KEY PLAN

KEYPLAN :
( B 105 )
IL:+5.4 m.
1No. 150mm Ø uPVC CONDUIT LAID
BELOW SLAB CONNECTING THE
450x450x800mm DRAW PIT FOR LIFE
EXTERNAL DRAW PIT / TRENCH FOR
SAFETY CABLE ENTRY
LIFE SAFETY CABLE FOR
CONTINUATION DUCT ROUTES REFER
TO DRAWING NO :
QINWP-QEM-G000-XX-SD-EE-0001-73

1
1 No. x 25 mm Ø CONDUIT RISES TO HIGH
LEVEL FOR FIRE ALARM CABLE

A E
Drawing Stamp

B105/00/CC2A/P01/L2/132
B105/00/CC2A/P01/L2/130 B105/00/CC2A/P01/L2/133

2
B105/00/CC2A/P01/L2/131
B105/00/CC2A/P01/L2/127
B105/00/CC2A/P01/L2/128 BXXX XF ST APSX CX XX
‫ﺍﻟﻣﺎﻧﻊ‬
B105/00/CT1/P01/L2/129 AL MANA
B105/00/ST/APS5/L1/01 P.O.Tel no. 44539888 Fax 44960734 P.O.Box 23300 Doha Qatar
www.rcalmana.com

TECHNICAL DEPARTMENT
Qetaifan Island North at Lusail Qatar

B
CC2A C -WaterPark-Package 3
C2
APS A BUILDING NO Reviewed by:_________________
15 Cd
W/P SPEAKER CABLE BACK TO FACP1 IN B100 Date:_____________
FLOOR LEVEL

F
TYPE
5
FIRE L2 BACK TO FACP1 IN B100
FIRE L2 FROM FACP1 IN B100 ST-STROBE
HS-SOUNDER/STROBE
D B105/00/MP/P01/L2/0126
SS-SPEAKER/STROBE Approval Stamp
APS NUMBER
CIRCUIT NUMBER
SPEAKER CABLE BACK TO POWER SUPPLY CABLE
CC2A BACK TO APS5 DEVICE NUMBER
KEY FOR SOUNDER/FLASHER/STROBE CIRCUIT (TYPICAL)

4 3 B-XXX XF SP PX AX XX
General Notes:
1. THE PROPOSED FIRE ALARM SYSTEM IS UL LISTED, QCDD APPROVED AND COMPLIES
WITH NFPA STANDARDS.
2. FOR EXACT DIMENSIONS OF PROPOSED EQUIPMENT, REFER TO EQUIPMENT
CATALOGUE SHEETS.
W/P 3. ISOLATOR BASE OR MODULE SHALL BE PROVIDED EVERY 15 TO 20 DEVICES AND
87 Cd WHEN THE LOOP TRAVELS BETWEEN FLOORS OR ZONES.
4. FIRE ALARM PANELS AND AUXULIARY POWER SUPPLIES SHALL BE FED FROM
B105/00/ST/APS5/L1/02
W/P
BUILDING NO DEDICATED BRANCH CIRCUITS.
5. FUSED CONNECTION UNIT FOR FIRE ALARM PANELS AND AUXILIARY POWER
87 Cd SUPPLIES SHALL BE "UNSWITCHED" TYPE.
B105/00/ST/APS5/L1/03 FLOOR LEVEL 6. CLASS A CIRCUITS SHALL FOLLOW NFPA 72 CLAUSE 12.3.8 WHICH DISCUSSES
PATHWAY SEPARATION.
W/P 7. ALL FIRE ALARM DEVICES INSTALLED ABOVE FALSE CEILING SHALL BE ACCESSIBLE.
70 Cd
B105/00/ST/APS5/L1/07
TYPE 8. ALL ABOVE FALSE CEILING DETECTORS SHALL BE CONNECTED TO AN LED
INDICATOR ON THE CEILING.
SP-SPEAKER 9. LOCATION OF ALL DEVICES SHALL BE COORDINATED. SMOKE/HEAT DETECTOR
SS-SPEAKER/STROBE SHALL NOT BE LOCATED IN A DIRECT AIRFLOW NOR CLOSER THAN 1 METER
FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR GRILLE.
10. CONTROL RELAY MODULES SHALL BE 1M AWAY FROM 3RD PARTY SYSTEM
PANEL NUMBER CONTROLLERS.
11. FINAL LABELING OF FIRE ALARM SYSTEM DEVICES WILL BE BASED ON SYSTEM
PROGRAMMING.
AMPLIFIER NUMBER 12. ALL FIRE ALARM DEVICES INSTALLATION DETAILS SHALL BE SUBMITTED
SEPARATELY.REFER TO TYPICAL INSTALLATION DETAILS DRAWING.
DEVICE NUMBER

KEY FOR SPEAKER CIRCUIT (TYPICAL)

E BXXX XF SD PX LX XXX NOTE - 1


00 ISSUED FOR APPROVAL 05/12/2020

BUILDING NO SD:- SMOKE DETECTOR


A SB:- SMOKE DETECTOR WITH SOUNDER BASE
HD:- HEAT DETECTOR
Rev. Description Date

FLOOR LEVEL References


MD:- MULTI SENSOR Rev. Model Name
MP:- MANUAL PULL STATION
DEVICE TYPE 0 QINWP-QEM-B105-ZZ-M3-BS-000001
CR:- CONTROL RELAY MODULE (CM) 0 QINWP-RCA-B105-ZZ-M3-AR-000001

3 4 PANEL NO
X=1,2,3...
CT1:- SINGLE INPUT MONITOR MODULE (MM)
CT2:-DUAL INPUT MONITOR MODULE (MM)
0
0
QINWP-RCA-B105-ZZ-M3-SE-000001
QINWP-QEM-B105-ZZ-M3-IT-000001
CC1:- SINGLE INPUT MODULE
LOOP NUMBER CC2A:-DUAL INPUT MODULE
RM:-RISER MONITOR MODULE
DEVICE NUMBER UM:-UNIVERSAL MODULE
001 - 125 : ODD LOOPS DETECTORS CC1S:-SYNCHRONIZATION OUTPUT MODULE
126 - 250 : ODD LOOPS MODULES IM:-ISOLATOR MODULE
87 Cd
W/P 251 - 375 : EVEN LOOPS DETECTORS RI:-REMOTE INDICATOR
B105/00/SS/APS5/L1/04 B105/00/ST/APS5/L1/06 376 - 500 : EVEN LOOPS MODULES
B105/00/SS/P01/A2/01
M

W/P KEY OF THE FIRE ALARM CIRCUIT (TYPICAL) Project Title:


87 Cd
W/P
C 70 Cd
C QETAIFAN ISLAND NORTH
B105/00/ST/APS5/L1/05
PHASE 1 - WATERPARK
Client:

CABLE IDENTIFICATION

2Cx1.5mm² FIRE RATED CABLE FOR DETECTION LOOP

2 D 1 B 2Cx2.5mm² FIRE RATED CABLE FOR SPEAKER CIRCUIT Architect/Engineer of Record:

5
1 LEVEL 00 FIRE ALARM SYSTEM LAYOUT 2Cx2.5mm² FIRE RATED CABLE FOR 24VDC POWER SUPPLY
00-0001-05 SCALE 1 : 100
4 CORE FIRE RATED SINGLE MODE FIBER OPTIC NETWORK CABLE Main Contractor:

FIRE ALARM LEGEND Sub- Contractor:

MOUNTING HEIGHT QUANTITIES


SYMBOL DESCRIPTION MODEL NO (FFL) (mm)
IFC REFERENCE DRAWINGS

F MANUAL PULL STATION SIGA-278 1200 (CENTER) 1


1. ENTRANCE GATE (B100) FIRE ALARM SCHEMATIC QINWP-ATK-B100-ZZ-DR-EE-662001
FIRE ALARM WALL MOUNTED STROBE CS405-8A-T 2300 (CENTER)
W/P (WP:WEATHERPROOF) 449 6
Drawing Title:
2. ENTRANCE PLAZA ROOF (B105) LEVEL 00 FIRE ALARM LAYOUT QINWP-ATK-B105-00-DR-EE-162001

M W/P
VOICE ALARM WALL MOUNTED SPEAKER/STROBE 757-8A-RS70 2300 (CENTER) 1 ENTRANCE PLAZA (B105)
(W/P:WEATHERPROOF)
3. WATERPARK FIRE POLICY LEGENDS & SYMBOLS QINWP-ATK-XX-XX-DR-EE-000002 LEVEL 00
CC2A DUAL INPUT MODULE SIGA-CC2A WALL MOUNTED 3 FIRE ALARM SYSTEM LAYOUT
4. WATERPARK FIRE DETECTION STANDARD DETAILS QINWP-ATK-XX-XX-DR-EE-062001

MAIN ENTRANCE COMPLEX (B102) ELECTRICAL QINWP-ATK-B102-ZZ-DR-EE-661001 APS AUXILIARY POWER SUPPLY PANEL APS10A/230 1800 (Top) 1 Drawn By : Checked By : Approved By : Scale : Size
5. 7D MF BK As indicated
EMERGENCY LIGHTING SCHEMATIC
1 Date : Date : Date : A1
6. SITEWIDE FIRE ALARM SCHEMATIC QINWP-ATK-XXXX-XX-DR-EE-662001 CT1 SINGLE INPUT MONITOR MODULE SIGA-CT1 WALL MOUNTED
05/12/2020 05/12/2020 05/12/2020
Drawing No Rev.

QINWP-QEM-B105-00-SD-EE-0001-05 00