Professional Documents
Culture Documents
Prn 10303320181129310018
Arc Furnaces:
Electric arc furnace loads often represent the single largest customer of an electric power
utility system. Today, it is not unusual to provide power to arc furnace plants with supply
transformer ratings in excess of 100 MVA. Installations with 200 MVA rating have also been
reported. A typical arc furnace will produce about 1 ton of steel per hour per MW of power
input. About 450 to 600 kWh of heat energy are required to process a ton of cold scrap into
usable molten steel. The arc is sustained by an alternating current, and direct current furnaces
are beginning to be popular. In the event that the arc length would not change with time, the
arc voltage/current characteristic would be time-invariant. The furnace would not give rise to
voltage fluctuations at the point of common coupling (PCC), but only to voltage and current
harmonics due to the intrinsic nonlinearity of the arc characteristic. Voltage Variation Studies
Extensive studies on arc furnace loads have shown that voltage variations, which it generates,
with multiple frequencies, can produce objectionable light flicker. Currently the main cause
of customer complaints due to light flicker is the voltage fluctuation generated by arc
furnaces. An arc furnace can operate without causing interference if the short circuit power at
the supply terminal, when at its lowest level, is at least 80 to 100 times higher than the
furnace power, a figure that should be halved when applied to dc furnaces. This
approximation is extensively used as a rule-of-thumb for initial assessment. However, the two
parameters that mainly determine voltage fluctuations produced by the furnace are the system
impedance up to PCC and the impedance of the transformer plus the furnace. In 1966, a new
constant was defined, the short circuit voltage depression (SCVD), which relates the arc
furnace size to the system strength, that is, the change in voltage at the PCC occurring when
the furnace electrodes are taken from open to short circuit by dipping them in the molten
charge. As the SCVD value changes with the arc furnace size, a survey was carried out in the
U.K. in order to find the relationship between this value and the number of customer
complaints. One of the actual trends is to use the SCVD value as a rough guide, in order to
determine if the present situation is acceptable or further study is necessary. Furthermore, it
can be decided at the design stage whether a planned installation of a new furnace will cause
objectionable flicker. The rapid improvements of power electronics technologies have
enabled ac competitive applications requiring high power rectification, one of which is the dc
arc furnace. The number of dc arc furnace installations has increased rapidly in recent years
(the first one was started in Germany in 1982), with the size of a single unit reaching over
200 MW. The dc furnace typically has less than one-third to one-half of the voltage
fluctuations of an ac arc furnace of similar size.
2. Shunt Capacitors: It is very economical to supply the base load vars by shunt capacitors.
The scheme has a relatively long response time and the possibility to compensate only for the
fundamental frequency reactive current of the load. One of the inconveniences is that a shunt
capacitor introduces harmonics; therefore, it must be combined with a passive filter bank.
Due to fast voltage variations, the only way to mitigate flicker is by switching the capacitors
at a speed comparable with that of the voltage fluctuation.
3. Series Capacitors: Being in series with the entire power circuit, they are instantaneous in
their corrective effect, which is a most valuable advantage since any change in line current
causes an immediate change in compensation voltage. The main disadvantage is that the
capacitors should be large enough to carry all loads beyond their points of installation.
Another inconvenience is originated in the presence of harmonics near the subharmonic
resonance frequency that can cause the spark over of the capacitor overvoltage protection
(spark gap). Generally, the cost is too high for the correction obtained.