Single Phase Smart Meter

USER MANUAL

Beijing Banner Electric Co. Ltd.


A.Overview
Single phase cost control smart electric meter AMI series products include
two models: DDZY88 type and DDZY88-M type. This series of cost control
smart energy meter uses advanced solid state integrated circuit technology and
SMT technology which is suitable to measure single phase active energy of AC
with 50HZ frequency, its performance complies with GB17215.321-2008
technical requirements.

B. Main Features:
These series products have characteristics like high precision, high reliability,
wide load range, power consumption, easy installation and easy management.
This product has two-way metering function, can accurately measure the positive
and negative active energy, accumulated positive active energy and display in
LCD.
This series of products have LCD display function, RS485 and infrared
communication function, PLC communication function (DDZY88-Z type,
DDZY88C-Z type), remote control power off function. The implementation
method for the fee control function is the remote mode. (DDZY88 type,
DDZY88-Z type).
Load switch is of two types: internal switch and external switch. After
purchasing electricity, consumer must perform switch on operation by local
method.
These series products have photoelectric coupling power pulse, multi-
function output interface, which can facilitate the power and clock accuracy test.

C. Specifications and main parameters:


a. Accuracy class: Class 1, Class 2
b. Rated voltage (Un): 220V
Extreme operating voltage: 0.7Un~1.2Un
c. Standardize current:5(60)A, 10(100)A
d. Basic error:meets the GB/T17215.321-2008 requirements.
e. Start and creep: meets the GB/T17215.321-2008 requirements.
f. Dimensions: 160 mm x 112 mm x 58mm (DDZY88 type),
160 mm x112 mm x 71mm (DDZY88-M type)
g. Installation size: 140(150)x 100mm

D. Points to consider for using and verifying smart meter:


a. Make sure the smart meters are qualified and sealed before they are shipped
from the factory.
b. Use pulse sampling for verifying meters.
c. Smart energy meters must be installed in dry, ventilated environment,
installation height is 1.8 meter, and the environment should not have corrosive
gas, the temperature range is -25℃ ~ 65℃, and relative humidity not more
than 95%.
d. The energy data display in LCD is combined active energy.
e. Wiring correctly according to wiring diagram, preferably with copper wire or
copper connector.
f. Press the key to active LCD display function when power is off.

E. Instructions for using functions


1. Electric energy measurement:
a) This energy meter has the function measuring positive and negative active
energy, and the combined active energy can be set accordingly.
b) This energy meter has a time-sharing function; active energy can be
accumulated and stored according to its tip, peak, flat, etc value at other time
energy and total energy.

2. Clock:
a) use built-in hardware clock circuit with temperature compensation function; in
the temperature range of -25℃ ~ 60℃: Clock accuracy ≤±1s/d; at the
reference temperature (23℃), the clock accuracy ≤±0.5s/d.
b) Clock has calendar, time, and leap year automatic conversion function.
c) Use environmentally friendly Li battery as a backup power supply, no need to
replace clock backup power supply during life span of meter, can maintain the
correctly working hours of internal clock for not tell than 5 years after power
off, and when the battery voltage is insufficient, the meter with display alarm
prompt.
d) There are security measures to prevent the unauthorized operation of date and
time settings.
e) The broadcast time is not limited by the password and the hardware
programming switch; the energy meter only accepts clock errors of less than or
equal to 5 minutes. The number of allowed verified time per day can be set
according to the requirements (the default is only allowed once per day), and
should avoid to perform before and after 5 minutes of settling data of energy
meter.
3. Multi-Tariff function
a) Support the tip, peak, flat, valley four tariffs.
b) Throughout the year can set maximum of 6 time zone, within 24 hours can be
set the minimum of 12 time period, minimum time period is 15 minutes, the
time period can be set across the zero point.
c) Supports the setting holidays and special tariff for holidays.
d) have two sets of tariffs and time period that can be programmed arbitrarily, also
can set the time to use another set of tariffs and time period.
4. Clearing
a) Clear the electric energy, freeze amount, event log record, etc data stored in the
meter.
b) Clear operation can clear permanent record of events, there are security
measures to prevent unauthorized operation, such as, set the hardware
programming switch, operate the password or seal the management and keep
the data before clearing.
c) The energy meter bottom value can only be cleared, and prohibit to set the
value.
5. Data Storage
a) Can store two-way data total energy and electric energy for each tariff for last
12 settlement day; data transfer time for saving is 24:00 of last day of the
month or 00:00 of starting of a month, or any hour in between 1 and 28 of the
month.
b) In case of power failure for power meter, all the data related to settlement can
be stored for at least 10 years and other data can be stored for at least 3 years.
6. Freeze
a) Definite time freezing: According to the agreed time and time interval to freeze
the energy data; can store data of last 60 times.
b) Instantaneous freezing: In unusual circumstances, freeze the current calendar,
time, all the energy and data of important measurement; instantaneous freezing
can save the data of last 3 times.
c) Daily freezing: store the electric energy of each day after 00:00, can store 62
such data.
d) Appointed Freezing:In the conversion of the old and new tariff/ time period,
during change of electricity price or specific requirement from electric power
company, freeze the conversion time of electric energy and other important
data.
e) Freezing in specific hour: store active energy for specific hour, can store 254
such data.
7. Event recording
a) Can record the total times of power outage as well as the starting and finishing
time of power outage of last 10 times.
b) Can record the total times of programming as well as data identification for
time of programming, programmer code, and programmed items for the last 10
times.
c) Can record total times of verification (not including the broadcast verification),
as well as the time of verification, operator for the last 10 times.
d) Can record total times of opening of meter cover, the time of meter cover
opening and closing of the last 10 times.
e) Always record the time for clearing meter function as well as energy data during
this clearing function.
f) Can record the last 10 times of remote control switch on event, last 10 times of
remote control switch off event, record time and electric energy, etc data
during switch on/off.
8. Communication
The communication channel is independent of each other; any of the
communication channel does not affect the normal operation of other channels.
a) RS485 Communication
a.1) Implementation of electrical isolation between RS485 interface and meter
internal circuit, and there is failure of circuit protection.
a.2) RS485 can meet all the electrical requirements of DL/T 645-2007 and can
withstand the AC voltage of 380 V, 2 minutes without damage to the test.
a.3) RS485 interface communication rate can be set, the standard rates are
1200bps, 2400bps, 4800bps, 9600bps,the default values is 2400bps.
a.4) RS485 interface communication complies with DL/T 645-2007 agreement
and its documents.
b) Infrared Communication
b.1) have modulation type infrared interface.
b.2) the electrical and mechanical properties of the infrared interface meet the
requirements of DL/T 645-2007.
b.3) the default communication rate of the modulated infrared interface is
1200bps.
b.4) infrared communication complies with DL/T 645-2007 agreement and its
documents.
c) PLC communication (DDZY88-Z type, DDZY88C-Z type)
c.1) the meter can be configured with narrowband or wideband PLC module.
c.2) the communication between the meter and PLC communication module
follows the DL/T 645-2007 agreement and its documents.
c.3) using external insert and use type PLC communication module, PLC
communication interface have failure to protect circuit, that is when no
access, or replacement of communication modules, in such case it will not
affect the performance of the electric meter, operating parameters and normal
measurement.
c.4) In PLC module, the measuring function, record of measured data as well as
data of the meter will be affected or changed.
9. Signal Output
a) Electric energy pulse output
a.1) has directly proportional optical output and electric pulse output to the
measured electric energy (active).
a.2) optic pulse output use super bright, long life LED devices, pulse width :
80ms±20ms.
a.3) the electrical pulse output is electrically isolated and can be collected from the
front.
b) Multi-function signal output
b.1) multi-function signal output terminal can output time signal, time switching
signal, two types of signal through software settings, conversion; when the
meter is first time powered up or powered on after power outage, the multi-
functional signal output is initialized as a time signal output.
b.2) time period signal for the second signal; time period switching signal is pulse
signal of 80ms±20ms.
10. Display
a) has two type of display method, automatic cycle and press key; time interval for
automatic cycle display can be set between 5-20 seconds; during press key to
display, LCD backlight is on, it will turn off automatically after 60 seconds
when the power is on.
b) Display content is of three types, numerical, code and symbol.
c) The meter can display electric energy, voltage, current, power, time, remaining
amount and other values, the value of the number of digits is not less than 8,
displayed decimal place can be set; display unit are national recognized units
such as kW, kWh, V, A, etc;
d) Displayed symbols include power direction, tariff, programming status, battery
under voltage, fault and other signs.
e) Displayed code includes the display content code, error code; if error occurs in
meter, the monitor immediately display the code; error code include the
following fault types, clock error, memory failure or damage.
f) Display content can be set by programming.
g) Have features of wake-up after power outage ( no backlight).
11. Measuring
a) Can measure the total active power, power factor, voltage, current (including
neutral line) and other operating parameters.
b) The measurement error (reference error) does not exceed ±1%。
12. Safety Protection
The meter has programming switch and programming password dual
protection measures, to prevent the unauthorized person from programming.
The meter can only be programmed in programming state, in broadcast and
reading operator cannot operate the programming switch.
a) Programming switch: The programming switch is designed with a pushbutton
and allows touching the programming switch only after opening the seal; in the
programming state, if there is no operation within 240 minutes, the meter will
automatically turn of the programming state.
b) Programming Password: The meter first must verify the password to perform
the programming or other special task. Password is managed by two levels,
each level password is composed of 6 digit Arabic numerals; with different
password permission level, the operation allowed to perform is also different;
users with high-level password privileges can modify low-level password and
perform all the operations with low level passwords. If entered password is
wrong for continuous 3 times, the meter will automatically turn off the
programming function for 24 hours.
13. Tariff control function
a) Tariff control function is implemented by remote mode; Implemented by remote
mode by virtual media such as RS485 and selling electricity system
b) In the case of ensuring safety, can set the electric parameter in the meter
through virtual medium.
c) The encryption device of remote main station/electric power selling system is
password machine. Remote tariff control meter, in local mainly implement the
measurement function, there is no billing function in local, billing function is
completed by remote main station/electric power selling system. When user
have no money balance in meter, the master station/electric power selling
system will send a trip command, stop supplying electricity to the user, and
when the user recharge the balance in meter, master station/electric power
selling system send switch on command, after command is valid allows user to
switch on. At this time user can manually reset and restore the power supply.
d) The master station/electric power selling system can send alarm instruction to
the meter, to issue alarm signal by meter, remind users to purchase electricity.
14. Step Tariff
Have two sets of step tariff, and can set time to enable calculate according to
the another set of tariff.
15. Alarm
a) Have light glowing alarm output.
b) Light glowing alarm uses red light indicator, and the alarm will be ended
automatically when the event returned to normal.
c) Alarm events include: battery under voltage, etc.

16. Safety Certification


It is necessary to ensure the security and reliability of data transmission by
setting up the parameters of the electric meter and operating the remote control
command through the virutal media, through sctric password authentication or
ESAM module. ESAM module encryption algorithm is in line with national
password management policy.

F. Transportation and storage :


1. The transportation and storage of electric meters should not be subject to sever
impact, handle with care and should handle according to the “UP” sign in the
box and keep in moisture proof position.
2. Storage temperature is -40 oC to 70 oC, relative humidity no more than 95% and
the air should not contain corrosive gases.
3. The electric meter during storage should be in original packaging on the stand,
stacking height should not exceed 5 layers.
G. Outline Drawing

脉冲 跳闸 红 外 报警

DDZY88型 单相费控 智能电能 表

激光刻制 条形码区域

北京博纳 电气有限公司 20XX年

DDZY88 type single phase tariff control smart meter


脉冲 跳闸 红 外 报警

R XD TX D

DDZY88-Z型 单相费控 智能电能表


X

激光刻 制条形码区域

2010年(远程载波 )

DDZY88-M type single phase tariff control smart meter

H. Wiring Diagram:

Direct access wiring diagram (External Load Switch)


Direct access wiring diagram (Internal Load Switch)

Serial number: BN0.464.1732.1


Address; South of Longcheng Garden, Huilongguan, Changping District, Beijing