You are on page 1of 54

ZJ - 4015D

TENSION CONTROLLER

MODEL LE-40MTA-E
INSTRUCTION MANUAL

Introduction:
• This instruction manual describes the minimum necessary operations and functions for the
optimum adjustment of machines by using the LE-40MTA-E tension controller in Sections
1 through 5 taking "One-reel unwinding powder" shown below as an example.
Before start setting any systems, thoroughly read these five sections first.

• When mechanism other than "One-reel unwinding powder" is used, read Section 6 "Mech-
anism other than one-reel unwinding powder" for setting. For the basic items such as the
initialization, wiring as well as zero and span adjustment, read Sections 1 through 5.

• When using functions other than the above, read Section 7 "Use of extensive functions"
and after.

• Note that this instruction manual is applicable to system ROM version 3.00 or later.

Example of "One-reel unwinding powder "

Tension detector

Powder brake

Tension controller
Cautions on Safety
(Make sure to read this page before using the unit .)

To assure safety
DANGER: When the unit is handled incorrectly , a
dangerous situation may occur and the
• Make sure the user thoroughly read this instruction manual possibility of death or serious injury is
before using the unit , and pay attention in assuring safety expected.
while using the unit .

• The unit is manufactured under the severe quality control . CAUTION: When the unit is handled incorrectly , a
When a severe accident or loss is expected in the dangerous situation may occur and the
equipment used due to failure of the unit , provide a backup possibility of medium or slight injury is
function or the fail -safe function in the system . expected or property damage exclusively
is expected.
In this manual , cautions of safety are classified into "DANGER"
and "CAUTION". Even an item is classified as "CAUTION", its contents are
important and it may lead to a serious result depending on the
situation. Make sure to observe every item .

DANGER Turn off all the phases of the external power


supply before starting installation and wiring .
Design the installation plan using the wire
DANGER size suitable to the current capacity .
Otherwise, electrical shock or damage in the unit may Use the wire size suitable to the current capacity to
occur. Make sure to turn off all the phases of the supply the power to the load . If a wire having smaller
external power supply before starting installation and current capacity is used,the insulation sheath will be
wiring. melted and insulation will become defective . In this
situation, electrical shock or a short-circuit may occur,
and fire may occur .

DANGER Perform grounding ( grounding registance


100Ω or less). Set up the emergency stop circuit
DANGER independently of the product .
Otherwise, electrical shock may occur. Perform
grounding ( grounding registance 100Ω or less) to the Otherwise, the unit may become out of order and an
2
unit using a wire of 2 mm or more, otherwise, electrical accident may occur when malfunction occurs in the
shock may occur. Never share the grounding with a tension controller. Make sure to assemble the
strong electric system. emergency stop circuit outside the tension controller .

Never open the covers while the power is


DANGER supplied to the unit or when the unit is DANGER Never use the unit in an atmosphere where
inflammation or explosion can occur .
operating.
Never supply the power to the unit nor operate the unit Otherwise, inflammation or explosion may occur .
while the main body cover and the terminal cover are
open. When the covers are open , a high voltage area
may be exposed and electrical shock may occur . Separate the wiring of the strong electric
CAUTION system from the wiring of the weak electric
system.
Separate the wiring of the strong electric system from the
DANGER Never touch a switch with a wet hand . wiring of the weak electric system, and make sure that
noises are not superimposed on the wiring of the weak
Never touch a switch with a wet hand , otherwise, electric system. Otherwise, the unit may not operate
electrical shock may occur. correctly.

Never drop cutting chips and wire chips CAUTION Confirm the ambient enviroments .
DANGER while screw holes are tapped and wiring
work is performed. Never install the unit with an enviroment where dusts , soot,
Damage , fume , fire, malfunction or others may be conductive dusts or corrosive gas is present or a place
caused in the unit . exposed to high temperature , condensation or wind and
rain. Otherwise, the unit may be damaged , malfunction or
be deteriorated .

DANGER Never modify nor disassemble the unit Do not use any unused terminals for any
CAUTION external lines.
Never modify nor disassemble the unit . Otherwise, the
unit may become defective or an accident such as fire , Correctly connect the AC power cable to the specified
damage , etc . may occur. terminal, and do not use any unused terminals for any
external lines. Improper connection may seriously
damage the product .

CAUTION • We shall not be responsible for any damage caused by repair , disassembly, modification, etc. performed
by a third party other than MITSUBISHI or a company specified by MITSUBISHI .
• The cautions on safety and the specifications described in the instruction manual are subject to change
without notice .
Table of Contents
1. Outline 7. Use of extensive functions
1.1 Outline of unit -------------------------------- 2 7.1 Control of excessive sag or tension in
1.2 Panel configuration ------------------------- 3 material during start and stop--------- 26
7.2 Control of excessive sag or tension in
material during acceleration and
2. Mounting and wiring (basics) deceleration -------------------------------- 27
2.1 Caution on mounting ----------------------- 4 7.3 Control of excessive winding tension
2.2 Wiring ------------------------------------------ 5 Internal reel diam eter taper control-- 28
7.4 External reel diameter taper control ----- 30
7.5 Change of control gains -------------------- 32
3. Operation 7.6 Output of contact when running out of
material -------------------------------------- 34
3.1 Setting and change of settings ---------- 6
7.7 Use for machines with frequent inching
3.2 Overall flow of screen ---------------------- 7
operation ------------------------------------ 34
7.8 Externally turns on or off control output -- 35
7.9 Setting of mechanical loss with two-reel
4. Basics of adjustment and operation switching -------------------------------------- 35
4.1 Adjustment flow for trial operation ------ 8 7.10 Use of cut torque ---------------------------- 36
4.2 Initial setting ---------------------------------- 8 7.11 Reduction of variation in tension readout 36
4.3 Adjustment of zero and span for tension
detector ------------------------------------- 10 8. Use of external analog signals
4.4 Automatic operation ------------------------ 11
8.1 Varies set tension ---------------------------- 37
8.2 Enters reel diameter data ------------------ 37
8.3 Varies stall ------------------------------------- 38
5. Basic knowledge for operation 8.4 Varies taper ratio ----------------------------- 38
5.1 Entering Run/stop signals (use of MC1) --12 8.5 Varies new reel torque ---------------------- 39
5.2 Use of stall setting 8.6 Enters external tension data--------------- 39
(output when operation is stopped)-- 13
5.3 Calling up engineer screen --------------- 15 9. Other functions
5.4 Display of operator screen---------------- 16
9.1 Records tension data------------------------ 40
9.2 Monitors input and output condition ----- 40
9.3 Returns all settings to initial factory
6. Mechanism other than settings -------------------------------------- 40
one-reel unwinding powder 9.4 Copies data settings to other controller --- 41
6.1 Use of AC servo motor -------------------- 18
6.2 Use of E/P regulator------------------------ 19
6.3 Use for winding operation----------------- 20
6.4 Use for both winding and unwinding 10. Inspection and maintenance
operation ----------------------------------- 20 10.1 Initial inspection ----------------------------- 42
6.5 Feed reel control ---------------------------- 21 10.2 Maintenance --------------------------------- 42
6.6 Simultaneous multi-reel control --------- 22 10.3 Error display --------------------------------- 43
6.7 Powder unwinding, two-reel switching- 23 10.4 Unintended operation---------------------- 44
6.8 Powder winding, two-reel switching------ 24
6.9 Servo winding and unwinding, 11. Specifications, miscellaneous
two-reel switching ------------------------ 25
11.1 Input and output specifications---------- 46
11.2 External connection diagram ------------ 48
11.3 Various setting values --------------------- 49
11.4 Select items and analog data------------ 50
11.5 Outline dimensions and environmental
conditions ----------------------------------- 51
11.6 Supplement ---------------------------------- 52

1
1. Outline

1.1 Outline of unit


The tension controller LE-40MTA-E automatically controls the tension of a long material during unwinding,
use of the feed reel and winding, and is used together with the fine displacement tension detector.
The applicable actuators are powder clutch/brake, hysteresis clutch/brake, servo motor (torque mode), and
air clutch/brake.

• The tension setting and the manual operation torque usually used by the operator can be adjusted
easily using the trimmers provided on the panel.
• The diversified system parameters and operation parameters which must be set by the engineer before
operation can be set using the NUMERIC INPUT (increase/decrease) keys while checking the LCD
display provided on the panel.
• The automatic zero adjustment function and the span adjustment function for the tension detector as
well as the automatic control gain adjustment function for automatic adjustment are offered.
• The operation data can be read and written using the memory cassette FX-EEPROM- 4 (or-8) sold sep-
arately.
External
Potensiometer
Tension Tension
setting detector

Stall
New reel preset
Taper rate
Diameter ,Tension

AC85~264V Contact
50/60Hz Power supply Input
LE-40MTA-E
Run/Stop
Reel change
Gain1
LE-40MTA-E TENSION CONTROLLER
×10N MONITOR
SELECT
Stall memory reset
OUTPUT
ON/OFF
Gain2 Output remorte
CURSOR MODE Inching Cut torque Selected
AUTO MANUAL
EXT Tension
POWER
TENSION SET
5
MANUAL SET
5 P/N Power Amplifier Output
ENTER
ON
PAGE
0~24V
INC/DEC

OFF CANCEL
0 10 0 10

New reel preset

Zero Power
Tension Amplifier
Output
Powder clutch/brake
hysteresis clutch/brake

Servo motor
E/P
Recorder regulator

Air clutch
Tension meter
brake

The above external devices may be connected to the input/output terminals of the tension controller.
The tension detector, actuator and some of the command input switches (those indicated with white let-
ters on a black background) are mandatory. Other devices are connected as necessary.

2
1.2 Panel configuration
The figure below shows the configuration of the panel of the tension controller LE-40MTA-E.
(5) (6) (7) (1) : POWER switch (11) : Door open screw
(8) (2) : Power LED (12) : MANUAL mode switch
(3) : Output ON/OFF switch (13) : Manual mode LED
(9) (4) : Output ON/OFF LED (14) : Manual torque set
(5) : LCD display trimmer
(4)
−E (6) : Bar graph (15) : AUTO mode switch
(10)
MONITOR

(3) OUTP UT
ON/ OFF
S ELE CT
Upper :Tension monitor (%) (16) : Automatic mode LED
CURS OR
MODE
(11) Lower :Target tension (%) (17) : TENSION SET trimmer
(2)
POWER
AUTO MANUAL
(7) : Scale (18)(19) : Screen scroll keys
TE NS ION S E T MANUAL S ET

ON ENTE R (8) : Seven-segment display (20)(21) : Cursor contorol keys


(1) OFF
INC/ DE C P AGE
(9) : Unit LED (22)(23) : Numeric input keys
CANCE L

(10) : DISPLAY SELECTOR (24) : CANCEL key


Tension and output are (25) : ENTER key
(25) (21) (20) (14) selected alternately.
(24) (22) (19) (17) (16) (13) Selection of kgf or N is
(23) (18) (15) (12) set by the parameter.

1. POWER switch and OUTPUT ON / OFF switch

Turn on the POWER switch and the OUTPUT ON/OFF switch to light the LEDs provided on the upper
portion of the both switches.
(Note) Use OUTPUT ON/OFF switch or OUT REMOTE input without using the POWER
switch when the output is turned on and off.
• Allowable power switch cycles : 20,000 times

2. DISPLAY SELECTOR switch

The monitored operating tension value is always displayed in the bar graph on the upper right of the
screen.
Under the bar graph, the operating tension or control output is displayed in numeric.
The control output or the operating tension is displayed on the seven-segment display in the same way.
The type of contents displayed is changed every time the Tension/Output selector switch is pressed. The
type of contents displayed on the seven-segment display is indicated by the LED provided on the left
side of the selector switch.
The unit of tension (×10N or N) is specified by the setting of the parameter.

3. Automatic operation ( Basic operation ) Full scale tension


→ Set tension (N)

When the AUTO switch is pressed, the unit performs automatic oper-
ation. However, automatic control is not performed if the operation/
stop input is not turned on.
The tension set value changes from 0 to full scale value in accor-
dance with the scale of the tension set trimmer of 0 to 10.
The full scale tension is set in the initial setting.
0 2 4 6 8 10
When the taper tension is controlled in accordance with the reel diam- Left Trimmer Right
eter, the tension set value subtracted by the taper tension is regarded Tension set
as actual target tension and used during automatic control.
100
→ Control output (%)
60 80

4. Manual operation

When the MANUAL switch is pressed, manual operation is available.


40

The control output of 0~100% can be obtained with the scale of the
20

manual torque set trimmer 0~10. (The output is 0~5V both in the ser-
vo mode and the powder mode.) 0 2 4 6 8 10
Left Trimmer Right
Manual set

3
2. Mounting,connection and wiring

2.1 Caution on mounting


DANGER • Never drop cutting chips and wire chips while screw holes are tapped and wiring
work is performed. Otherwise, damage, fume, fire, malfunction or others may be
caused in the unit.
• Make sure to turn off all the phases of the power supplies outside before starting
installation and wiring.
• Make sure to turn off all the phases of the power supplies outside also before at-
taching or removing the memory cassette.Otherwise, electric shock or damage in
the unit may occur.
• Make sure to attach the terminal block cover offered as an accessory to the unit
to prevent electrical shock before supplying the power after the wiring work.
CAUTION • Never install the unit in a place with dusts, soot, conductive dusts or corrosive gas
or a place exposed to high temperature, condensation, wind or rain. Never install
the unit directly in a place in which vibration or impact is applied.
Otherwise, damage, malfunction or deterioration may be caused.

The tension controller can be installed on the floor, wall or panel surface.

Installed on floor Installed on wall Installed on Panel surface


4-M4×12
Mounting screw The unit is fixed
from rear face
with pressure
LE -40 MTA - E
welding and
TENSI O N CO NTRO LLER ×10N M O NI TO R
N SELECT
O UTPUT %
O N/ O FF
16 8

fixing screws.
MO D E
CUR S OR

POWER A U TO MA N U A L

TE N S I O N S E T MA N U A L S E T

E N TE R
ON
I N C/ D E C P A GE

O FF CANCEL


256 FG on
20 or less 172.5 2~4 metal plate
36.5 or less 140

Perform the solid grounding in either


position marked with * in which the main
body mounting plate is not fixed.

Screw hole dimensions for Memory cassette


mounting on floor or wall.
4 -M4
80±0.5

+3
244 -0.5

Panel cut dimensions for


mounting on panel surface.

Front door
15 0±0.5

Lead wire hole


Terminal block ( with cover )
The terminal block to connect external devices is provided inside the box .
When the front door is open, the terminal block can be seen. Pull the lead wire out of the
box from the lead wire hole provided on the lower portion of the box.
232 ±0.5

General description on wiring work


• Use crimp-style terminals whose dimensions are as shown in the figure on the left.
7.8 or

• The terminal tightening torque shall be 0.5 to 0.8 N•m (5 to 8 kgf•cm). Tighten the termi-
less

nals securely so that malfunction will not be caused.


M3.5 • Perform Class 3 grounding to the analog I/O cables and the winding shaft pulse input
cable with shielded cables on the signal receive side.
7.8 or

• Never let the I/O cables pass through a duct together with other power cables. Never bind
less

the I/O cables together with other power cables.


• Generally, the allowable wiring length shall be 10 m or less to assure safety against noise.
General description on wiring work

4
2.2 Wiring
• Set the emergency stop circuit outside the tension controller. If the tension con-
troller performs malfunction, the unit may become out of order and an accident
may occur in the case in which the emergency circuit is built in the unit.
DANGER Connect the AC power supply to the terminals PSL and PSN as shown in the
figure above.
• If the AC power supply is connected to the I/O terminal or DC supply terminal, the
tension controller will be burn out.
Do not use the spare terminal for an external device. Otherwise, the unit may
be damaged. Perform the solid grounding to the ground terminal and FG using a
wire of 2mm2 or more.
• Never perform grounding together with the strong power system. Otherwise, mal-
functionmay be caused.
The minimum connection reguired for the one-reel unwinding are as follows :
1. Connect AC100 to 240V 50/60 Hz power supply to power supply terminals PSL and PSN. The power
consumption is 400VA when the output of the power amplifier is at the maximum .
2. Perform the solid grounding to the ground terminals and metal plate according to Class D grounding.
3. Connect the tension detector.
4. If the actuator is a powder type, connect it between terminals P and N. If it is a torque-controllable
servomotor, connect it between terminals SA and SN. If it is an electric-pneumatic regulator of 4-
20mA, connect it between terminals EAP and EAN.
5. Connect the Run/stop signals to the terminal MC1.
When using other functions, refer to Section 6 and after.

Power supply PSL LE-40MTA-E


AC100~240V PSN
50~60Hz P DC24v, 4A
Powder clutch/brake
Class D grounding N Hysteresis clutch/brake
( 100Ω or less )
FG
Tension detector
(Right)
GRR SA DC0~5V
WHR Servo amplifier
SG 5V SN Power amplifier
RED
BLK
GRL
WHL EAP
4~20mA
SG
Tension detector E/P regulator
EAN
(Left)
Run /
MC1
Stop

MCC
8V

Wiring of Tension Detector


• The figure on the right shows the connection diagram when the load is applied to the detector in
the compression direction.
When the load is applied in the tension direction, exchange the terminals GRR and WHR each
other as well as the terminals GRL and WHL each other.
• When one tension detector is used, connect it to the right side. And make sure to short-circuit the
terminals GRL and WHL on the left side.

5
3. Operation

3.1 Setting and change of settings

1. Selection of item on screen

When two or more items are displayed on the screen, one of them can be selected using the following pro-
cedure. The selected item is marked with " „ ", and held in the memory even while the power is interrupted.
When the menu items cannot be displayed on one screen, they can be scrolled and displayed using the
cursor control keys ( T S ).

T S Flashing cursor is T S Flashing cursor is ENTER


placed at the top item . Cursor placed at the top item. „ mark is lit.
Select screen
is moved Selection is
„ mark flashes „ mark flashes
registered.

2. odification of set value on screen

When numeric will When numeric will be


be set for one item set for two or more
onthe screen . items on the screen.

Select the desierd item using the cursor


control keys and ENTER key.
This selection procedure is not required for an
already selected item .
External analog input
Setting of items in use Normal setting
Set by external trimmer Set through panel
The fixation of a
When indicated as "External" on Perform the tension setting numeric input should
the screen, the setting changes (TENSION SET) and manual
according to the external setting (MANUAL SET) using the push the " ENTER "
controller setting to display on the trimmer provided on the panel key.
screen. (Setting can be made (Entering of a numeric directly is
without screen display .) not possible .).
When the "External" indication The set value is modified even if
goes out , it indicates that the the value is not displayed on the • When an item which can
external controller set value has screen. be modified is selected,
become smaller than the panel under-cursor " _ " is
set value. Increase or decrease the displayed in the numeric
displayed value using the
numeric input field.
input keys , then press the
ENTER key for determination. • When an item which can
Tension setting and manual not be modified is selected,
setting are set by the trimmer , but the under -cursor " _ " is
cannot set by the numeric input
key. not displayed.

6
3.2 Overall flow of screen
The figure below shows the overall configuration of screen displays.
The data can be read in turn using the T and S keys.
Four major screens are available. Those are the initial setting screen, operator screen of usual operation,
engineer screen for system setting and memory cassette data transfer screen. This section shows the over-
all flow of the operator screen that is used in usual operation and the engineer screen. For other screens,
refer to the relevant sections.

Operator screens Initial setting


(usual operation) screens
AUTO Tension set Power on
switch screen for the
first time
T S

Stall setting T Initial setting


(New reel setting) Pass word
Taper setting S Full scale setting
Zero/Span adjustment
T S
MANUAL Manual set T S
switch screen
Confirm setting
T S

Tension monitor 1 T
Tension monitor 2
Diameter monito S

T S
Password Instal mode only
screen Including all functions except the password setting on the initial setting screen.
Settings made during the initial setting can be changed as necessary.
T S
Engineer screens (system parameters and operation parameters )

Switch Tension Start Reel change Reel Others Gain


and stop
Unit Filter Preset T Mech.loss Contact Gain
Control (Display) Start T Cut torque Diameter monitor adjustment
reels Filter Stop T Voltage
T Number of (Output) Stop G monitor
S reels ZT Set
Taper Zero Stop B
Actuator adjustment Out G inhibition
Stall Span
AI2 adjustment Initialize
AI3 Full scale memory
MC5
MC6

T T T T T T T

7
4. Basics of adjustment and operation

4.1 Adjustment flow for trial operation


Carry out the following start-up adjustment as the preparatory step for the automatic operation.

(1) (2) (3)

Controller Controller Check the driving


installation and * Initial setting system in manual
wiring * Adjust tension detectors operation mode

See pages 8 through 10.


(4) (5) (7)
Check by automatic Operating parameter Completion of
operation adjustment as necessary adjustment
Operational check See page 26 and after.

(6)
Check for abnormalities when
error occurs.
See pages 43 through 45.

4.2 Initial setting


Select the items using the W and X keys.
Press the [Enter] key to finalize the setting.
Then, switch the screens using the T and S keys.
When the setting of the items marked with "„" is not changed,
switch the screens using the T and S keys without press-
ing the [Enter] key.

Power ON

L E - 4 0 M T A - E T e n s i o n C o n t r o l l e r V e r . V # . # #
C o p y r i g h t M I T S UB I S H I E L E C T R I C CO RP .

When the power is turned on, the version display screen appears for a few seconds.

S T A R T T HE I N I T I A L The password "4095" is originally registered. When a password other


OR C HA N G E T O M
than this is used, enter the new password on the "Password registration"
screen and press the [Enter] key to register it. Both the newly registered
T password and the original value "4095" are valid.
P A S S W . E N T .
S E T→# # # # # E N T E R P A S S WO R D

T N S N . UN I T S E L E C T T E N T I O N U N I T
… × 10 N : „ N

8
C N T L . P A R T S E L E C T R E E L OR RO L L
„ UNW I ND : … W I N D : … F E E D

T
R E E L NUM . S E L E C T RE E L NUMB E R
• When using the NRO
FEED

„ 1 R E E L : … R E E L S (new reel output), select


"Multi-reel" mode.
T ( See page 24 and after )

T A P E R S E L E C T T A P E R T EN S I ON CON T RO L
• Normally, the taper control is
„ O F F : … ON not used for unwinding
control.
T
• This is to select whether to use the internal
T P R . D I A . S E L E C T T A P E R S I GN A L
„ I N T . : … E X T .
signals of the tension controller or to
OFF

receive the external reel data to calculate


T the reel diameter for the taper control.
Receiving the external reel diameter results
INT

T A P E R MD . S E L E C T T A P E R MOD E in better taper control accuracy.See page


„ L I N E A R : … NON - L I N E A R 28 for details.
T
D I A . S E T S E T D I AME T E R
„M I N . D I A→ # # # # mm φ : …MA X . D I A→ # # # # mm φ

T • Select "POWDER" when using


A C T U A T OR S E L E C T A C T U A T OR hysteresis or air clutch/brake.
„ P OW D E R : … A C S E R VO MO T OR • When using an AC servo, if it is
not desired to reverse the
T direction of torque control
between resurrection and power
run, select "POWDER".
S T A L L MD . S E L E C T S T A L L S E T T NG MOD E • This is to select the input
… K E Y S E T : „ MA N . V O L .
method of the stall settings.
Good to " MAN.VOL " See page 13 for the details
T related to stall.
S T A L L R S T S E L E C T S T A L L MEMOR Y R E S E T MOD E • This is to select the input
… MC 4 o n l y : „ MC 4 + OU T SW . method for resetting the stall
Good to " MC4+OUTSW " memory. The output on/off
switch can also control stall
T
memory reset.
A I 2 S E L E C T A I 2 AN A L OG I NP U T
…D I A . : …S T A L L : …NEW R . : …T A P E R : …T N SN .
• This is to select AI … (analog)
input and MC …(contact) input.
See page 26 and after for the
T
use of these functions.
A I 3 S E L E C T A I 3 AN A L OG I NP U T These settings can be made on
…D I A . : …S T A L L : …NEW R . : …T A P E R : …T N SN . screens other than the initial
setting.
T It is all right if these settings are
made later on.
MC 5 S E L E C T MC 5 I N P U T
…GA I N 2 : … I NC HNG : …OU T RMT . : …CU T T RQ .

MC 6 S E L E C T MC 6 I N P U T
…GA I N 2 : … I NC HNG : …OU T RMT . : …CU T T RQ .

9
4.3 Adjustment of zero and span for tension detector
T
F U L L S C A L E S E T T E N S I ON F U L L S CA L E • This is to set the full-scale
„S E T →# # # # N : …× 1 0 : „× 1 : … × 0 . 1 tension (maximum
mechanical tension) and the
T number of display digits.
Z ERO T UN E E X ECU T E T E N S I ON Z E RO T UN I NG
For example, if desired to
PU S H < E N T E R > OR < C A N CE L > have "50.0N" displayed,
select " 500 " and " × 0.1 ".
T ENTER CANCEL • Zero adjustment should be
made with the tare weight of
Stand- by(for approximately 10sec) the detection reel and
without material.
S
Finished • If unable to make zero
Z ERO T UN E
adjustment, check the
C OMP L E T E ! Error
system referring to pages 43
Z ERO T UN E - - - Z ERO T U N I NG E RROR and 45.
T H E D E T E C T I ON RO L L E R I S T OO H • If the tension full scale is
changed, carry out the
T
zero/span adjustment again.

S P AN T UN E E X ECU T E T E N S I ON S P A N T UN I NG • Install the tension detectors


PU S H < E N T E R > OR < C A N CE L > on both ends of the
detection reel as shown in
T ENTER CANCEL the left figure. For a short
detection reel, only one
tension detector may be
used. Use the following
screen to select one or two
tension detectors.
• Suspend weight W (N).
Stretch a string The weight should be a
in the center of static load as close to the
the roller. full-scale tension value as
possible
(Should be between 1 to 1/3
S P AN T UN E S E T NUMB E R OF T N S N . D E T E C TOR
T N S N . D T : „ T OW : …ON L Y ON E
of the full scale).
• When, for example, a mass
X W ENTER T of 10 kg is suspended,
multiply it by the
S P AN T UN E S U S P E N D T E S T WE I GH T
gravitational acceleration
WE I G H T → # # # # N S E T WE I GH T
(9.8) to make it 98N.
• Do not alter the load during
the adjustment. Otherwise,
NUMERIC ENTER T the system may not be able
to adjust or may generate
S P AN T UN E CON T . T EN S I ON S P A N T UN I NG ? an error.
PU SH < E N T E R > OR < C A N CE L > • By the display unit setting,
the system shows the value
T ENTER CANCEL in the magnitude of "N" or
"×10N". When one tension
detector is used, the left
Finished S display shows zero. When
S P A N T UN E COMP L E T E ! two detectors are used, the
L E F T → # # # # N : Error left and right readings are
S P AN T UN E - - - S P A N T U N I NG E R ROR balanced.
S P AN T U N I NG T A RGE T WE I GH T I S • When unable to adjust the
span, check the system
T referring to pages 43 and
45.
C H EC K CH EC K T H E P A R AME T E R S ENTER
P U SH < E N T E R > S • If an error message
appears, the system can
Error Message not complete the
S E T T H E DR I V I NG P AR AME T E RS
adjustment. Set the
system again.
• Initial setting completed.
T
The system setting screen
P A S SWO R D „„„„„„„„„„„„„„„„ appears hereafter. Set the
S E T→# # # # # S E T NUMB E R parameters as necessary.

10
4.4 Automatic operation
Having completed the steps described up to the preceding pages, the minimum necessary processes
shown in (1) and (2) below would be finished as the system controls the tension.
(1) Controller installation and wiring
(2) Initial setting (zero span adjustment of the tension detectors in particular)
Now, check the drive system in manual operation mode in step (3). Follow the procedure below.
• Press the power on/off switch to connect the system to the power supply.
• Press the manual mode switch. Use the manual torque controller to check the system opera-
tion.

Automatic mode switch

Display selection switch

Output on/off switch

LE-40MTA -E × 10N MONITOR

SELECT
OUTPUT
ON/OFF

CURSOR MODE

AUTO MANUAL
POWER
TENSION SET MANUAL SET

ON ENTER

INC/DEC PAGE
Manual mode switch
Power switch OFF CANCEL

Tension controller Manual torque controller

When completing the system check in manual operation mode perform operational check by the automatic
operation in step (4) following the procedure below.

• Set the tension controller. See page 18 for the operator screen.

T N S N . S E T M N T . → „„„ „„ „„„ „„ „„„ „„„


S E T→ # # # # N → „„„ „„ „„„ „„ „„„ „„„

• Press the automatic mode switch to enter automatic mode.


• Turn on the MC1 contact input to start automatic operation.

This completes the basic adjustment for operation.


Where a different mechanism or other functions are used, refer to Section 6 and after.
If any problem in the operation, refer to Section 10.

11
5. Basic knowledge for operation

5.1 Entering Run / stop signals (use of MC1)


The minimum necessary preparation for tension control is described in "Adjustment flow for trial operation"
on page 10.
This section explains the use of start/stop (MC1) contacts essential to the step (4) operational check in au-
tomatic mode.

1. Run / stop (MC1 input) ------ Usually on during operation

• The contacts interlocked with the Run/


stop operation of the machine (such as
the feed motor Run/stop) are connected. ON
MC1 input OFF OFF
Press the automatic mode switch to en-
ter automatic mode. With the MC1 input
made and after a lapse of time set in the Stop timer
start timer, the automatic control will Main shaft speed
start. See the figure on the right.
Start timer
Control output
• When this input is turned off, the stop
Stall Automatic control Stall
gain and the stop bias become valid until
the stop timer times up. After that, the
stall values become valid.
(The start timer and stop timer will be
discussed later. See the next page for
more about the stall.)

2. Automatic mode indicator lamp

• The lighting conditions of the auto-


ON
matic mode switch, start/stop in- Automatic mode OFF
put (MC1) and the state of the
Operation command ON
automatic mode indicator are as (MC1) OFF OFF
the figure on the right.
Automatic mode LED Blink Light Blink Extinguish
Start timer Stop timer

3. Connection

• Use a micro signal switch commensurate with DC8V


Operation / Stop Photo coupler
4mA as the input contacts. Connect the contacts
across MC1 and MCC. MC1
1.6kΩ

MCC
8V

12
5.2 Use of stall setting (output when operation is stopped)
Stall output is a constant torque given during the automatic control to the machine while it is stationary. At
this stage, the feedback control does not take place. This torque is the initial torque for the machine to start
with in the automatic control.
• When Run/stop signal MC1 is turned off to stop the material, the stall memory retains the control output
values used immediately before the stop. The system resumes the operation using the memorized
control output values to stabilize the tension in the material.
The stall memory function is a part of the basic functions, no need to be specially set.
• When changing materials, for example, the stall memory is reset to the output values appropriate to the
initial material diameter. These output values are called the stall setting value.
The system uses an EEPROM memory to keep the stall memory values even when the power supply is
turned off. No reset operation takes place even when the power supply is turned off or automatic or manual
modes switching is performed.

Large
Large side:
side:
Preferenced
Preferenced Torque
Torquecontrol
controloutput
output
Internal
Internal Tension
Tension detection
detection Memory
Memory
stall
stall setting
setting
External Reading
Reading
stall setting Target
Target tension
tension -- PP
AI3
AI4
Selection
Selection Stall
Stallmemory
memory SA
SA
of
of terminal
terminal
Stall
Stall setting
setting value
value
EAP
EAP
0~100%
0~100% output
outputagainst
against0~5V
0~5V
Stall memory
memory reset
reset command
command
MC4

Items
Items in
in square
square::Setting
Settingon
onpanel
panelsurface
surface

1. Resetting stall memory value

• Two methods are available to reset


the stall memory value as follows:
Operation input MC1 ON ON Stall memory
• An output on/off switch is used to re-
set the stall memory value.
• Stall memory reset input MC4 con- Main reel speed
tacts are used for reset.
In either case, the switch is normally Control output
turned on when the reel is changed. Stall seting Stall seting
value
• When the initial setting "MC4 + OUT. value
Stall memory value
SW" at the "STALL RESET" screen is
selected (see page 9), the control MC4 input or
output on/off switch
output is switched from "ON" to
(On when reel is exchanged)
"OFF" by the output on/off switch on
the panel at the time of changing the
material. The stall memory value will
be preset to the stall setting value.
• When MC4 is kept "on" for approximately 0.5 second or longer, the stall memory value is preset to the
stall setting value.

2. Entering stall setting value

• The manual torque controller is used to set the stall setting value in the initial setting. Therefore, the
manual torque value will be the stall setting value (stall torque value) in the automatic control.

13
3. Connection
Stall memory reset Photo coupler
• To reset the stall memory externally, the MC4 contacts
MC4
are used.
1.6kΩ
• Use a micro signal switch commensurate with DC8V
4 mA as the input contact. MCC
• If the stall memory reset input MC4 and MCC are 8V
short-circuited, the stall output is always the same as
the stall setting value.
• If a signal interlocked with the reel shaft release signal
and shaft removal signal is connected to the MC4
contacts, the stall memory can be reset automatically
when changing the material.

4. Method of entering stall setting value without using manual torque controller

----------------A special use of stall function


• In addition to the method by the manual torque controller, following two methods are available to enter
the stall setting value.

• Setting by key input on the operator screen


• Setting by external analog input

• To change the stall setting value by key input on the operator screen, use the "STALL MD." screen with
”SWITCH" on the initial setting screen or the engineer screen.
S T A L L MD. S E L E C T S T A L L S E T T N G MOD E
„ K E Y S E T : … MA N . V OL .

Select "KEY SET ".

• To enter the stall setting value by key input on the operator screen, use the "STALL SET" screen.
S T A L L S E T „„„ „„ „„„ „„ „„„ „„„
S T A L L S ES TE T → # # # % →„ „#„# „#„#„N„ „ „ „ „ „ „
T N S N„. „ „
S E T→ # # # % OU T P U T→ # # # %

• To change the stall setting value input by the external analog input setting, refer to page 40.

5. Resetting stall memory only by MC4 -------- A special use of stall function

• The system can be set so as to reset the stall memory value only by the MC4 contacts without using
the output on/off switch.

• Use the "STALL RST" screen within "SWITCH" on the initial setting screen or the engineer screen.
S T A L L R S T S E L E C T S T A L L M EMOR Y R E S E T MO DE
„ MC 4 o n l y : … MC 4 + O UT SW .

Select "MC4 only".

14
5.3 Calling up engineer screen
• Follow this operation to make changes from the state of initial setting.
• Enter the password on the password screen. Press the enter key to enter the engineer screen.

Reel diameter Complete


monitor or tension
monitor screen. initial setting

T T
P A S SWO R D „„„„„„„„„„„„„„„„
S E T→# # # # # S E T NUMB E R

Numeric input ¾ Enter"4095" or the value


¾ registered in the initial
4095
setting as the password
ENTER (Refer to page 8.)
Error input
T S
message

Enginneer screen
S E T T I NG S E L E C T ME NU B Y CU R SOR
„SW I T C H : …T E N S I ON : …S T R T . S T P : …R E E L CHG :
X

S E T T I NG S E L E C T ME NU B Y C UR SOR
W …R E E L C H G : „M E N U : …O T H E R : …GA I N

T S For setting of these items,refer to the initial setting.

Seting screen

Standard of volume set output


The control output by the manual torque and the stall setting are set
by the following standard .

Feed control Feed control


Dmax : Maximum diameter
Manual D F F D : Diameter
N= • × 100 N = × 100
torque D max F max F max F : Control tension
D0 : Initial diameter
D0 F0
~ ~
F
Stall F : Average drive tension
N= • × 100 N = × 100
New reel preset D max F max F max

Ratings torque of actuators


Fmax = × The maximum drive tension
The maximum use torque of actuators

• Obtaining stall value and new reel torque by operating actual machine
Operate the machine in automatic control mode with the target tension . Display the
output on the output indicator (4-digit, 7-segment display ).
Read the output value where the reel diameter is close to the initial diameter . It is
recommended to use this value as the stall value .

15
5.4 Display of operator screen
The usual operations (setting operations) are performed on the following screen.

Automatic
Operation • The bar graph in the upper right corner always
Mode selected indicates the detected tension (%). The "100%"
indication corresponds to the full -scale tension.
Tension set
T N S N . S E T M N T . → „„„ „„ „„„ „„ „„„ „„„ • This displays the set
T N SN . S E TS E T → # # # # N M N→ →„
T „. „ „„„„„„„„„„„„„„„„„„„„„„„„„„„ „„ tension.
S E T → # # # . # × 10 N → „ „ „ „ „ „ „ „ „ „ „ „ „ „ „ „ • The unit of tension such
as "×10N" and " N " and
the position of the
T S decimal point are
determined depending on
Stall set the parameter setting .
S T A L L S E T „„„ „„ „„„ „„ „„„ „„„
S T A L L S E TS E T → # # # % TN S . „→
„ N„ „ „ „ #„ #„ #
„ #„ N
„ „„„ „„
• This is to enter the stall
S E T→ # # #% OU T P UT→ # # # %
values .
Refer to pages 13 and 14
for more about the stall
functions.
T S
When new reel and taper
functions are in use .
Manual
Operation
Mode selected
• Sets the operation torque
for the manual operation .
Refer to page 15 for the
Manual setting guideline of setting .
M A NU . S E T „„„ „„ „„„ „„ „„„ „„„
M AN U . S E T S E T→ # # # % T N„
S„N „. „ „→„ „ # „# „
# „# „
N„ „ „ „„
MA N U . S E T S E T→ # # # % T N„S„ →„# „
N „. „ „ #„# „. „
# „× 10
„„ N„ „ „
S E T→ # # # % OU T P U T→ # # # %

• Displays the tension or


the output by the
T S tension/output select
switch on the panel.
Total tension monitor
T N S N . MN T . „„„ „„ „„„ „„ „„„ „„„ • When carrying out the
T N S N . MT NA T
RG. E T → # # # # N → „ „„
„„„„
„„„„
„„„„
„„„„
„„„„
„„„„
„„„„ „ taper control , the taper
T A RG E T → # # # . # × 10 N → „ „ „ „ „ „ „ „ „ „ „ „ „ „ „ „ ratio is taken into the
"target (target tension )"
value.
T S
Tension monitor left and right
T N S N . MN T . L E F T → # # # # N „„„ „„ „„„ „„ „„„ „„„ • This displays the left and
R .I LG EH FT →
T N S N . MN T T →
# ## ## ## N
. # × 10 NT A „
R„G„E„T„→„ „# „# „
# „# „
N„ „ „ „„ right tension
R I G H T → # # # . # × 10 N T A R G E T → # # # . # × 10 N measurement . This
allows to check whether
the tension in the material
is balanced.
T S
Use of reel diameter input
Password
screen

16
• The unit of tension (N or × 10N) and the decimal point position are determined by setting the parameter.
• The DISPLAY SELECTOR (TENSION /OUTPUT) switches over the tension display and output display.
• On the screen of Tension set, Stall set, New reel set, Taper ratio, the internal setting or the external setting
which is effective is displayed on the screen. When the external setting is effective, "EXT." is displayed on
the screen.

New reel set ( When multi-shaft mode is selected. )


N EW R . S E T „„„„„„„„„„„„„„„„
N EW R . S E T S E T→ # # #% T N„
S„ →„ „
N „. „ „ #„# „# „
#„N„ „ „ „ „
S E T→ # # #% OU T P U T→ # # #%

T S
Linear taper set ( When taper is selected. )
T A P E R S E T „„„„„„„„„„„„„„„„
T A P E R S E T S E T→ # # #% T N„
S„ . „→
N„ # „
„„„ #„#„
# „
N „„„„„
S E T→ # # # % OU T P U T→ # # #%

Nonlinear taper set ( When non linear taper is selected.)


T A P E R S E T „„„„„„„„„„„„„„„„
„CN R 1 # # # # m m φ →… T P R . 1 # # # % : …C N R 2 # # # # mm φ→
X

T A P E R S E T „„„„„„„„„„„„„„„„
W …T P R . 3 # # # % : …CN R 4 # # # # m m φ →… T P R . 4 # # # %

Reel diameter monitor (When reel diameter input is used .)


D I A . MN T . „„„ „„ „„„ „„ „„„ „„„
A T. →
D I A .D MI N . # # # # mmφ T N„
S„ →„ „
N „. „ „ # „# „
# „# „
N„ „ „„ „
D I A . → # # # # mmφ O U T P U T→ # # # %

17
6. To use other than one - reel unwinding powder

6.1 Use of AC servo motor


The system is equipped with the SA-SN terminals for controlling an AC servomotor or a vector inverter mo-
tor that can control torque.
The SA terminal can be connected to some servo amplifiers for the simultaneous multi-reel operation.

1. Wiring (example)

„ Provide the torque command input of the servo amplifier with the following input.
During operation and during normal stop : Torque command SA of the tension controller
Emergency stop : Output from the braking torque controller
„ Provide the speed limit input of the servo amplifier with the following input.
During operation and during normal stop : Upper speed limit setting
Emergency stop : Set the speed limit input to zero.

Torque Limit Upper Limit


Servo amplifier
Upper Limit
Speed Limit

LE-40MTA-E
Torque command
SA
Torque input
SN
EMG.stop

Speed Limit input


Normal opelation

2. Setting

• For the setting, use the "ACTUATOR" screen within "SWITCH" on the initial setting screen or the engi-
neer screen.
• In servo mode, the control values of -100% to 100% correspond to the SA output of -5 to 5V. In powder
mode, the control values of 0 to 100% correspond to the SA output of 0 to 5V. The powder mode is
completely no problem if the torque is in one direction.
A C T UA T O R S E L E C T A C TU A TO R
… P OW D E R : „ A C S E R V O MO T OR

Select "AC SERVO MOTOR".

Handling of servo motor


Setting and changing servo Basic operation check
amplifier parameters
• Use the upper speed controller to set the speed limit
With the servo-on input terminal turned input . Enter the torque command while the tension
off, turn on the servo amplifier power controller is in the manual operation . Then , check if
supply. Change the settings of the the motor rotates in the correct direction . Note,
following parameters . however, that the unwinding motor rotates in the
• Put the servo loop in torque mode . correct direction when it reverses , because the
• Set the system so that the servo material during the unwinding operation pulls it .
motor output torque is equal to the • Check that the output torque is adjustable manually to
rated torque when the 5V torque produce the specified torque even when paper is
command is issued. running through the system .
For more details of the wiring and In the manual operation , however , the dial readings of
setting, observe the servo amplifier zero to 10 on the manual torque controller correspond
instruction manual . to the output of 0 to 5 V in the manual operation .

18
6.2 Use of E/P regulator
When using an air clutch/brake instead of the powder
20

→ Output current (mA)


clutch/brake or the hysteresis clutch/brake, the control out-
put of 4 to 20 mA (load resistance to be 470Ω or less) can
be supplied to the electric-pneumatic regulator.
The control output of 0 to 100% at this stage corresponds
to 4 to 20 mA.
4
Adjust the zero/span of the electric-pneumatic regulator so
0
that the specified output may be generated in response to 0 20 40 60 80 100
the control output of 0 to 100%. → Control output (%)

1. Wiring

• When using an electric-pneumatic regulator of 4 to


20 mA input current type, connect it as per the fig- 4~20mA
ure shown on the right. EAP
E/P
• When using an electric-pneumatic regulator of 0 to Regulator
5V voltage input type, connect it between termi- EAN
nals SA and SN. 470Ω or less

2. Setting

• Use the "ACTUATOR" screen within "SWITCH" on the initial setting screen or the engineer screen to
set or change the settings.
• Use this output in powder mode. It can not be used in AC servo mode.

A C T UA T O R S E L E C T A C TU A TO R
„ P OW D E R : … A C S E R V O MO T OR

Select "POWDER"

19
6.3 Use for winding operation
The basic setting and connection are the same as those for the unwinding operation described in up to sec-
tion 5. Items particular to the winding operation are described below.

Winding control
• The taper control takes place in normal cases to prevent the material from winding too tight. Refer to
page 28 and after for the taper control.
• The direction of increasing and decreasing tension in the material in acceleration and deceleration be-
comes opposite of that for the unwinding control. Refer to pages 26 and 27 for details.
• For the winding operation, the stall setting value and the new reel preset value when switching two reels
are relatively small due to a small initial diameter. Refer to page 15 and other relevant sections.
• The winding machine or two-reel switch-over winding machine tends to get effect of significant mechan-
ical loss. To minimize the effect of such mechanical loss, mechanical loss setting is recommended for
such machines.

1. Setting

• Use the "CONTL.PART" screen within "SWITCH" on the initial setting screen or the engineer screen to
set or change settings.
CN T L . P A RT S E L E C T R E E L O R R O L L
… U NW I N D : „ W I N D : … F E E D

Select "WIND"

6.4 Use for both winding and unwinding operation


There will be no functional differences between the selection of "Unwinding" and "Winding" in the LE-
40MTA-E. Therefore, for the switch-over type that functions both as the winder and unwinder, there will be
no problem in the winding or unwinding operation. However, observe the following
• The taper control to prevent excessively tight winding is not necessary for the unwinding operation. It
is therefore recommended that the taper ratio be controlled externally. Refer to page 28 and after for
the taper control.
• The inertia compensation in the acceleration and deceleration operation needs to be changed in be-
tween winding and unwinding. Use of gains 1 and 2 is recommended. Refer to pages 26 and 27.
• When performing the taper control with the real diameter over the unwinding operation of the spindle-
less machine, as the taper reel diameter external, input the winding diameter to A12, 3 input terminals.
This allows the taper control to take place on the unwinding side in response to the changes in the reel
diameter. Refer to page 28 and after for the taper control.

20
6.5 Feed reel control
The basic settings and connection are the same as those described up to section 5. Items particular to the
feed reel control are described below.
When using an auxiliary brake/clutch for the feed reel, it is convenient to adjust the output manually using
the new reel preset output NRO.

1. Connection (powder)

P21-1 Connect the powder clutch (out feed)/brake (in feed)


Pow der clutch / brake of DC24V system 4A or less. (The same with the
H ysteresis clutch / brake
P
hysteresis clutch/brake in the same manner.)
When the NRO output is used, use the following set-
N ting. See page 9.
0.1Ω In feed : Unwinding, multiple reels
Out feed : Winding, multiple reels
NR O
Power
am plifier
AO C

2. Connection (servo)

Torque When the servo motor operates


command Servo amplifire
both at the resurrection and power
SA
Torque input running sides, the control may be-
terminal come unstable near zero. In such
SN
case, use an auxiliary clutch or
brake for the feed reel so that the
Reel exchange input Torque mode control output is used either for the
MC2
is always OFF
resurrection side only or power run-
Power amplifire ning side only.
NRO SP SP
New reel
preset AOC SN SN

3. Setting

• For the feed reel control, use the "CONTL.PART" screen within "SWITCH" on the initial setting screen
or the engineer screen to set as follows:
• When the NRO is used, select "UNWIND" (unwinding) or "WIND” (winding).

CN T L . P A RT S E L E C T R E E L O R R O L L
… U NW I N D : … W I N D : „ F E E D

Select "FEEDl"

21
6.6 Simultaneous multi-reel control
When controlling multiple reels by the tension detection from one-reel, the basic setting and connection are
the same as those described up to section 5. This section therefore describes the connection related only.

This example is applicable to :


• Cutters to cut off several sheets at one time.
• The machine using two powder brakes simultaneously or one of the two powder brakes because the
machine cannot be controlled by one powder brake due to the wide range of torque control.

1. Connection

Connect DC24V system powder


Powder clutch / brake
Hysteresis clutch / brake clutch (winding)/brake (unwinding).
Connect the hysteresis clutch and
P
brake in the same manner.
N
When using two or more powder
0.1Ω clutches/brakes, connect them in
the manner that the total of the rat-
SA ed current will be 4A or less.
Power
amplifier Note, however, that torque variation
SN
occurs between the powder clutch
and brake.
Power
amplifier

• When the P-N output is insufficient, up to 10 pcs. power amplifiers for powder clutches and brakes can
be connected to terminals SA-SN.
• Two or more servo amplifier can also be connected. Note, however, that the load resistance should be
1 kΩ or greater.
• If the torque variations between the reels need to be restricted, connect an adjusting resistor.
• When connecting an adjusting resistor between terminals P-N, the capacity and resistance should be
appropriate.
• When the power amplifier and servo amplifier are connected, adjust the gain on the power amplifier or
the servo amplifier as much as possible.

22
6.7 Powder unwinding, two-reel switching
In the two-reel operation, the contacts inter- MC2 input
Reel exchange A reel B reel A reel
locking with the reel change are connected to
MC2. When this contact input changes from
ON to OFF or OFF to ON, the control output Preset timer

is preset to the new reel preset value. When P-N


the preset timer times up, the automatic con- control output New reel preset
trol starts here. Interlock this signal with the
cutter operation. Switch SW1 at the same Auxiliary
power output
time as SW2 and SW3. Old reel stop
At this stage, as the previous reel is stopped, PA (control output +
turn on the auxiliary power supply in a few auxiliary power output )
seconds but not later than 10 seconds.
PB (control output +
auxiliary power output )
PA and PB is control output for powder to A/B shaft.

1. Connection of switch-over 2-reel powder

Reel exchange
PA
SW2 DA, RA
P PB
SW3 DB, RB
N
0.1Ω
SW4 PA , PB : Powder clutch/brake
S1 (hysteresis clutch/brake)
Reel exchange 12V DA , DB : Commutation diode
MCC S2 200V,5A
RA , RB : Protection resistance
0.1Ω
SW5 10W,47Ω
MC2
SW1
New reel
preset

2. Setting

• Use the “REEL NUM.” ( number of reels ) screen within "SWITCH" in the initial setting screen or the
engineer screen to set reel switch-over or change the setting. Select “REELS” ( multiple reels ).
R E E L NUM . S E L E C T RE E L N UMB E R
… 1 RE E L : „ RE E L S

Select "REELS” (multiple reels)

• Use the “NEW R.SET” ( new reel set ) screen on the operator screen to set or change the new reel
preset value. Refer to the guideline for controller setting on page 15 to determine the settings.
N EW R . S E T „„„ „„ „„„ „„ „„„ „„„
N EW R . S E T S E T→ # # # % T N„
S„ →„ „
N „. „ „ # „# „
# „# „
N„ „ „ „„
S E T→ # # # % O U T P U T→ # # # %

• Use the "PRESET T" screen within "REEL CHANGE" on the engineer screen to set or change the pre-
set time. Include a margin in the preset value so that the tension feedback will not take place while
the tension is unstable after switching the reels.
P R E S E T T S E T P R E S E T T I ME R
S E T→ # # . # s

23
6.8 Powder winding, two-reel switching
In the two-reel operation, the contacts inter-
locking with reel change are connected to
MC2 input
MC2. When this contact input changes from Reel exchange A reel B reel A reel
ON to OFF or OFF to ON, the control output
is preset to the new reel preset value. When Preset timer
the preset timer times up, the automatic con- New reel preset
P-N
trol starts here. Interlock this signal with the control output
cutter operation. Switch SW1 at the same
time as SW2 and SW3. Auxiliary
For the preparatory drive of the new reel, turn power output
Old reel stop
on the auxiliary power supply in a few sec-
onds but not later than 10 seconds immedi- PA (control output +
auxiliary power output )
ately before switching the reels.
In the two-reel winding operation, the me-
PB (control output +
chanical loss cancel torque MLA and MLB auxiliary power output )
are changed over. When it is OFF, the me- PA and PB is control output for powder to A/B shaft.
chanical loss cancel value set to the reel A
becomes valid. When it is ON, the mechani-
cal loss cancel value set to the reel B is valid.
This is effective when the mechanical loss of
the reel A differs greatly from that of reel B.
See page 35.

1. Connection of switch-over 2-reel powder

Reel exchange
PA
SW2 DA, RA
P PB
SW3 DB, RB
N
0.1Ω
SW4 PA , PB : Powder clutch/brake
S1 (hysteresis clutch/brake)
Reel exchange 12V DA , DB : Commutation diode
MCC S2 200V,5A
RA , RB : Protection resistance
0.1Ω Predrive
SW5 10W,47Ω
MC2 torque
SW1 adjustment
New reel
preset

2. Setting

For setting the new reel preset value and preset time, refer to Section 6.7 "Powder unwinding, two-reels
switching" on the previous page.

24
6.9 Servo winding and unwinding, two-reel switching
The control output from the terminal SA is input to the TLAP of the reel A or reel B servo amplifier through
the reel change, and controls the servo motor torque.
To stop the previous reel, set the speed limit command to 0 and give another torque limit input separately
as described on page 18.
The NRO output is to give the torque limit value while the new reel is in the preparatory drive operation. The
servo motor speed limit input (VC) should be controlled so that the rotational speed of the preparatory drive
(pre-drive) is commensurate with the spindle speed.
When the NRO output is used, select the control reel setting to multiple reels. See page 9.
See "Use of AC servo motor" on page 18 for the operation of the servo motor.

1. Connection of switch-over 2-reel powder

Torque command Servo amplifier


SA
Torque input
terminal
SN

MC2 Reel exchange Torque mode

Torque limit Servo amplifier


NRO
Torque input
terminal
AOC
New reel
preset

Torque mode

2. Setting

• Use the “REEL NUM.“ ( Number of reels ) screen within "SWITCH" in the initial setting screen or the
engineer screen to set reel switch-over or change the setting. Select "REELS“ ( multiple reels ).
R E E L NUM . S E L E C T RE E L N UMB E R
… 1 RE E L : „ RE E L S

Select "REELS” (multiple reels)

• Use the “NEW R.SET” ( new reel set ) screen on the operator screen to set or change the new reel
preset value. Refer to the guideline for controller setting on page 15 to determine the settings.
N EW R . S E T „„„ „„ „„„ „„ „„„ „„„
N EW R . S E T S E T→ # # # % T N„
S„ →„ „
N „. „ „ # „# „
# „# „
N„ „ „ „„
S E T→ # # # % O U T P U T→ # # # %

• Use the "PRESET T" screen within "REEL CHANGE" on the engineer screen to set or change the pre-
set time. Set a relatively longer time than the actual switch-over time to include a margin.
P R E S E T T S E T P R E S E T T I ME R
S E T→ # # . # s

25
7. Use of extensive functions

7.1 Control of excessive sag or tension in material during start and stop
The following control is possible to limit the tension variation due to material inertia during machine start
and stop.
1. Outline

• The start timer is used to reduce the tension varia-


MC1 input OFF ON OFF
tion by shock at the time of starting. The control
output from starting the operation (after turning on Stop timer
MC1) to entering the automatic control is fixed to Main shaft speed
the stall value. Start timer
The stop timer, stop gain and stop bias are used to Control output Stall
limit the tension variation by material inertia when Stall Automatic Stop gain
the machine is decelerated to halt. control Stop bias

• During the time after the Run/stop input MC1 changes from ON
to OFF and before the stop timer times up, the following stop Unwinding use
gain and stop bias are valid. After that, the output before stop Fix selected
(stall memory value) are generated. Feed back selected
Stop gain : The control output is adjusted to 5 to 400% of
the control output immediately before stop.
Stop bias : While the above stop gain is in effect, 0 to Stall
50% of the rated output can be added. This
A B C=A
limits the tension variation by machine inertia
when the control output is small.
The control output by the total of the stop gain and the stop bias Stop
Stop timer
is controlled to 100% or less.
A : Output prior to stop
• Two types of the control output in the stop timer operation can α β
be selected as follows. The feedback control is selected at the B=A× + Tr × ≤ Tr
100 100
time of shipping from the factory. α: Stop gain
(1) The feedback control takes place while the stop timer is in β : Stop bias
operation. Tr: Ratede output
• This is selected when non-abrupt stop. C(=A) : Stall memory value
(2) The output is fixed while the stop timer is in operation.
• This is selected when the tension during the stop in (1) above is zero.
Select "Feedback" or "Fixed" on the "Stop T set" screen to select (1) or (2), respectively.

2. Setting

S T RT . T S E T S E T S T A R T T I ME R
• Set the start timer.
S E T→ # # . # s

T Good to "FEED BACK"


S TO P . T S E T S E T S TO P T I ME R • Select the output for the
S E T→ # # . # s : „ F E E D B A C K : … F I X E D
stop timer.
T
S TO P . GA I N S E T S TO P GA I N
S E T→ # # # % • Set the stop gain.

T
S TO P . B I A S S E T S TO P B I A S
S E T→ # # # % • Set the stop bias.

• For the unwinding operation, set the stop gain to 100% or more so as not to let the tension become
zero.
• For the winding operation, set the stop gain to 100% or less and the stop bias to zero to avoid excessive
tension in the material.
• Refer to Section 11.6 "Minimum operating tension" to calculate the actual settings.
An approximate value is entered in general. A longer time is recommended.

26
7.2 Control of excessive sag or tension in material during acceleration
and deceleration
The following control is possible to limit the tension variation by material inertia during abrupt acceleration
or deceleration of the machine.

1. Setting

Deceleration
Speed
Acceleration
Terminal Stop

Time

MC1 Start/stop ON OFF

MC3 Gain 1
MC5 Gain 2
or
MC6
Control output

Start timer Stop timer


Stop gain
Unwinding Stall + Stop bias
control example Gain 1
Gain 1 Gain 2 Stall

Time

Gain 1 : While the input at terminal MC3 is on, the control output is 5 to 400% of the control output before
the MC3 was turned on. This function makes the acceleration inertia compensation or deceler-
ation inertia compensation possible.
In the unwinding control, for example, the acceleration inertia compensation is possible by turn-
ing on the MC3 input with controlling gain 1 at 100% or less during the acceleration. The de-
celeration inertia compensation is possible by turning it on and controlling the gain at 100%or
more.
Gain 2 :While terminal MC5 or MC6 is on, the gain 2 settings are valid in the similar manner as described
above.
As an example, gain 1 may be used during acceleration and gain 2 during deceleration.

2. Connection

• Use the micro signal switch commensurate with DC8V 4mA Photo coupler
as the input contacts. Gain 2 MC5
MC6
• Connect the gain 1 contact signal to MC3. Connect the gain
2 contact signal to MC5 or MC6, whichever is used. Gain 1 MC3
1.6kΩ

MCC
3. Setting 8V

• Use the "OUT.GAIN" screen within "START / STOP" on the engineer screen to change the setting val-
ue of gain 1 and gain 2.
Use the numeral input keys to set the data.
OU T . GA I N S E T O U T P U T G A I N
„G A I N 1→ # # # % : …G A I N 2 → # # # %

• Use the "MC5" or "MC6" setting screen within "SWITCH" on the initial setting screen or the engineer
screen to set the gain 2 contact or change settings.
MC 5 S E L E C T MC 5 I N P U T
„G A I N 2 : … I NCH NG : …OU T RM T . : …CU T T RQ .

Select "GAIN2"

27
7.3 Control of excessive winding tension

1. Outline of taper control

Such control as to increase/decrease the working tension, depending on the change in winding diameter
is called "Taper tension control", in which the tension is controlled in accordance with the preset pattern,
to suit the change in winding diameter. This function is mainly used to prevent the material from winding
too tight or too loose on the reel.

Following two methods are peresently available to determine the current reel diameter:
(1) By calculating internal reel diameter.
(2) By entering the reel diameter externally through analog voltage (high precision taper ten sion
control is possible).
In the internal reel diameter calculation, the reel diameter is calculated based on the torque control out-
put. Since it is not necessary to enter the reel diameter, the accuracy is not very high.

Two methods are available to set the taper ratio as follows :


(1) By setting the taper ratio (key entry) internally.
(2) By entering the taper ratio externally through analog voltage.

Two methods are available to enter the taper curves as follows :


(1) Linear line taper control.
(2) Non-linear line taper control.

Tension Torque
detected control output
Internal
tension setting
+
Torque control output
-
- Target P

Taper reel Tension


detected tension
Internal taper diameter Inside SA
ratio setting Calculation of
internal winding
External taper diameter Taper to use
ratio setting /Taper not EAP
Outside to use
AI2 Taper ratio
Calculation of Linear line
AI3 linear line
taper
Selection

AI2 Calculation of
non-linear
AI3 Reel diameter line taper Non-linear line
External reel
diameter
Data table corner 1~4 Minimum diameter
Items in square are set Taper 1~4 Maximum diameter
on the panel surface

28
Internal reel diameter taper control

The figure on the right shows the tension characteris- 1.0 Taper ratio τ=0%
tics in the taper control by calculating internal reel diam-

F0 (Setting tension)
F (Target tension)
eter. This figure assumes that the actuator torque is
0.8
proportional to the control output. τ=25%
When calculating the internal reel diameter, the calcu-
0.6
lation is based only on the torque control output. Al-
though the reel diameter input is not necessary in this
0.4
control, the taper control accuracy is lower than the
control by the external reel diameter input. τ=80%
Enter the reduction rate from the set tension as the 0.2
taper ratio. Dmax = 2
TR (Rated actuator torque)
Since the torque control output is not zero at the start of Fs (Full-scale tension)
winding, the target tension for the minimum diameter D (Current diameter)
differs from the set tension. Dmax (Maximum diameter)

1. Selection of internal reel diameter

• For setting the internal reel diameter taper, select "ON" on the "TAPER" screen on the initial setting
screen or the engineer screen. Then, select "INT.” ( internal ) on the "TPR.DIA.” ( taper reel diameter)
screen.
T A P E R S E L E C T T A P E R T EN S I O N CO N TR O L
… O F F : „ O N

Select "ON"
T
T P R . D I A . S E L E C T T A P E R S I G N A L
„ I N T . : … E X T .

Select "INT"

2. Setting of taper ratio

• Two methods are available to set the taper ratio as follows:


Setting by key entry on the operator screen (standard)
Setting by external analog input (see page 39.)
• Use the "TAPER SET" screen on the operator screen to set the taper ratio by key entry.
T A P E R S E T „„„ „„ „„„ „„ „„„ „„„
T A P E R S E T S E T→ # # # % T N„
S„ →„ „
N „. „ „ # „# „
# „# „
N„ „ „ „„
S E T→ # # # % O U T P U T→ # # # %

3. Display

The "Target" value in which the taper ratio is taken can be confirmed on the "TNSN.MNT.” ( tension mon-
itor ) screen of the operator screen.
T N S N . MN T . „„„ „„ „„„ „„ „„„ „„„
T N S N . MT NA T
RG. E T → # # # # N → „ „„
„„„„
„„„„
„„„„
„„„„
„„„„
„„„„
„„„„ „
T A RG E T → # # # . # × 10 N → „ „ „ „ „ „ „ „ „ „ „ „ „ „ „ „

29
7.4 External reel diameter taper control
Entering the reel diameter externally results in high precision taper When touch lever is used
tension control.
Two methods are available to set the taper ratio as follows: Touch lever
(1) Setting the taper ratio by key entry (see page 29).
(2) Setting the taper ratio externally through analog voltage.
Two methods are available to enter the taper curves as follows:
(1) Linear line taper control. Potentiometer Reel
(2) Non-linear line taper control.

1. Connection
+5V
• Use the externally installed potentiometer as shown in the fig-
ure above to enter the reel diameter signal of 0V (minimum di- Detecting AI2
ameter) to 5V (maximum diameter) to terminals AI2 or AI3. diameter AI3
• When the external analog input is valid, "EXT." appears on the
"DIA.MNT.” ( reel diameter monitor ) screen. 100kΩ
AIC

2. Setting

• For setting the external reel diameter taper, select "ON" on the "TAPER" screen on the initial setting
screen or the engineer screen. Then select "EXT.” ( external ) on the "TPR.DIA.” ( taper reel diameter)
screen.

T A P E R S E L E C T T A P E R T EN S I O N CO N TR O L
… O F F : „ O N

Select "ON"
T
T P R . D I A . S E L E C T T A P E R S I G N A L
… I N T . : „ E X T .

Select "EXT"
T • Select which taper to
T A P E R MD . S E L E C T T A P E R MOD E use, the linear line
„ L I N E A R : … NO N - L I N E A R taper or non-linear
taper.
See the next page.

• To change the reel diameter input values by the external analog input, change the data on the "AI2" or
"AI3” setting screen within "SWITCH" on the initial setting screen or the engineer screen.
A I 2 S E L E C T A I 2 A N A L O G I N P U T
„D I A . : … S T A L L : … NEW R . : … T A P E R : … T N S N .

Select "DIA"

• To change the maximum or minimum value of the reel diameter, change the data on the "DIA.SET”
screen within "REEL" on the initial setting screen or the engineer screen.
• The minimum and maximum diameters should be the machine specifications, and basically not
changed according to the material.

D I A . S E T S E T D I A ME T E R
„M I N . D I A→ # # # # mm φ : …MA X . D I A→ # # # # φ

30
3. Linear line taper

• When the non-linear taper "LINEAR" is selected, the sys-


Setting tension
tem enters in the linear line taper mode. The control takes
place according to the taper ratio on the panel or to the

Tension
Portion of
taper ratio determined by the external controller, whichev- decrease due
er is larger.
The taper ratio entered is the reduction rate from the set Target tension
tension.
• The tension characteristics appears to be linear against Minimum Maximum
the reel diameter signals as shown in the right figure. diameter diameter
Reel diameter
• To set the taper ratio by key entry, use the taper set screen
on the operator screen. For the taper ratio setting by the
external controller, see page 38.

T A P E R S E T „„„ „„ „„„ „„ „„„ „„„


T A P E R S E T S E T→ # # # % T N„
S„ →„ „
N „. „ „ # „# „
# „# „
N„ „ „ „„
S E T→ # # # % O U T P U T→ # # # %

4. Non-linear line taper

Taper 1 Setting tension


• When the non-linear line data is set through the pan-
Tension

el, the taper tension control takes place as follows: Portion of decrease
Set the taper data as follows: due to taper4
Taper 2
Corner 1 < corner 2 < corner 3 < corner 4 Taper 3
Target
• When the 4-stage non-linear line taper control is not tension Taper 4
necessary, for instance, when the tension is con-
stant from the minimum diameter to corner 1 and the Corner Corner Corner
2 3
Corner
4
1
linear line taper is given from corner 1, set the taper Reel diameter
as shown in the right figure (Corner 1, Taper 1) (Cor- Taper 1
Setting tension
ner 2, Taper 2). The linear line taper control may
Tension

take place from corner 1 to corner 2. Portion of decrease


Set the data as follows: due to taper4
corner 1 ≥ Dmin, corner 2 ≥ Dmax
Target
Not necessary to set data to corners 3 and 4. tension Taper 2

Corner
Minimum Maximum 2
Corner diameter
diameter 1 Reel diameter

T A P E R S E T „„„ „„ „„„ „„ „„„ „„„


X
„CN R 1 # # # # m m φ →… T P R . 1 # # # % : …C NR 2 # # # #mm φ→

T A P E R S E T „„„ „„ „„ „„„ „„„ „„ „


W
… T P R . 3 # # # % : …C NR 4 # # # # m m φ →„ T P R . 4 # # # %

5. Display

The "TARGET" value in which the taper ratio is taken can be confirmed on the "TNSN.MNT.” ( tension
monitor ) screen of the operator screen.
T N S N . MN T . „„„ „„ „„„ „„ „„„ „„„
T N S N . MT NA T
RG. E T → # # # # N → „ „„
„„„„
„„„„
„„„„
„„„„
„„„„
„„„„
„„„„ „
T A RG E T → # # # . # × 10 N → „ „ „ „ „ „ „ „ „ „ „ „ „ „ „ „

31
7.5 Change of control gains
The gains can be adjusted during operation. Adjust the auto-gain in the manual operation or automatic op-
eration. To perform fine adjustment, adjust the manual gain. No need to change the gain if the tension is
stable.

1. Automatic gain adjustment

Addition
• Ιn the operational condition, when the specified output is added to the

Torque
output in actual operation, the tension shows step-like changes. The
control gain can be adjusted automatically based on the response
characteristic of that tension.
Set the additive output on the automatic gain adjustment screen.
The right figure shows the operating characteristics of the automatic Time
gain adjustment in the manual operation.

Tension
• To execute automatic gain adjustment
(1) Operate the machine at the initial value of the control gain.
(2) Select "AUTO" on the "GAIN" screen within "Gain" on the engi- Time
neer screen.
G A I N S E L E C T A U TO / MA NU A L G A I N T UN I NG
„ A U T O : … MA N UA L

Select "AUTO"
T
A U T O G T UN E S E T O F F S E T O U T P U T
S E T→ # # # % OU T P U T→ # # # %

Additional output Output monitor of now


T

• Set the additive output (percent value for the maximum output) as large as possible
on the premises it does not adversely affect the material. Press the enter key to set
the value.
• When adjusting the automatic gain, the output increases instantaneously. When
handling the material easily elongated or ruptured, set the additive output to a small
value for adjustment.

A U T O G T UN E E X E CU T E A U TO G A I N T UN I NG
P U S H < E N T E R > O R < CA N C E L >

ENTER

A U T O G T UN E E X E CU T I NG A U TO G A I N T UN I NG
P U S H < C A N CE L > A T S TO P

Stand-by (for approximately 10sec)

A U T O G T UN E
A U TO G A I N T UN I NG COMP L E T E !

• When errors generated during the automatic gain adjustment, add as large a torque as possible.
An error will also be generated if accurate response waveforms cannot be obtained. Adjust the
manual gain in such a case.

(3) Repeat the above steps two to three times for a higher accuracy.

32
1. Manual gain adjustment

• When fine adjustment of the gain is required, first set the integral time, then adjust the proportional gain
according to the following procedure.
• The dead zone gain and dead zone width are not required to be changed in normal cases. However,
adjust these values if it takes too long time to reach the target tension when starting the system, switch-
ing to a new reel, changing the tension settings.
• Select "MANUAL" on the "GAIN" screen within "GAIN" on the engineer screen.

G A I N S E L E C T A U TO / MA NU A L G A I N T UN I NG
… A U T O : „ MA N UA L

Select "MANUAL"
T

Set the value to as large a value as possible as long as the follow-


up action is not too slow when changing the tension setting, or no
hunting occurs while nearing the minimum diameter. Reduce this value if deviation
(Guideline: A value smaller by approximately 20% than the value between the target tension and
at which hunting occurs.) the actual tension remains.

M A NU . G T UN E MA NU A L G A I N TU N I NG
„ P R O P . G A I N→ # # #% : … I N T G . T I M E→ # # # % :
X
MA NU . G T UN E MA N UA L G A I N TU N I NG
W … A DD G A I N →# # # % : „D E A D Z O N E→ # # # %

Not necessary to change in normal cases. If required to change, change


the dead zone gain first to obtain the optimum value. Then, reduce the
dead zone width to a smaller value.

[1] Integral time (Initial set value: 50%)


The integral time determines the time responsibility against the deviation between the target tension
value and the operating tension value.
When a small value is set, the controllability is improved but hunting easily occurs. When a large val-
ue is set, the control is stabilized but the responsibility at the time when the unit is activated, the new
axis is changed over, the tension set value is changed, etc. is deteriorated.
Set a large value with which the follow-up delay generated when the tension set value is changed is
acceptable and hunting does not occur with a value near the minimum diameter.
[2] AProportional gain (Initial set value: 50%)
The proportional gain corrects the output in proportion to the deviation between the target tension val-
ue and the operating tension value.
When a large value is set, the target tension is reached faster but hunting easily occurs.
Set a value with which overshoot slightly remains when the target tension is changed.
The dead zone gain and the dead zone width are not required to be set (so that they remain in the
initial setting) usually. However, if it takes considerable time to reach the target tension value when
the unit is activated, the new axis is changed over, the tension set value is changed, etc., adjust them
together with the integral time and the proportional gain.
[3] Dead zone width (Initial setting: 50%)
The dead zone width specifies the deviation generated when the proportional gain is changed over.
When a small value is set, the responsibility becomes faster but hunting easily occurs.
[4] Dead zone gain (Initial setting: 0%)
When the deviation is larger than the dead zone width, the dead zone gain set here is added to the
proportional gain to increase the gain.
When a large value is set, the time required until the deviation enters the dead zone range can be
made shorter. However, if the set value is to large, hunting easily occurs. Enter a value with which
appropriate responsibility can be obtained when combined with the dead zone width and the propor-
tional gain.

33
7.6 Output of contact when running out of materials
This contact output can be used to detect an abnormality
such as material running out. There is hysteresis of
about 3% of tension

Tension set value


The contact output will be turned on when the detected fullscale between ON
tension is smaller than the set parameter. When the pa- →OFF and OFF → ON
rameter is set to zero, the contact output is OFF normally. "ZT" outputting.
If an abnormality occurs in the internal program, this con-
tact output will be turned ON regardless of the settings or Detected tension
tension values.
ON
The zero tension detection takes place with respect to the OFF
tension monitor display value. The zero tension detection
Hysteresis
timing therefore changes depending on the tension display
filter setting.

1. Connection Relay
ZT
The capacity of the zero tension output contacts is as follows:
AC 250V 0.5A
ZT
DC 30V 0.5A
Connect loads matching with the capacity.

2. Setting

To use the zero tension output, set it on the "ZERO TNSN." screen within "TENSION" on the engineer
screen.
Z E RO T N S N . S E T Z E RO T E N S I ON D E T E C T L E V E L
→O # T# N# S#
S ZE ET R N. S E T
N Z E R O( 0 T E= N SN O T N UD
I O S EE T
D E) C T L E V E L
S E T→# # # . # × 1 0 N ( 0 = NO T US E D )

7.7 Use for machines with frequent inching operation


This function is used to control the loss of tension by machine MC5 ON
inching. MC6 OFF
When this input is ON, the control output will not be smaller than
the stall memory value. Undershoot does not occur
Control output

Stall memory value

Time

1. Connection
Inching Photo coupler
• Use a micro signal switch commensurate with DC8V 4 mAas MC5
MC6
the input contact. 1.6kΩ
• Connect the inching signals to the terminal MC5 or MC6 set MCC
as follows. 8V

2. Setting

• To set the inching function, use the "MC5" or "MC6" setting screen within "SWITCH" on the initial setting
screen or the engineer screen.
MC 5 S E L E C T MC 5 I N P U T
…G A I N 2 : „ I NCH NG : …OU T RM T . : …CU T T RQ .

Select "INCHNG"

34
7.8 Externally turns ON or OFF control output
Turning ON or OFF this input allows remote control MC5
MC6
of the control output.
This takes precedence over the output on/off switch OUTPUT
on the panel. ON/OFF Switch

Control output

1. Connection
• Use a micro signal switch commensurate with DC8V 4 mA as
the input contacts. Out remote Photo coupler
MC5
• Connect the "OUT remote" to terminal MC5 or MC6 set as fol- MC6
1.6kΩ
lows.
MCC
8V

2. Setting

• To set the "OUT RMT.” ( out remote ), use the "MC5" or "MC6” setting screen within "SWITCH" on the
initial setting screen or the engineer screen.
MC 5 S E L E C T MC 5 I N P U T
…G A I N 2 : … I NCH NG : „OU T RM T . : …CU T T RQ .

Select "OUT RMT"

7.9 Setting of mechanical loss with two-reel switching


In automatic operation mode, the control output
plus mechanical loss will be generated. In manual
operation mode, the manual control value plus me-
chanical loss will be generated. OFF OFF
MC2 input (rell A) ON (rell B) (rell A)
In the two-reel winding operation, the system
switches between mechanical loss correction Mechanical loss
MLA MLB MLA
correction
torque MLA and MLB. If off, the mechanical loss
cancel value for reel A setting is valid. If on, the
mechanical loss cancel value for reel B setting is
valid.
This setting is recommended in the case of the
great mechanical loss in single reel winding.

1. Setting

• To set the mechanical loss, use the "MECH.LOSS” ( mechanical loss ) screen within "REEL" on the
engineer screen.
M E CH . L O S S MC H . L O S S COMP E NS A T I O N
„A - RE E L→ # # # % : …B - R E E L→ # # # %

35
7.10 Use of cut torque
In the automatic paper-jointing control, this func-
tion facilitates the material cutting while the cut-
ter is in operation by fixing material tension at a Fixed control output
(during this period)
greater value.

Torque

Torque
When the MC5 or MC6 contact input is ON, the
control output is fixed and maintained at a con-
Cut torque setting value Cut torque
stant level. setting value
The lower limit of the control output is limited to Time Time
the cut torque setting value.
When the reel change signal is entered, the val-
ue changes to the new reel preset value. MC5 or MC6 MC5 or MC6
The reel change signal takes precedence over
the cut torque. However, turn off the cut torque
before the new reel preset timer times up.

1. Connection

• Use a micro signal switch commensurate with DC8V 4 mA as the


input contacts. Cut torque Photo coupler
MC5
MC6
1.6kΩ
• Connect the cut torque to the terminal MC5 or MC6 set as follows.
MCC
8V

2. Setting

• Use the "MC5" or "MC6” setting screen within "SWITCH" on the initial setting screen or the engineer
screen to set or change the cut torque setting.
MC 5 S E L E C T MC 5 I N P U T
…G A I N 2 : … I NCH NG : …OU T RM T . : „CU T T RQ .

Select "CUT TRQ."

7.11 Reduction of variation in tension readout


To reduce variation in the tension readout, select "Display filter" within "Tension" on the engineer screen.
Increase the value to make the response slower. This makes the tension reading more stable and com-
fortable when it varies quickly.
MN T . F L T . S E T T E NS I O N MON I T OR F I L T E R
… 1 / 4 s : „1 / 2 s : …1 s : …2 s : … 4 s

36
8. Use of external analog signals
When entering settings externally by analog voltage, prohibit the settings change from the panel. This
makes the setting value change only by the external analog input (controller installed externally) valid.

Notes
Regarding the tension setting , stall setting, new reel presetting and taper ratio setting , the
setting through the panel or the setting by external analog input , whichever is greater , takes
precedence in shipping -setting condition . By prohibiting change of the setting value from the
panel on the "Setting prohibited " screen, only the external analog input (controller installed
externally ) is made valid.
If prohibited to change setting value from the panel , the setting value from the panel will be fixed
at the value immediately before the prohibition .

1. Setting

To set setting prohibition, use the "INH.ENT." screen within "OTHERS" on the engineer screen.
I N H . E N T . I N H I B I T P A N E L EN T R Y
… TN S N . S E T : „S T A L L S E T : …N EW RS E T : … T A P E R S E T

If "Stall set" prohibition has made valid, the stall setting change
from the panel will be prohibited. The setting value will be fixed
at the value immediately before the prohibition.

8.1 Varies set tension


1. Connection

• Instead of setting the tension from the panel, input signal of


+5V
0 to 5V can be used for the tension setting.
When the input of 0 to 5V is given the tension setting value Ecternal
becomes 0 to 100%. tension AI1
• Connect the signal to the terminal A11 as per the figure at setting
right. 100kΩ
The tension setting from the panel or the tension setting by AIC
the external input, whichever is greater, becomes valid. See
the notes above.

2. Display

If the external analog input is valid, message "EXT." appears on


the "Tension set" screen as shown below. If "EXT." is gone, the
key setting is greater and is therefore valid.
T N S N . S E T E X T . MN T . → „„„ „„ „„„ „„ „„„ „„„
S E T→ # # # # N → „„„ „„ „„„ „„ „„„ „„„

8.2 Enters reel diameter data


Refer to page 30 Section 7.4 "External reel diameter taper control".

37
8.3 Varies stall
1. Connection

• Given 0 to 5V input, the stall setting value becomes 0 to 100%


output. Connect this signal to the terminal A12 or A13. +5V
• When the stall memory reset input [ MC4 ] is turned ON or the
output on/off switch on the panel changes from ON to OFF, this AI2
Stall AI3
value is preset in the stall memory value.
• This input is valid if it is greater than the internal stall settings.
100kΩ
See the notes on the page 37. AIC

2. Setting

• To change the stall setting input to the setting by the external analog input, use the "A12" or "A13” set-
ting screen within "SWITCH" on the initial setting screen or the engineer screen.
A I 2 S E L E C T A I 2 A N A L O G I N P U T
…D I A . : „ S T A L L : … NEW R . : … T A P E R : … T N S N .

Select "STALL"

3. Display When the external analog input is valid, message "EXT."


appears on the "Stall set" screen as shown below. If "EXT." is
gone, the key setting value is greater and is therefore valid.
S T A L L S E T E X T . „„„ „„ „„„ „„ „„„ „„„
S E T→ # # # % T NS N . → # # # # N

8.4 Varies taper ratio


1. Connection

• Given 0 to 5V input by, for example, an external controller, the


taper ratio setting value becomes 0 to 80% when the reel diam- +5V
eter is set internally or 0 to 100% when the reel diameter is set
externally. Taper AI2
Connect this input to the terminal A12 or A13. ratio AI3
• This input is valid if it is greater than the taper ratio setting value
by the key entry. See the notes on the page 37. 100kΩ
AIC

2. Setting

• To change the stall setting value input to the setting by the external analog input, use the "A12" or "A13”
setting screen within "SWITCH" on the initial setting screen or the engineer screen.
A I 2 S E L E C T A I 2 A N A L O G I N P U T
…D I A . : … S T A L L : … NEW R . : „ T A P E R : … T N S N .

Select "TAPER"

3. Display

When the external analog input is valid, message "EXT."


appears on the "Taper set" screen as shown below. If "EXT."
is gone, the key setting value is greater and is therefore valid.
T A P E R S E T E X T . „„„ „„ „„„ „„ „„„ „„„
S E T→ # # # % T NS N . → # # # # N

38
8.5 Varies new reel torque
1. Connection
+5V
• When the system changes to the new reel in the two-reel op-
eration, the external input of 0 to 5V sets the control output AI2
New reel
from 0 to 100%. torque AI3
• Connect this input to the terminal A12 or A13.
This input is valid if it is greater than the internal new reel pre- 100kΩ
AIC
set value. See the notes on the page 37.
• In the two-reel operation, the system performs this input des-
ignation and gives the switch-over signal from reel change
input MC2.

2. Setting

• To enter the new reel torque by the external analog input, use the "A12" or "A13” setting screen within
"SWITCH" on the initial setting screen or the engineer screen.
A I 2 S E L E C T A I 2 A N A L O G I N P U T
…D I A . : … S T A L L : „ NEW R . : … T A P E R : … T N S N .

Select "NEW R."

3. Display
When the external analog input is valid, message "EXT."
appears on the "new reel set" screen as shown below. If "EXT."
is gone, the key setting is greater and is therefore valid.
N EW R . S E T E X T . „„„ „„ „„„ „„ „„„ „„„
S E T→ # # # % T NS N . → # # # # N

8.6 Enters external tension data


1. Connection

• Signals of 0 to 5V (zero to full scale tension) from the auxil- +5V


iary tension detector are entered to the terminal A12 or A13
through LM-10TA type tension amplifier or similar device. External AI2
tension AI3
• This input is compared with the signal detected value by the
signal
tension detector which is connected directly to the LE-
100kΩ
40MTA-E. The automatic control is carried out using the AIC
greater value.
• If Mitsubishi tension detector is not used, carry out zero ad-
justment according to the instruction on page 10. In this
case, short-circuit the terminals GRR and WHR and termi-
nals GHL and WHL.

2. Setting

• To enter the external tension signal by the external analog input, use the "A12" or "A13” setting screen
within "SWITCH" on the initial setting screen or the engineer screen.
A I 2 S E L E C T A I 2 A N A L O G I N P U T
…D I A . : … S T A L L : … NEW R . : … T A P E R : „ T N S N .

Select "TNSN."

3. Display

• The 4-digit, 7-segment display shows the tension for confirmation.

39
9. Other functions

9.1 Records tension data


Corresponding to the tension detection from zero to full scale,
the output from 0 to 5V is generated. The full scale tension 0~5V
TMO Tension meter
is set by the parameter.
recorder

Load
AOC resistance
1. Connection 1k Ω or more

• Connect this signal between TMO and AOC.


• The load resistance should be 1 kΩ or greater.

2. Setting

• The output filter can be adjusted to 1/4, 1/2, 1, 2 or 4 seconds by the parameter.
• To change the response characteristic of the TMO tension monitor output, select "TMO FLT." within
"TENSION" on the engineer screen. Increasing the value slows the response characteristic.
T MO F L T . S E T T MO OU T P U T F I L T E R
… 1 / 4 s : „1 / 2 s : …1 s : …2 s : … 4 s

9.2 Monitors input and output condition


To check condition of the contacts and analog data input and output, use the "CONTACTS" screen or similar
one within "OTHERS" on the engineer screen.
( Contact input / Output monitor screen )
CO NT A C T S CO NT A C T S MO N I T OR
… M C 1 : … M C 2 : … M C 3 : … M C 4 : … M C 5 : …M C 6 : … Z T

T
( Analog input monitor screen )
MO N I T OR 1 S I G NA L I NP U T MON I T OR
A I 1→ # . # V : A I 2→# . # V : A I 3 →# . # V

T
( Analog output monitor screen )
MO N I T OR 2 S I G NA L O U T P U T MO N I T OR
S A → # . # V : T M O→ # . # V : N R O→ # . # V

9.3 Returns all settings to the initial factory settings


To reset all the settings to the factory settings, use the "MEMORY INIT." screen within "OTHERS" on the
engineer screen. Note that the data having been established will disappear.
M EMOR Y I N I T .
P U S H < E N T E R > O R < CA N C E L >

ENTER

M EMOR Y I N I T . S T A R T
P U S H < E N T E R >

ENTER After several second


M EMOR Y I N I T . COMP L E T E
S T A R T T HE I N I T I A L TU N I NG

T
After completing the initialization, refer to page 8 and after to
Initial setting screen
re-establish the initial settings.

40
9.4 Copies data settings to other controller
• All the set data saved in the tension controller except the
external input from the trimmer or others and internal mon- Memory
itor values can be written, read and compared between the cassette.
memory cassette FX-EEPROM - 4 (or FX-EEPROM-8).

• By transferring the data from the memory cassette in


which the operation constants and parameters in accor-
dance with each material to the tension controller, the unit
can be activated easily at a local site.

1. Storing data on cassette

Read the data from the original controller to copy the settings.

Turn off the power supply. Load the memory


No control output will be generated
cassette. Before writing on the memory
while the memory cassette is loaded.
cassette, turn off the memory protect switch.

Power ON
Select " LE - 40→CASS "
M EM . C A S S . CA S S E T T E D A T A TR A N S F E R
…C A S S →L E - 4 0 : „ L E - 4 0 →C A S S : …CA S S = L E - 4 0

If the model name does not agree or the write


X W ENTER protect switch is turned on,"DATA ERROR"
message is displayed.

"Completed" is After completion, switching items by the


displayed X or W key is not possible
.

Turn off the power. Remove or When executing other operation after completing
replace the memory cassette this process, turn on the power supply again.

2. Writing data on cassette

Writes the settings of the original controller on the new controller.

Turn off the power supply. Load the memory Note that, if the data is transferred from
cassette. Turn on the memory protect switch the cassette to the main system, the data
on the memory cassette. having been established will disappear.

Power ON

M EM . C A S S . C A S S E T T E D A T A TR A N S F E R
„C A S S→ L E - 4 0 : … L E - 4 0 →C A S S :… CA S S = L E - 4 0

Select " CASS → LE - 40" If the model name does not agree or the write
X W ENTER protect switch is turned on,"DATA ERROR"
message is displayed.

"Completed" is After completion, switching items by the


displayed X or W key is not possible
.

This completes copying the data.


Turn off the power. Remove or Adjust the zero and span and set the password
replace the memory cassette again before starting the trial operation and
adjustment.

41
10. Inspection and Maintenance

10.1 Initial inspection

1. Confirmation of selection

• Before starting operation, make sure that the tension detector, actuator, power-amplifier, servo ampli-
fier and E / P regulator are selected correctly.

• The P-N output of the tension controller LE-40MTA-E is designed as 24 VDC, 4 A or less.
The actuator capacity is selected based on the line speed multiplied by the operating tension.
A larger tension can be set in the LE-40MTA-E. However, in the case, the actuator may be burned out.
Make sure that the operator is instructed appropriately as to the allowable maximum operating tension.

• If the set tension is too small, the tension fluctuation become too large compared with the operation
tension when the unit is started or stopped, and operation may be difficult.
Make sure that the operator is instructed appropriately as to the allowable minimum operating tension
also. The guideline of the minimum operating tension is shown below.

2. Operation sequence

• Check the operation sequence and emergency stop sequence.


Especially when the servo motor is used as actuator, the motor may become out of order if the material
is cut.
Use the material cut detector and the zero tension detection output of the LE-40MTA-E together , and
set the speed limit input of the motor to 0 when the material is cut.

3. Wiring check

• Erroneous connection of the power terminal (Pay attention to the phase order in the motor system al-
so.), contact of the DC I/O cable with the power cable, and short-circuit of the output cable may cause
serious damage.
Before turning on the power, make sure that the power and ground are connected correctly and that
the I/O cable is wired correctly.

• Never perform the megger test (measurement of insulation resistance).

10.2 Maintenance
• Check periodically the following items:
The temperature inside the panel is not abnormally high due to heat generating substance or direct
sunlight.
Dusts and conductive dusts are not inserted into the panel.
Incorrect wiring, loose terminals and other abnormality are not detected.

• It is ideal to adjust the zero point and span in the tension detector again at each periodic inspection.
Especially when a tension detector used has a larger rated load compared with the actual tension, the
mechanical stress of the tension detector may contribute considerably to aging deterioration.

• The zero tension relay offers the service life of 500,000 ( five hundred thousands ) times against the
load of 35 VA or less. Accordingly, no problem will occur in the zero tension relay if it is not actuated
abnormally frequently.

42
10.3 Error display
The table below shows the error messages displayed on the screen and the countermeasures.

Type Message Trouble shooting


Turn on the OUTPUT ON/OFF switch on the panel or
OUTPUT OFF
OUT remote switch.

Hardware Open the auxiliary power output terminal(S1~S2) and check


AUX.OUT.IS SHORT the output voltage. If the output voltage is DC 12V, check the
load (less 2A or not) and outer wiring. If the output voltage is
not obtained, the LE-40MTA-E is defective.
Check *2 and *3 of selection
REEL ERROR When completion of the ini-
item described in page 50.
tial setting is confirmed or
System The minimum diameter and when the AUTO switch is
parameter maximum diameter must be set pressed while the operation
SET PARAMETER /stop input is turned off,
in accordance with the reel
diameter input of 0~ 5V. error check is performed.

It is thought that the mass of the tension detection roller is


THE DETECTION heavier than the rated load of the tension detector. Check the
ROLLER IS TOO HEAVY! mass of the detection roller. It is necessary to select the
detector again if necessary. Refer to page 45 for details.

The weight at the span adjustment is too light in 1/3 or less of


SPAN TUNING TARGET
the tension full scales. Make the weight heavy and execute
WEIGHT IS TOO LIGHT!
the span adjustment again.

The output voltage of the tension detector is too low.


DETECTED LOAD IS Because the rated load of the tension detector is larger than
Tension TOO LIGHT! that of the drive tension, it is necessary to select the tension
detector detector again. Refer to page 45.
Zero/Span
adjustment The wiring for the tension detector is opposite. Exchange the
CHANGE WH _ - GR _ terminals [GRR] and [WHR]each other as well as the termi-
CONNECT WIRE! nals [GRL]and [WHL]each other. Refer to the part of the ten-
sion detector on page 14 for details.

NO LOAD TO THE Put the weight on the tension detection roller and execute
DETECTION ROLLER! the adjustment again.

The output voltage of the tension detector is too high.


DETECTED LOAD Because the rated load of the tension detector is smaller
IS TOO HEAVY! than that of the drive tension, it is necessary to select the
tension detector again. Refer to page 45.
CASSETTE TYPE ERROR Use the memory cassette FX-EEPROM-4/8 sold separately.

Data transfer WRITE PROTECT ON.


Turn off the write protect switch in the memory cassette.
between TURN OFF SW
memory
cassette After writing or reading, data is automatically collated.
DATA ERROR If this error message is displayed,replace the memory cas-
sette.

43
10.4 Unintended operation
Check the abnormality of the major components during trial operation and adjustment and during actual op-
eration using the following procedure.
Item Problem Disposal
• Make sure the supply voltage between the terminals [PSL] and [PSN] is
When the POWER 100 to 240VAC (+10% to -15%), 50/60 Hz. If this value is not correct,
Power switch is turned ON, perform the correct wiring.
supply the POWER LED is • The fuse may be melted by insertion of foreign objects or abnormal loads.
not lit. If simply replacing the fuse may not solve the problem. Contact our ser-
vice department.
• The tension signal from the tension detector is too high. The applied
On the display, the load may exceed the rated load of the tension detector. Lower the ten-
tension value or the sion set value.
unit of the tension • Check the rated load of the tension detector. If no problem is detected,
flashes. increase the full-scale tension value. (After changing the full-scale ten-
sion value, be sure to tune the zero point and the span.)
• Turn ON or OFF the [MC1] input signal depending on the run/stop status
When restarting after of the machine . If the [MC1] input signal is kept at on status, restarting
stopping the mate- operation may send out the maximum control output, and an extremely
high tension may be applied.
rial, the tension read-
• When stopping the machine, if the turning-OFF timing of the [MC1] input
ing goes beyond the signal is delayed, the control output may be extremely increased, and
scale from the begin- an extremely high tension may be applied at starting operation. To pre-
Tension ning. vent this problem, be sure to turn OFF the [MC1] input signal when
display stopping the machine.
and
abnormal The output increases
• The [MC1] input signal may not be turned OFF.
tension while the machine
• While the machine is stopped, be sure to turn off the [MC1] input signal.
halts.
After replacement of
• Check that the output set for the OFF status of the [RUN] input signal is
the material, an
optimum for the reel diameter of the replaced material.
extremely high or low
• Reset the stall memory.
tension is applied.
• Check whether similar fluctuations occurs during manual operation.
• Fluctiations during manual operatinon is generally caused by changes in
Fluctuating tension tension as a result of machine vibration ,mechanical loss,etc. In this
case please check the machine.
control
• If fluctuations do not occur during manual operation, this is generally
caused by high control gain set by the LE-40MTA-E tension controller.
In this case, please adjust the control gain factor refer to Sec. 7.5.
• Make sure that the OUTPUT ON/OFF switch is turned on.
• When 0 to 24 V output is obtained between the terminals [P] and [N] by
the manual torque setting, check the wiring to the powder clutch/brake.
When no abnormality is detected , the clutch/brake is defective or se
lected inappropriately.
• If the output voltage is not obtained in the no-load condition when the
power is changed from off to on ,the LE-40MTA-E is defective.
If the short-circuit protection function between the terminals [P] and [N]
Output cannot be is actuated, the unit becomes the normal condition when the wiring is
Actuator obtained in the man- corrected and the power is turned on again.
ual mode. • If 0~5V output is not obtained between the terminals[SA] and [SN] and
the terminals [NRO] and [AOC], remove the external load (1kΩ or more)
and check whether 0~ 5V is obtained.
• If 4~20mA output is not obtained between the terminals [EAP] and
[EAN] , remove the E/P regulator (470Ω or less),connect the ammeter
between the terminals [EAP] and [EAN] , then check whether 4~20mA
output is obtained.
• While the memory cassette is attached, the control output is not gener
ated.

44
Item Problem Disposal
• Compare the ON/OFF status of the input contact signal with the sta-
tus shown on the monitor screen. In addition, check the input contact
The contact signal for poor contact. If the input signal is properly turned ON and OFF
and the analog volt- but the ON/OFF status is not displayed on the monitor, the LE-
Input signal
age signal are not 40MTA-E tension controller is defective.
input properly. • Compare the voltage of the analog input terminal with the voltage val-
ue displayed on the monitor. Also check that noise is not influencing
the input line.
Material gets loose • The material tends to get loose if the acceleration/deceleration time is
during acceleration too short or the material inertia is too high. Use gain 1 or gain 2 to
or deceleration. compensate the inertia during acceleration and deceleration.
Others
Material is displaced
or gets too tight dur- • The taper control is recommended.
ing winding.

Check the system as per the following procedure if the zero/span adjustment would not complete.
Item Problem Disposal
• If the voltage between the terminals [RED] and [BLK] is not approxi-
mately 5.0 VDC, remove the wiring of this terminal and measure
Zero adjustment is the voltage. If the specified voltage is not obtained, the LE-40MTA-
not possible. E is defective.
If the specified voltage is obtained, the external wiring or tension de-
tector is defective.
• Remove the wiring in the tension detector.
Short-circuit the terminals [WHR] and [GRR] as well as the terminals
[WHL] and [GRL] . If zero adjustment is not possible still, the LE-
40MTA-E is defective.
• Connect the terminals [RED] and [BLK] exclusively to the tension de-
tec tor. If the voltage between the white and green cables in the ten-
Check the wiring in sion detec tor is 120 mVDC (150mV DC x 0.8)or less with which the
accordance with current is not applied in the material and zero adjustment is not pos-
page 5. sible, the LE- 40MTA-E is defective. If the measured voltage ex-
Tension ceeds 120mV, the tension detector selected is not appropriate .
detector (The tare weight is 80% or more of the rated load.)
• Perform zero adjustment at first. Connect the terminals [RED] and
[BLK] exclusively to the tension detector. Measure the voltage be
tween the white and green cables in the tension detector.
Span adjustment is
not possible. • When span adjustment is not possible even if the difference between
the voltage measured when the material tension is set to 0 and the
voltage measured when the material tension is set to full scale value
is 30mV (150mVDC x 0.2) or more, the LE-40MTA-E is defective .

• When the difference in voltage is less than 30mV, the tension load ap-
Check the wiring in plied on the tension detector is insufficient and the tension detector
accordance with selected is not appropriate. Even if the span adjustment is normally
page 5. completed, the tension detection error increases.
Use a tension detector having a less rated load.
• If the load is changed while the span is adjusted, adjustment may be-
come disabled .

45
11. Specifications

11.1 I / O Specifications
Items Terminal Specifications
PSL 100 ~ 240V AC +10 ~ –15% 50/60 Hz 400VA
Input Power fuse (250V 8A) built in
PSN Allowable instantaneous power interruption:10ms
S1(+)
Auxiliary power supply: 12 VDC, 2 A, Rating: 10 s
Power S2(–)
supplies
RED(+)
Output Power supply for tension detectors
BLK(–)
+5V(+) Service power supply for external trimmer
AIC(–) 5V DC, 50mA or less
MCC Contact input common terminal
Operation/stop
MC1
ON=Automatic operation, OFF=Stop
Reel exchange signal
MC2
OFF=Reel A, ON=Reel B
MC3 Gain 1 Gain 1 is effective during ON.
Stall memory reset
MC4 8V DC,
Input One-shot input for approx. 0.5 s
4mA/terminal
MC5 Gain2 : Gain 2 is effective during ON.
Inching : Lower output limit is effective.
Contact
Stall memory update is stopped.
signals
OUT remote : Control output is ON during ON.
MC6 Cut torque : Lower output limit is effective during ON
(for cutter).

Each function is assigned by parameter.


• Zero tension detection output.
ZT Set value : 0~1999 N (199.9 kgf)
• Output becomes ON when tension does not exceed set value.
Output
• Output is always OFF when "0" is set. (However, output becomes ON
ZT regardless of set value and tension when watch dog timer is actuated.)
• 250V AC, 0.5A or 30V DC, 0.5A
GRL Tension detector signal. GR=green, WH=white
Left • Number of detectors(one or two) is specified by parameter.
WHL • Connection varies depending on load type(compression or ten-
GRR sion).
Analog Right • When one detector exclusively is used,terminals[GRL] and
Input WHR [WHL] must be short-circuited.
signals
AI1 External tension setting
0 ~ 5 VDC corresponding to 0 ~ full-scale tension
Internal resistance : 100 kΩ
AIC
Recommended trimmer: 10 kΩ

46
Items Terminal Specifications
Diameter : Reel diameter signal for external taper control.
0 ~ 5 V corresponding to minimum value to maximum value.
Stall : External stall setting signal.
AI2 0 ~ 5 V corresponding to 0 ~ 100% output torque.
New reel : New reel preset
0 ~ 5 V corresponding to 0 ~ 100% output torque.
Taper ratio: External taper ratio setting
Input 0 ~ 5 V corresponding to:
• 0 ~ 80% (internal diameter taper)
• 0 ~ 100% (external diameter taper)
Tension : Auxiliary tension input
AI3 0 ~ 5V corresponding to 0 to full-scale tension

• Function is specified by parameter.


• Internal resistance:100kΩ
SA Control signal output
• Powder mode : 0 ~ 5 VDC
Analog • AC servo mode : 0 ~ ±5 VDC
SN
signals • Load resistance : 1 kΩ or more
For power amplifier
NRO New reel preset output servo amplifier
• Effective exclusively when "REELS" mode is
selected.
AOC • 0 ~ 5 VDC
• Load resistance : 1 kΩ or more
Output TMO Tension monitor output
• Filter can be adjusted by parameter. For tension
AOC • 0 ~ 5 VDC meter recorder
• Load resistance : 1 kΩ or more
EAP Control signal output for E/P regulator For
• 4 ~ 20 mADC air clutch
EAN • Load resistance : 470 Ω or less air brake
P Power output for 24 VDC system powder clutch/brake and hysteresis
clutch/brake.
N • 0 ~ 24 VDC, 4 A or less

47
11.2 I / O interface

250V 8A
AC100~240V +10% Power supply for
PSL 5V +5V trimmers
-15%
50/60 Hz RED Power supply for
Power supply PSN BLK tension detector

SG
Class D grounding SG Shielded cable
( 100Ω or less )

FG on metal plate
P DC24V 4A
Powder clutch/brake
Hysteresis
N clutch/brake
Tensino detector GRL Zero/span
adjustment 0.1Ω
Left WHL
SA Power amplifier
+
0~5V
Tension detector GRR Zero/span
Servo amplifire
Right WHR adjustment SN 0~±5V

+5V EAP E/P regulator


External EAN 4~20mA
tension setting AI1
5V
10KΩ 100KΩ TMO
Tension
AI2 monitor output
*1 AOC 0~5V
100KΩ New rell
preset output
NRO 0~5V
AI3
*1

S1
100 KΩ DC12V 2A,Rating:10s
AIC 12V Auxiliary powe output
S2
1.6KΩ Photo coupler 0.1Ω
*2 MC6
ZT
*2 MC5 Zero tension
RY detection output
Stall memory reset MC4
ZT
Gain 1 input MC3
Reel exchange MC2
LSA
Operation/stop MC1
LSB
MCC
‚W‚u LFG
The function to be assigned *1,*2
is specified by the parameter.

PSL PSN ZT P SI MCC MC2 MC4 MC6 +5V AI2 GRL RED BLK GRR SA EAP AOC NRO LSA
• ZT N S2 MC1 MC3 MC5 AIC AI1 AI3 WHL SG SG WHR SN EAN TMO LSB LFG

48
11.3 Various settng values
The items indicated with white letters on a black ground must be always set. Another items are set in ac-
cordance with the functinon used.
*1 *2
Set range Mainly
Initial Memory Setting
Set items Set values Unit refer
value cassette during
Minimum Maximum page
transfer operation
Tension Tension set value (N) N 0.1 ,1 or 10 ~ FS tension – NG c 18
setting Tension set value(×10N) N 0.01 ,0.1 or 1 ~ FS tension – NG c 18
Full scale value – 1 1999 500 c × 12
Full scale
Decimal point (N) – 0.1, 1.0 or 10 ×1 c × 12
tension
Decimal point (×10N) – 0.01 ,0.1 or 1 ×0.1 c × 12
Tension

Zero adjustment – 0 0 0 NG × 12
Tension
Span adjustment N 1 digit ~ FS tension 500
detector c × 12
target value ×10N (1/3 or more of FS tension) 50.0
Display time constant s 1/2 c c 35
Filter 1/4, 1/2, 1, 2,or 4
TMO output time constant s 1/2 c c 42
Zero tension Zero tension (N) N 0 1999 0 c × 36
detection
value Zero tension (×10N) ×10N 0 199.9 0.0 c × 36
Manual setting Manual set value % 0 100 – c c 18
Linear Taper ratio(int. diameter) % 0 80 0 c c 31
taper Taper ratio(ext. diameter) % 0 100 0 c c 32
Taper

Non-linear Corner 1~4 mmφ 0 2000 0 c c 33


taper Taper 1~4 % 0 100 0 c c 33
Stall Stall set value % 0 100 20 c c 15
Start

Timer Start timer s 0.0 10.0 4.0 c c 28


Gain 1 % 5 400 100 c c 29
Output gain
Gain 2 % 5 400 100 c c 29
New reel New reel preset value % 0 100 50 c c 25
/old reel Preset timer s 0.0 30.0 4.0 c c 25
switch-over Old reel cut torque % 0 100 10 c c 38
Stop timer s 0.0 100.0 6.0 c c 28
Stop control Stop gain % 5 400 100 c c 28
Stop bias % 0 50 0 c c 28
Reel Powder mode % 0 100 0 c c 37
Mechanical loss A AC servo mode % –50 100 0 c c 37
correction Reel Powder mode % 0 100 0 c c 37
B AC servo mode % –50 100 0 c c 37
Minimum diameter mmφ 0 2000 100 c × 32
Reel diameter Minimum set
Maximum diameter mmφ 2000 1000 c × 32
diameter
Proportional gain (P gain) % 0 100 50 c c 35
Integral time % 1 100 50 c c 35
Control gain

Manual
setting Dead zone gain % 0 100–P gain 0 c c 35
Dead zone width % 0 100 50 c c 35
Automatic
Addition torque % 0 100 20 c c 34
gain setting
Password – 0 32767 4095 × c 10

*1 : These parameter avail setting data copy by using memory cassette.


*2 : The setting of the item marked with " × " on the " Setting during operation " column cannot be changed
while the MC input is turned on.

49
11.4 Selection item and analog data
1. Selection item -------- The items cannot set during operation.

Memory
Setting Mainly
Initial
cassett
Set item Description during refer
set transfer
operation page
*1
Control while stop timer feed back / Fixed feed back c × 28
Unit of tension ×10N / N N c × 10
Control reel Unwinding / Winding / Feed Unwinding c × 11
Number of reels One reel / Multi reels One reel c × 11
Taper control OFF / ON OFF c × 31
Taper signal Internal / External Internal c × 31
Selection item

Taper mode Linear / Nonlinear Linear c × 32


Actuator Powder / Servo Powder c × 11
Stall mode Key set / MANUAL vol. MANUAL c × 16
Stall reset MC4 / MC4+OUT SW. MC4+OUT SW. c × 15
Diameter / Stall / New reel preset 48
AI2/AI3 setting Not set c ×
/ Taper ratio / Ext. tension *2
Gain 2 / Inching / OUT remote 48
MC5/MC6 setting Not set c ×
/ Cut torque *3
Number of detectors 2/1 2 c × 12
Automatic gain Automatic / Manual Manual c × 34
*1 : Refer to the note in the previous page.
*2 : Setting of MC5, MC6
When the control reel is set to one reel or the feed reel, never set the [cut torque] to MC5 or MC6.
Set the [cut torque] exclusively when multiple reels are selected.
*3 : Setting of AI2, AI3
When the control reel is set to the feed reel, never set the[taper ratio]or the[diameter] to AI2 or AI3.
Set the[taper ratio] or the[diameter] exclusively when the control reel is set to[winding] or[unwinding]
When the taper signals set to [external], make sure to set the winding diameter to AI2 or AI3.
When the control reel is set to one reel or the feed reel, never set the [new reel preset] to AI2 or AI3.
Set the [new reel preset] exclusively when multiple reel are selected.

2. Analog data

Name Unit Digital data for analog value of 0~5V Increment Remark
Manual torque % 0 ~ 100 1
Internal

N 1
Tension setting 0 ~ full scale tension
×10N 0.1
Tension N 1
0 ~ full scale tension
setting(AI1) ×10N 0.1
Tension detec- N 1
0 ~ full scale tension
tor (auxiliary) ×10N 0.1
External

Taper ratio 0 ~ 80%(0=Set tension):Int.diameter


% 1 Terminals AI2 and AI3
setting 0 ~100%(0=Set tension):Ext.diameter
are set by parameters.
Stall setting % 0 ~100% 1
New reel preset % 0 ~100% 1
Diameter input mmφ min. diameter ~ max. diameterÅÖ2000 11
• These inputs are always valid even if set screen is not displayed.
• These analog values are digitized by 12-bit A/D converter.

3. Monitor data

The monitor data contains the following items, and is not saved if power is interrupted.
• Tension monitor, total( N,x10N) • Tension, target (N,x10N)
• Tension monitor, left (N,x10N) Value based on the set tension while taking the
• Tension monitor, right (N,x10N) decrease ratio of the taper tension into account.
• Control output(0~100%) • Reel diameter input(min. diameter ~ max. diameter)

50
11.5 Outside dimensions and general specification

1. Outside dimensions

246 16.5 140

16

5
−E MONITOR

SELECT
OU TP UT

156
ON/OFF

100
148
80
MODE
CURSOR

AUTO MANUAL
POWER
TENSION SET MANUAL SET

ON
ENTER

INC/DEC PAGE

OFF CANCEL

20 or less
228
80
12

244
256 15 100

Accessories Weight : Approximately 3.5 kg


Main unit mounting plate : One pair Painting color : Munsell 7.5Y 7.5/1
Screws fixing main unit and mounting legs : M4 × 10 ,4screws

Screws of 10 mm or more are not applicable because


such screws may make contact with parts inside the
main unit.
When the unit is installed on the floor or wall, use
these screws to fix the main unit and mounting legs.

2. General and environmental specifications

Ambient temperature 0 ~ 40°c during operation


Ambient humidity 80% RH or less ( no condensation) during operation

Vibration resistance In accordance with JIS C0040. 10 to 55 Hz, 0.5mm (4. 9m / s2 maximum),
2 hours in each of three axis directions .
Impact resistance In accordance with JIS C0041. 98m / s2, 3 times in each of three axis directions.
By noise simulator with 1,000 Vp-p noise voltage, 1 µs noise width and 30 to 100 Hz
Supply noise resistance
cycle.
Withstand voltage 1,500V AC, 1 minute Entire terminals as a whole andbetween the
Insulation resistance 5MΩ or more by 500V DC megger ground terminal.
Grounding Solid grounding (100Ωor less)
Operating atmosphere No corrosive gas and little dust
Power switch cycles Less than 20,000 times

51
11.6 Supplement
1. Rough estimate of minimum drive tension

The minimum drive tension which can be driven in torque controller can be requested by next outline
type. When this is graphed, it is a right picture.

De-and acceleration degree

30
300
f V 25
⎯⎯⎯⎯ ≥ 8.5 ( ⎯⎯ )

Minimum drive tension ( N )


20
W + 0.2 t
15
200
f : Minimum drive tension(‚m)
w : Maximum reel weight (ton) 10
v
⎯ : De-and acceleration degree 100
t

0
0 0.5 1.0 1.5
Maximum reel weight W (ton)

2. Sliding timer

The function is used to execute the operation smoothly, for prevention of undershoot due to sudden de-
crease of tension when the mode is changed from manual control mode to the automatic control mode.
It is determined automatically during operation.

Sliding timer
Tension

Time
MANU AUTO

The sliding timer is determined automatically in accordance with the following equation.
Sliding timer
= [{(Tension detected during manual operation) – (Target tension for automatic operation)}
/ full-scale tension] × 25 sec.

JZ990D30601D

52

You might also like