)
ELECTRICAL RATING 5-12 VDC/50mA
5395
operation.
LISTED
UL
8T29
R
4.66" (11.84cm)
1.68" (4.27cm)
Back View
to 1" (2.54cm)
diameter hole
3/8" ( .95cm)
WIRING CONNECTIONS
+DC Ground Data 0 Data 1 Shield Green Red Beeper Hold Card
Ground LED LED Present
Red Black Green White Drain Orange Brown Yellow Blue Violet
BACK VIEW
1.35" (3.43cm)
3.14" (7.98cm)
2.69" (6.83cm)
DRAIN - SHIELD GROUND
WHITE - DATA 1/CLOCK
GREEN - DATA 0/DATA
ORANGE - CARD PRESENT
BLACK - GROUND
RED - 4.75 VDC TO 16 VDC
3/8" ( .95cm)
to 1" (2.54cm)
diameter hole
1.70" (4.32cm)
2. Remove the PC board from the backplate using the snaps 8. Mount the battery insulator (provided) over the battery.
at the top of the backplate. Make sure the battery leads are covered and the battery
wires are located to the left side of the battery.
Caution: Observe static-sensitive handling procedures. 9. Secure the battery and insulator using the Velcro straps.
3. Determine the mounting location. Remember to leave 10. Connect all wiring.
clearance for cover removal.
11. Attach the cover with a right-to-left or left-to-right motion.
4. Mount the CRC backplate to a compatible electrical box. This will properly engage the tamper switch.
5. Install the PC board to the backplate. Position the board in
the slots at the bottom of the backplate, then snap it into
place with the snaps at the top of the backplate.
Wiring diagram
- SAC bus IN
Reader GND
GREEN LED
Strike PWR
+24 V OUT
Strike GND
-24 V OUT
Loop GND
RED LED
Loop 2 IN
Loop 1 IN
+24 V IN
Sounder
-24 V IN
Data 0
Data 1
NO
NC
TB-1
C
J1
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
16.5 Vac IN 2
Security Access
16.5 Vac IN 1 Dry contact Control Bus See Application
TB-2 connections wiring diagram
Listed
power supply
Control Panel
[1] 24 Vdc power supply from PPS/M [3] The -24 Vdc wire acts as the circuit common when using an additional power supply
[2] SAC bus from 3-SAC [4] Power supply must have ground fault detection circuits disabled
CRCs wired to an integrated control panel with an additional remote power supply
Circuit Optional
Control Panel common [3] +24 Vdc
[4]
[1]
To next
[2] CRC
AC
AC
[3] The -24 Vdc wire acts as the circuit common when using an additional
AC
power supply
transformer
[4] We recommended that you connect the +24 Vdc wire to all CRCs
[1]
24 Vdc +
24 Vdc -
... ...
TD B+
GND
TD A-
... ...
2 3 4 17 18 19 20 2 3 4 17 18 19 20
Converter TB-1 TB-1
1 1
2 CRC/ 2 CRC/
TB-2 CRCXM TB-2 CRCXM
CRCs wired to the ACDB-KE through a converter and powered from a remote power supply
... ...
TD B+
GND
TD A-
... ...
2 3 4 17 18 19 20 2 3 4 17 18 19 20
Converter TB-1 TB-1
1 1
2 CRC/ 2 CRC/
TB-2 CRCXM TB-2 CRCXM
GND
AC
AC
GND
AC
AC
through the surge protector
AC AC
[2] SAC bus, wiring as specified
transformer transformer
CRCs wired to the ACDB-KE through a converter and powered from AC transformers
BA BA BT
BA BT BA
Compatibility lists
Essex Electronics KTP-102-LI Thinline 2 x 6 Keypad, 26-bit Wiegand, Black Lexan Overlay,
Illuminated, Surface or Mullion Mount, 5 or 12V
Essex Electronics KTP-103-SN 3 x 4 Keypad, 26-bit Wiegand, Stainless Steel Bezel, Non-
Illuminated, Surface or Flush Mount, 5 or 12V
HID Corporation 5355ABK0009 ProxPro™ proximity card reader with Wiegand output
HID Corporation 5355AG00 ProxPro™ proximity card reader with Wiegand output
HID Corporation 5355AGK0009 ProxPro™ proximity card reader with Wiegand output
HID Corporation 5355ABK0009 ProxPro™ proximity card reader with Wiegand output
HID Corporation 5365CBP02 MiniProx™ proximity card reader with Wiegand output
Mercury Security MR-10 Mag Stripe Reader, Format Selectable (inc. 26-bit Wiegand), Die
Cast Aluminum, 12V
Motorola ARK-501+ PinProx™ proximity card reader with keypad
Motorola ASR-603 SecureProx™ I proximity card reader
Motorola ASR-605 SecureProx™ II proximity card reader
Position Technology CR-R880 Posi-Prox Proximity Card Reader
System power calculations If the load exceeds the panel power supply capacity, you need
an additional power supply for the SAC bus devices.
Use Form A to determine the load created by SAC bus
devices. Follow the instructions given below. Add this load to Note that the SAC current load consists of the current drawn
the load created by fire alarm devices to determine the total by the CRC or KPDISP devices plus any readers, strikes, and
load for the panel power supply. maglocks.
To determine the need for additional power (Form A): Locks, readers, and CRCSNDs = (C3 = C2)
2. Fill in the rated current draw at 12 Vdc (mA) (C1) for each KPDISPs = (C3 = Q x 35)
type of device used. 5. Fill in the duty cycle (as a percentage).
3. Enter or calculate the total current (mA) at 24 Vdc (C2) Example: A duty cycle of 30 seconds in every 5 minutes
using: (300 seconds) is a 10% duty cycle.
Locks = (Q x C1 x 0.98) - 5 6. Fill in the standby hours
Card readers with 12 V current draw equaling 99 mA or Standby hours are the number of hours after which lock
less = (Q x C1 x 0.98) - (55 x C1 / 100) and reader loads should be shed when operating on
Card readers with 12 V current draw over 99 mA = battery power.
(Q x C1 x 0.98) - 55 Note that load shedding of locks and readers requires
CRC, CRCSND, KPDISP = Q x C1 3-SDU programming.
4. Calculate the standby current (mA) (C3) as follows. When used for fire alarm applications, CRCs and
KPDISPs require at least 24 hours of standby power, but
8. Calculate the active load by totaling total current (C2). Estimated voltage drop
9. Calculate the battery size by totaling battery capacity (BC). To estimate the voltage drop use Table 3 and Table 4, which
show the maximum length of a SAC bus for a given number of
10. Calculate the Derated battery size as follows. devices and a total load current. (One table is for 16 AWG
Derated battery size = Battery size x 1.2 wire, the other for 14 AWG wire.) (The tables are based on a
3.2 V drop.)
11. Add the Active load figure to the corresponding totals
calculated for the remainder of the system. These tables were calculated based on even spacing between
doors and an equal load at each door.
12. If the Active load is greater than the available panel supply
capacity, you must add an additional power supply. To check for adequate device voltage:
13. Use the system-wide Derated battery size to determine 1. Determine the total active current for a typical door. To do
the battery required for the panel. this, add the active current of the CRC, the active current
of the door lock, the active current of the card reader, and
the active current of the sounder (if used).
2. Determine the number of doors you need to secure.
3. In Table 3, find the intersection of the number of doors and
the load current you determined in steps 1 and 2.
This is the maximum length (in feet) of the SAC bus using
16 AWG wire.
4. If the distance from the control panel to the last device on
the SAC bus is less than this distance, no further
calculations are needed.
5. If the distance to the last device in you installation is
greater than this distance, repeat steps 1 through 4 using
Table 4.
6. If changing the gauge of the wire does not result in a
sufficient length for a single SAC, you will need to design
the system with an additional power source, then repeat
the steps. This power source may be an additional
connection to the same or another 3-PPS/M located in the
same cabinet as the 3-SAC that connects these devices,
another fire rated power supply with ground isolation, or a
CRCXF.
The CRCRL is a fire, security, and access control accessory. 7. Connect the CRCRL control wiring as shown in the wiring
Use the CRCRL in conjunction with an external power supply diagram.
to control a device which requires voltage or current outside 8. Attach the CRC cover.
the control unit's operating range.
Wiring diagram
Specifications
CRC applications
Operating voltage: 12 Vdc
Operating current: 34 mA at 12 Vdc
Contact rating
2 A at 28 Vdc at 0.6 PF
2 A at 120/250 Vac at 0.6 PF
Dimensions
Width: 0.8 in (2.0 cm)
Height: 1.8 in (4.6 cm)
Depth: 1.2 in (3.1 cm)
Operating environment
Temperature: 32–120 °F (0–49 °C)
Humidity: 93% RH, non-condensing
Leads
Free length: 6.0 inches (15.25 cm)
Wire: 18 AWG stranded, tinned
Insulation: 0.03 in (0.76 cm) minimum
Installation instructions
CRC applications
When used with power-limited wiring, the CRCRL can be
mounted inside the CRC housing. When used with nonpower-
limited wiring the CRCRL must be mounted in an electrical
box. You can use the electrical box the CRC is mounted on.
To TB1-16 (Sounder)
on card reader controller module
Either terminal
connection can
+
be used
+
+
The sounder is a small horn that mounts inside the card reader
controller module. The sounder operates if an emergency exit
door is opened without an exit request and locally indicates
that a door has been left open.
Note: This device is for supplementary use only.
Specifications
Operating voltage: 12 Vdc
Operating current: 7 mA
Operating environment
o o
Relative humidity: 93% @ 104 F (40 C)
o o
Temperature: 32 - 120 F (0 - 49 C)
Installation instructions
1. Remove power from the card reader controller module.
2. Remove the card reader controller cover.
3. Snap the sounder into the molded brackets in the card
reader controller cover.
A trouble is sent to a
monitoring module or circuit A ground fault is placed on
(the relay contacts on the the monitoring circuit
GFD change state) (i.e. fire alarm panel)
JP1
3 2 1
When JP1 is in the 1-2 position, the GFD connects the COM
output (terminal 3 of the terminal block) to earth ground
The GFD Ground Fault Detector is used to detect ground faults through a 1 kΩ resistor. The COM output can be connected to
on power-limited isolated circuits. The GFD provides ground the minus side of the input power or supervisory module so
fault monitoring for up to two isolated signals. A ground fault on that a ground fault can be transferred to the panel.
any wire is detected within 20 seconds. Built-in relay contacts
are available for indicating trouble and ground fault conditions,
or the GFD can be configured to put a ground fault on the Installation instructions
monitoring circuit. Note: The GFD is shipped from the factory as an assembled
The GFD is a stand-alone unit. Its dry contacts can be unit; it contains no user-serviceable parts and should not be
monitored by other system input devices. The GFD also has a disassembled.
watchdog circuit, which keeps the relay energized. To install the module:
Specifications 1. Verify that all field wiring is free of opens, shorts, and
ground faults.
Operating voltage range: 10 to 28 Vdc
Current draw: 110 mA 2. Make all wiring connections as shown in the wiring
Trouble contact rating: 1 A @ 30 Vdc (resistive) diagram.
Ground fault detection: < 20 seconds (up to 10 kΩ) 3. Using the 4-24 x 5/16 in (8 mm) self-tapping screw
Ground fault monitoring: 2 circuits, 2 wires (every 16 seconds) provided, mount the wall plate to the module.
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C) 4. Using the four 6-32 x 1/2 in (13 mm) machine screws
Humidity: 0 to 93% RH (noncondensing) provided, mount the module to the electrical box.
Construction: High impact engineering polymer Notes
Compatible electrical boxes
North American 2-1/2 in (64 mm) deep 2-gang box Wire in accordance with NFPA 70, National Electrical Code.
Standard 4 in square box 1-1/2 in (38 mm) deep with
2-gang cover
LED outputs
The GFD has two yellow LEDs. The LEDs indicate which
circuit pair and which conductor pair has a ground fault. The
LEDs light to indicate which conductors have a ground fault.
• Ground fault on conductor 1: LED 1 ON steady
• Ground fault on conductor 3: LED 2 ON steady
Note: When a 3-NSHM is used, the following takes place:
• Ground fault on conductor 1 or 2: LED 1 ON steady
• Ground fault on conductor 3 or 4: LED 2 ON steady
Strip 1/4 in (about 6 mm) from the ends of all wires that
connect to the terminal block of the module.
Wiring diagram
Pair one in +
+ Pair one out
16 15 14 13 3-2-1 12 11 10 9
IN OUT JP1 IN OUT
Circuit pair 1 Circuit pair 2
LED1 LED2
Earth Trouble/GF Contacts
GND Power NC COM NO
8 7 6 5 4 3 2 1
+24 VDC R C R C
24VDC OUT
+
P1 R T T O R T T O
X X S M X X S M
COMMON
- SUPV
1 1 1 1 2 2 2 2
RS232 IN
IOP3A
3
TB1
COM
TB2
4
1
RXD TXD
IN OUT
TB1
P3 P4
3
6
JB1
24VDC OUT
+
1
4
24 Vdc
UP SW1
1
2
3
- SUPV
PROGRAM
2
Switch shown in 6
3
7
UP position.
COM
4
8
RXD TXD
IN OUT
5
9 J1
6
10
JB1
UP SW1
JB4
1
2
3
PROGRAM
P7
J2 Switch shown in
UP position.
CM Motherboard
IOP3A
JB2 INSTALLED
(PROVIDES 12V TO POWER MODEM)
SUPVCOMTXD RXD
RS232 #2 OUT
RS232 #1 OUT
1
4
TB3
TB2
Power Limited
Not supervised
TB1
24VDC OUT
+
TB3 TB3
- SUPV
NAC SMOKE/AUX
3
POWER POWER
COM
4
RXD TXD
IN OUT
POWER POWER
JB1
UP SW1
1
2
3
PROGRAM
Switch shown in
UP position.
2-PPS/6A 2-PPS
JB4
SUPVCOMTXD RXD
RS232 #1 OUT
1
4
TB3
TB2
printer.
HH:MM:SS MM/DD/YYYY
1 2 3 The KPDISP must be connected to a 3-SAC module. The
KPDISP communicates with the system control panel via the
GHI JKL MNO
SYSTEM BANNER LINE 1
SYSTEM BANNER LINE 2
4 5 6
0-9)Password:_______
PRS
7
TUV
8
WXY
9 3-SAC. The 3-SAC supports the SAC bus (an RS-485 line)
#)Clear
which can be configured as Class A or Class B, depending on
? 0 #
application requirements.
In addition to security messaging, the SAC bus transmits
database updates and life safety event messages to the
KPDISP.
Description The KPDISP is shipped with a service password of 0000000 to
The Keypad Display (model KPDISP) is a control and display allow initial testing. When any password is downloaded to the
module used in security and life safety applications. After keypad, the service password is removed.
entering a password, the user can:
• Arm and disarm partitions
Specifications
• Review off-normal points Dimensions
• Bypass or include points Closed size: (W x H x D): 7.22 x 4.70 x 1.13 in (18.34 x
• Perform various life safety functions 11.94 x 2.86 cm)
Open height: 8.72 in (22.15 cm)
The KPDISP has a compact, covered enclosure which houses: Cover swing (from wall): 5.2 in (13.21 cm)
Cover removal clearance: ~1 in on right side
• An LCD display
Material: High impact polymer, white
• A telephone-style keypad
Operating temperature range: 32 to 120 °F (0 to 49 °C)
• A variable-tone sounder
Operating humidity range: 0 to 93 % RH, non-condensing
• An internal processor
Storage temperature range: –4 to 140 °F (–20 to 60 °C)
The module is compact enough to mount near exit doors or Compatible electrical boxes
behind counters. Mounting holes in the back cover fit standard North American 2-1/2 in (64 mm) deep 2-gang box
electrical boxes. Standard 4 in square box 1-1/2 in (38 mm) deep box
European 100 mm square box
Features Wire size: 14 to 22 AWG (1.50 to 0.25 sq mm)
A removable, hinged front cover protects the keys and Power: 18.4 to 26.4 Vdc
provides space for basic operating instructions. Grooves in the Current: 95 mA
cover transmit light from the illuminated keypad. Partitions: 255 maximum
Users: 200 maximum
The display is a backlit LCD which lights when in use. It can Languages: 2 (user-selectable)
display 8 lines of 21 characters. Each KPDISP supports two
user-selectable languages and can display text in most
languages.
Installation instructions
The telephone-style keypad is continuously backlit. The keys You may find it easier to install the KPDISP if you remove the
are wear-resistant silicone rubber. They have a perceptible hinged cover. You’ll need the LRM removal tool (P/N 210415)
range of travel, and provide positive tactile and audible to remove the back plate, a small screwdriver to tighten the
feedback. terminal screws, and a standard screwdriver to mount the back
plate to the electrical box.
A variable-tone sounder is part of the KPDISP module. This
can be programmed to emit tones of a specific frequency and Note: Leave about 1 inch of clearance between the right side
duration, so as to provide audible feedback to the user. of the KPDISP and the door (or other obstructions) to insert the
LRM removal tool when removing the cover.
1. Use the LRM removal tool to press the locking tab inward
(toward the wire hole) and remove the back.
2. Mount the back to the electrical box, pulling the wires
through the hole in the back.
3. Strip the wires to the correct length, approximately 1/4
inch (~6 mm).
4. Attach the power cable wires to the top terminal block.
Observe the correct polarity.
5. Attach the communication cable wires to the bottom
terminal block.
6. Insert the hinge tabs on the left side of the body into the
slots in the back, then press the right side of the body onto
the back to engage the locking tab. 2-gang box
7. Attach the front cover if you removed it for installation. Surface mounting,
4 in box, or 100 mm box
Locking tab
Wiring diagram
Note: All wiring is supervised and power-limited.
IN OUT IN OUT
24 VDC
– +
24 Vdc – –
from last device or 24 Vdc
power supply + to next device
+
– +
SAC bus
IN OUT IN OUT
Front view of the backplate as mounted on the electrical box, showing terminal connections
Not used
Switch Function 1 2 3 4
Serial ports
5 6 7 8 10BASE-T
EN60950
TX- 42 4 5 5 7 SG
TX+ 6 3
(out) 3 3 6 RXD
RJ-45 serial connectors DTR
2 2 7 7 6 DSR
(out)
RS-232 limits: 15 m (50 ft) in length at 9600 K baud and RTS 1 1 8 8 5 CTS
2 m (6 ft) at 115.2 K baud (out)
12345678 1 RTS (out) If you are connecting an RJ-45 port to a DTE device (such as a
2 DTR (out) terminal) that has a DB-25 connector, you will need to use an
3 TX+ (out) RJ-45-DTE DB-25 adapter. To connect an RJ-45 port to a
4 TX-
5 RX- DB-25 connector on a DCE device, you will need an RJ-45 to
6 RX+ (in) DCE DB-25 adapter.
7 DSR (in)
8 CTS (in) RJ-45 to DB-9
DCE - DB-25 adapter pinout Note: The arrows represent the direction of the signal. The
pinouts assume that the 8-conductor cable connecting the unit
RJ-45 RJ-45 to DB-25
and the adapter block is a swapped cable. Both the transmit
serial adapter
Cable RJ-45 DB-25 and receive ground signals on the unit connector are wired to
port
(server) (modem) the signal ground on a DB-9 adapter.
CTS
(in) 86 8 1 1 5 CTS
DSR
(in) 75 7 2 2 8 DCD
RX+
(in) 64 6 3 3 3 RXD
RX- 53 5 4 4
TX- 42 4 5 5 7 SG
TX+ 3 3 6 6 2 TXD
(out)
DTR 2 7 7 20 DTR
(out) 2
RTS 1 1 8 8 4
(out) RTS
3-CPU1
Character size: 8
Parity: None
Access: Remote
Flow control: None
Stop bits: 1
Speed: 19200
Step 1: Review Section 1, "Introduction," in the Step 8: After all installation, wiring, and communication
NETCOM-1F User Guide. This will help you to settings are complete, test the communication of
become familiar with the NETCOM-1F's each NETCOM-1F with each component they are
specifications, LEDs, RJ-45 connection, and fiber connected to.
optic connections.
Step 2: Follow the procedures in Section 2, "Getting
Started," in the NETCOM-1F User Guide for 24 Vdc from
connecting the NETCOM-1F to a computer control panel [1]
and/or Ethernet network and for assigning an IP
address to the NETCOM-1F. Also refer to the
topic "System setup procedures and worksheets"
in the Network Applications Manual 10Base-FL (fiber optic)
(P/N 3100576) for obtaining IP addresses. Ethernet network connection
(receive) [4]
Step 3: Follow the procedures in Section 3, "Configuring RJ-45 Ethernet 10Base-T
the Unit," in the NETCOM-1F User Guide for 10Base-FL (fiber optic)
network connection [4] Ethernet network connection
configuring the NETCOM-1F to communicate on (transmit) [4]
a network.
Note: See pages 2 and 3 of this installation sheet
for device configuration settings. Refer to both
the "Overview" and "Application" settings.
Step 4: Disconnect the NETCOM-1F from your PC or
network.
DB-9 and DB-25 serial port (RS-232)
Step 5: Install the NETCOM-1F in a cabinet using the
from control panel [2] [3]
NETCOM-BRKT mounting bracket. See
installation sheet P/N 3100575.
Figure 1: Wiring connections
Step 6: Connect all wiring. See Figure 1.
Notes
- Connect the 24 Vdc power wiring
- Connect the RJ-45 or fiber optic network wiring [1] Remove the transformer from the supplied power cable
- Connect the DB-25 RS-232 wiring and connect the wires to a 24 Vdc power source on the
control panel.
Note: To provide a proper interface for the device
server, EST2 and IRC-3 panels require an • Solid black wire = positive (+)
IOP3-A and FCC panels require an FCOM-232 • White striped wire = negative (-)
card.
[2] Pinout requirements can be found in the NETCOM-1F
Caution: When using a NETCOM-1F between a User Guide in Section 1, "Introduction" and in the table
FireWorks computer and CCTV controllers, if below.
either of the two transmit or receive wires are [3] The NETCOM-1F can be configured to operate on CH1 or
shorted, you will lose communications. To CH2.
reestablish communications, shut down and
restart FireWorks. [4] Either the Ethernet connection or the fiber optic
connection can be used, but not both simultaneously.
Fireworks with CCTV (TCP/IP) using a NETCOM-1S Data terminal device server connecting to an EST2, IRC-3,
• FireWorks Communications Manager = serial port: or FCC device server (such as the printer and VDU-3
applications)
- COM port set to virtual COM port in NETDIRECT
- Baud rate: 9600 • Device server connected to the panel:
- Parity: even - Baud rate: baud rate of the panel
- Stop Bits: 1 - I/F mode: 7C
- EST3 port type: N/A - Flow: 00
• NETDIRECT settings: - Port number: 10001
- Connect mode: C1
Install the NETDIRECT software on the FireWorks - Remote IP address: IP address of the device server
computer and set it up to communicate with your CCTV connected to the DTE device
controller. Follow the procedures in Section 4, - Remote port: 10001
"NETDIRECT," in the NETCOM-1S User Guide for - DisConnMode: 00
installation and setup information. - FlushMode: 00
- DisConnTime: 00:00
- Create a virtual COM port (one that does not physically
- SendChar1: 00
exist)
- SendChar2: 00
- Set the IP address to the device server xx.xx.xx.xx
- Set the TCPPort to 3001 (acceptable range: 3001 to 3009) • Device server connected to the DTE device:
• Device server settings: - Baud rate: baud rate of the panel
- I/F mode: 7C
- Baud rate: 9600
- Flow: 00
- I/F mode: 7C
- Port number: 10001
- Flow: 00
- Connect mode: C0
- Port number: 11000 + TCPPort value set in NETDIRECT
- Remote IP address: 00.00.00.00
(acceptable range: 14001 to 14009)
- Remote port: 00
- Connect mode: C0
- DisConnMode: 00
- Remote IP address: 00.00.00.00
- FlushMode: 00
- Remote Port: 00
- DisConnTime: 00:00
- DisConMode: 00
- SendChar1: 00
- Flush mode: 00
- SendChar2: 00
- DisConnTime: 00:00
- Send char: 00
- Send char: 00
The NETCOM-BRKT is a metal bracket that is installed in a Mount up to two NETCOM-1S modules on the bracket using
3-CHAS7 or MFC-A cabinet and is used for mounting a the diagram below.
NETCOM-1S or NETCOM-1F device server or a NETSW hub.
Holes for top device
Installation instructions
You must first install the NETCOM-BRKT to either a 3-CHAS7 NETCOM-BRKT
or an MFC-A cabinet before connecting a device to the
bracket. Use the instructions below to install the bracket and NETCOM-1S
connect the device servers.
Mounting the NETCOM-BRKT in a 3-CHAS7
Mount each bracket using the diagram below. Note: Different
mounting holes are used to attach the bracket to the left and
right positions on the 3-CHAS7.
6-32, 1/4-inch Holes for bottom device
pan head screws
NETCOM-BRKTs
NETCOM-BRKT
NETCOM-1F
6-32, 5/16-inch
countersunk screws
6-32, 1/4-inch
pan head screws
Mounting the NETCOM-BRKT in an MFC-A cabinet
Mount the bracket using the diagram below.
Mounting a NETSW on the NETCOM-BRKT
MFC-A cabinet Mount a NETSW on the bracket using the diagram below.
NETCOM-BRKT
6-32, 1/4-inch
NETCOM-BRKT pan head screws
NETSW
6-32, 1/4-inch
countersunk screws
Product description
This installation checklist is a supplement to the NETSW-EIS
Series Technical Reference Manual. Use this checklist to set
up and install your switch. Make sure you follow the
procedures in the order shown.
Parts you will need:
• NETSW-EIS6-MM or NETSW-EIS6-SM RJ-45 Ethernet network connections
• NETCOM-BRKT mounting bracket (to computers and device servers)
• NETSW-EIS Series Technical Reference Manual
(P/N 3100620)
Fiber optic RX
• Network Applications Manual (P/N 3100576) 5
• NETCOM-CD Fiber optic TX Network backbone
Fiber optic RX connections
Steps for setting up and installing an 6
Fiber optic TX
NETSW
10 Vdc 36
Product description secured to the assembly using snap rivet fasteners. The
monitor module has a hinged front panel for mounting displays
or a blank protective faceplate.
3-BPS/M(-230) Booster Power Supply and 3-BBC/M(-230)
Booster/Charger Supply
TB1
TB2
+BATTERY-TEMP
MON
chassis modules as well as 24 Vdc for operating ancillary
equipment.
Heat sink Monitor
assembly module A 3-BPS/M(-230) supply can share a common set of standby
batteries with the 3-PPS/M(-230) or 3-BBC/M(-230). Each 3-
BPS/M(-230) supervises its own battery connection but does
This installation sheet applies to the following models: not have any battery charging capability. The 3-BBC/M(-230) is
• 3-PPS/M(-230) Primary Power Supply capable of charging standby batteries.
• 3-BPS/M(-230) Booster Power Supply Each booster supply shares the panel's 24 Vdc electrical load
• 3-BBC/M(-230) Booster/Charger Supply with the 3-PPS/M(-230). In the event of a booster power supply
3-PPS/M(-230) Primary Power Supply failure, a trouble is annunciated, and the panel load is
distributed among the remaining operational power sources.
The 3-PPS/M(-230) Primary Power Supply provides the Should the load ever exceed the ability of the operable power
required power and related supervision functions for the control sources to supply the power, as in the event of an alarm, the
panel. The 3-PPS/M(-230) comprises a heat sink assembly system automatically switches to standby batteries.
and a monitor module. The monitor module plugs into the rail,
and the heat sink and the heat sink assembly mounts onto the The booster supply monitor module provides the interface
rail chassis. between the booster power supply and the panel, making the
required data and power connections to and from the rail
The 3-PPS/M(-230) provides filtered, regulated power to the chassis. The monitor module requires one rail space and is
rail chassis modules as well as 24 Vdc for operating ancillary secured to the assembly using snap rivet fasteners. The
equipment. AC power and battery connections are made to monitor module has a hinged front panel for mounting displays
fixed terminals on the heat sink assembly, away from the or a blank protective faceplate.
panel's power limited wiring.
The 3-PPS/M(-230) provides a dual rate constant current Specifications
battery charger circuit with automatic temperature
compensation. To prevent memory problems and total battery 3-PPS/M(-230), 3-BPS/M(-230), and 3-BBC/M(-230)
discharge, a battery monitor circuit supervises the standby Installation
batteries and disconnects them when they reach the low Heat sink assembly: Mounts onto the rail chassis
battery threshold. Monitor module: Mounts in one rail space
The 3-PPS/M(-230) checks the AC input source and Power input: 120 Vac, +10%, -15%, 3.0 A, 50 – 60 Hz
automatically switches to battery power in the event of a 230 Vac, +10%, -15%, 1.5 A, 50 – 60 Hz (-230
brownout or loss of AC power. In the event of a failure of one only)
or more booster power supplies, the 3-PPS/M(-230)
determines its ability, along with the surviving booster supplies, Brownout level: 102 Vac
to supply the load. If the load exceeds the ability of the primary 195 Vac (-230 only)
and surviving booster supplies to meet the demand, the 3-
Outputs
PPS/M(-230) automatically switches in the standby batteries.
Total: 24 Vdc at 7.0 A (internal and auxiliary outputs)
The 3-PPS/M(-230) also switches in the standby batteries if an
Internal DC: 24 Vdc at 7.0 A, max.
overload causes the heat sink temperature to reach a high
Auxiliary DC: Two 24 Vdc at 3.5 A max. Power-limited and
level.
supervised for ground faults and shorts.
The power supply monitor module provides the interface
Termination
between the 3-PPS/M(-230) and the panel, making the
AC Input: Terminals on heat sink assembly
required data and power connections to and from the rail
Batteries: Terminals on heat sink assembly
chassis. The monitor module requires one rail space and is
Standby: 70 mA
J8
J11
J10
Operating environment
Temperature: 32 to 120 F (0 to 49 C)
Humidity: 0 to 93% RH noncondensing at 32 C
3-PPS/M(-230) and 3-BBC/M(-230)
Battery charging
Capacity: 10 to 65 Ah
P2
Type: Temperature compensated dual rate (1.5 amps and
3.0 amps)
Supervision
Low AC #8-32 lock nut
Low battery: < 22.5 Vdc 6-32 x 1/2 pan head screw (4 places)
#6 lock washer
High battery #6 flat washer
Discharged battery: < 18 Vdc (2 places)
Ground fault: < 10 k
3-BPS/M(-230) only Figure 1: Heat sink assembly installation
Supervision Installing a monitor module
Low AC
Low Battery: < 22.5 Vdc Caution: This product contains components that are sensitive
Ground Fault: < 10 k to static electricity. Failure to follow proper handling procedures
will result in equipment damage.
Installation instructions To install a monitor module:
Installing a heat sink assembly 1. Plug the cable harness and ribbon cable into the monitor
module as shown in Figure 2. Ensure the cable
Heat sink assemblies are installed on the rail chassis behind
connections are secure.
the rail module connectors. Refer to Figure 1.
2. For a power supply monitor module, align the module to
To install a heat sink assembly:
the guide posts on slot 3 of the rail chassis.
1. Attach the heat sink assembly to the four threaded For a booster supply monitor module, align the module to
mounting studs on the rail chassis using lock nuts the guide posts on slot 3 or slot 5 of the rail chassis,
provided in the hardware kit. whichever is closest to the heat sink assembly.
2. Secure the bottom edge of the heat sink assembly to the 3. Route the cable harness over and behind the bottom rail
threaded standoffs on the rail chassis using screws and connect it to P2 on the heat sink assembly. Push in
provided in the hardware kit. until the connector clicks.
3. Secure the top edge of the heat sink assembly to the rail 4. Route the ribbon cable under the bottom rail and connect
chassis using the two threaded standoffs provided in the it to P3 on the heat sink assembly.
hardware kit.
5. Plug the module into the rail connectors and lock it into
4. Attach the AC terminal block cover to the threaded place using the snap rivet fasteners.
standoffs using two 6-32 x 1/2 pan head screws.
Notes
• Always mount the heat sink assembly for the primary
power supply onto the left mounting space of the rail
chassis in which the central processor module is installed
• Booster supplies, if installed, can be mounted on any rail
chassis, but no more than three booster supplies may be
installed in the same enclosure
TB1
Ribbon cable
P/N 250189 (primary monitor module)
P/N 250188 (booster monitor module)
TB1 TB1
J9
J8
J11
J10
TB2
Figure 4: Mains power wiring
TEMP
MON
Wiring instructions
All wiring must be made in accordance with the national
electrical code and all other local requirements.
Mains power wiring
Connect the mains power wiring after all power supplies have
been installed. No more than one primary power supply and
three booster supplies may be connected to a single mains AC
circuit. All mains power wiring must be double insulated.
TB2
AUXILIARY POWER
1 2 BATTERY TEMP
MON
TB1 TB2
24 Vdc
0 Vdc Not used
24 Vdc
0 Vdc
To plus and minus terminals
on cabinet battery or to plus and
Figure 5: 24 Vdc riser wire connections minus terminals on power
distribution bus in remote cabinet
Standby battery wiring
Connect the standby batteries to TB2 on the heat sink
Figure 6: Standby battery wire connections
assembly as shown in Figure 6 and according to the following
requirements: Table 1 lists typical battery and power supply combinations.
• Each set (pair) of batteries must be connected to a
separate battery charging circuit, either on a 3-PPS/M(- Table 1: Typical battery and power supply combinations
230) or on a 3-BBC/M(-230).
Total Power supplies Battery sets
• Each power supply must be connected to only one set of current required required
batteries. A 3-PPS/M(-230) and a 3-BPS/M(-230) can be
wired to the same set of batteries, as well as a 3-BBC/M(- 7A 1 (3-PPS/M(-230)) 1 set, 65 Ah max.
230) and a 3-BPS/M(-230), but never a 3-PPS/M(-230) 1 (3-PPS/M(-230))
and a 3-BBC/M(-230). 1 set, 65 Ah max.
1 (3-BPS/M(-230))
14 A
• Each power supply must have its own separate pair of 1 (3-PPS/M(-230))
wires connecting it to a set of standby batteries. Daisy 2 sets, 65 Ah max
1 (3-BBC/M(-230))
chaining battery connections from power supply to power
supply is not allowed. 1 (3-PPS/M(-230))
1 set, 65 Ah max.
2 (3-BPS/M(-230))
• All battery wiring must be the same length and wire gauge 21 A
1 (3-PPS/M(-230))
• All batteries connected to the same control panel must 3 sets, 65 Ah max
2 (3-BBC/M(-230))
have the same ampere-hour rating, be from the same
manufacturer, and have the same manufacturing date 1 (3-PPS/M(-230))
code 1 set, 65 Ah max.
3 (3-BPS/M(-230))
28 A
• Batteries greater than 17 Ah and any additional batteries 1 (3-PPS/M(-230))
must be installed in an external battery cabinet 4 sets, 65 Ah max
3 (3-BBC/M(-230))
• If an external battery cabinet is used to house standby
batteries, the cabinet must be installed within three feet
and in the same room as the control panel.
Product description chassis. The monitor module requires one rail space and is
secured to the assembly using snap rivet fasteners. The
monitor module has a hinged front panel for mounting displays
L N or a blank protective faceplate.
TB1
3-BPS/M-230-E Booster Power Supply and 3-BBC/M-230-E
Booster/Charger Supply
The 3-BPS/M-230-E and 3-BBC/M-230-E booster power
supplies are used to provide additional power over and above
that of the 3-PPS/M-230-E. Each model is composed of a heat
sink assembly and a monitor module. The monitor module
plugs into the rail and the heat sink assembly mounts onto the
rail chassis.
Depending on the size of the cabinet, up to three booster
TB2 TB3
power supplies can be added to make a total of 28 amps
AUX ILI ARY P OW ER
1 2
Current requirements
3-PPS/M-230-E: Included with CPU current requirements
3-BPS/M-230-E: Alarm: 50 mA
Standby: 50 mA
3-BBC/M-230-E: Alarm: 70 mA
J9
J8
J11
Standby: 70 mA
J10
Operating environment
Temperature: 23 to 104 F (-5 to 40 C)
Humidity: 0 to 93% RH noncondensing
3-PPS/M-230-E and 3-BBC/M-230-E
Battery charging
Capacity: 10 to 65 Ah
P2
Type: Temperature compensated dual rate (1.5 amps and
3.0 amps)
Supervision #8-32 lock nut
Low AC 6-32 x 1/2 pan head screw (4 places)
Low battery: < 22.5 Vdc #6 lock washer
High battery #6 flat washer
Discharged battery: < 18 Vdc (2 places)
Ground fault: < 10 k
Figure 1: Heat sink assembly installation
3-BPS/M-230-E only
Supervision Installing a power distribution assembly
Low AC Installing a power distribution assembly is required only when
Low Battery: < 22.5 Vdc installing a 3-PPS/M-230-E.
Ground Fault: < 10 k
The power distribution assembly is installed on the rail chassis
behind the rail module connectors to the right of the primary
Installation instructions power supply heat sink assembly. Refer to Figure 2.
Installing a heat sink assembly To install a power distribution assembly:
Heat sink assemblies are installed on the rail chassis behind
1. Attach the power distribution assembly to the six threaded
the rail module connectors. Refer to Figure 1.
standoffs on the rail chassis.
To install a heat sink assembly:
2. Attach the earth ground braid to the backbox ground stud
1. Attach the heat sink assembly to the four threaded located just above the power distribution assembly (see
mounting studs on the rail chassis using lock nuts Figure 3).
provided in the hardware kit.
2. Secure the bottom edge of the heat sink assembly to the Earth ground stud
threaded standoffs on the rail chassis using screws on enclosure backbox
provided in the hardware kit. 6-32 x 3/8 pan head screw
#6 internal tooth washer Earth ground braid
3. Secure the top edge of the heat sink assembly to the rail (6 places)
chassis using the two threaded standoffs provided in the
L N
hardware kit. TB1
Mains
earth conductor
P6
L N
TB1
Earth ground stud on the bottom
edge of the power distribution assembly
To primary power
supply TB1-E
L N L N
TB2 TB3
E N L E N L E N L E N L
230 VAC 230 VAC 230 VAC 230 VAC
Primary power supply Booster power supply 1 Booster power supply 2 Booster power supply 3
(optional) (optional) (optional)
TB2
TB1
AUXILIARY POWER
1 2
BATTERY TEMP
MON
AUXILIARY POWER
1 2
TB2
• Each set (pair) of batteries must be connected to a Total Power supplies Battery sets
separate battery charging circuit, either on a 3-PPS/M- current required required
230-E or on a 3-BBC/M-230-E
7A 1 (3-PPS/M-230-E) 1 set, 65 Ah max.
• Each power supply must be connected to only one set of
batteries. A 3-PPS/M-230-E and a 3-BPS/M-230-E can be 1 (3-PPS/M-230-E)
1 set, 65 Ah max.
wired to the same set of batteries, as well as a 3-BBC/M- 1 (3-BPS/M-230-E)
14 A
230-E and a 3-BPS/M-230-E, but never a 3-PPS/M-230-E 1 (3-PPS/M-230-E)
and a 3-BBC/M-230-E. 2 sets, 65 Ah max
1 (3-BBC/M-230-E)
• Each power supply must have its own separate pair of 1 (3-PPS/M-230-E)
wires connecting it to a set of standby batteries. Daisy 1 set, 65 Ah max.
2 (3-BPS/M-230-E)
chaining battery connections from power supply to power 21 A
supply is not allowed. 1 (3-PPS/M-230-E)
3 sets, 65 Ah max
2 (3-BBC/M-230-E)
• All battery wiring must be the same length and wire gauge
1 (3-PPS/M-230-E)
• All batteries connected to the same control panel must 1 set, 65 Ah max.
3 (3-BPS/M-230-E)
have the same ampere-hour rating, be from the same 28 A
manufacturer, and have the same manufacturing date 1 (3-PPS/M-230-E)
code 4 sets, 65 Ah max
3 (3-BBC/M-230-E)
• Batteries greater than 17 Ah and any additional batteries
must be installed in an external battery cabinet
Audio Amplifier
16.2 in
Battery space (41.15 cm)
Notes
Bottom View
1 Run the AC power only through the top left
knockouts.
PRODUCT DIAGRAM
Route battery wiring to the power supply through
2
a protective channel. Wiring must stay within this
area, and must remain 1/4 inch (6.4 mm) from
power-limited wiring.
3 See the appropriate module installation sheets
for detailed mounting and wiring instructions.
INSTALLATION
Mount the wallbox
INSTALLATION SHEET:
RACCR
Remote Audio Closet Cabinet (Red)
INSTALLATION SHEET P/N: 387578 FILE NAME: 387578.CDR
REVISION LEVEL: 1.0 APPROVED BY: J. Massing
DATE: 30MAR00 CREATED BY: B. Graham
6.12 in
(15.55 cm)
2.75 in 2.75 in
(6.99 cm) (6.99 cm)
7.60 in 7.60 in
(19.31 cm) (19.31 cm)
TOP TOP
RCLM/B-S RCLM/B
Notes
1. Make sure that the wallbox is level and at the
proper height and location before securing. Use
fasteners of acceptable size and type.
2. All wiring shall be power-limited.
RLCM/B(-S)
The RLCM/B(-S) Remote Annunciator Cabinet wallbox Remote Annunciator Cabinet
houses the electronics for the 3-LCDANN(-E) Remote
LCD Command Module Annunciator. The RLCM/B is Wallbox
used in semi-flush mount applications. The RLCM/B-S
is used for surface mountings. INSTALLATION SHEET P/N: 387559 FILE NAME: 387559.CDR
REVISION LEVEL: 1.0 APPROVED BY: K. Patterson
DATE: 08DEC99 CREATED BY: G. Sutton
Signature Data
Circuit Card assembly while voltages are present on the rail. Failure to de-
energize the panel before plugging in the rail module may
result in equipment damage.
OUTPUT MODULE
Specifications
Installation: 1 LRM space on rail chassis
Module configuration
3-SSDC1: 1 Signature Data Circuit Card
3-SDDC1: 2 Signature Data Circuit Cards
Smoke power: 24 Vdc @ 85 mA
Maximum wire size: 12 AWG (1.5 sq mm)
Signature Controller Termination: Removable plug-in terminal strips on module
LOOP2
B B
2
SP
LOOP2
MW A A S
LOOP2
B B
Module Circuit configuration: Class B (Style 4) or Class A (Style 6)
Circuit capacity: 125 Signature Series detectors and 125
KR H
Circuit 2
CIRCUIT 1
Wiring diagram
Circuit 2
LOOP2 S P LOOP2 LOOP2
MW
B B KR A A S B B
2 H
B B S A A SP B B
H MW
LOOP1 LOOP1 K1R LOOP1
Circuit 1
Notes
1. All wiring supervised and power-limited
[2] Shield, if used, must be continuous and free from earth ground