You are on page 1of 64

INDUSTRIAL AIR

COMPRESSOR
TS-2
20
V200TS
100-250HP/75-187KW
AIR-COOLED & WATER-COOLED
STANDARD & 24KT

OPERATOR’S
RY MANUAL AND
N A PARTS LIST
M I
I
L PY
R E O 0 4 KEEP FOR
P C 6 / FUTURE
2 / 0
0 REFERENCE
Part Number
02250146-047
©Sullair Corporation
AIR CARE
SEMINAR TRAINING

Sullair Air Care Seminars are 3-day courses that provide hands-on instruction in the proper operation,
maintenance and service of Sullair equipment. Individual seminars on Industrial compressors and com-
pressor electrical systems are presented at regular intervals throughout the year at a dedicated training
facility at Sullair’s corporate headquarters in Michigan City, Indiana.

Instruction includes discussion of the function and installation of Sullair service parts, troubleshooting of
the most common problems, and actual equipment operation. The seminars are recommended for main-
tenance and service personnel.

For detailed course outlines, schedule and cost information contact:

Sullair Corporate Training Department


1-888-SULLAIR or
219-879-5451 (ext. 5363)
www.sullair.com

- Or Write -

Sullair Corporation
3700 E. Michigan Blvd.
Michigan City, IN 46360
Attn: Service Training Department
TABLE OF CONTENTS

OPERATOR IS REQUIRED TO READ


ENTIRE INSTRUCTION MANUAL

Section 1 PAGE
SAFETY 1 1.1 GENERAL
1 1.2 PERSONAL PROTECTIVE EQUIPMENT
1 1.3 PRESSURE RELEASE
2 1.4 FIRE AND EXPLOSION
2 1.5 MOVING PARTS
2 1.6 HOT SURFACES, SHARP EDGES AND SHARP CORNERS
2 1.7 TOXIC AND IRRITATING SUBSTANCES
3 1.8 ELECTRICAL SHOCK
3 1.9 LIFTING
4 1.10 ENTRAPMENT

Section 2
DESCRIPTION 5 2.1 INTRODUCTION
5 2.2 DESCRIPTION OF COMPONENTS
5 2.3 SULLAIR COMPRESSOR UNIT,
FUNCTIONAL DESCRIPTION
6 2.4 COMPRESSOR COOLING AND LUBRICATION SYSTEM,
FUNCTIONAL DESCRIPTION
8 2.5 COMPRESSOR DISCHARGE SYSTEM,
FUNCTIONAL DESCRIPTION
8 2.6 CONTROL SYSTEM, FUNCTIONAL DESCRIPTION
11 2.7 AIR INLET SYSTEM, FUNCTIONAL DESCRIPTION
11 2.8 INSTRUMENTATION, FUNCTIONAL DESCRIPTION

Section 3
SPECIFICATIONS 15 3.1 SULLAIR TS-20 SPECIFICATIONS
16 3.2 LUBRICATION GUIDE- STANDARD COMPRESSORS
16 3.3 APPLICATION GUIDE

Section 4
INSTALLATION 17 4.1 MOUNTING OF COMPRESSOR
17 4.2 VENTILATION AND COOLING
17 4.3 SERVICE AIR PIPING
17 4.4 COUPLING ALIGNMENT CHECK
17 4.5 FLUID LEVEL CHECK

Continued on next page


TABLE OF CONTENTS
Section 4
INSTALLATION (CONT). 18 4.6 ELECTRICAL PREPARATION
18 4.7 MOTOR ROTATION DIRECTION CHECK

Section 5
OPERATION- ELECTRO-
MECHANICAL 19 5.1 GENERAL
19 8.2 PURPOSE OF CONTROLS
20 5.3 INITIAL START-UP PROCEDURE
20 5.4 SUBSEQUENT START-UP PROCEDURE
20 5.5 SHUTDOWN PROCEDURE

Section 6
SUPERVISOR CONTROLLER™
22 Figure 6-1 Supervisor Controller Panel

Section 7
MAINTENANCE 23 7.1 GENERAL
23 7.2 DAILY OPERATION
23 7.3 MAINTENANCE AFTER INITIAL 50 HOURS
OF OPERATION
23 7.4 MAINTENANCE AFTER FIRST 1000 HOURS
23 7.5 FLUID CHANGE
24 7.6 FILTER MAINTENANCE
24 7.7 SEPARATOR MAINTENANCE
24 7.8 PARTS REPLACEMENT AND ADJUSTMENT
PROCEDURES
24 FLUID FILTER ELEMENT REPLACEMENT
(100-150HP/75-112KW)
24 FLUID FILTER ELEMENT REPLACEMENT
(200-250HP/ 150-187KW)
24 AIR FILTER MAINTENANCE (100-150HP/75-112KW)
26 AIR FILTER MAINTENANCE (200-250HP/ 150-187KW)
26 SEPARATOR ELEMENT REPLACEMENT
27 CONTROL SYSTEM ADJUSTMENT
28 DRIVE COUPLING INSTALLATION AND ALIGNMENT

Section 8
TROUBLESHOOTING 29 8.1 TROUBLESHOOTING
29 8.2 TROUBLESHOOTING GUIDE

Continued on next page


TABLE OF CONTENTS
Section 9
VARIABLE SPEED DRIVE
APPLICATIONS 33 9.1 DESCRIPTION OF COMPONENTS
33 9.2 CONTROL SYSTEM, FUNCTIONAL DESCRIPTION
40 Figure 9-2 V200TS Piping and Instrumentation (Air-cooled)
44 Figure 9-3 V200TS Piping and Instrumentation (Water-cooled)
48 Figure 9-4 Identification- V200TS Air-cooled with Enclosure
100-150HP/75-112KW
49 Figure 9-5 Identification- V200TS Air-cooled with Enclosure
125-200HP/93-150KW
50 Figure 9-6 Identification- V200TS Water-cooled with Enclosure
125-150HP/75-112KW
51 Figure 9-7 Identification- V200TS Water-cooled with Enclosure
125-200HP/93-150KW
52 Figure 9-8 Wiring Diagram V200TS Non-CE
53 Figure 9-9 Wiring Diagram V200TS CE

Section 10
SPARE PARTS
LIST 55 10.1 PROCEDURE FOR ORDERING PARTS
55 10.2 SPARE PARTS LIST- TS-20 AND V200TS
Section 1
SAFETY
1.1 GENERAL the service air outlet and the shut-off (throttle)
Sullair Corporation and its subsidiaries design and valve, either at the compressor or at any other point
manufacture all of their products so they can be along the air line, when an air hose exceeding
operated safely. However, the responsibility for 13mm inside diameter is to be connected to the
safe operation rests with those who use and main- shut-off (throttle) valve, to reduce pressure in case
tain these products. The following safety precau- of hose failure, per OSHA Standard 29 CFR
tions are offered as a guide which, if conscientious- 1926.302(b)(7) and/or any applicable Federal,
ly followed, will minimize the possibility of accidents State and Local codes, standards and regulations.
throughout the useful life of this equipment.
B. When the hose is to be used to supply a mani-
The compressor should be operated only by those fold, install an additional appropriate flow-limiting
who have been trained and delegated to do so, and valve between the manifold and each air hose
who have read and understood this Operator’s exceeding13mm inside diameter that is to be con-
Manual. Failure to follow the instructions, proce- nected to the manifold to reduce pressure in case
dures and safety precautions in this manual may of hose failure.
result in accidents and injuries.
C. Provide an appropriate flow-limiting valve at the
NEVER start the compressor unless it is safe to do beginning of each additional 23m of hose in runs of
so. DO NOT attempt to operate the compressor air hose exceeding13mm inside diameter to reduce
with a known unsafe condition. Tag the compressor pressure in case of hose failure.
and render it inoperative by disconnecting and lock-
ing out all power at source or otherwise disabling its D. Flow-limiting valves are listed by pipe size and
prime mover so others who may not know of the flow-rated. Select appropriate valves accordingly, in
unsafe condition cannot attempt to operate it until accordance with their manufacturer’s recommen-
the condition is corrected. dations.

Install, use and operate the compressor only in full E. DO NOT use air tools that are rated below the
compliance with all pertinent OSHA regulations maximum rating of the compressor. Select air tools,
and/or any applicable Federal, State, and Local air hoses, pipes, valves, filters and other fittings
codes, standards and regulations. accordingly. DO NOT exceed manufacturer’s rated
safe operating pressures for these items.
DO NOT modify the compressor and/or controls in
any way except with written factory approval. F. Secure all hose connections by wire, chain or
other suitable retaining device to prevent tools or
While not specifically applicable to all types of com- hose ends from being accidentally disconnected
pressors with all types of prime movers, most of the and expelled.
precautionary statements contained herein are
applicable to most compressors and the concepts G. Open fluid filler cap only when compressor is not
behind these statements are generally applicable to running and is not pressurized. Shut down the
all compressors. compressor and bleed the sump (receiver) to zero
internal pressure before removing the cap.
1.2 PERSONAL PROTECTIVE EQUIPMENT
Prior to installing or operating the compressor, own- H. Vent all internal pressure prior to opening any
ers, employers and users should become familiar line, fitting, hose, valve, drain plug, connection or
with, and comply with, all applicable OSHA regula- other component, such as filters and line oilers, and
tions and/or any applicable Federal, State and before attempting to refill optional air line anti-icer
Local codes, standards, and regulations relative to systems with antifreeze compound.
personal protective equipment, such as eye and I. Keep personnel out of line with and away from the
face protective equipment, respiratory protective discharge opening of hoses or tools or other points
equipment, equipment intended to protect the of compressed air discharge.
extremities, protective clothing, protective shields
J. Use air at pressures less than 2.1 bar for clean-
and barriers and electrical protective equipment, as
ing purposes, and then only with effective chip
well as noise exposure administrative and/or engi-
guarding and personal protective equipment per
neering controls and/or personal hearing protective
OSHA Standard 29 CFR 1910.242 (b) and/or any
equipment.
applicable Federal, State, and Local codes, stan-
1.3 PRESSURE RELEASE dards and regulations.
A. Install an appropriate flow-limiting valve between K. DO NOT engage in horseplay with air hoses as

1
Section 1
SAFETY
death or serious injury may result. environment unless the compressor has been spe-
1.4 FIRE AND EXPLOSION cially designed and manufactured for that duty.
A. Clean up spills of lubricant or other combustible 1.5 MOVING PARTS
substances immediately, if such spills occur. A. Keep hands, arms and other parts of the body
B. Shut off the compressor and allow it to cool. and also clothing away from couplings, fans and
Then keep sparks, flames and other sources of other moving parts.
ignition away and DO NOT permit smoking in the B. DO NOT attempt to operate the compressor with
vicinity when checking or adding lubricant or when the fan, coupling or other guards removed.
refilling air line anti-icer systems with antifreeze C. Wear snug-fitting clothing and confine long hair
compound. when working around this compressor, especially
C. DO NOT permit fluids, including air line anti-icer when exposed to hot or moving parts.
system antifreeze compound or fluid film, to accu- D. Keep access doors, if any, closed except when
mulate on, under or around acoustical material, or making repairs or adjustments.
on any external surfaces of the air compressor.
Wipe down using an aqueous industrial cleaner or E. Make sure all personnel are out of and/or clear
steam clean as required. If necessary, remove of the compressor prior to attempting to start or
acoustical material, clean all surfaces and then operate it.
replace acoustical material. Any acoustical material F. Disconnect and lock out all power at source and
with a protective covering that has been torn or verify at the compressor that all circuits are de-
punctured should be replaced immediately to pre- energized to minimize the possibility of accidental
vent accumulation of liquids or fluid film within the start-up, or operation, prior to attempting repairs or
material. DO NOT use flammable solvents for adjustments. This is especially important when
cleaning purposes. compressors are remotely controlled.
D. Disconnect and lock out all power at source prior G. Keep hands, feet, floors, controls and walking
to attempting any repairs or cleaning of the com- surfaces clean and free of fluid, water or other liq-
pressor or of the inside of the enclosure, if any. uids to minimize the possibility of slips and falls.
E. Keep electrical wiring, including all terminals and 1.6 HOT SURFACES, SHARP EDGES AND SHARP
pressure connectors in good condition. Replace CORNERS
any wiring that has cracked, cut, abraded or other- A. Avoid bodily contact with hot fluid, hot coolant,
wise degraded insulation, or terminals that are hot surfaces and sharp edges and corners.
worn, discolored or corroded. Keep all terminals B. Keep all parts of the body away from all points of
and pressure connectors clean and tight. air discharge.
F. Keep grounded and/or conductive objects such C. Wear personal protective equipment including
as tools away from exposed live electrical parts gloves and head covering when working in, on or
such as terminals to avoid arcing which might serve around the compressor.
as a source of ignition.
D. Keep a first aid kit handy. Seek medical assis-
G. Remove any acoustical material or other materi- tance promptly in case of injury. DO NOT ignore
al that may be damaged by heat or that may sup- small cuts and burns as they may lead to infection.
port combustion and is in close proximity, prior to
1.7 TOXIC AND IRRITATING SUBSTANCES
attempting weld repairs.
A. DO NOT use air from this compressor for respi-
H. Keep suitable fully charged Class BC or ABC fire ration (breathing) except in full compliance with
extinguisher or extinguishers nearby when servic- OSHA Standards 29 CFR 1910 and/or any applica-
ing and operating the compressor. ble Federal, State or Local codes or regulations.
I. Keep oily rags, trash, leaves, litter or other com-
bustibles out of and away from the compressor.
J. DO NOT operate the compressor without proper
Death or serious injury can result from inhaling
flow of cooling air or water or with inadequate flow compressed air without using proper safety
of lubricant or with degraded lubricant. equipment. See OSHA standards and/or any
applicable Federal, State, and Local codes, stan-
K. DO NOT attempt to operate the compressor in dards and regulations on safety equipment.
any classification of hazardous

2
Section 1
SAFETY
contact any other portion of the compressor when
B. DO NOT use air line anti-icer systems in air lines making adjustments or repairs to exposed live parts
supplying respirators or other breathing air utiliza- of the electrical system. Make all such adjustments
tion equipment and DO NOT discharge air from or repairs with one hand only, so as to minimize the
these systems into unventilated or other confined possibility of creating a current path through the
areas. heart.
C. Operate the compressor only in open or ade- C. Attempt repairs in clean, dry and well lighted and
quately ventilated areas. ventilated areas only.
D. Locate the compressor or provide a remote inlet D. DO NOT leave the compressor unattended with
so that it is not likely to ingest exhaust fumes or open electrical enclosures. If necessary to do so,
other toxic, noxious or corrosive fumes or sub- then disconnect, lock out and tag all power at
stances. source so others will not inadvertently restore
power.
E. Coolants and lubricants used in this compressor
are typical of the industry. Care should be taken to E. Disconnect, lock out, and tag all power at source
avoid accidental ingestion and/or skin contact. In prior to attempting repairs or adjustments to rotating
the event of ingestion, seek medical treatment machinery and prior to handling any ungrounded
promptly. Wash with soap and water in the event of conductors.
skin contact. Consult Material Safety Data Sheet for 1.9 LIFTING
information pertaining to fluid of fill. A. If the compressor is provided with a lifting bail,
F. Wear goggles or a full face shield when adding then lift by the bail provided. If no bail is provided,
antifreeze compound to air line anti-icer systems. then lift by sling. Compressors to be air-lifted by hel-
icopter must not be supported by the lifting bail but
G. If air line anti-icer system antifreeze compound by slings instead. In any event, lift and/or handle
enters the eyes or if fumes irritate the eyes, they only in full compliance with OSHA standards 29
should be washed with large quantities of clean CFR 1910 subpart N and/or any applicable Federal,
water for fifteen minutes. A physician, preferably an State, and Local codes, standards and regulations.
eye specialist, should be contacted immediately.
B. Inspect points of attachment for cracked welds
H. DO NOT store air line anti-icer system antifreeze and for cracked, bent, corroded or otherwise
compound in confined areas. degraded members and for loose bolts or nuts prior
I. The antifreeze compound used in air line to lifting.
antifreeze systems contains methanol and is toxic, C. Make sure entire lifting, rigging and supporting
harmful or fatal if swallowed. Avoid contact with the structure has been inspected, is in good condition
skin or eyes and avoid breathing the fumes. If swal- and has a rated capacity of at least the weight of
lowed, induce vomiting by administering a table- the compressor. If you are unsure of the weight,
spoon of salt, in each glass of clean, warm water then weigh compressor before lifting.
until vomit is clear, then administer two teaspoons
of baking soda in a glass of clean water. Have D. Make sure lifting hook has a functional safety
patient lay down and cover eyes to exclude light. latch or equivalent, and is fully engaged and latched
Call a physician immediately. on the bail or slings.
1.8 ELECTRICAL SHOCK E. Use guide ropes or equivalent to prevent twisting
A. This compressor should be installed and main- or swinging of the compressor once it has been lift-
tained in full compliance with all applicable Federal, ed clear of the ground.
State and Local codes, standards and regulations, F. DO NOT attempt to lift in high winds.
including those of the National Electrical Code, and G. Keep all personnel out from under and away
also including those relative to equipment ground- from the compressor whenever it is suspended.
ing conductors, and only by personnel that are
trained, qualified and delegated to do so. H. Lift compressor no higher than necessary.

B. Keep all parts of the body and any hand-held I. Keep lift operator in constant attendance whenev-
tools or other conductive objects away from er compressor is suspended.
exposed live parts of electrical system. Maintain dry J. Set compressor down only on a level surface
footing, stand on insulating surfaces and DO NOT capable of safely supporting at least its weight and
its loading unit.

3
Section 1
SAFETY
K. When moving the compressor by forklift truck, attempt to forklift a compressor that is not secured
utilize fork pockets if provided. Otherwise, utilize to its pallet, as uneven floors or sudden stops may
pallet if provided. If neither fork pockets or pallet are cause the compressor to tumble off, possibly caus-
provided, then make sure compressor is secure ing serious injury or property damage in the
and well balanced on forks before attempting to process.
raise or transport it any significant distance. 1.10 ENTRAPMENT
L. Make sure forklift truck forks are fully engaged A. If the compressor enclosure, if any, is large
and tipped back prior to lifting or transporting the enough to hold a man and if it is necessary to enter
compressor. it to perform service adjustments, inform other per-
M. Forklift no higher than necessary to clear obsta- sonnel before doing so, or else secure and tag the
cles at floor level and transport and corner at mini- access door in the open position to avoid the pos-
mum practical speeds. sibility of others closing and possibly latching the
door with personnel inside.
N. Make sure pallet-mounted compressors are
firmly bolted or otherwise secured to the pallet prior B. Make sure all personnel are out of compressor
to attempting to forklift or transport them. NEVER before closing and latching enclosure doors.

4
Section 2
DESCRIPTION
2.1 INTRODUCTION On air-cooled models, a separate motor-driven fan
Your new Sullair lubricated rotary screw air com- blows air through the cooler/aftercooler assembly,
pressor will provide you with a unique experience in thereby removing the heat of compression from the
improved reliability and greatly reduced mainte- cooling fluid.
nance. On water-cooled models, fluid is piped into a four-
Compared to other types of compressors, the pass exchanger where the heat of compression is
Sullair rotary screw is unique in mechanical reliabil- removed from the fluid. A fan is used to supply suf-
ity, with "no wear" and "no inspection" required of ficient ventilating air to compressors equipped with
the working parts within the compressor unit. a canopy.
Read Maintenance section to see how surprisingly Both air-cooled and water-cooled versions have
easy it is to keep your air compressor in top oper- easily accessible components such as the fluid fil-
ating condition. Should any questions arise which ters and control valves. The inlet air filters are also
cannot be answered in the following text, call your mounted for easy access and servicing.
nearest Sullair representative or the Sullair 2.3 SULLAIR COMPRESSOR UNIT, FUNCTIONAL
Corporation Service Department. DESCRIPTION
2.2 DESCRIPTION OF COMPONENTS Sullair tandem air compressors feature the Sullair
Refer to Figure 2-1. The components and assem- compressor unit, a two-stage, positive displace-
blies of the air compressors are clearly shown. The ment fluid lubricated-type compressor. This unit
complete package includes compressor, electric provides continuous (pulse-free) air compression to
motor, compressor inlet system, compressor dis- meet your needs.
charge system, compressor cooling and lubrication Fluid is injected into the compressor unit in large
system, capacity control system and instrument quantities where it mixes directly with the air as the
panel all mounted on a heavy gauge steel frame. internal rotors turn, compressing the air. The fluid
Figure 2-1 Sullair TS-20 Rotary Screw Air Compressor

5
Section 2
DESCRIPTION
flow has three basic functions: fluid is cooled in preparation for injection.
1. As coolant, it controls the rise of air temperature
normally associated with the heat of compres-
sion.
2. It seals the leakage paths between the rotors and
the stator and also between the rotors them- With a Sullair compressor, there is no mainte-
selves. nance or inspection of the internal parts of the
compressor unit permitted in accordance with
3. It acts as a lubricating film between the rotors the terms of the warranty.
allowing one rotor to directly drive the other,
which is an idler. 2.4 COMPRESSOR COOLING AND LUBRICATION
After the air/fluid mixture is discharged from the SYSTEM, FUNCTIONAL DESCRIPTION
compressor unit, the fluid is separated from the air. Refer to Figures 2-2. The cooling and lubrication
At this time, the air flows to the service line and the
Figure 2-2 Compressor Cooling, Lubrication and Discharge System- Air-cooled (Typical)

6
Section 2
DESCRIPTION
Figure 2-3 Compressor Cooling, Lubrication and Discharge System- Water-cooled (Typical)

system (air-cooled version) consists of a fan, radia- where it lubricates, cools and seals the rotors and
tor-type cooler/aftercooler assembly, full-flow fluid the compression chamber.
filter, thermal valve, fluid stop valve and intercon- As the discharge temperature rises above 170ºF
nection piping. For water-cooled models, a shell (77ºC), due to the heat of compression, the thermal
and tube fluid cooler, aftercooler and water-flow valve begins to close and a portion of the fluid then
regulating valve are substituted for the radiator-type flows through the cooler. From the cooler, the fluid
cooler on air-cooled compressors. flows to the fluid filter, and on to the compressor
The pressure in the receiver/sump causes fluid flow unit.
by forcing the fluid from the high pressure area of A portion of the fluid flowing to the compressor is
the sump to an area of lower pressure in the com- routed to the anti-friction bearings which support
pressor unit. the rotors inside the compressor unit.
Fluid flows from the bottom of the receiver/sump to The fluid filter has a replacement element and an
the thermal valve. The thermal valve is fully open integral pressure bypass valve. An associated serv-
when the fluid temperature is below 170ºF (77ºC). ice gauge shows red when the filter needs servic-
The fluid passes through the thermal valve, the ing. This gauge has a pressure setting lower than
main fluid filter and directly to the compressor unit that of the bypass valve. After the initial 50 hour fil-

7
Section 2
DESCRIPTION
ter change, the gauge will rarely show red under replacement is necessary.
normal operating conditions. The receiver is an ASME pressure vessel. A combi-
The fluid stop valve prevents fluid from filling the nation minimum pressure/check valve, located
compressor unit when the compressor is shut downstream from the separator, assures a mini-
down. When the compressor is operating, the fluid mum receiver pressure of 50 psig (3.5 bar) during
stop valve is held open by air pressure from the full load operation. This pressure is necessary for
compressor unit allowing a free flow of fluid from proper air/fluid separation and proper fluid circula-
the receiver/sump back to the compressor unit. On tion while supplying air to the system. This valve
shutdown, the compressor unit pressure is also acts as a check valve preventing compressed
reduced, causing the fluid stop valve to close and air in the service line from bleeding back into the
isolate the compressor unit from the cooling sys- receiver on shutdown and during operation on the
tem. compressor in an unloaded condition.
Water-cooled versions of the compressor have a A pressure relief valve (located on the wet side of
water-flow regulating valve which operates to con- the separator) is set to open if the sump pressure
serve water during periods of varying load on the exceeds 175 psig (12.1 bar).
compressor. The same valve automatically shuts All Sullair compressor models are equipped with a
off the water supply when the compressor is shut high pressure shutdown switch to shut down the
down. In addition, water-cooled models have a compressor at 135 psig (9.3 bar). This prevents the
water pressure switch to prevent operation with pressure relief valve from opening under normal
inadequate water pressure. conditions, thereby preventing fluid loss through the
2.5 COMPRESSOR DISCHARGE SYSTEM, FUNC- pressure relief valve. A temperature switch will shut
TIONAL DESCRIPTION down the compressor if the discharge temperature
Refer to Figures 2-3. The compressor unit dis- reaches 240ºF (116ºC).
charges the compressed air/fluid mixture through a
discharge check valve into the combination receiv-
er/sump. The discharge check valve prevents air in
the receiver from returning to the compression DO NOT remove caps, plugs, and/or other compo-
nents when compressor is running or pressur-
chamber after the compressor has been shut down. ized.
The receiver has three basic functions:
Stop compressor and relieve all internal pressure
1. It acts as a primary fluid separator. before doing so.
2. It serves as the compressor fluid sump.
Fluid is added to the sump via a capped fluid filler
3. It houses the final fluid/air separator elements. opening, placed low on the receiver tank to prevent
The compressed air/fluid mixture enters the receiv- overfilling of the sump. A sight glass enables the
er and is directed against the far side of the tank, operator to visually monitor the sump fluid level.
where its direction of movement is changed and its 2.6 CONTROL SYSTEM, FUNCTIONAL DESCRIP-
velocity significantly reduced. This causes large TION
droplets of fluid to collect, separate and fall to the Refer to Figure 2-4. The purpose of the compres-
bottom of the receiver/sump. The fractional per- sor control system is to regulate the amount of air
centage of fluid remaining in the compressed air being compressed to match the amount of com-
collects on the surface of the dual separator ele- pressed air being used.
ments (primary and secondary) as the compressed
air flows through them. Two return lines (or scav- The capacity control system consists of a Sullicon
enge tubes) lead from the bottom of each separator Control, a butterfly valve (located on the compres-
element to the low pressure inlet region of the com- sor air inlet), a spiral valve, a pressure switch, two
pressor unit. Fluid collecting on the bottom of each (2) solenoid valve pressure regulators, and two (2)
separator is returned to the compressor by a pres- control line filters. The functional description of the
sure difference between the receiver and the com- control system is described below in four distinct
pressor inlet. Sight glasses are located in the return phases of compressor operation. The following
lines to observe this fluid flow. A gauge, located on applies to all TS-20 Series compressors. This
the instrument panel, will be in the red zone when description applies to any compressor with an oper-
excessive pressure drop through the separator ating range of 100 to 110 psi (6.9 to 7.6 bar). A com-
develops. At this time, separator element(s) pressor with any other pressure range would oper-

8
Section 2
DESCRIPTION
Figure 2-4A Control System TS-20 (with Spiral Valve)(Typical)

9
Section 2
DESCRIPTION
Figure 2-4B Control System TS-20 (with Spiral Valve) (Typical)

10
Section 2
DESCRIPTION
ate in the same manner except for the stated pres- used, the service line pressure keeps on rising.
sures. When it exceeds 110 psig (7.6 bar), the air pressure
START MODE - 0 TO 50 PSIG (0 TO 3.5 BAR) switch opens de-energizing the solenoid valve. The
When the compressor START button is depressed, line pressure through the solenoid valve holds inlet
the sump pressure will quickly rise from 0 to 50 psig butterfly valve closed, and at the same time it
(0 to 3.5 bar). During this period, the spiral valve opens the blowdown valve. Reduced sump pres-
fully closes, while the inlet butterfly valve fully sure during blowdown results in low unload power
opens. As a result, the compressor runs at full consumption. While the compressor is running
capacity. unloaded, the inlet butterfly valve remains in the
unload position. As the line pressure fluctuates
FULL LOAD MODE - 50 TO 100 PSI (3.5 TO 6.9 between 100 and 110 psi (6.9 to 7.6 bar), the spiral
BAR) valve will modulate.
When the sump pressure rises above 50 psi (3.5
bar), the minimum pressure valve opens, allowing When the line pressure falls to 100 psi (6.9 bar),
compressed air to flow into the service line. Both due to an increase in the air demand, the air pres-
the spiral valve as well as the inlet butterfly valve sure switch closes. The solenoid valve is then ener-
remain in the full load position as long as the com- gized allowing the air pressure behind the Sullicon
pressor is running at 100 psi (6.9 bar) or below. Control to be vented through the solenoid valve
exhaust port. The blowdown valve closes, and the
MODULATION MODE - 100 to 110 PSIG (6.9 TO inlet butterfly valve opens. Also at this time, the air
7.6 BAR) pressure at the diaphragm of the spiral valve actu-
As air demand drops below the rated capacity of ator has been released through a vent hole in the
the compressor, the line pressure will rise above spiral valve differential pressure regulator. This
100 psig (6.9 bar). As a result, the differential pres- allows the spiral valve to close as a result of the
sure regulator for the spiral valve gradually opens movement of the rack and pinion. The compressor
applying air pressure to the spiral valve actuator. Air is now running again in full load mode. The spiral
pressure at the actuator assembly expands the valve as well as the inlet butterfly valve are in full
diaphragm. The rack, which engages with the pin- load position.
ion mounted on the spiral valve shaft assembly,
begins to stroke. This results in a rotary motion. As For a compressor with varied periods of time when
the spiral valve rotates, it starts opening the bypass there are no air requirements, a "Dual Control"
ports gradually. Excess air is then being returned option is available. This option allows you to set the
back to suction. Now the compressor is compress- compressor in an automatic position whereby the
ing only that amount of air which is being used. As compressor will shut down (time delayed) when no
air demand keeps on dropping further, the spiral compressed air requirement is present and restart
valve opens gradually until all the bypass ports are as compressed air is needed.
fully open. At this point, the spiral valve has moved 2.7 AIR INLET SYSTEM, FUNCTIONAL DESCRIP-
into the unload position. TION
The spiral valve provides a modulation range from Refer to Figure 2-5. The compressor inlet system
50 to 100%. During this period, the pressure rises consists of a dry-type air filter, a restriction gauge
approximately from 100 to 108 psi (6.9 to 7.5 bar). and an air inlet valve.
As the air pressure exceeds 108 psi (7.5 bar), the The restriction gauge, located on the compressor
differential pressure regulator controlling the instrument panel, indicates the condition of the air
Sullicon Control opens. This allows the air pressure filter. When the pointer reaches the red zone, filter
to the diaphragm chamber of the Sullicon Control maintenance is required.
which starts to close the inlet butterfly valve partial- The butterfly-type air inlet valve directly controls the
ly. The inlet butterfly valve provides modulating amount of air intake by the compressor in response
range from 40 to 50%. During this period, the pres- to the operation of the Sullicon Control (Section
sure rises approximately from 108 to 110 psi (7.5 to 2.6).
7.6 bar). Within this range, the spiral valve remains
in the unload position. 2.8 INSTRUMENTATION, FUNCTIONAL DESCRIP-
TION
UNLOAD MODE - IN EXCESS OF 110 PSI (7.6 Refer to Figure 2-6 for specific location of parts
BAR) described. The panel group consists of a number of
When a relatively small amount, or no air is being gauges, buttons and status indicator lights. Refer to

11
Section 2
DESCRIPTION
Figure 2-5 Compressor Air Inlet System er reaches the red zone, filter service is
required (see Figure 2-6).
• The start push-button turns the compressor
on and resets the compressor.
• The stop push-button turns the compressor
off.
• The hourmeter records cumulative hours of
operation of the compressor. It is useful for
planning and logging service operations.
• The separator maintenance gauge monitors
the condition of the separator elements.
Pointer will move into the red zone when the
elements should be replaced. This gauge is
automatically reset after the elements have
been replaced.
• The fluid filter maintenance gauge monitors
the condition of the fluid filter element.
Pointer will move into the red zone when the
element should be replaced. This gauge is
also automatically re-set after elements
have been changed (for fluid filter location
see Figure 2-3).
• The red light on the instrument panel indi-
cates when power to the compressor is sup-
plied.
• The green light indicates when the com-
pressor is running.

Figure 2-6 Instrument Panel Group


Figure 2-6 as you read this segment. Locate the fol-
lowing: line pressure, sump pressure and dis-
charge temperature gauges and the air filter, sep-
arator and fluid filter restriction gauges, along with
start and stop buttons and an hourmeter.
Refer to Figure 2-7 for functional locations of the
following indicators and controls:
• The line (terminal) pressure gauge is con-
nected to the dry side of the receiver down-
stream from the check valve. It continually
monitors the air pressure.
• The sump pressure gauge continually mon-
itors the sump pressure at the various load
and/or unload conditions.
• The discharge temperature gauge monitors
the temperature of the air leaving the com-
pressor unit.
• The air filter restriction gauge monitors the
condition of the air intake filter. When point-

12
Section 2
DESCRIPTION
Figure 2-7 Piping and Instrumentation Diagram (Typical)

13
NOTES

14
Section 3
SPECIFICATIONS
3.1 SULLAIR TS-20 SPECIFICATIONS
50 Hz Model
DIMENSIONS
TS-20 KW M3/MIN BAR LENGTH WIDTH HEIGHT (I) WEIGHT (II)
(MM) (MM) (MM) (KG)
100L 75 15 7.5 3048 1829 1727 3674
100H 75 14.1 8.5 3048 1829 1727 3674
100HH 75 12.1 10 3048 1829 1727 3674
125L 93 19.5 7.5 3048 1829 1727 3719
125H 93 17.8 8.5 3048 1829 1727 3719
125HH 93 16.4 10 3048 1829 1727 3719
150L 112 22.3 7.5 3048 1829 1727 3810
150H 112 20.5 8.5 3048 1829 1727 3810
150HH 112 19.5 10 3048 1829 1727 3810
200H 150 26.6 8.5 3048 1829 1727 3900
200HH 150 25.6 10 3048 1829 1727 3900
60 Hz Model
DIMENSIONS
TS-20 HP ACFM PSIG LENGTH WIDTH HEIGHT (I) WEIGHT (II)
(IN.) (IN.) (IN.) (LBS.)
100L 100 560 110 120 72 68 8100
100H 100 515 125 120 72 68 8100
125L 125 694 110 120 72 68 8200
125H 125 635 125 120 72 68 8200
150L 150 827 110 120 72 68 8400
150H 150 755 125 120 72 68 8400
200L 200 1041 110 120 72 68 8600
200H 200 965 125 120 72 68 8600
250L 250 1142 110 120 72 68 8800
(I) 78in./198 cm required to service separator filter elements.
(II) With enclosure.
COMPRESSOR: STANDARD MODELS
Type: Rotary Screw
Standard Operating Pressure (III) : See Specifications
Bearing Type Anti-Friction
Ambient Temperature (Max.) (IV) : 105ºF (41ºC)
Cooling: Pressurized Fluid
Lubricant: Sullube
Sump Capacity: 30 gallons (114 liters)
Control: Electro-Pneumatic
MOTOR: (50 Hz Compressors) STANDARD MODELS
Size: 100 - 150 HP/75 - 112KW
Type: Open Dripproof, Three Phase, 50 Cycles
A.C., 105ºF (41ºC) Maximum Ambient Temperature
Starter: 380/415V Full Voltage Magnetic
Speed: 1500 RPM
(III) Special compressors are available for operation at higher pressures.
(IV) Special compressors are available for operation in higher ambient temperatures.

15
Section 3
SPECIFICATIONS
MOTOR: (60 Hz Compressors) STANDARD MODELS
Size: 100 - 250 HP/75 - 187KW
Type: Open Dripproof, 460V, A.C., Three Phase,
60 Cycles
105ºF (41ºC) Maximum Ambient Temperature,
TEFC also Available
Starter: 460V Full Voltage Magnetic
Options Available: 200 to 230 and 575V

3.2 LUBRICATION GUIDE-STANDARD COMPRES- analysis program with the fluid suppliers. This could
SORS result in a fluid change interval differing from that
Sullair TS-20 compressors are filled with Sullube. stated in the manual.
For more information on a fluid analysis program,
contact your local Sullair representative or the
Mixing of other fluids within the compressor will
Sullair Factory Service Department.
void all warranties.

Sullube fluid should be changed every 8000 hours


or once a year, whichever occurs first. The fluid "The Plastic Pipe Institute recommends against
should be changed more frequently under severe the use of thermoplastic pipe to transport com-
pressed air or other compressed gases in
operating conditions, such as high ambient temper- exposed above ground locations, e.g. in
atures coupled with high humidity, high particulate exposed plant piping." (I)
level, corrosive or strong oxidizing gases are pres- PVC piping should not be used with Sullube sys-
ent in the air. tems. It may affect the bond at cemented joints.
Certain other plastic materials may also be
Maintenance of all other components is still recom- affected.
mended as indicated in the Operator's Manual.
(I) Plastic Pipe Institute, Recommendation B,
3.3 APPLICATION GUIDE Adopted January 19, 1972.
Sullair encourages the user to participate in a fluid

16
Section 4
INSTALLATION
4.1 MOUNTING OF COMPRESSOR cooled/aftercooled compressor without adequate
A foundation or mounting capable of supporting the freeze protection where it will be exposed to tem-
weight of the compressor, and rigid enough to perature less than 32ºF(0ºC).
maintain the compressor frame level and the com- 4.3 SERVICE AIR PIPING
pressor in alignment is required. The compressor Service air piping should be installed as shown in
frame must be leveled and secured with foundation Figure 4-1. A shut-off valve should be installed to
bolts, and full uniform contact must be maintained isolate the compressor from the service line if
between the frame and foundation. The compres- required. Also notice that the service line should be
sor unit and driver must be aligned after installation equipped with water legs and condensate drains
as specified in the Operator's Manual. No piping throughout the system.
loads shall be transmitted to the compressor at the
external connections.
4.2 VENTILATION AND COOLING
For air-cooled compressors, select a location to
"The Plastic Pipe Institute recommends against
permit sufficient unobstructed air flow in and out of the use of thermoplastic pipe to transport com-
the compressor cooling package to keep the oper- pressed air or other compressed gases in
ating temperature stable. The minimum distance exposed above ground locations, e.g. in
that the compressor should be from surrounding exposed plant piping." (I)
walls is three (3) feet (91.4cm). To prevent exces- PVC piping should not be used with Sullube sys-
sive ambient temperature rise, it is imperative to tems. It may affect the bond at cemented joints.
Certain other plastic materials may also be
provide adequate ventilation. affected.
For water-cooled compressors, it is necessary to (I) Plastic Pipe Institute, Recommendation B,
check the cooling water supply. The water system Adopted January 19, 1972.
must be capable of supplying the following flows:
WATER WATER FLOW (TYPICAL) 4.4 COUPLING ALIGNMENT CHECK
TEMP. (GPM/LPM) In preparation for the factory test, the coupling sup-
ºF/ºC 100HP/ 125HP/ 150HP/ 200HP/ 250HP/ plied with your compressor is properly aligned for
75KW 93KW 112KW 150KW 187KW operation. However, due to shipping and handling,
70/21 14/15.3 17.5/66 21/79.5 40/151 49/185 it is necessary to recheck the coupling alignment.
80/27 18.75/71 23.5/89 28/106 44/166 54/204 Refer to Coupling Alignment procedure explained in
Water pressure should be between 25 and 75 psig (1.7 and 5.2 bar). the Maintenance Section of this manual.
4.5 FLUID LEVEL CHECK
Table 1 below indicates the ventilation require- Your air compressor is also supplied with the prop-
ments necessary to keep the compressor running er amount of fluid. However, it is necessary to
at a normal operating temperature. The fan air check the fluid level at installation. The level is
requirement is the volume of air which must blow checked by looking at the sight glass located on the
through the compressor for proper ventilation. The sump. If the sump is properly filled, the coolant level
specified heat rejection requirement is the amount should fill the sight glass.
of heat that is radiated by the compressor. This heat
must be removed to assure a normal operating 4.6 ELECTRICAL PREPARATION
temperature. With air-cooled compressors it is pos- Interior electrical wiring is performed at the factory.
sible to use this heat for space heating, providing Any other wiring should be performed by a qualified
excessive pressure drop is not created across the electrician and in full compliance with OSHA,
fan. Consult a Sullair office for assistance in utiliz- National Electrical code and/or any applicable
ing this heat. Federal, State and Local codes, standards and reg-
ulations concerning isolation switches, fuse discon-
DO NOT install a water-cooled or an air-
TABLE 4-1 VENTILATION REQUIREMENTS (TYPICAL)
COOLING TYPE AIR-COOLED WATER-COOLED
Motor HP/KW: 100/75 125/93 150/112 200/150 250/187 100/75 125/93 150/112 200/150 250/187
Vent Fan Flow
CFM/M3/MIN (I): 13,000/368 14,500/411 14,500/411 19,000/538 19,000/538 2,370/67 2,370/67 2,370/67 2,370/67 2,370/67
Heat Rejection:
BTU/Hour 285,100 353,940 412,500 545,040 699,875 22,410 28,110 33,610 50,390 55,990
KCAL/Hour 71,848 89,196 103,954 137,355 176,375 5,648 7,084 8,470 12,700 14,110
(I) Applies to compressors with canopy only (vent fan).

17
Section 4
INSTALLATION
Figure 4-1 Service Air Piping (Typical Installation)

nects etc. Customer wiring is very minimal. Sullair START button and check all protective devices
provides a wiring diagram for use by the installer. to be sure that they will de-energize the starter
A few electrical checks should be made for a trou- coil when activated.
ble-free start-up. 5. Re-connect the three (3) motor leads and jog the
motor for a direction of rotation check, as
explained in Section 4.7.

Lethal shock hazard inside. Disconnect all power


4.7 MOTOR ROTATION DIRECTION CHECK
at source before opening or servicing starter or After the electrical wiring has been done, it is nec-
control panel. essary to check the direction of the motor rotation.
This can be done by jogging the START and STOP
1. Check incoming voltage. Be sure that the incom- buttons on the instrument panel. When looking at
ing voltage is the same voltage that the com- the motor from the end opposite the compressor
pressor was wired for. unit, the shaft should be turning clockwise. If the
2. Check starter and overload heater sizes (see motor shaft is not turning in the proper direction,
electrical parts in Parts Manual). disconnect the power to the starter and exchange
any two of the three power input leads, then re-
3. Check all electrical connections for tightness. check rotation. A "Direction of Rotation" decal is
4. "DRY RUN" the electrical controls by disconnect- located on the coupling guard between the motor
ing the three (3) motor leads from the starter. and compressor to show proper motor/compressor
Energize the control circuits by pushing the rotation.

18
Section 5
OPERATION-
ELECTRO-MECHANICAL
5.1 GENERAL will call for service or indicate the beginning of a
While Sullair has built into this compressor a com- malfunction. Before starting your Sullair compres-
prehensive array of controls and indicators to sor, read this section thoroughly and familiarize
assure you that it is operating properly, you will yourself with the controls and indicators - their pur-
want to recognize and interpret the reading which pose, location and use.

5.2 PURPOSE OF CONTROLS


CONTROL OR INDICATOR PURPOSE
START push-button Depress to turn the compressor ON.

STOP push-button Depress to turn the compressor OFF.

HOURMETER Records cumulative hours of compressor operation; useful


for planning and logging service schedules.

LINE PRESSURE GAUGE Continually monitors service line air pressure. Located on
dry side of receiver downstream from check valve.

SUMP PRESSURE GAUGE Continually monitors receiver/sump pressure at various load


and/or unloaded conditions.

DISCHARGE TEMPERATURE GAUGE Monitors temperature of the air leaving the compressor unit.
For both air and water-cooled compressors, the normal
reading should be approximately 180ºF to 205ºF (82ºC to
96ºC ) for ambient temperatures up to 105° F.

FLUID FILTER MAINTENANCE GAUGE Indicates when a fluid filter element change is required. It
shows red when the pressure drop through the filter is
excessive.

SEPARATOR MAINTENANCE GAUGE Indicates when separator element change is required. It


shows red when pressure drop through the separator is
excessive.

"POWER ON" LIGHT (RED) Indicates when the starter is energized.

"RUNNING" LIGHT (GREEN) Indicates when compressor is in operation.

FLUID LEVEL SIGHT GLASS Monitors fluid level in the sump. Proper level should fill the
sight glass. Check the level when the compressor is shut
down. DO NOT OVERFILL.

SEPARATOR RETURN LINE SIGHT Used to indicate fluid flow in the return lines. When the
GLASSES compressor is running at full load, fluid flow should be visi-
ble in these sight glasses. There may be little or no flow
when the compressor is running unloaded, but a sluggish
flow at full load indicates a need to clean the return line
strainers.

Cuts off flow of fluid to compressor unit at compressor shut-


FLUID STOP VALVE down and allows flow of fluid to the unit on start-up.

DISCHARGE CHECK VALVE Cuts off the reverse flow of air/fluid mixture through com-
pressor discharge system at compressor shutdown.
Continued ...
19
Section 5
OPERATION-
ELECTRO-MECHANICAL
5.2 PURPOSE OF CONTROLS (CONTINUED)
CONTROL OR INDICATOR PURPOSE
THERMAL VALVE Regulates the flow of fluid to and around the cooler.
Designed to maintain a minimum operating temperature of
170ºF (77ºC); used for fast warm-up on start-up.

MINIMUM PRESSURE/CHECK VALVE Maintains minimum of 50 psig (3.5 bar) in the compressor
sump when the compressor is loaded. Valve piston restricts
receiver air discharge from receiver/sump when pressure
falls to 40 psig (2.8 bar). Prevents line pressure backflow
into the sump during unload conditions and after shutdown.

COMPRESSOR DISCHARGE Designed to shut the compressor down when the discharge
TEMPERATURE SWITCHES temperature reaches 240ºF (116ºC).

HIGH PRESSURE SHUTDOWN SWITCH An added protective device designed to shut down the com-
pressor when the pressure becomes too high. This switch is
set for shut-down at approximately 135 psi (9.3 bar).

WATER PRESSURE SWITCH Prevents compressor operation if water pressure is insuffi-


(water-cooled compressors only) cient.

PRESSURE RELIEF VALVE Opens sump pressure to the atmosphere should pressure
inside the sump become too high (175 psi [12.1 bar]).
Operation of this valve indicates that the high pressure
switch is either faulty or out of adjustment.

SULLICON CONTROL Regulates the amount of air allowed to enter the air inlet
valve. This regulation is determined by the amount of air
being used at the service line.

PRESSURE REGULATOR (SULLICON) Opens a pressure line between the sump and Sullicon
Control allowing the Sullicon Control to regulate air delivery
according to the air demand.

PRESSURE REGULATOR (SPIRAL VALVE) Opens a pressure line between the service line and the spi-
ral valve actuator allowing the spiral valve to regulate air
delivery according to air demand.

SOLENOID VALVE Bypasses the pressure regulator valve causing the Sullicon
Control to hold the inlet valve closed when the compressor
reaches maximum operating pressure.

PRESSURE SWITCH Senses service line pressure. When line pressure reaches
maximum setting the pressure switch signals the solenoid
valve to unload the compressor.

BLOWDOWN VALVE Vents sump pressure to the atmosphere during unload con-
ditions and shutdown.

WATER REGULATING VALVE Regulates the amount of cooling water used in the (water-
cooled only) cooler to keep the compressor running at a
normal operating temperature.

20
Section 5
OPERATION-
ELECTRO-MECHANICAL
5.3 INITIAL START-UP PROCEDURE 7. Observe the operating temperature. If the oper-
The following procedure should be used to make ating temperature exceeds 205ºF (96ºC), the
the initial start-up of the compressor: cooling system or installation environment
1. Read the preceding pages of this manual thor- should be checked.
oughly. 8. Observe return line sight glasses and mainte-
2. Be sure that all preparations and checks nance indicators.
described in the Installation Section have been 9. Open shut-off valve to service line.
made. 10. Reinspect the compressor for temperature and
3. Crack open the shut off valve to the service line. leaks the following day.
4. Start the compressor by pushing the START but- 5.4 SUBSEQUENT START-UP PROCEDURE
ton. On subsequent start-ups, check that the proper
5. Check for possible leaks in piping. level is visible in the fluid sight glass and press the
START button. When the compressor is running,
6. Slowly close the shut-off valve and check that the observe the instrument panel and maintenance
setting on the pressure switch is set correctly. If indicators.
set correctly, the compressor will unload at the
desired unload pressure. If adjustments are nec- 5.5 SHUTDOWN PROCEDURE
essary, see Control System Adjustments in the To shut the compressor down, press the STOP but-
Maintenance Section of the manual. ton.

21
Section 6
SUPERVISOR CONTROLLER™
Figure 6-1 Supervisor Controller Panel

For information concerning all aspects of the Supervisor Controller,


consult the Supervisor Controller manual.

22
Section 7
MAINTENANCE

7.1 GENERAL Figure 7-1 Compressor Fluid Filter


As you proceed in reading this section, it will be (P/N 250025-522; 100-150HP/75-112KW)
easy to see that the Maintenance Program for the
air compressor is quite minimal yet important. The
use of the service indicators provided for the fluid
filter, air filter and fluid separator will alert you when
service maintenance is required. When the mainte-
nance gauge shows red, maintenance for that spe-
cific item is required. See instructions for each item
in Section 7.7, Parts Replacement and Adjustment
Procedures.

For general locations of machine components,


refer to Figures 2-1, 2-7 (TS-20), and 9-1A, 9-1B, 9-
1C, 9-2 and 9-3 (V200TS).

7.2 DAILY OPERATION


Prior to starting the compressor, it is necessary to
check the fluid level in the sump. Should the level
be low, simply add the necessary amount. Frequent *Replacement Element Kit P/N 250025-526
fluid additions to maintain correct level would be
5. Clean the control line filters.
indicative of excessive fluid consumption, and
should be investigated - see the Troubleshooting 7.4 MAINTENANCE AFTER 1000 HOURS
Section of this manual for probable cause and rem- After 1000 hours of operation, it will be necessary
edy. to perform the following:
After a routine start has been made, observe the 1. Clean the return line strainers.
instrument panel gauges and be sure they monitor 2. Lubricate the Sullicon Control linkage.
the correct readings for that particular phase of 3. Replace the fluid filter element.
operation. After the compressor has warmed up, it
is recommended that a general check of the overall 4. Clean the control line filters.
compressor and instrument panel be made to 7.5 FLUID CHANGE
assure that the compressor is running properly. Standard models are filled with Sullube. Sullube
should be changed under the following conditions,
whichever occur first:
DO NOT remove caps, plugs, and/or other com- 1. Every 8000 hours.
ponents when compressor is running or pressur-
ized. 2. Once a year.
Stop compressor and relieve all internal pressure 3. As indicated by fluid analysis.
before doing so.
A fluid sample at every 1000 hours is recommend-
7.3 MAINTENANCE AFTER INITIAL 50 HOURS OF ed. For a free Sullube analysis, send fluid to:
OPERATION Dow Chemical
After the initial 50 hours of operation, a few mainte- Lubricant Technology Center
nance requirements are needed to rid the system of Building B-1605
any possible foreign materials. Perform the follow- Freeport, TX 77541
ing maintenance operations to avoid operational
To facilitate this, a sample bottle is included with the
problems:
compressor.
1. Clean the return line strainers.
2. Clean the return line orifices.
3. Clean the compressor unit gear housing, bearing Change intervals may vary with alternate fluids.
and shaft seal orifices. Consult factory to determine change intervals for
fluids other than Sullube.
4. Change the fluid filter element.

23
Section 7
MAINTENANCE

7.6 FILTER MAINTENANCE the compressor injection port. When servicing the
Replace the fluid filter under any of the following main filter, shut the compressor down and follow
conditions: the instructions below. For element replacement
1. As indicated by the maintenance gauge. order kit number 250008-956.
2. Every 1000 hours. 1. Remove the four (4) capscrews which secure
the filter head to the canister.
3. Every 6 months.
2. Pull the canister away from the filter head. The
4. Every fluid change. filter element will be attached to the head.
7.7 SEPARATOR MAINTENANCE 3. Separate the element from the canister.
Replace the separator elements when your separa-
tor maintenance gauge shows red or after one (1) 4. Remove the canister seal.
year, whichever comes first. The separator ele- 5. Thoroughly clean the filter head and canister in
ments must be replaced. DO NOT clean the sepa- solvent.
rator elements. 6. Lubricate the new seals with the same type of
7.8 PARTS REPLACEMENT AND ADJUSTMENT fluid used in the compressor and position each
PROCEDURES seal in its appropriate place.
FLUID FILTER ELEMENT REPLACEMENT (100- 7. Carefully push the element back into position on
150HP/75-112KW) the filter head.
Refer to Figure 7-1. 8. Hold the canister in position under the housing
and replace the capscrews, securing the canis-
ter and filter head.
To minimize the possibility of filter element rup-
AIR FILTER MAINTENANCE (100-150HP/75-
ture, it is important that ONLY replacement ele-
ments identified with the Sullair name, logo and 112KW)
appropriate part numbers be used, and that sub- Refer to Figure 7-3. Air filter (P/N 408399) mainte-
stitute elements NOT be used, due to the fact that nance should be performed when the maintenance
such filters may have inadequate or questionable
gauge is showing red or once a year, whichever
working pressure ratings.
occurs first. If the filter needs to be replaced, order
1. Using a strap wrench, remove the old element
and gasket. Figure 7-2 Compressor Fluid Filter
2. Clean gasket seating surface. (P/N 250007-219; 200 & 250HP/ 150 & 187KW)
3. Apply a light film of fluid to the new gasket.
4. Hand-tighten new element until new gasket is
seated in the gasket groove.
5. Continue tightening element by hand an addi-
tional 1/2 to 3/4 turn.
6. Re-start the compressor and check for leaks.
FLUID FILTER REPLACEMENT (200-250HP/ 150
-187KW)
Refer to Figure 7-2.

To minimize the possibility of filter element rup-


ture, it is important that ONLY replacement ele-
ments identified with the Sullair name, logo and
appropriate part numbers be used, and that sub-
stitute elements NOT be used, due to the fact that
such filters may have inadequate or questionable
working pressure ratings.

The main filter (P/N 250007-219) is located


schematically between the compressor cooler and *Replacement Element Kit P/N 250008-956

24
Section 7
MAINTENANCE

Figure 7-3 Air Filter (P/N 408399) element no. 405158. Below you will find procedures
(100-150HP/ 75-112KW) on how to replace the air filter element.
AIR FILTER ELEMENT REPLACEMENT
1. Clean the exterior of the air filter housing.
2. Remove the air filter cover by loosening the wing
bolt securing the cover.
3. Remove element and clean interior of housing
using a damp cloth. DO NOT blow dirt out with
compressed air.
4. At this time, replace the element.
5. Re-assemble in reverse order of the disassem-
bly.
ELEMENT INSPECTION
1. Place a bright light inside the element to inspect
for damage or leak holes. Concentrated light
shines through the element and locates any
holes.
2. Inspect all gaskets and gasket contact surfaces
of the housing. Should faulty gaskets be evi-
dent, correct the condition immediately.
3. If the clean element is to be stored for later use,
it must be stored in a clean container.
4. After the element has been installed, inspect and
*Replacement Element Kit P/N 405158 tighten, if necessary, all air inlet connections
Figure 7-4 Air Filter (P/N 409264 or P/N 02250140-798) Consult Charts Below to Determine Proper Filter

AIR FILTER NO. 409264: AIR FILTER NO. 2250140-798:


HP/KW L H HH XH HP/KW L H HH XH
100/75 X X 125/93 X X
125/93 X X 150/112 X X X X
USE: 200/187 X X
*Primary Element no. 409853 USE:
**Secondary Element no. 409854 *Replacement Element no. 02250135-150

25
Section 7
MAINTENANCE

prior to resuming operation. PRIMARY ELEMENT REPLACEMENT


AIR FILTER MAINTENANCE (200-250HP/ 150- 1. Place the element in position on the cover and
187KW) replace the lockring to secure the cover and ele-
Refer to Figure 7-4. Air filter (P/N 048456) mainte- ment.
nance should be performed when the air filter main- 2. Install the cover/element assembly and replace
tenance indicator shows red. The maintenance indi- the wingnut. Tighten the wingnut so to fully seat
cator is located on the filter outlet. The air filter is the element gasket.
equipped with a primary element and a secondary SEPARATOR ELEMENTS REPLACEMENT
element. As previously stated, the restriction indica- Refer to Figure 7-5. The separator elements must
tor will alert you as to when primary element main- be changed when the maintenance gauge is show-
tenance is necessary. When removing the primary ing red, or once a year whichever occurs first. Order
element, always check the secondary element for separator elements no. 250034-121 (primary) and
visible dirt, grease or damage. The secondary ele- no. 250034-134 (secondary). Follow the procedure
ment must be changed after every third element explained below for separator element replace-
change or once a year, whichever comes first. ment.
DO NOT reconnect the secondary element once it
is removed.
ELEMENT REMOVAL Relieve all pressure from the separator and all
1. Clean the exterior of the air filter housing. compressor lines prior to disconnecting any
pipes, tubing, etc.
2. Remove the cover assembly by loosening the
wingnut securing the cover clamp. 1. Disconnect all piping connected to the separator
cover to allow removal (return lines, service
3. Remove the element assembly from the hous- lines, etc.).
ing by unscrewing the wingnut.
4. Clean the interior of the housing by using a Figure 7-5 Separator Elements
damp cloth. DO NOT blow dirt with compressed
air as this may introduce dust downstream.
5. Inspect the secondary element restriction indi-
cator. Replacement element if necessary.
6. To remove the secondary element, unscrew the
secondary restriction indicator from the thread-
ed rod running through the element. Pull the ele-
ment out of the housing.
7. Install the new secondary element and replace
the restriction indicator.
8. With the secondary element in place, replace
the primary element.
ELEMENT INSPECTION
1. Place a bright light inside the element to inspect
for damage or leak holes. Concentrated light will
shine through the element and disclose any
holes.
2. Inspect all gaskets and gasket surfaces of the
housing. Should faulty gaskets be evident, cor-
rect the condition immediately.
3. If the clean element is to be stored for later use,
it must be stored in a clean container.
4. After the element has been installed, inspect
and tighten all air inlet connections prior to
resuming operation. *Replacement Element P/N 250034-121(primary)
**Replacement Element P/N 250034-133 (secondary)

26
Section 7
MAINTENANCE

Figure 7-6 Pressure Switch (P/N 040694) control system, it is necessary to determine the
desired operating pressure range and also the
maximum pressure at which your compressor is to
operate. (The pressure must not exceed the maxi-
mum operating pressure which is stamped on the
compressor serial number nameplate). The follow-
ing explanation applies to a typical installation with
a desired operating range of 100 to 110 psi (6.9 to
7.6 bar). This information applies to a compressor
with any other operating range except for the stat-
ed pressures.
With the shut-off valve closed or slightly cracked
open, start the compressor. Observe the line pres-
sure gauge and pressure switch contacts. When
the line pressure reaches the desired unload (max-
imum) pressure, the pressure switch contacts
should open. If the pressure switch contacts DO
NOT open, or they open prior to the desired pres-
sure, the pressure switch setting will require adjust-
ment (refer to Figure 7-6).

2. Loosen and remove the twelve (12) hex head DO NOT touch the electrical contacts, terminal or
3/4" x 2 1/2"capscrews from the cover plate. leads with any metallic object. Severe electrical
shock may occur.
3. Lift the cover plate from the sump.
4. Remove the primary and secondary separator PRESSURE RANGE ADJUSTMENT:
elements. 1. Remove cover to pressure switch.
5. Scrape the old gasket material from the cover 2. Turn the range-adjusting screw to the high pres-
and flange on the sump being careful not to let sure setting. Turning the screw counterclock-
the scraps fall in the sump. Figure 7-7 Sullicon Control (P/N 011682-003)
6. Inspect the receiver/sump for rust, dirt, etc.
7. DO NOT remove grounding staples from the gas-
kets. DO NOT use any type of gasket eliminator.
Re-insert the separator element with the gas-
kets attached into the sump taking care not to
dent it against the tank opening.
8. Clean the underside of the receiver/sump tank lid
and remove any rust. Paint surface with an
epoxy paint as required.
9. Replace the cover plate, washers and cap-
screws. Torque to 200 ft.-lbs. (272 Nm).
10. Re-connect all piping making sure return line
tubes extend to the bottom or 1/4" (6mm) above
the bottom of the separator element. This will
assure proper fluid return flow to the compres-
sor.
11. Check the return line strainer before re-starting
the compressor.
CONTROL SYSTEM ADJUSTMENT
Refer to Figures 7-6 and 7-7. Prior to adjusting the
*Repair Kit P/N 250020-353

27
Section 7
MAINTENANCE

Figure 7-8 Drive Coupling Alignment by an indicating rod that protrudes from the sump
tank side of the first stage stator. When the rod is
fully extended, the spiral valve is fully open
(unloaded position). The spiral valve rack should
start to move at this time.
Above 108 psi (7.4 bar), the regulator should allow
pressure to flow into the control chamber of the
Sullicon. The Sullicon lever should start to move at
this time. Cycle the Control System several times
and re-check all pressure settings.
DRIVE COUPLING INSTALLATION AND ALIGN-
MENT)
wise lowers both the high and low pressure Refer to Figures 7-8. For coupling installation and
equally. alignment, the tools required are a straight edge, a
DIFFERENTIAL ADJUSTMENT: measuring scale, one set of feeler gauges, a set of
Differential is the difference between the high and standard Allen wrenches, one set of standard sock-
low pressure settings; 10 psi (0.7 bar) is typical. et wrenches and a set of dial indicators are recom-
Turn the differential adjusting screw to the lower mended.
(reset) setting. Turning the screw counterclockwise The first step in coupling installation is assembling
widens the differential by lowering the re-set (lower) the taper lock bushings to each hub. Proceed
setting only. according to the following instructions for assembly
When the pressure switch adjustment is complete, of the bushings and hubs:
the pressure regulators should be adjusted for the
pressure at which modulation of air delivery should
TABLE 6-1 INSTALLATION DATA Disconnect all power lines at their source before
attempting maintenance or adjustments.
Max. Operating Misalignment
Tightening Coupling Coupling Capscrew
Torque Gap Parallel Angular 1. Clean the shafts, bores, keys and keyseats. Be
in.-lbs. +0.30 in./7.6mm Offset degrees in./mm (I) sure the keys fit properly - file if necessary.
T.I.R. (II)
2. Place the bushing in the hub and match the half
370 1.50 .005 .5 .005
41.8Nm 38mm .127mm .5 .127mm
holes of the bushing with the half holes of the
hub.
(I) Angular misalignment (length) equals maximum A minus mini-
mum B as shown in Figure 7-8. DO NOT exceed values in Table 3. Oil the threads and points on the setscrews.
6-1 above. Place the setscrews in the holes loosely.
(II) Total Indicator Run-out.
4. Be sure the bushing is in the hub loosely and
begin. In this case, that pressure will be 100 psi (6.9 then slip the assembly onto the shaft.
bar) for the spiral valve, and 108 psi (7.4 bar) for the 5. Tighten the setscrews alternately and evenly until
Sullicon. The regulator is adjusted by loosening the they are pulled up securely. Torque to 410 in.-
jam nut on the end of the cone-shaped cover of the lbs. (46.1 Nm).
pressure regulator. When the jam nut is loosened, 6. Hammer against the large end of the bushing,
turn the adjusting screw clockwise to increase or using sleeve or block to avoid damage. Turn
counterclockwise to decrease the setting. setscrews slightly. Repeat this procedure until
Above 100 psi (6.9 bar), the regulator should allow the screws will no longer turn. DO NOT exceed
pressure to flow into the control chamber of the spi- 410 in.-lbs. (46.1 Nm).
ral valve. Movement of the spiral valve is indicated

28
Section 8
TROUBLESHOOTING
8.1 TROUBLESHOOTING a. Check for loose wiring.
The information contained in the Troubleshooting b. Check for damaged piping.
chart is based upon both actual applied situations
and extensive testing at the factory. It contains c. Check for parts damaged by heat or an electri-
symptoms and usual causes for the described prob- cal short circuit, usually apparent by discol-
lems. However, DO NOT assume that these are the oration or a burnt odor.
only problems that may occur. All available data Should your problem persist after making the rec-
concerning the trouble should be systematically ommended check, consult your nearest Sullair rep-
analyzed before undertaking any repair or compo- resentative or the Sullair Corporation factory.
nent replacement procedures.
A detailed visual inspection is worth performing for
almost any problems which may prevent unneces- For additional troubleshooting information, con-
sary damage to the compressor. Always remember sult the Supervisor Controller Manual.
to:
8.2 TROUBLESHOOTING GUIDE
SYMPTOM PROBABLE CAUSE REMEDY
COMPRESSOR WILL Main Disconnect Switch Open Close switch.
NOT START
Line Fuse Blown Replace fuse.

Control Transformer Fuse Blown Replace fuse.

Motor Starter Overloads Tripped Re-set. Should trouble persist, check whether
motor starter contacts are functioning properly.

Low Incoming Line Voltage Check voltage. Should voltage check low, consult
power company.

COMPRESSOR SHUTS Loss of Control Voltage Re-set. If trouble persists, check that line pres-
DOWN WITH AIR sure does not exceed maximum operating pres-
DEMAND PRESENT sure of the compressor (specified on nameplate).

Low Incoming Voltage Consult power company.

Excessive Operating Pressure Defect in pressure switch; check pressure at


which contact points open.

Separator requires maintenance; check mainte-


nance indicator under full load conditions.

High pressure shutdown switch is adjusted too


low; re-adjust to 135 psig (9.3 bar).

Defective solenoid valve; solenoid valve should


cause control lever to move to unload stop when
the pressure switch contacts open. Repair if
defective.

Defective blowdown valve; blowdown valve


should exhaust sump pressure to 40 to 55 psi
(2.7 to 3.8 bar) when maximum operating pres-
sure is reached. Repair if defective.

Discharge Temperature Switch Open Cooling water temperature too high; increase
water flow (water-cooled only).

Cooling water flow insufficient; check water lines


and valves (water-cooled only).
Continued ...
29
Section 8
TROUBLESHOOTING

8.2 TROUBLESHOOTING GUIDE (CONTINUED)


SYMPTOM PROBABLE CAUSE REMEDY
COMPRESSOR SHUTS Discharge Temperature Switch Open Cooler plugged; clean tubes. If plugging persists,
DOWN WITH AIR (Continued) install water conditioner (water-cooled only).
DEMAND PRESENT
(CONTINUED) Cooling air flow restricted; clean cooler and
check for proper ventilation.

Ambient temperature is too high; provide suffi-


cient ventilation.

Low Fluid Pressure Low fluid level; add fluid.

Clogged filter; inspect the fluid filter element


and/or change the fluid filter element if mainte-
nance indicator is showing red.
Thermal valve not functioning properly; change
(air-cooled only).

Low Water Pressure Water flow regulating valve not functioning prop-
erly; change (water-cooled only).

Defective discharge temperature switch; check


for a short or open circuit to probe and correct
wiring.

Check the fluid stop valve to be sure it is opening


properly on start-up of compressor.

COMPRESSOR WILL NOT Air Demand is Too Great Check service lines for leaks or open valves.
BUILD UP FULL DIS-
CHARGE PRESSURE Dirty Air Filter Check the filter indicator and change element if
required.

Pressure Regulators Out of Adjust regulators for spiral valve and inlet butter-
Adjustment fly valve according to control adjustment instruc-
tions in the Maintenance Section.

Defective Pressure Regulator Check diaphragm and replace if necessary (kit


available).

LINE PRESSURE RISES Leak in Control System Causing Loss Check for leaks.
ABOVE CUT-OUT PRES- of Pressure Signals
SURE SETTING ON
PRESSURE SWITCH Defective Pressure Switch Check that diaphragm and contacts are
functioning properly and are not damaged.
Replace if necessary.

Defective Solenoid Valve Check that Sullicon Control lever might have
moved to unload stop when the pressure switch
contacts open. Repair or replace if necessary
(kit available).

Defective Blowdown Valve Check that sump pressure is exhausted to the


atmosphere when the pressure switch contacts
open; repair or replace if necessary (kit avail-
able).

High Pressure Shutdown is Defective Re-adjust or replace.


or Adjustment is Incorrect
Continued ...
30
Section 8
TROUBLESHOOTING

8.2 TROUBLESHOOTING GUIDE (CONTINUED)


SYMPTOM PROBABLE CAUSE REMEDY
LINE PRESSURE RISES Plugged Control Line Filter Clean or repair if necessary.
ABOVE CUT-OUT PRES-
SURE SETTING ON
PRESSURE SWITCH
(CONTINUED)

EXCESSIVE COMPRES- Clogged Return Line or Orifice Clean strainer (screen and o-ring replacement kit
SOR FLUID CONSUMP- available).
TION
Clean orifice.

Separator Element Damaged or Not Change separator.


Functioning Properly

Leak in the Lubrication System Check all pipes, connections and components.

EXCESSIVE COMPRES- Excess Fluid Foaming Drain and change.


SOR FLUID CONSUMP-
TION (CONTINUED) Fluid Level Too High Drain until an acceptable level occurs.

Running with Pressure Too Low Check control adjustments and plant air usage.

PRESSURE RELIEF High Pressure Shutdown Switch is Re-adjust below pressure relief valve setting (175
VALVE OPEN REPEATED- Defective or Out of Adjustment (135 psig [12.1 bar]) or replace.
LY psig [9.3 bar])

Defective Pressure Relief Valve Replace pressure relief valve.

Check Separator Differential


(Plugged)

LIQUID WATER IN COM- Water Vapor Condensation From Remove the water vapor from compressed air
PRESSED AIR LINES Cooling and Compression Occurs prior to distribution through the air system. Check
Naturally operation of aftercooler and moisture separator.
Install a compressed air dryer sized for the flow
and dryness level required. (Note: Filters may
also be required to remove particulates, liquid oil
aerosols or for oil vapor removal. Change car-
tridges as recommended by the filter manufactur-
er.) Check all drain traps routinely to insure their
proper operation. Maintain them regularly.

31
NOTES

32
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

9.1 DESCRIPTION OF COMPONENTS speed and the sump pressure will quickly rise from
Refer to Figures 9-1A, 9-1B, 9-1C and 9-1D. The 0 to 50 psig ( 0-3.4 bar). During this period, both the
components and assemblies of the air compressor regulator and solenoid valves are closed, the inlet
are clearly shown. The complete package includes valve is fully open and the air-end delivers full
compressor, electric motor, variable speed capacity to the sump tank. The rising compressor
drive, Supervisor™ Controller, compressor inlet air pressure is isolated from the service line in this
system, compressor discharge system, com- phase by the minimum pressure valve set at
pressor lubrication and cooling system, capaci- approximately 50 psig (3.4 bar).
ty control system, instrument panel, aftercooler, FULL LOAD MODE- 50 TO 100 PSIG (3.4 TO 6.9
and combination separator and trap, all mounted BAR)
on a heavy gauge steel frame. When the compressed air pressure rises over 50
On air-cooled models, a fan draws air over the psig (3.4 bar) the minimum pressure valve opens
motor and forces it out through the combined after- allowing compressed air to flow into the service line.
cooler and fluid cooler thereby removing the com- From this point on the line pressure is continually
pression heat from the compressed air and the monitored by the Supervisor Controller, which con-
cooling fluid. trols the variable speed drive. The pressure regula-
On water-cooled models, a shell and tube heat tor and solenoid valve remain closed with the inlet
exchanger is mounted on the compressor frame. valve fully open running at 100 psig (6.9 bar) or
Fluid is piped into the heat exchanger where com- below.
pression heat is removed from the fluid. Another VARIABLE SPEED DRIVE PART LOAD CON-
similar heat exchanger cools the compressed air. TROL
Both air-cooled and water-cooled versions have If less than rated capacity of compressed air is
easily accessible items such as the fluid filters and being used, the service line pressure will rise
control valves. The inlet air filter is also easily above 100 psig (6.9 bar). Consequently, the
accessible for servicing. Variable Speed Drive will begin to decelerate the
motor, thereby reducing the output capacity to
9.2 CONTROL SYSTEM, FUNCTIONAL DESCRIP- match demand. The drive will continuously adjust
TION the motor speed (accelerate or decelerate) to main-
Refer to Figures 2-5B and 2-5C. The purpose of the tain a line pressure of 100 psig (6.9 bar). In this
compressor control system is to regulate the mode the VSD will operate within the appropriate
amount of the air being compressed to match the frequency range determined by the Supervisor
amount of compressed air being used. The Controller.
Capacity Control System consist of variable
MODULATING MODE WITH SPIRAL VALVE:
speed drive, solenoid valve, regulating valve,
As demand decreases, the variable speed drive
and the inlet valve. The functional description of
reduces motor speed to maintain the set point pres-
the control system is described below in six distinct
sure. When the speed approaches the minimum
phases of operation. The following description text
setting, a solenoid valve opens feeding air pressure
applies to V200TS series variable speed drive com-
to the spiral valve actuator. This in turn expands the
pressors with Supervisor Controller. Depending on
diaphragm and engages the pinion mounted on the
the model, the compressor can be operated at a
spiral valve shaft assembly, resulting in a rotary
setpoint pressure from 60 to 175 psig (4.1 to
motion and full opening of the spiral valve, effec-
12.1 bar). Refer to the nameplate for operating
tively reducing the rotor length by 50%. Excess air
pressure range. The Supervisor Controller will
will be returned back internally to the suction side of
automatically set the frequency range based on
the compressor unit. In this mode, the VSD will
the selected pressure. For explanatory purposes,
modulate the motor speed within a specified range
this description will apply to a compressor with an
to maintain the set point pressure as follows:
operating pressure of 100 psig (6.9 bar). A com-
pressor with any other pressure range would oper- Increasing demand condition:
ate in the same manner except stated pressures. If demand increases, the VSD increases the motor
speed until the set point pressure is achieved. If set
START MODE- 0 – 50 PSIG (0 TO 3.5 BAR)
point pressure is not achieved while at maximum
When the Supervisor Controller (START) button speed, the controller will close the spiral valve,
is depressed, the VSD ramps the motor to full thereby eliminating internal air bypass.

33
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Consequently, the VSD will regulate the motor valve. Simultaneously, the solenoid valve sends a
speed to achieve the set point pressure. pneumatic signal to the blow down valve. The blow-
Decreasing demand condition: down valve opens to the atmosphere, reducing the
While the spiral valve is open, if demand continues sump pressure. The check valve in the air service
to decrease the VSD will reduce the motor speed line prevents line pressure from returning to the
until the set point pressure is achieved. This action sump. The compressor will shut down after the
will continue until the minimum speed is reached. unload time setting expires if programmed (the
While at minimum speed, if the system pressure default setting is zero [0] seconds for an immediate
reaches 106 psig (7.3 bar), or alternatively set shutdown upon unload).
unload pressure, the compressor unloads, or turns When the line pressure drops to the low setting
off. pressure of 100 psig (6.9 bar) The Supervisor
UNLOAD MODE- IN EXCESS OF 106 PSIG (7.3 Controller starts the motor and energizes the sole-
BAR) noid valve which closes the blow down valve.
When a relatively small amount or no air is being AUTOMATIC OPERATION
used, the service line pressure continues to rise. For VSD applications, the Supervisor Controller
When it exceeds 106 psig (7.3 bar), or alternative- should be set in the “Automatic” mode. This mode
ly set unload pressure, the Supervisor control sys- allows the compressor to shutdown when no com-
tem de-energizes the solenoid valve allowing sump pressed air requirement is present and restarts
air pressure to be supplied directly to close the inlet when compressed air is needed.

34
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-1A Sullair V200TS Rotary Screw Air Compressor- Air-cooled (typical component layout)

35
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-1B Sullair V200TS Rotary Screw Air Compressor- Air-cooled (I) (typical component layout)

(I) Applies to the following models:


HP/KW 380V 460V 575V
125/93 X
150/112 X X
200/150 X X X

36
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-1C Sullair V200TS Rotary Screw Air Compressor- Water-cooled (typical component layout)

37
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-1D Sullair V200TS Rotary Screw Air Compressor- Water-cooled (I) (typical component layout)

(I) Applies to the following models:


HP/KW 380V 460V 575V
125/93 X
150/112 X X
200/150 X X X

38
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

NOTES

39
Section 9
VARIABLE SPEED DRIVE APPLICATIONS
Figure 9-2 V200TS Piping and Instrumentation (Air-cooled)

02250145-601R02

40
Section 9
VARIABLE SPEED DRIVE APPLICATIONS
Figure 9-2 V200TS Piping and Instrumentation (Air-cooled)
key description part part part quantity
number number number number
100HP/ 125-150HP/ 200HP/
75KW 93-112KW 150KW

1 filter, air inlet 409264 02250140-798 02250140-798 1


2 valve, inlet butterfly 040336 040336 040338 1
3 control, Sullicon 011682-003 011682-003 011682-003 1
4 valve, shuttle 1/4” 408893 408893 408893 2
5 valve, solenoid 1/4” 3-way 115vac 02250125-657 02250125-657 02250125-657 2
6 filter, control 1/4” npt 02250112-032 02250112-032 02250112-032 2
7 orf, plug brass 1/8” x 1/32” 02250125-774 02250125-774 02250125-774 1
8 vlv, 1/2” bldwn 1.8:1 250 psig 02250100-042 02250100-042 02250100-042 1
9 silencer, air 1/2” 041006 041006 041006 1
10 p, rtd 100ohm platinum 12ft 250039-909 250039-909 250039-909 4
11 xdcr, press 0-250psi 1-5vdc n4 w/10’cable 02250078-933 02250078-933 02250078-933 4
12 orf, plug brass 1/8”npt x 1/16” 02250125-775 02250125-775 02250125-775 1
13 gl,sight/orf blk-sae 02250126-129 02250126-129 02250126-129 2
14 fltr, assembly genisis filter 02250117-782 02250117-782 02250117-782 2
15 valve, min press check 242405 250033-821 250033-821 1
16 element, primary separator 250034-121 250034-121 250034-121 1
17 element, secondary separator 250034-133 250034-133 250034-133 1
18 valve, spiral (I) (I) (I) 1
19 valve, relief 1 1/4” 175# 410103 410103 410103 1
20 tnk, oil sep ls25-200 20”dia 4”asa inlt flg 02250108-073 02250108-073 02250108-073 1
21 glass, fluid level 1 1/2” sight 040279 040279 040279 1
22 valve, globe 3/4” 200# 02250117-792 02250117-792 02250117-792 1
23 vlv, rlf 1-1/4 “x2” 65# vit.seal 02250083-571 02250083-571 02250083-571 1
24 thermal valve assy, 12/16s 014512 014512 014512 1
25 filter, fluid 250025-522 250025-522 02250121-656 1
26 cooler, fluid/combo 250022-529 250022-529 250022-529 1
27 separator, moisture (I) (I) (I) 1
28 valve, oil stop ci 2”npt 016742 016742 016742 1
29 sw, vac 22”wc n4 6ft cable 5a 02250078-249 02250078-249 02250078-249 1
30 unit, compressor ts20 (I) (I) (I) 1
31 vlv, sol 2wnc 1/4 200# n4 110/120 02250125-674 02250125-674 02250125-674 1
32 strainer, y 1/4” 241771 241771 241771 1
33 orf, cap 0.031 x 1/4”npt 02250132-934 02250132-934 02250132-934 1
34 ga, air press 2-1/2” 0-200 psi 02250117-009 02250117-009 02250117-009 1
35 regulator, press-1/4npt 2-150# 02250046-568 02250046-568 02250046-568 1
36 valve, ball 1/4” npt 047115 047115 047115 1
MOISTURE SEPARATOR HEATER OPTION:
37 heater, trap 50watt 120v spcl 245572 245572 245572 1
Continued on page 43

(I) This part number may vary in accordance with your machine construction. To determine correct part
number, consult factory with serial number of machine.

41
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-2 V200TS Piping and Instrumentation (Air-cooled)

02250145-601R02

42
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-2 V200TS Piping and Instrumentation (Air-cooled) (continued)


key description part part part quantity
number number number number
100HP/ 125-150HP/ 200HP/
75KW 93-112KW 150KW

EES SOLENOID VALVE OPTION:


38 vlv, sol 4way 1/4 150# n4 110/120v 02250125-674 02250125-674 02250125-674 1
SUMP HEATER OPTION:
39 heater, sump 1800w 120v pad 02250043-014 02250043-014 02250043-014 1
SCD DRAIN OPTION:
40 valve, ball 1/4” npt 047115 047115 047115 1
41 drain, elec condensate scd 02250130-866 02250130-866 02250130-866 1
FOR OPERATING PRESSURES ABOVE 150PSI/10.3 BAR:
42 ga, air press 2-1/2” 0-200 psi 02250117-009 02250117-009 02250117-009 1
43 regulator, press-1/4npt 2-150# 02250046-568 02250046-568 02250046-568 1

43
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-3 V200TS Piping and Instrumentation (Water-cooled)

02250145-638R02

44
Section 9
VARIABLE SPEED DRIVE APPLICATIONS
Figure 9-3 V200TS Piping and Instrumentation (Water-cooled)
key description part part part quantity
number number number number
100HP/ 125-150HP/ 200HP/
75KW 93-112KW 150KW

1 filter, air inlet 409264 02250140-798 02250140-798 1


2 valve, inlet butterfly 040336 040336 040338 1
3 control, Sullicon 25s 011682-003 011682-003 011682-003 1
4 valve, shuttle 1/4” 408893 408893 408893 2
5 valve, solenoid 1/4” 3-way 115vac 02250125-657 02250125-657 02250125-657 2
6 filter, control 1/4” npt 02250112-032 02250112-032 02250112-032 2
7 orf, plug brass 1/8’ x 1/32” 02250125-774 02250125-774 02250125-774 1
8 vlv,1/2” bldwn 1.8:1 250 psig 02250100-042 02250100-042 02250100-042 1
9 silencer, air 1/2” 041006 041006 041006 1
10 p, rtd 1000hom platinum 12ft 250039-909 250039-909 250039-909 4
11 xdcr, press 0-250psi 1-5vdc n4 w/10’cable 02250078-933 02250078-933 02250078-933 4
12 orf, plug brass 1/8”npt x 1/16” 02250125-775 02250125-775 02250125-775 1
13 gl, sight/orf blk-sae 02250126-129 02250126-129 02250126-129 2
14 fltr, assembly genisis filter 02250117-782 02250117-782 02250117-782 2
15 valve, min. press. check 242405 250033-821 250033-821 1
16 switch, low water press. 250017-992 250017-992 250017-992 1
17 valve, water reg. 1 1/4” 049474 049474 049474 1
18 element, primary separator 250034-121 250034-121 250034-121 1
19 element, secondary separator 250034-133 250034-133 250034-133 1
20 valve, spiral (I) (I) (I) 1
21 valve, relief 1 1/4” 175# 410103 410103 410103 1
22 tnk, oil sep ls25-200 20”dia 4”asa inlt flng 02250108-073 02250108-073 02250108-073 1
23 glass, fluid level 1 1/2” sight 040279 040279 040279 1
24 valve, globe 3/4” 200# 02250117-792 02250117-792 02250117-792 1
25 vlv, rlf 1-1/4 “x2” 65# vit.seal 02250083-571 02250083-571 02250083-571 1
26 thermal valve assy, 12/16s 014512 014512 014512 1
27 filter, fluid 02250121-656 02250121-656 02250121-656 1
28 ga, air press 2-1/2” 0-200 psi 02250117-009 02250117-009 02250117-009 1
29 cooler, fluid 043031 043031 043031 1
30 aftercooler 043008 043009 042541 1
31 separator, moisture (I) (I) (I) 1
32 valve, oil stop ci 2”npt 016742 016742 016742 1
33 regulator, press - 1-1/4npt 2-150# 02250046-568 02250046-568 02250046-568 1
34 sw, vac 22”wc n4 6ft cable 5a 02250078-249 02250078-249 02250078-249 1
35 unit, compressor 20/16 (I) (I) (I) 1
36 vlv, sol 2wnc no 1/4 200# n4 110/120 02250125-674 02250125-674 02250125-674 1
37 strainer, y 1/4” 241771 241771 241771 1
38 orf, cap .031 x 1/4” 02250132-934 02250132-934 02250132-934 1

Continued on page 47

(I) This part number may vary in accordance with your machine construction. To determine correct part
number, consult factory with serial number of machine.

45
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-3 V200TS Piping and Instrumentation (Water-cooled)

02250145-638R02

46
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-3 V200TS Piping and Instrumentation (Water-cooled) (continued)


key description part part part quantity
number number number number
100HP/ 125-150HP/ 200HP/
75KW 93-112KW 150KW

39 valve, ball 1/4” npt 047115 047115 047115 1


WATER SHUT-OFF SOLENOID OPTION:
40 valve, solenoid water shutoff 250035-291 250035-291 250035-291 1
SCD DRAIN OPTION:
41 valve, ball 1/4” npt 047115 047115 047115 2
42 drain, elec condensate scd 02250130-866 02250130-866 02250130-866 1
SUMP HEATER OPTION:
43 heater, sump 1800w 120v pad 02250043-014 02250043-014 02250043-014 1
FROST-FREE TRAP OPTION:
44 heater, trap 245572 245572 245572 1
FOR OPERATING PRESSURES ABOVE 150PSI/10.3 BAR:
45 ga, air press 2-1/2” 0-200 psi 02250117-009 02250117-009 02250117-009 1
46 regulator, press - 1-1/4npt 2-150# 02250046-568 02250046-568 02250046-568 1

47
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-4 Identification- V200TS Air-cooled with Enclosure 100-150HP/75-112KW

02250147-156R01

48
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-5 Identification- V200TS Air-cooled with Enclosure 125-200HP/93-150KW

02250147-155R01

49
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-6 Identification- V200TS Water-cooled with Enclosure 100-150HP/75-112KW

02250147-197R01

50
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-7 Identification- V200TS Water-cooled with Enclosure 125-200HP/93-150KW

02250147-196R01

51
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-8 Wiring Diagram V200TS Non-CE

02250145-403R02

52
Section 9
VARIABLE SPEED DRIVE APPLICATIONS

Figure 9-9 Wiring Diagram V200TS CE

02250145-404R02

53
NOTES

54
Section 10
ILLUSTRATIONS AND PARTS LIST

10.1 PROCEDURE FOR ORDERING PARTS


Parts should be ordered from the nearest Sullair Representative or the Representative from whom the com-
pressor was purchased. If for any reason parts cannot be obtained in this manner, contact the factory directly
at the addresses, phone or fax numbers below. When ordering parts always indicate the Serial Number of the
compressor. This can be obtained from the Bill of Lading for the compressor or from the Serial Number Plate
located on the compressor.

SULLAIR ASIA, LTD. SULLAIR CORPORATION SULLAIR EUROPE, S.A.


Sullair Road, No. 1 3700 East Michigan Boulevard Zone Des Granges BP 82
Chiwan, Shekou 42602 Montbrison Cedex, France
Michigan City, Indiana 46360 U.S.A.
Shenzhen, Guangdong PRV. Telephone: 33-477968470
PRC POST CODE 518068
www.sullair.com
Fax: 33-477968499
Telephone: 755-6851686 Telephone: 1-800-SULLAIR (U.S.A. Only) www.sullaireurope.com
Fax: 755-6853473 or 1-219-879-5451
www.sullair-asia.com Fax: (219) 874-1273
PARTS DEPARTMENT
1-888-SULLAIR (U.S.A. Only)
Fax: (219) 874-1835
www.sullair.com
SERVICE DEPARTMENT
Fax: (219) 874-1205
www.sullaircompressors.com

10.2 SPARE PARTS LIST- TS-20 AND V200TS


DESCRIPTION KIT NUMBER QTY
element for air filter no. 408399 (100-150HP/ 75-112KW) 405158 1
element (primary) for air filter no. 409264(100HP/ 75KW) 409853 1
•element (secondary) for air fitler no. 409264(125-250HP/112-187KW) 409854 1
element for air filter (200-250HP/ 75-187KW) 02250135-150 1
repair kit for fluid filter no. 250025-522 (100-150HP/ 75-112KW) 250025-526 1
repair kit for fluid filter no. 250007-219 (200-250HP/ 75-187KW) 250008-956 1
repair kit for primary separator element 250034-121 1
repair kit for secondary separator element 250034-133 1
repair kit for Sullicon Control no. 011682-003 250020-353 1
replacement seal for compressor shaft seal 02250049-020 1
tool kit for shaft seal installation 606174-001 1
repair kit for thermal valve no. 014512 001168 1
repair kit for fluid stop valve no. 016742 001684 1
replacement kit for blowdown valve no. 02250100-042 02250100-042 1
repair kit for control air filter no. 02250112-032 02250112-031 1
reducing regulator valve no. 02250046-568 02250055-911 1
repair kit for minimum pressure/check valve no. 242405 001176 1
repair kit for minimum pressure/check valve no. 250033-821 250018-262 1
repair kit for water separator no. 410144 250033-038 1
repair kit for moisture separator no. 02250106-113 02250144-791 1
repair kit for moisture separator no. 02250144-632 02250144-732 1

Continued on page 56

PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR

55
Section 10
ILLUSTRATIONS AND PARTS LIST
10.2 SPARE PARTS LIST- TS-20 AND V200TS (CONTINUED)
DESCRIPTION KIT NUMBER QTY
repair kit for air cylinder 250016-183 (I) 608311-001 1
repair kit for discharge check valve 018435 606206-001 1
repair kit for solenoid valve no. 02250125-653 02250125-843 1
•replacement coil for solenoid valve no. 02250125-653 02250125-855 1
repair kit for solenoid valve no. 02250125-656 02250125-828 1
•replacement coil for solenoid valve no. 02250125-656 02250125-858 1
repair kit for solenoid valve no. 02250125-657 02250125-829 1
•replacement coil for solenoid valve no. 02250125-657 02250125-861 1
repair kit for pressure regulator valve 406929 250028-693 1
repair kit for pressure regulator valve 408275 041742 1
repair kit for strainer 241771 241772 1
lubricant, Sullube (5 gallon/20 liters) (II) 250022-669 30 gal (III)

(I) Order actuator diaphragm repair tool kit no. 02250052-625.


(II) Sullube available in 55 gallon/115 liter drum (P/N 250022-670).
(III) Sump capacity.
PLEASE NOTE: WHEN ORDERING PARTS, INDICATE SERIAL NUMBER OF COMPRESSOR

56
NOTES

57
WORLDWIDE SALES AND SERVICE

SULLAIR ASIA, LTD.


SULLAIR EUROPE, S.A.
Sullair Road, No. 1
Zone Des Granges BP 82
Chiwan, Shekou
42602 Montbrison Cedex, France
Shenzhen, Guangdong PRV.
Telephone: 33-477968470
PRC POST CODE 518068
Fax: 33-477968499
Telephone: 755-6851686
www.sullaireurope.com
Fax: 755-6853473
www.sullair-asia.com

SULLAIR CORPORATION
3700 East Michigan Boulevard
Michigan City, Indiana 46360 U.S.A.
www.sullair.com
Telephone: 1-800-SULLAIR (U.S.A. Only)
or 1-219-879-5451
Fax: (219) 874-1273
PARTS DEPARTMENT
Fax: (219) 874-1835
www.sullair.com
SERVICE DEPARTMENT
Fax: (219) 874-1205
www.sullaircompressors.com

Printed in the U.S.A.


Specifications Subject To
Change Without Prior Notice
E04

You might also like