Professional Documents
Culture Documents
Part. No 272491100
CONTENTS
Section: QUICK SET-UP PROCEDURE
CONTENTS
Section: STEERING AND WIRE GUIDANCE
CONTENTS
Section: STEERING AND WIRE GUIDANCE
NOTES:
QUICK SET UP
STEERING AND
WIRE GUIDANCE
QUICK SET UP
PROCEDURES
´ 1.0 PRELIMINARY SET-UP PROCEDURE ................................................... PAG.2
QUICK SET-UP PROCEDURE RTC (RETURN TO CENTER) / TACH STEERING AND WIRE
GUIDANCE
This set-up procedure is intended to be a quick reference for the technician who is familiar with the system
and should ALWAYS be used in conjunction with the service manual. All settings should be performed in an
open area away from warehouse racking.
The quick set-up procedure gives the possibility to quickly access the various adjustment and set up phases
to obtain optimal truck performance in manual and automatic drive modes. To aid consultation, the quick set-
up procedure is divided into 4 principle chapters, in each of these chapters it is also explained when
necessary to carry out each procedure.
QUICK SET UP
B) Check for correct steer demand from Tach generator
(Section 12.2.D of steering section of service manual)
D) Check the steering limit switches (B39 and B40) to make sure they are functional.
(Sections 12.2.G and 12.2.H of steering section of service manual)
The limit switches prevent the MDU from reaching the mechanical stops and damaging the controller.
Carefully trip the switches using a screwdriver, and check that the steering is disabled in the corresponding
direction. The rear limit switch, closest to the doors, disables steering in the RTC (or Tach) handle CCW
direction. The front limit switch, closest to the battery, disables steering in the RTC (or Tach) handle CW
direction.
If steering limit switches are not functional, refer to service manual for repairs, before continuing
with set-up procedure.
Fig A.
View of Steering Motherboard with Optional Wire Guidance Card Attached (This picture details
where the various trimmer pots are used for setting up the system)
1) Setting Manual Steering (to then be able to carry out Set Battery Type – step 2)
(Section 12.4.H of steering section of service manual)
NOTE: Option #1 is not the correct configuration for the RTC system but it is necessary to carry out this
step because Set Battery Type is not present on the Option #3 & 4 configuration menu.
NOTE: If the steer controller is set for the wrong voltage, the steering speed and response will be greatly
affected.
3) Setting Manual Steering (per poter poi eseguire il Set Battery Type – step 2)
QUICK SET UP
(Section 12.4.H of steering section of service manual)
a) Set System Config to Option #3 or #4: (#3 if wire guided, #4 no wire guidance)
NOTE: Unit may need to have travel energized to keep steering from timing out.
1) Config Menu Æ Adjustments Æ Set Steer 0-Pos (begin with the setting of 2500.00 MV)
2) Adjust parameter for straight travel. Drive unit in load wheel direction (30 Feet) and check for
straight travel
3) Adjust Set Steer 0-Pos until vehicle travels straight
4) Save settings - (Out, Enter)
(If MDU dithers or straight travel is inconsistent, perform Adjust Steering Precision steps
before continuing)
Adjust KP and KD to achieve best amount of steering speed and accuracy with least amount of
correction (dither).
NOTE: If the previous step 7 is not performed, then the steering speed will be reduced regardless of how
step 8 is set. (May take MDU 12 seconds to steer lock to lock if step 7 is set wrong)
QUICK SET UP
1) Setting Manual Steering
(Section 12.4.H of steering section of service manual)
Config Menu à Set Options à System Config
- Set System Config to Option #1:
1) Option #1 = Tach with Wire Guidance (adjustment suggested with and without wire
guidance)
2) Option #2 = Tach without wire guidance
3) Option #3 = RTC with Wire Guidance
4) Option #4 = RTC without Wire Guidance
Fig. B.
View of Test Point card fitted to the Wire Guidance Card
Fig. C.
View of Wire Guidance Card Adjustment Pot locations
REFER TO FIGURE B FOR TEST POINTS AND FIGURE C FOR TRIMMER POTS WHILE
ADJUSTING THE WIRE GUIDANCE SYSTEM
1) Setting TM13, 14 and 15 on a brand new guidance card prior to installation into the ECM
QUICK SET UP
using an ohm meter.
There are two ways to set up trimmer pots TM13, 14 and 15 on a brand new guidance card before it is
installed into a ECM unit.
TM13 to position 7
TM14 to position 8
TM15 to position 9
There are four extra test points on the guidance card that are not defined in the service manual (TP16, 17,
18, 19). These test points require the use of a clip on type adapter on your Ohm meter leads.
Referring back to the previous figures (1,2), we can use an ohm meter connected in a certain way to set up
QUICK SET UP
trimmer pots TM13, 14 and 15. Refer to Figure 3 below for ohm meter connections.
Figure 3
Hook up points for Ohm Meter
TM13 adjustment – Hook up ohm meter as shown in figure 3 (negative lead to TP16, positive lead to diode)
and adjust TM13 to 15.5Kohms
TM14 adjustment – Hook up ohm meter as shown in figure 3 (negative lead to TP17, positive lead to TP18)
and adjust TM14 to 56Kohms
TM15 adjustment – Hook up ohm meter as shown in figure 3 (negative lead to TP15, positive lead to TP19)
and adjust TM15 to 20Kohms
Caution: Make these adjustments with the card out of the ECM
2) Install the guidance card on the mother board (ECM) and make sure that all the
connectors are in the correct position.
3) Switch on the power supply (Emergency switch ON, key switch ON, Side Gateds closed).
4) Check For Power To Guide Wire (guidance switch does not need to be on)
a) Check that LED’s on steering controller (DL1 and DL2) are on with unit over the wire or
b) Drive unit near wire (in manual mode) and unit will slow if both antennas are close to the wire.
a) Locate the center of the MDU end of truck and install a pointer
b) Locate the center of the load wheel end of truck and install a pointer
SUPPORT
QUICK SET UP
6) Set Plugging Detect Threshold
(Section 9.0.A of steering section of service manual)
Put the truck on the wire (far from the line driver generator).
VERY IMPORTANT: the traction and load wheel aerials have to be perfectly centered on the wire (consider
pointer in point 5 as center).
a) Move truck to position center of MDU end pointer over wire and load end pointer close to wire.
b) Connect voltmeter to TP9(+) and TP15(-)
c) Adjust TM1 to 180 mV RMS AC
d) Connect voltmeter to TP10(+) and TP15(-)
e) Adjust TM2 to 180mV RMS AC
9) Balance Load End Sensor Coils (Note: Coil voltages must be equal)
QUICK SET UP
a) Insure steer wheel is straight (To do this travel down the wire in MDU direction 10 meters in
guidance and coast to a stop - Truck may be parallel to wire at this point as illustrated in figure
D on next page)
b) Connect Handset
c) Config Menu Æ Set Options Æ Special Pot Adj. Æ Set parameter ON (Enter)
(This disables the steering system during adjustment. Don’t worry about the buzzer alarm
enabled)
d) Connect volt meter to TP6 and TP15
e) Adjust TM10 as close to 0 VAC as possible
f) When finished set Special Pot Adj back to “off” (switch the key off to stop the buzzer)
QUICK SET UP
Figure D
Dotted Line illustrates centerline of truck. Truck is travelling parallel to the wire
11) Steering Error Offset (Zero Reference for Steer Angle Shutdown Points)
(Section 9.0.D of steering section of service manual)
12) Test wire guidance system with truck traveling in traction wheel (MDU) direction only
QUICK SET UP
a) Truck travels parallel to wire as in Fig.D: to center the truck on the wire, adjust trimmer TM10.
Start with 2 turns one way and test the truck, if the parallel travel is worse, it means you have turned
the trimmer the wrong way, turn the trimmer 4 turns in the opposite direction and try the truck again.
If this adjustment is not sufficient, proceed by turning the trimmer 1 turn at a time until the truck
travels perfectly over the wire.
b) The truck makes corrections that are too wide or fast: go to point 13.
a) TM13 (setting described at point 1- To high of a setting will cause MDU oscillation – too low
will cause acquisition problems)
b) TM15 (setting described at point 1 - Turning clockwise increases sensitivity to the guide wire)
(Set TM13 and TM15 together to reduce wander and oscillation of steering)
NOTE: to reduce oscillation, we suggest that only trimmer TM15 is used, adjustment to TM13
other than that suggested could lead to difficulty during signal acquisition.
Set up of the Wire Guidance system in MDU direction is now complete, the relative settings
must not be touched any more !
14) Test wire guidance system with truck traveling in load wheel direction
QUICK SET UP
only (Ratio pot adjustment).
If the truck carries out the corrections precisely on the center of the wire, go to g), otherwise, if the truck
travels parallel to the wire, carry out the complete procedure.
Fig. E
Dotted line represents center of Load wheel sensor
This illustration demonstrates behavior of truck if Load Wheel sensor needs to have an offset
adjustment made to it.
If the procedure has been carried out correctly and precisely, the wire guidance system will
work correctly, otherwise, go to point 18. If even after having carried out the tests in point 18,
the system continues to work incorrectly, repeat the whole procedure from point 1.
QUICK SET UP
a) Connect meter to TP5(+) and TP15(-), set for DC voltage
b) Drive the truck both directions while on Guidance
c) Voltage should be close to 2.5 volts +/- .1 volts
d) If the voltage stays low or stays high, then TM9 or TM10 could be out of adjustment.
e) Connect meter to TP3(+) and TP15(-), set for DC voltage
f) Voltage should stay close to 2.5 volts +/- .1 volts.
g) If the voltage stays low or high then a sensor may need adjustment or TM9 or TM10 may need
adjusting.
h) If the voltage at TP5 and TP3 stays close to 2.5 volts while traveling either direction in guidance,
then the wire guidance setup is complete.
TP-5 – This testpoint will show you the Pot Wiper in Real Time. Ideally while the truck is guiding down the
guidepath you want the voltage to stay roughly between 2.4 and 2.6 volts +/- .1 volt. This testpoint is what
the microprocessor in the ECM uses to determine shut down alarm “POT OUT OF RANGE”. If the voltage
at test point 5 stays either high (2.8 to 3.1 volts) or low (2.3 to 2 volts) the truck will be to sensitive to a
shutdown alarm based on how the parameters for UPPER ERROR POT and LOWER ERROR POT are
set. TM9/TM10 affect this voltage.
TP-3 – This will show in real time the Antenna position over the wire. You should see 2.5 volts with a
perfectly centered antenna. The closer the guidance system is set to keep this 2.5 volt signal at TP-3 the
better the guidance system is running. Use this Test Point and TP-5 to determine Guidance performance.
This test point is what the ECM uses to determine when the LATERAL OUT alarm will occur depending on
how the parameters FWD UPP ERR ANT, FWD LOW ERR ANT, REV UPP ERR ANT, REV LOW ERR ANT
are set. If the voltage stays to high (2.7 to 3 volts) or to low (2.3 to 2 volts) the truck will be sensitive to a
shutdown alarm.
TM9 and TM10 both can cause the truck to guide parallel to the guidewire. TM10 will show up going MDU
direction while TM9 can cause the truck to guide parallel to the guidewire both directions. So it is easy to
confuse which trimmer is out of adjustment. TP-5 can assist in this determination.
TM13 (amount of steer correction) and TM15 (sensitivity to a guidance error) – These two trimmer pots are
QUICK SET UP
extremely difficult to set. Improper setting could cause the truck to go sideways in an aisle when coming off
the wire. As a starting point be sure TM13 is set to 6 and TM15 is set to 9.
Test Point Definitions
4.0 Wire Guidance system adjustment (procedure to carry out on delivery of a new truck
QUICK SET UP
with standard factory settings).
When the wire guidance system has been installed on the truck by the factory, it is not necessary to carry
out all the calibrations described in chapter 3 because the system has already been calibrated. It is
necessary only to ‘adapt’ the settings relative to the amplification of the aerials using the following procedure
point by point. It is taken for granted that the Line Driver is connected to the wire and set up correctly (see
paragraph 2.1).
AERIALS
SUPPORT
Firstly you have to mark the centre of the aerials forward and backward. This is important to check if the
system is correcting well.
2) Put the truck on the wire (far from the line driver generator). VERY IMPORTANT: the traction wheel aerials
have to be perfectly centred on the wire.
3) Open the EPS controller to access the trimmers and test point (see picture “A”)
4) Aerials setting. Use a multimeter able to read AC signals 10 kHz (suggested FLUKE 85 or 87)
- Multimeter: Volt AC (or volt AC if there are) and connect the terminals as shown below.
QUICK SET UP
TP10 TP9
TM2 TM1
+TP10
- TP15 ] Adjustable though TM2 - WRITE
DOWN THE VALUE READ
+TP9
-TP15 ] Adjustable through TM3 - WRITE
DOWN THE VALUE READ
TP12 TP11
TM4 TM3
- Check how many mVolts (we will call this value X mVolt) you have to increase (or decrease) the aerial
value from the lower signal to reach the standard adjustment of 180 mVAC
X = 180 - Lower signal (between the two measured TP10-TP15 & TP9-TP15)
- YOU HAVE TO INCREASE (OR DECREASE) ALL AERIALS (forward and backward) BY “X mVolts”.
TEST POINT
QUICK SET UP
EXAMPLE:
TP9
TM1
TP10
TM2
Figure E
Truck perfectly on the wire
- QUESTION: How many mVolt do I have to increase/decrease each aerial to reach the
right adjustment?
- ANSWER: 180 mVolt – 155 mVolt = +25 mVolts
ALL AERIALS HAD TO BE INCREASED BY +25 mVOLT. (if the result was negative, you had to
decrease by the X value).
Now the truck is adjusted and we have just to check its behaviour during the automatic wire guidance.
5) FINE ADJUSTMENTS – Look at the behaviour of the truck driving in automatic wiring guidance.
QUICK SET UP
- PROBLEM: THE TRUCK DRIVES PARALLEL TO THE WIRE IN TRACTION WHEEL DIRECTION
Figure D
Dotted Line illustrates
centerline of truck. Truck is
travelling parallel to the wire
SOLUTION:
Turn TM10 anticlockwise if the truck drives to the left side of the wire, until the sensors
will be centered. Turn it clockwise if the truck drives on the right side of the wire (as in
picture D)
TM10
- PROBLEM: DRIVING IN AUTOMATIC GUIDANCE IN THE TRACTION WHEEL DIRECTION THE
CORRECTIONS ARE TOO WIDE OR TOO TIGHT
- PROBLEM: THE TRUCK DRIVES PARALLEL TO THE WIRE IN LOAD WHEEL DIRECTION
NOTE:
QUICK SET UP
NOTES:
QUICK SET UP
´ 1.0 INTRODUCTION.............................................................................PAG.2
1.0 INTRODUCTION
This equipment provides manually controlled electric power steering and automatic straight line wire guided
steering. Manually controlled steering is available in either of the following options:
- manually operated multi-turn steering using a tach-generator fixed to the steering handle
- manually operated return-to-center steering using a potentiometer attached to the spring returned steering
handle that automatically centers the steering when the handle is released
In addition, this hardware controls the guide wire acquisition when the truck is approaching and seeking the guide
STEERING & WIRE GUIDANCE
wire for transition to automatic wire guided steering. Automatic straight line wire guided steering is possible for
both directions of travel. Configuration options, manual steering adjustment, measurement functions, and
troubleshooting operations are simplified with the use of a hand held controller. Improved safety and operation
are provided by one microprocessor to perform logic operations and a second microprocessor to perform
supervisory operations.The microprocessors combined with the hand held controller make service interfacing
easy and direct, reducing adjustment and trouble shooting time. Increased steering motor performance and
reduced noise levels are achieved by using MOSFET technology operating at 18 kHz, which is above the range
of human hearing.
- Hand set used for adjusting and diagnosing electric power steering and wire guidance.
- Digital multimeter that can measure true RMS AC voltages up to 10 kHz.
Seperate service manuals are available for the US versions of both the line driver and guide wire installation,
please contact your service dept. for details.
TM1
FIG.A
On installation of a new system, the strength of the AC signal from the line driver may need adjustment
depending on the application and resistance of the wire. To adjust the strength of the signal it is necessary to
connect a multimeter in Amp AC in series on the wire and act on TM1 on the line driver (see FIG.A) until the
correct current is obtained (78mA / 35mA).
78 mA Line
Driver
STEERING & WIRE GUIDANCE
Multimeter
TM1
in Amp AC
FIG.B
BATTERY VOLTAGE RANGE: Voltage input range for the ECM is 24 - 80 VDC.
STEER MOTOR CURRENT RANGE : IMAX </= 21 AMPS DC. ADJUSTABLE WITH TM3.
GUIDE WIRE SIGNAL: 6.25 KHZ @ 78 MAMPS RMS (± 50 HZ AND 60 - 90 MAMPS)
OTHER FREQUENCIES AVAILABLE: 5.2 kHz @ 35 mAmps RMS
As the guidance frequency changes, a different guidance card (ref. ACSZPBOB) has to be installed, whose
narrow band pass filters are tuned to the different frequency. Usually, due to changing signal strength associated
with changing frequencies, new guidance sensors will also be required. The sensors have to be changed to
ensure that adequate signal strength arrives at the control card.
Engineering Application Note: If the signal strength and frequency change according to the following formula, then
no new sensors are required when changing the frequency.
At rated RPM, the steer motor with a gear reducer should turn the MDU lock to lock in 5 seconds. There should
also be adequate torque generated to statically steer the truck on smooth concrete.
The bottom edge of each sensor must be positioned approximately 2.4" - 3.2" (6 to 8 cm) above the embedded
guide wire. This assumes the guide wire is 5/8" below the surface of the floor.
1.7" to 2.5"
Fig. 1
The center of the sensor should be aligned with the center line of the truck. The DRIVE END sensor is mounted
behind the MDU (MASTER DRIVE UNIT). The LOAD END sensor may be mounted on the load wheel axle line.
Fig. 2
The forward and reverse antennas must be mounted so that both their coil sides face the same direction.
ALLOWEDFACTORYMOUNTING
Fig. 3
ALLOWED
STEERING & WIRE GUIDANCE
Fig. 4
NOTALLOWED
Fig. 5
This option uses a potentiometer attached to the steering handle to convert handle motion into an electrical
signal. The response speed and precision are adjustable by using the hand held controller.
Manual Steering Mode - All steering input is controlled by the operator. The guidance switch is in off position
and the red MANUAL light is on.
Wire Acquisition Mode - The operator selects automatic steering using the toggle switch on the console. The
steering operation changes to "Search" Mode. The operator continues to manually steer the truck. The ECM
automatically reduces truck travel speed by opening a speed reduction relay.
If the truck is approaching the wire load wheel first, then both sensors have to detect the guide wire before manual
steering is taken from the operator and automatic steering attempts to capture the wire. This requires an approach
angle of not more than ± 5 degrees to the guide wire. The operator is responsible for avoiding obstacles until the
wire is fully captured. After capturing the guide wire, the operator is responsible for stopping the truck if obstacles
are in the aisle.
If the truck is approaching the wire DRIVE WHEEL first, then only the DRIVE WHEEL sensor has to detect the
guide wire before manual steering is taken from the operator and automatic steering attempts to capture the wire.
This requires an approach angle of not more than ± 30 degrees to the guide wire. The operator is responsible
for avoiding obstacles until the wire is fully captured. After capturing the guide wire, the operator is responsible
for stopping the truck if obstacles are in the aisle.
Fig. 6
Automatic Wire Guided Steering Mode - When both antennas are aligned with the guide wire, then full
automatic steering is enabled. The truck may now travel at full speed. The ECM is in full control of steering
and the auto-shutdown system is enabled. The signal from the guidewire to the sensors is used to steer the
truck.
If the truck is not aligned with the guide wire in Automatic Mode, then the auto-shutdown system automatically
stops the truck, brakes are applied, both the AUTO and MANUAL lights are on, and the buzzer has the error
audibly encoded.
STEERING & WIRE GUIDANCE
Fig. 7
The functional diagrams concerning possible steering configurations are shown on the following pages. Four
different operating options (Tach-generator + wire guidance, Tach-generator steering only, Pot steering + wire
guidance, and Pot steering only) are provided. "Tach-generator steering only" and "Pot steering only" also
support "Automatic Centering".
Fig. 9
Interface description:
a) The MDU potentiometer should be rigidly mounted on the steering linkage with no play.
b) The DRIVE END sensor is mounted on the DRIVE UNIT end of the truck.
c) The LOAD END sensor is mounted on the LOAD END of the truck.
d) The DRIVE END travel input corresponds to travel in the drive unit direction. The LOAD END travel input
corresponds to travel in the load end direction.
e) Pins 4 on connector D on the ECM is connected to the DRIVE END travel input. This pin is common with
Pin 1 of the guidance board (eight poles) connector. Pin 2 on connector D on the ECM is connected to REV
Fig. 10
Interface description:
a) The 5k MDU potentiometer should be rigidly mounted on the steering linkage with no play. The pot wiper
is connected to Pin 18 of connector E on the ECM. The ends of the pot are connected to Pins 16 and 17
of connector E on the ECM.
b) The DRIVE END travel direction request should be connected to Pin 4 on connector D on the mother
board. The LOAD END travel direction request should be connected to Pin 2 on connector D on the
mother board.
Applications with pot steering and without wire guidance require these inputs to stop steering dither
when the truck is motionless.
c) The guidance board is not required for automatic centering with rail guidance. Also, the AUTOLAMP is
not installed. The Automatic Centering feature is requested by the PLC after the guide rails are detected
by photoswitches.
d) The MAN LAMP is on during manual operation.
e) Pin 3 of connector D on the ECM is internally connected to a normally open (NO) contact on the ECM.
This contact is closed when the key switch is turned on. The contact opens when there is an alarm. This
contact provides ground (GND) reference to the brake relay and the main steering relay. When the brake
relay loses this ground and opens, the brakes are applied and traction enable ground to the traction card
is lost.
f) Pin 5 of connector D on the ECM is not used
g) Only for Tach Generator steered trucks - Pin 14 of connector E on the ECM provides 0 - 4 VDC to control
the steer angle indicator gauge LEDs. Pin 4 of connector E on the ECM provides negative and Pin 5 of
connector E on the ECM provides positive 12 VDC to the steering angle indicator gauge.
5.3 POT (SMART STEER) CONTROLLED STEERING PLUS WIRE GUIDANCE ELECTRICAL DRAWING
Fig. 11
Interface description:
a) The MDU pot should be rigidly mounted on the drive unit steering linkage with minimum play.
b) The steering handle pot wiper is connected to Pin 10 of connector E on the ECM. The end points of the
pot are connected to Pins 11 and 12 of connector E on the ECM.
c) The MDU sensor is mounted on the DRIVE UNIT end of the truck.
d) The Load Wheel Sensor is mounted on the LOAD WHEEL end of the truck.
e) Request to travel in the DRIVE UNIT direction should be connected to Pin 4 of connector D on the ECM.
Request to travel in the LOAD WHEEL direction should be connected to Pin 2 of connector D on the ECM.
STEERING & WIRE GUIDANCE
Select the operation mode using the hand held controller (see 12.4.b).
f) Pin 9 of connector D on the ECM is connected to the highest voltage potential side of the traction motor
armature. This pin is common with pin 4 of the guidance card (eight pole) connector. Pin 11 of connector
D on the ECM should be connected to the lowest voltage potential side of the traction motor armature.
This pin is common with pin 8 of the guidance card (eight pole) connector (see 6.1.d).
g) When the AUTO SEL switch is turned on, the AUTO LAMP starts blinking when the truck is in the
"SEARCH" mode and is lit continuously when the truck is in full guidance mode. The active (for automatic
guide) AUTO SEL level (low=closed or high=open) can be selected using the hand held controller (see
12.4.l). The active AUTO SEL level is "low".
h) MAN LAMP is on when the truck is in the manual steering mode. The MAN LAMP blinks in all slow down
conditions. It goes out as soon as the truck steers automatically and there is no slow down condition.
i) Pin 3 of connector D on the ECM is internally connected to a normally open (NO) contact on the ECM.
This contact is closed when the key switch is turned on. The contact opens when there is an alarm. This
contact provides ground (GND) reference to the brake relay and the main steering relay. When the brake
relay loses this ground and opens, the brakes are applied and traction enable ground to the traction card
is lost.
j) Pin 5 of connector D on the ECM is not used.
k) Pin 6 and 15 of connector E on the ECM are internally connected to a normally open contact on the ECM.
This contact is closed by the key switch and open in case one of the following speed reduction conditions
occurs:
1) If the truck is in the manual steering mode and is close to a guide wire (minimizes possibility that an
operator will go fast when inside an aisle and not on wire guidance.)
2) When the truck is in the wire acquisition mode until both sensors are aligned with the guide wire.
3) When the truck is in the wire guided mode and has shifted sideways, from the guidepath, more than
2/3 of the "lateral out" alarm threshold (see 9.0.l).
l) Only for Tach Generator steered trucks - Pin 14 of connector E on the ECM provides 0 - 4 VDC to control
the steer angle indicator gauge LEDs. Pin 4 of connector E on the ECM provides negative and Pin 5 of
connector E on the ECM provides positive 12 VDC to the steering indicator gauge.
The steering system does not use the Automatic Centering feature with Pot steering because the steering
normally centers itself when the steer handle is released. (NOTE: If the Automatic Centering feature was used
with Pot Steering, it would disable the tiller handle input and center the steer wheel.)
This is similar to Pot Controlled Steering with wire guidance. Here the steer angle feedback pot and steer handle
pot connections have been moved down to the ECM from the guidance card. This application does not require
a guidance card.
Interface description:
a) The MDU pot wiper should be connected to Pin 18 of connector E on the ECM. The ends of the MDU pot
should be connected to Pins 16 and 17 of connector E on the ECM. The pot should be rigidly mounted on
the steering linkage to minimize play.
b) Pin 4 of connector D on the ECM is connected to the travel request in the DRIVE END direction of truck
travel. Pin 2 of connector D on the ECM is connected to travel request in the LOAD WHEEL direction of
truck travel.
c) AUTO LAMP IS NOT USED ON POT CONTROLLED STEERING WITHOUT WIRE GUIDANCE.
d) MAN LAMP IS NOT USED ON POT CONTROLLED STEERING WITHOUT WIRE GUIDANCE.
e) Pin 3 of connector D on the ECM is internally connected to a normally open (NO) contact on the ECM. This
contact is closed when the key switch is turned on. The contact opens when there is an alarm. This contact
provides ground (GND) reference to the brake relay and the main steering relay. When the brake relay loses
this ground and opens, the brakes are applied and traction enable ground to the traction card is lost.
f) Pin 5 "Locking Steering Device" is not used.
g) STEERING DIRECTION INDICATOR LEDS ARE NOT USED ON POT CONTROLLED STEERING
TRUCKS.
This section of the manual describes the connection procedures for the electric steering and wire guidance.
Carry out the following steps with the steering motor disconnected. Disregard alarms that appear during the
first and second step. Work in the manual mode.
of the steering wheel produces an increasing (higher positive) command voltage. This may be measured two
ways: using the hand held controller (see the TESTER MENU, 12.2.d) or using a DC voltmeter connected to
the tach-generator wire that is disconnected from Pin 8 of connector D on the ECM (DT+) and the minus terminal
on the battery.
b) POT (SMART STEER) STEERING - The steer handle pot has 3 wires; two end wires and a wiper wire.
Connect the two "end wires" from the steer handle pot so that clockwise rotation of the handle produces an
increasing (higher positive) command voltage. This may be measured two ways: using the hand held controller
(see the TESTER MENU, 12.2.a) or using a DC voltmeter connected to the handle pot wiper wire that is
disconnected from Pin 10 of connector E on the ECM and the minus terminal on the battery.
c) Perfect adjustment of the steering handle pot center point is not necessary. The center point value will be
memorized later using the hand held controller (see 12.5.d).
Fig. 13
b) Physically adjust the MDU pot using the handset so that with the drive unit straight ahead, the wiper voltage
is 2.5 VDC. This will require a small amount of trimmer pot adjustment to get wire guidance performance as
required. If wire guidance is not required on the truck, then this precise adjustment is not necessary, because
the manual mode zero point for the steer angle feedback pot can be adjusted using the hand held controller (see
the CONFIG MENU, 12.5.a).
Fig. 14
NOTE: It is very important that the coils on each antenna are mounted so that they face the same direction.
Fig. 15
Tab. 2
The preferred wire colors are shown in bold print, but the others may be provided when the preferred ones are not
available.
CONNECTOR D PINS
STEERING & WIRE GUIDANCE
5 K3 - NOT USED
12 CH - KEYSWITCH
Fig. 17
STEERING & WIRE GUIDANCE
Fig. 18
CCLS (7): It is possible to interrupt steering in the counterclockwise direction by opening the connection between
CCLS (pin 7) and negative (GND = pin 17 of connector D on the ECM). Therefore, connection of a
normally closed switch between pin 7 and pin 17 on connector D of the ECM acts as a counterclockwise
steering limit switch. This keeps the MDU from physically hitting the mechanical stops during powered
steering.
C O N N E C T O R E P IN S
3 G ND - NOT USED
4 G N D - B AT T E R Y N E G AT IV E
5 + 1 2 - 1 2 V D C P O S IT IV E S U P P LY
N R V - S P E E D R E D U C T IO N
6
S W IT C H
A U T O L A M P - W IR E G U ID A N C E
7
O N LAM P
Fig. 19
8 C KO U T - N O T U S E D
9 + 5 - 5 V D C P O S IT IV E S U P P LY
IN D IC - S T E E R A N G L E IN D IC ATO R
14
(TA C H S T E E R O N LY )
15 R V - S P E E D R E D U C T IO N
N P O T - M D U P O T N E G AT IV E (N O N
16
W IR E G U ID E D O N LY )
P P O T - M D U P O T P O S IT IV E (N O N
17
W IR E G U ID E D O N LY )
C P O T - M D U P O T W IP E R (N O N
18
W IR E G U ID E D O N LY )
Tab. 4
Connector E on the ECM is used for steer handle pot input, travel speed reduction and to support recently
introduced manual steering options.
NK2 (1): Not used.
NK3 (2): Not used.
GND (3,4): Pin 3 not used. Pin 4 is Internally connected to ground (battery minus) reference, these may be
used for Steer Angle Direction LED gauge connections or other interface cards.
+ 12 VDC (5): Output for internally provided + 12 VDC stabilized supply. It may be used for Steer Angle
Direction LED gauge connections or other interface cards. The maximum rated output is 40
mAmp.
WARNING: Do not short circuit this pin, because it is common with the Electric Power Steering
card supply.
NRV (6): This is the one side of the second speed reduction switch connection. The first connection is
pin 15 on connector E of the ECM. This pin is one side of a switch and is typically connected
in series with other similar switches feeding the traction controller speed reduction input.
AUTOLAMP (7): Provides a switched ground reference for the AUTOLAMP that is capable of switching a
maximum lamp rating of 50 mAmps @ +24 VDC. This reference is switched on when the
AUTOSEL switch is turned on. Connect the AUTOLAMP between this point and an external
supply of + 24 VDC maximum.
CHOUT (8): Not used.
+5 VDC (9): Outputs regulated + 5 VDC supply. WARNING: Do not short circuit this pin or the power supply
STEERING & WIRE GUIDANCE
The wire guidance card 11 pin connector needs no description since it is only connected to the wire guidance
antennas and input for automatic steering and is described earlier.
CONNECTOR CODE
Tab. 5
The ECM has 4 trimmer pots. Two of the trimmer pots (TM1 and TM2) are for factory adjustment only. The other
settings should be made with reference to the equipment options on the truck being adjusted. Use the following
instructions.
Fig. 21
Pot steering:
The following procedure should be used only after the "Preliminary Set Up Procedure" in Section 5.5 is
STEERING & WIRE GUIDANCE
TRIMMER
DESCRIPTION TEST POINT(S)
POT
TM6
TM7
TM11
coils to 180 mV RMS using a multimeter that can measure true RMS AC voltages up to 10 kHz
(Refer to your owner's manual.) Trimmer Pot 1 (TM1) adjusts the AC voltage at Test Point 9 (TP9).
Trimmer Pot 2 (TM2) adjusts the AC voltage at Test Point 10 (TP10). Turning the pots clockwise reduces
the signal.
9.0.c. MDU POT OFFSET ADJUSTMENT
TM10 The MDU pot must be installed so that with the drive unit straight ahead the voltage on Test Point
6 (TP6) (MDU pot wiper) measures as close to 0 VAC as possible. If, during mechanical tightening
of the MDU pot shaft, the signal level from the pot shifts, it is possible to use this adjustment to bring
the required value back to the 0 VAC using Trimmer Pot 10 (TM10).
Adjustment Procedure:
- Travel 10 meters (30 feet) on wire guidance in DRIVE END direction . If TM10 is not correctly
adjusted, the truck will travel parallel to the guide wire some distance but always with a straight
wheel.
- Use the hand set SPECIAL POT ADJ setting (see 12.4.g). "ON" disconnects power from the
steer motor so steering angle does not change during adjustment. This causes an immediate
steering alarm and disables the control unit.
- Now adjust TM10 to give as close to 0 VAC as possible at Test Point 6 (TP6) corresponding to
a straight drive wheel position.
9.0.d. STEERING ERROR OFFSET ADJUSMENT
TM9 (Only adjust after performing 9.3 Potentiometer Offset adjustment). Adjustment Procedure:
- Travel 10 meters (30 feet) on wire guidance in DRIVE END direction.
- Stop all travel demand.
- Wait 30 seconds for the guidance system to go into TIME OUT status and stop steering until
there is again a travel demand.
- Use a voltmeter attached to Test Point 4 (TP4) adjust TM9 until 0VDC is measured.
(Improper adjustment causes the truck to travel parallel to the guide wire similar to TM10 being
out of adjustment.)
Fig. 23
Fig. 24
If the problem persists, travel on the guide wire in the load wheel direction and stop the truck at a point
where the misalignment is very evident. At this point check TP11, corresponding toTrimmer 3 (TM3)
and TP12, corresponding to Trimmer 4 (TM4) . Adjust whichever point is higher, through trial and
observation, until the lateral shift is zero when traveling in the load wheel direction on guidance.
- Use the hand set to read the ANTENNA ERROR (see 12.2.c) value and adjust TM8 to obtain an error
value of 4.5 VDC (or 0.5 VDC if the truck is on the opposite side of the wire.)
Note: if the truck is centered over the wire, then the ANTENNA ERROR will be 2.5 VDC.
NOTE: The ANTENNA ERROR read using the hand set will correspond to the antenna on the end of
the truck that was leading the last direction traveled/selected.
Fig. 25
To modify the alarm tolerance four parameters are provided (see 12.1.e - 12.1.h)
1) FWD UPP ERR ANT = Adjusts the sideways alarm threshold relative to a lateral shift of the DRIVE
END sensor that increases over 2.5 VDC the ANTENNA ERROR measurement. (UPPer is for higher
than 2.5 VDC. We do not use right and left references in this section. They are too easily confused.)
FWD UPP ERR ANT level = 0 gets alarm for 3.5 VDC on ANTENNA ERROR point. This is a very
sensitive alarm threshold.
FWD UPP ERR ANT level = 8 gets alarm for 4.5 VDC on ANTENNA ERROR point. This is a very
insensitive alarm threshold.
FWD UPP ERR ANT level = 9 disables the alarm for this pickup coil side.
2) FWD LOW ERR ANT = Adjust the sideways alarm threshold relative to a lateral shift of the DRIVE
END sensor for an ANTENNA ERROR measurement that is below 2.5 VDC.
FWD LOW ERR ANT LEVEL = 0 gives an alarm for 1.5 VDC on ANTENNA ERROR point. This is a
very sensitive alarm threshold.
FWD LOW ERR ANT LEVEL = 8 gives an alarm for 0.5 VDC on ANTENNA ERROR point. This is a
very insensitive alarm threshold.
FWD LOW ERR ANT LEVEL = 9 disables the alarm for this pickup coil side.
3) REV UPP ERR ANT = Adjusts the sideways alarm threshold relative to a lateral shift of the LOAD
END sensor for an ANTENNA ERROR measurement that is above 2.5 VDC.
REV UPP ERR ANT level = 0 gets alarm for 3.5 VDC on ANTENNA ERROR point. This is a very
sensitive alarm threshold.
REV UPP ERR ANT level = 8 gets alarm for 4.5 VDC on ANTENNA ERROR point. This is a very
insensitive alarm threshold.
REV UPP ERR ANT level = 9 disables the alarm for this pickup coil side.
4) REV LOW ERR ANT = Adjusts the sideways alarm threshold relative to a lateral shift of the LOAD
END sensor for an ANTENNA ERROR measurement that is below 2.5 VDC.
REV LOW ERR ANT level = 0 gets alarm for 1.5 VDC on ANTENNA ERROR point. This is a very
sensitive alarm threshold.
REV LOW ERR ANT level = 8 gets alarm for 0.5 VDC on ANTENNA ERROR point. This is a very
insensitive alarm threshold.
REV LOW ERR ANT level = 9 disables the alarm for this pickup coil side.
If the "PRELIMINARY SET UP PROCEDURE" was performed correctly, the following information is not
necessary. If problems were found, then the information below gives you some ideas to solve them.
- Position the truck over the guide wire using manual mode steering.
- With the truck positioned over the guide wire, turn on the wire guidance using the AUTOSEL switch on the
operator console.
- Travel a few cm (inches) in the DRIVE END direction.
- The truck goes into automatic steering.
STEERING & WIRE GUIDANCE
- If all goes well the MDU will set itself in a direction leading the truck to capture the guide wire. The MDU should
be angled to intercept the guide wire as shown below:
Fig. 26
If this does not occur, then there are two possible sources of the problem.
Fig. 27
10.0.b. REVERSED SENSOR FEEDBACK:
If the MDU corrects in a proportional manner, but away from the wire when the truck is parked over and not on
the guide wire, then swap the wires going to FL (10) and FR (11) for the DRIVE END sensor and the connections
RL (3) and RR (4) for the LOAD END sensor on the big connector on the wire guidance board (see 7.0).
Fig. 28
- A 3 amp fuse (F2) in series with the key and placed on the ECM motherboard to protect the logic card.
If the key is switched on and the steering system shows no response, check the 3 amp logic fuse. If the fuse (F1)
on the power portion of the unit is blown, an alarm "I=0 EVER" is produced.
If the Fuse (F2) is intact, the system signals through a combination of lights (AUTOLED and MANLED) and an
audible device (BUZZER) of any problems:
Each alarm or failure is encoded on the BUZZER with a number of high frequency beeps, repeated in bursts,
corresponding with the alarm numbers in the list below. Low frequency beeps are reserved for wire SEEK mode
only. To discriminate between manual mode and automatic mode alarms, the lights (AUTOLED and MANLED)
are frozen when an alarm occurs to give information on the mode of operation the truck was in when the error
occurred. The same information is repeated in a more direct fashion on the hand set. Below is a list of the alarms
with the numbers that correspond to the beep code.
supervisor microcontroller finds one of the two switches disagrees with the commands, during
initial phase, this alarm occur.
2) The supervisor microcontroller has missed receiving an update (every 16 msec) from the
master microcontroller. The master microcontroller is reading commands (tach-generator,
pots, limit switches, etc.) and informs the supervisor with a regular signal. If this interrupt is
missed, the supervisor behaves as through the command inputs are not being processed and
stop the truck opening its own alarm switch.
3) The supervisor microcontroller has missed the fixed time (48 msec) watchdog timer pulse on
the power portion functionality test. Every 48 msec the master microcontroller sends an update
pulse to the supervisor microcontroller. If a pulse is missed it looks like the power portion
diagnosis was not executed so the supervisor stops the truck.
4) The supervisor microcontroller has determined a command action that disagrees with
generated by the master controller.
5) The supervisor microcontroller has determined a measured steer angle feedback pot evolution
disagrees with the command pot voltage.
Remedy: Switch off the machine and power it up again. If the problem persists, replace the unit or contact
the factory.
ALARM 2 I=0 EVER: Indicated by repeated two beep burst on the BUZZER and a lighted MANLED.
Cause: Occurs if there is a power failure on the power portion of the steering controller and in
any case where steer motor current cannot increase above zero and with the
appropriate voltage (+ or -) when commanded.
Remedy: Check that fuse F1 (32 A) on the logic board is intact. Check that the steering motor and
its wires have not been cut off. Check that the motor is mechanically loaded. With the
motor running free it should require a running current greater than 6% of IMax. If the
problem persists, replace the unit.
Fig. 30
ALARM 5 HIGH TEMPERATURE: Indicated by repeated 5 beep burst on the BUZZER and a lighted MANLED.
Cause: Occurs if temperature of the power base exceeds 78°C (172°F).
Remedy: Let the unit cool down. If the alarm occurs repeatadly, it is necessary to improve the unit heat
dissipation capability.
ALARM 6 STBY I HIGH: Indicated by repeated 6 beep burst on the BUZZER and a lighted MANLED.
Cause: Occurs if truck is at rest when there should be no steering current for a disabled power unit state
STEERING & WIRE GUIDANCE
Fig. 31
ALARM 7 RELE'KO: Indicated by repeated 7 beep burst on the BUZZER and a lighted MANLED.
Cause: Two alarm switches are connected in series and allow the traction to move. The first switch is closed
by the master microcontroller. The second switch is closed by the supervisor microcontroller. Both
microcontrollers execute diagnostic tests on their own and on the other opened or closed state
switches. If the master microcontroller finds its own switch closed before it commands it closed or
finds its own switch open before it commands it opened, then this alarm occurs.
If this error occurs immediately after switching on the key, then the contact may be shorted (welded)
without a driving signal. If the error occurs later, then the contact may be in a locked open position
Fig. 32
ALARM 2 LATERAL OUT: Indicated by repeated two beep burst of the BUZZER and both AUTOLED and
MANLED are lit.
Cause: It occurs in case the threshold for lateral shift during wire guided mode of operation (see 12.1.e
through 12.1.h) is set at a higher value. The guidance sensor is too far from the wire side during
guided operation.
Remedy: Confirm that during motion the sensor error signal does not exceed the threshold.
WARNING: A disconnected antenna coil wire or a swiftly changing magnetic field deformation around
the guide wire (crooked wire, reinforcing rod, AC motor wires in the floor) can cause an alarm
condition.
STEERING & WIRE GUIDANCE
ALARM 3 PATH: Indicated by repeated 3 beep burst on the BUZZER and both AUTOLED and MANLED
are lit.
Cause: Occurs if the sensor signal used for guidance in the traveling direction goes below the
required threshold. The alarm occurs at the same time when the guidepath presents LED
DL1 for DRIVE END sensor and DL2 for LOAD END sensor are off.
Remedy: This alarm may occur if the guide wire on the floor is cut, if the signal picked up by the sensor
is too low, or if the sensor(s) is/are not adjusted correctly.
ALARM 4 EEPROM KO: Indicated by repeated 4 beep burst on the BUZZER and both AUTOLED and MANLED are lit.
Cause and Remedy: See 11.2.1 ALARM 4 in manual mode.
ALARM 5 HIGH TEMPERATURE: Indicated by repeated 5 beep burst on the BUZZER and both AUTOLED and
MANLED are lit.
Cause and Remedy: See 11.2.1 ALARM 5 in manual mode.
ALARM 6 LOOP: Indicated by repeated 6 beep bursts on the BUZZER and both AUTOLED and MANLED are lit.
Cause: Occurs when in wire guided mode the MDU pot error will not neutralize the sensor error (regardless
of travel direction). It is as if the closed loop control on steer angle feedback pot has opened.
STEERING & WIRE GUIDANCE
Remedy: Try to reduce the truck oscillation on the guide wire by adjusting TM15 (clockwise increases steering
speed response) and TM13 (counterclockwise causes the truck to make larger steering corrections)
on the wire guidance card.
This alarm can also be caused by an open in the MDU pot, damage to the MDU pot, loose
mechanical connection of the MDU pot, broken steer chain, broken steering gear box, broken steer
motor, or noise induced by a guidance sensor.
ALARM 7 RELE' KO: Indicated by repeated 7 beep bursts on the BUZZER and both AUTOLED and
MANLED are lit.
Cause and Remedy: See 11.2.1 ALARM 7 in manual mode.
ALARM 8 STEER HAZARD: Indicated by repeated 8 beep burst on the BUZZER and both
AUTOLED and MANLED are lit.
Cause: Occurs if a limit switch opens during an automatic controlled wire guided steering
AUTOMATIC mode or SEEK mode.
Remedy: To get out of the alarm, select the MANUAL mode steering using the AUTOSEL switch
on the operator console.
ALARM 9 POT OUT OF RANGE: Indicated by repeated 9 beep burst on the BUZZER and both AUTOLED and
MANLED are lit.
Cause: During guidance AUTOMATIC mode the drive unit has too large a steer angle. The maximum
allowable steer angle is adjustable using the hand set and TM7 (see 9.0.m).
Remedy: If the alarm occurred during normal guidance mode operations without an excessive steer angle and
it is practical to increase the steer angle limit, then you may use the hand set and TM7 as described
in 12.1.f through 12.1.l and 9.0.m sections.
STEERING & WIRE GUIDANCE
This section describes the hand set functions. Numbers inside the triangles correspond to the same
number on the hand set keyboard buttons shown in the figure below. The orientation of the triangle
indicates the shift direction of the button effect.
Fig. 33
Fig. 34
Fig. 35
The manual steering mode parameters are partially different between Tach-Generator and Pot Steering as
described in paragraphs 12.0.a. and 12.0.b.
Each parameter is described below, there is no separation between Tach-Generator and Pot steering options.
To locate each parameter inside its host menu, see the Function Maps in paragraphs 12.0.a. and 12.0.b. In
every case a specific attribute is given to each parameter.
After modifying a parameter, memorize it with the hand set by pushing the "4" (OUT) button and a "3" (IN) button.
Double pushing the OUT button gets out without saving the modifications.
Fig. 36
12.1.a. SPEED LIMIT: Used with Tach-Generator Steering only, it regulates the maximum turning speed
of the MDU.
- Level 0 is for slow turning
- Level 9 is for fast turning
Intermediate levels are for proportionally increasing speed settings. Maximum MDU speed has to be
regulated after SET BATTERY TYPE is done (see 12.5.f). The higher the battery type is set to, the higher
the MDU turning speed for a given value of the SPEED LIMIT parameter.
12.1.b. SENSITIVITY: Used with Tach-Generator steering only, it provides a non-linear relationship between
steering handle input (command) and MDU steering speed at small command input changes. This
parameter produces increasing steering sensitivity with small changes in steering input.
- Level 0 is for steering response that is less sensitive to small steer handle movements
- Level 9 is for steering response that is very sensitive to small steer handle movements
Intermediate levels are for proportionally increasing speed settings. This parameter does not influence
the maximum MDU steering rate.
12.1.c. KP: Used with Pot Steering and Automatic Centering Option only. It modifies the static precision of
the position control loop. To obtain precise return to center MDU pot voltage, increase the KP
value. If dither or overshoot becomes evident, try to lower the KP value.
- Level 0 is for less responsive and precise steering.
- Level 9 is for very responsive and precise steering (but "busy").
Intermediate levels are for proportionally increasing speed settings.
12.1.d. KD: Used with Pot Steering and Automatic Centering Option only. It modifies the dynamic behavior
of the position control loop. To reduce MDU pot overshoot or oscillations, adjust this parameter.
- Level 9 is for a complete proportional controlling algorithm.
- Level 0 is for a maximum leading contribution controlling algorithm. This causes the MDU to slow down
as it approaches near a steady state position. This is maximum overshoot (dither) reduction.
12.1.e FWD UPP ERR ANT: Used with Wire Guided Steering only. It modifies the threshold for a lateral shift
that causes a "LATERAL OUT" alarm. This parameter adjusts the threshold limit corresponding to the
DRIVE END sensor's lateral shift from the wire. This is relative to the coil that increases the ANTENNA
ERROR test value over 2.5 volts. 2.5 VDC ANTENNA ERROR value is for a perfectly centered sensor.
- Level 0 is for a lateral out alarm threshold of 3.5 VDC (consistent with ANTENNA ERROR value.)
- Level 8 is for a lateral out alarm threshold of 4.5 VDC (consistent with ANTENNA ERROR value.)
- Level 9 disables this alarm in the specified direction.
12.1.f. FWD LOW ERR ANT: Used with Wire Guided Steering only. It modifies the threshold for a lateral shift
that causes a "LATERAL OUT" alarm. This parameter adjusts the threshold limit corresponding to the
DRIVE END sensor's lateral shift from the wire. This is relative to the coil that increases the ANTENNA
ERROR test value over 2.5 volts. 2.5 VDC ANTENNA ERROR value is for a perfectly centered sensor.
- Level 0 is for a lateral out alarm threshold of 1.5 VDC (consistent with ANTENNA ERROR value.)
- Level 8 is for a lateral out alarm threshold of 0.5 VDC (consistent with ANTENNA ERROR value.)
- Level 9 disables this alarm in the specified direction.
12.1.n. 1ST ANGLE FINE: Used with Pot Steering only. It modifies in small steps the MDU maximum steer
angle in the direction of increasing MDU pot voltage above 2.5 VDC. If the "PRELIMINARY SET UP
PROCEDURE" was performed correctly this direction of MDU movement corresponds to a clockwise
steering handle movement. This parameter is used to regulate the 90 degree MDU steer angle, in the
specified direction, corresponding to 90 degrees of steer handle movement.
- Level 0 is for the smallest maximum MDU steer angle
- Level 9 is for the largest maximum MDU steer angle
Intermediate levels are for proportionately increasing angle.
STEERING & WIRE GUIDANCE
12.1.o. 2ND ANGLE COARSE: Used with Pot Steering only. Itt modifies in large steps the MDU maximum
steer angle in the direction of decreasing MDU pot voltage below 2.5 VDC. If the "PRELIMINARY SET
UP PROCEDURE" was performed correctly this direction of MDU movement corresponds to a
counterclockwise steering handle movement. This parameter is used to regulate the 90 degree MDU
steer angle, in the specified direction, corresponding to 90 degrees of steer handle movement.
- Level 0 is for the smallest maximum MDU steer angle
- Level 9 is for the largest maximum MDU steer angle
Intermediate levels are for proportionately increasing angle.
12.1.p. 2ND ANGLE FINE: Used with Pot Steering only. It modifies in small steps the MDU maximum steer
angle in the direction of decreasing MDU pot voltage below 2.5 VDC. If the "PRELIMINARY SET UP
PROCEDURE" was executed correctly this direction of MDU movement corresponds to a counterclockwise
steering handle movement. This parameter is used to regulate the 90 degree MDU steer angle, in the
specified direction, corresponding to 90 degrees of steer handle movement.
- Level 0 is for the smallest maximum MDU steer angle
- Level 9 is for the largest maximum MDU steer angle
Intermediate levels are for proportionately increasing angle.
12.1.q. ACCELERATION: Used with Pot Steering only. It controls how long it takes to complete a 180 degree
steer angle sweep
- Level 0 is for about 9 seconds for 180 degrees of steering
- Level 9 is for about 3 seconds for 180 degrees of steering
- Intermediate levels are for proportional time changes
12.1.r. DESENSITIZE: Used with Pot Steering only. It slows the MDU steering motion as the MDU pot voltage
begins to equal the command pot voltage. Its action can be observed with the steering handle turned ±
30 degrees from the center position. This parameter proportionately reduces the MDU steering speed.
- Level 0 is for no slowing of MDU steering near center steer handle position
- Level 9 is for slowing the MDU steering 10 times more than what is imposed with the ACCELERATION
parameter.
- Intermediate levels are for proportional changes in response
The TESTER function list is common for both tach-generator and pot steering options. Each TESTER function
provides information for the specified parameter. To locate each parameter inside its host menu, see the
function maps in paragraph 12.0.a and 12.0.b Descriptions of each TESTER function are given below.
12.2.a. SET POINT POT: Used with Pot Steering only. It provides the steering handle command voltage in real
time.
12.2.b. FEEDBACK POT: Used with Pot Steering and Wire Guidance only. It provides the MDU Pot voltage
in real time. When the system is in manual mode, then the hand set measured value is equal to the voltage
present on the central terminal of the (FB) MDU pot with respect to the GND point.
When the system is in wire guidance mode, the (FB) MDU pot is supplied with AC voltage, so the hand set
displays an AC/DC converted value. 2.5 VDC equals steer angle straight ahead. Higher or lower values
are for a turned MDU.
Exception: When the SPECIAL POT ADJ is set ON, regardless of steering mode, the FEEDBACK POT
value is always measured as though the truck is in the wire guided mode of steering.
12.2.c. ANTENNA ERROR: Used with Wire Guidance only. It provides the sensor error in real time. The sensor
error is the voltage difference between the right and left coil on the sensor that leads the last travel direction
Inside the "ALARMS" menu of the hand set, the last five alarm events are memorized with the number of
repetitions and the hour of the last occurrence for each kind of alarm.
The SET OPTIONS function list is used for all steering options. These options modify the system configuration.
To locate the function inside its host menu, see the function maps in paragraph 12.0.a. and 12.0.b. A description
of each option follows on the following page.
Fig. 37
12.4.a. HOUR COUNTER: there are two possible value options for what will appear in the root menu hand set
display.
- RUNNING = Run time when the steering is enabled - Use this setting.
- KEYON = Time counted continuously when the ECM is powered.
12.4.b. INP ACTIVE LOW: There are two possible options for this value regarding travel direction request.
- ON = External travel requests are active LOW.
- OFF = External travel requests are active HIGH. Use this setting.
12.4.c. LONG VEHICLE: There are two possible options for wire guidance. This is used to reduce the
combined wire guidance sensor error when traveling in the LOAD END direction (for a short truck).
- ON = Normally weighted combined sensors error. Use this setting.
- OFF = Reduced weighted combined sensors error (for a short truck).
12.4.d. STB I=0 EVER: There are two options for manual mode steering. If set on the power stage functionality.
If the motor current goes down near zero when commanded a corresponding alarm occurs. Is continually
monitored (also in the rest position)
- ON = Continuous diagnosis (with tiresome audible noise, but an alarm condition could be discovered
in advance of the steering motion)
- OFF = Diagnosis inhibited at steering rest position. Use this setting.
12.4.e. MICRO CHECK: this feature is to support the debugging activity option. It is used to inhibit the
Supervisor microprocessor operation and allow the system to run with just the Main processor support.
This operating mode does not allow the supervisor controlled alarm switch to close. Therefore,
- OPTION #4 = Pot steering plus automatic centering (Use this option for trucks with pot steering and
no wire guidance).
12.4.i. ANTENNA REF SEL: use with wire guidance option. It selects which antenna signal must be used to
supply the feedback pot. (It was decided to requireboth the drive unit and load wheel sensors to be close
to the guide wire to change to guided steering mode when traveling load wheels first. This option is not
required any longer.)
- OPTION #1 = The pot is supplied with the antenna signal corresponding to the direction of travel
actually selected.
- OPTION #2 = The pot is supplied with the FWD (drive unit) antenna signal.
STEERING & WIRE GUIDANCE
- OPTION #3 - The pot is supplied with the REV (load wheel) antenna signal.
12.4.l. AUTO INP ACTIVE: use with all steering options. It sets the active logic level (or edge) for the automatic
mode request (AUTOSEL). It is common for both wire guidance or automatic steering centering requests.
- OPTION #1 = External automatic request is active LOW ("LOW" means lower than +4 VDC).
- OPTION #2 = External automatic request is active HIGH ("HIGH" means higher than +5 VDC).
- OPTION #3 = The external automatic request is active for falling edge of odd numbering (i.e., the first
falling edge is for automatic, the second is return to manual, the third is for automatic, etc.)
- OPTION #4 = The external automatic request is active for rising edge of odd numbering (i.e., the first
falling edge is for automatic, the second is return to manual, the third is for automatic, etc.).
12.5.a. SET STEER 0-POS: Used only for Pot Steering option. It is used to set the MDU pot wiper voltage
corresponding to the center position of steering for the manual steering mode. The steering handle must
be released when adjusting this parameter. Adjust this setting by Entering SET STEER 0-POS and
pressing Enter (3) again. The default value is 2500.0 mV. You may roll the value up and down using the
(5) and (6) keys in 5 mV increments. For VNA trucks a higher value turns the MDU in the counterclockwise
direction.
12.5.b. SET STEER MIN: Used with all steering options. It is used to adjust the scaling of the clockwise 90
degree rotation of the MDU for use with the LED steer angle indicator gauge.
Adjust this setting with steering in MANUAL mode after completing 2ND SPEED FINE and 2ND SPEED
COARSE adjustments. Turn the MDU completely clockwise and with the SET STEER MIN in the hand
set display, push the ENTER (3) button. The display changes to the present feedback pot value. Push
the ENTER (3) button again to memorize this new reading.
12.5.c. SET STEER MAX: Used with all steering options. It is used to adjust the scaling of the counterclockwise
90 degree rotation of the MDU for use with the LED steer angle indicator gauge.
Adjust this setting with steering in MANUAL mode after completing 1ST ANGLE FINE and 1ST ANGLE
COARSE adjustments. Turn the MDU completely counterclockwise and with the SET STEER MAX in the
hand set display, push the ENTER (3) button. The display changes to the present MDU pot value. Push
the ENTER (3) button again to memorize this new reading.
NOTE: If not set, MDU steering speed is reduced.
12.5.d. ZERO SP. POT: Used only for Pot Steering option. It is used to capture the zero setting of the steer
handle pot for manual mode steering. Adjust this setting by releasing the steer handle on a pot steered
truck. With ZERO SP. POT in the display, press ENTER (3) button on the hand set. The display changes
to the present steer handle pot voltage. Press ENTER (3) button again to memorize this new reading.
12.5.e. ZERO AUTO FB: this setting is used for wire guided operations. It is used to modify the 2.5 V default
value used to calculate POT OUT OF RANGE limits. The alarm situation occurs if:
1) the FEEDBACK POT (MDU Pot) in wire guidance mode is over ZERO AUTO FB plus the set limit.
The set limit is 1 VDC if UPPER ERROR POT parameter is set to 0 and the set limit is 2 VDC if the
UPPER ERROR POT parameter is set to 8.
2) the FEEDBACK POT (MDU Pot) in wire guidance mode is less than ZERO AUTO FB minus the set
limit. The set limit is 1 VDC if UPPER ERROR POT parameter is set to 0 and the set limit is 2 VDC
if the UPPER ERROR POT parameter is set to 8.
Only a small modification of the 2.5 VDC default value is permitted (2.5 ± 0.4 VDC). To adjust this setting,
Fig. 38
Reclose internal current loop verifies in real time the current set point (I*) and the real current of the
motor (I) have the same sign. Since this internal current loop includes the power section and the motor
itself, a defect in either of these will cause this alarm.
WARNING: This alarm is activated if the steer motor requires less than 6% of IMax when it is running.
There may be no problem with the steer motor, power section, or any connections. This false alarm
may be prevented by setting IMax low enough that a running steer motor will always require more than
6% of the allowed current.
Approximately: PREQ
I MAX = ⋅3
VBATT
STEERING & WIRE GUIDANCE
b) Failures in the steer handle tach generator due to short circuits and broken or disconnected wires are
detected by monitoring the presence of the expected resistance on the control lines.
c) Failures in the pot wiring are detected by monitoring for a voltage higher than 4.9 VDC indicating a short
circuit or lower than 0.1 VDC indicating a broken or disconnected wire. Each pot is polarized with a
pair of resistors that restrict its wiper voltage between these two limits in normal operation when
correctly connected. (See fig. 30)
d) The microcontrollers continuously monitor the steer motor output current when the steering is at rest.
If steer motor output current is greater than zero an alarm condition occurs.
e) If the MDU pot voltage does not change for more than 0.5 seconds after there has been a change in
the steer handle pot, then an FB POT LOCKED alarm occurs.
f) The Master and Superviosor microcontrollers independently read the command input from the steer
handle tach-generator or pot. Then each microcontroller calculates a consequent controlling action.
While the Master micro creates the control signals, the Supervisor micro creates matching compari-
son values. Each microcontroller receives both its own and the other microcontroller's values. If these
values are mismatched each microcontroller may open its own alarm switch
All six of these alarm conditions cause a relay to open that disables traction.
Fig. 39
If the system fails to accomplish this condition due to a malfunction the LOOP alarm is activated.
b) If, during AUTOMATIC (guided) mode, the leading guidance sensor is to the side of the guide wire further
than set with TM8 (wire guidance card trimmer pot) and with the hand set, then the LATERAL OUT alarm
occurs immediately.
c) If, during AUTOMATIC (guided) mode, the drive unit steer angle (MDU pot voltage) is greater than set
with TM7 (wire guidance card trimmer pot) and the hand set, then POT OUT OF RANGE alarm occurs
immediately.
d) If the leading guidance sensor signal goes to zero volts or near zero volts, then the PATH alarm occurs
immediately.
Any of these alarm conditions causes a relay to open, which disables traction.
- Check power steering contactor tips for wear. Replace when contacts are worn.
- Check mechanical movement of the power steering contactor. It must be free and not jamb.
- Check power wiring going to the battery and steering motor. The terminals must be tight and firmly
connected. The insulation must be in good repair.
- Check control wiring going to and from the steering and guidance control box. The insulation must be in
good repair and connections must be tight.
- Check pot set screws and fastening hardware to ensure they are tight.
- Check steering chain tension. Tighten if necessary.
- Check steering motor and gear box mounting bolts. Ensure they are tight.
- Check wheel and drive unit bolts. Ensure they are tight.
- Check the steering and wire guidance operation. Adjust mechanical and electrical settings as necessary.
NOTES:
NOTES:
STEERING & WIRE GUIDANCE