Conversion Wiring Diagrams for


RM7800/RM7840
These diagrams and instructions are for converting the following model programmers to RM7800/RM7840 microprocessor
based integrated burner control.

TABLE OF CONTENTS
Page
Section I ............................................................................................................................................................................... 6
BC7000
Section II ........................................................................................................................................................................... 12
Honeywell R4140, R4150
Section III .......................................................................................................................................................................... 31
Honeywell R4126, R4127, R4181
Section IV .......................................................................................................................................................................... 44
Fireye C, D, and E Series
Section V ........................................................................................................................................................................... 50
Fireye P Series
Section VI .......................................................................................................................................................................... 59
Eclipse 5602

WARNING
Improper configuration jumper selection could cause a fire or explosion hazard that could lead to property
damage, severe injury or death.

CAUTION
1. Installer must be a trained, experienced, flame safeguard control service technician.
2. Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. More
than one power supply disconnect may be involved.
3. All wiring must comply with applicable local electrical codes, ordinances, and regulations.
4. All line voltage terminal wiring shall be no. 14, 16 or 18 copper conductor TTW (60C) or THW (75C) or THHN
(90C), 600 volt insulation wire. A maximum of two conductors can be wired to each Q7800 Subbase terminal.
5. Voltage and frequency of the power supply and flame detector(s) connected to this control must agree with those
marked on the device.
6. Loads connected to the control terminals must not exceed ratings listed in Specification sheets 65-0087 or 65-0117,
or on the RM7800/RM7840 label.
7. All external timers must be listed or component recognized by authorities having jurisdiction for the specific
purpose for which they are used.
8. Perform all required checkout tests after installation is complete.

B.M./L.Z. • Rev. 2-95 • ©Honeywell Inc. 1995 1 65-0100—2


65-0100-2
IMPORTANT: found to comply with the limits for a Class B comput-
1. For on-off gas-fired systems, some authorities having ing device of Part 15 of FCC rules which are designed
jurisdiction prohibit the wiring of any limit or operat- to provide reasonable protection against such inter-
ing contacts in series between the flame safeguard ference when operated in a commercial environment.
control and the main fuel valve(s). Operation of this equipment in a residential area may
2. Do not connect more than two C7012E,F or C7076A,D cause interference, in which case, users at their own
Ultraviolet Flame Detectors (with self-checking shut- expense may be required to take whatever measures
ter) in parallel to the same terminals. are required to correct this interference.
3. This equipment generates, uses and can radiate radio 4. This digital apparatus does not exceed the Class B
frequency energy and if not installed and used in limits for radio noise for digital apparatus set out on
accordance with the instructions may cause interfer- the Radio Interference Regulations of the Canadian
ence to radio communications. It has been tested and Department of Communications.

NORMAL OPERATION:
Pilot Flame Main Flame
Establishing Period Establishing Period
Device Initiate Standby Purge (PFEP) (MFEP)1 Run Postpurge
RM7800/7840E 10 sec. * ** 4 or 10 sec. 10 or 15 sec. * 15 sec.
RM7800/7840G 10 sec. * ** 4 or 10 sec. 10, 15, 30 or Int. * 15 sec.
RM7800/7840L 10 sec. * ** 4 or 10 sec. 10 or 15 sec. * 15 sec.
RM7800/7840M 10 sec. * ** 4 or 10 sec. 10 sec. or Int. * 15 sec.
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which ST7800A Purge Card is selected.
1 The MFEP will be determined by which terminal, configuration jumper and jumper wire is selected.

APPROVAL BODIES: DATA CONTROLBUS MODULE™


Underwriters Laboratories Inc. Listed: File No. MP268 —part no. S7810A1009.
Guide No. MCCZ. Dust Cover
Canadian Standards Association Certified, LR9S329-3. —part no. 221729 (RM7840 only).
Factory Mutual Approved: Report No. JI1V9A0.AF. Electrical Access Slot Cover
Industrial Risk Insurers Acceptable. —part no. 203765.
Federal Communications Commission: Part 15, Class B. Expanded Annunciator
Canadian Department of Communications: CS-03, Certi- —part no. S7830A1005
fication No. 5733459A. Flame Simulators
MOUNTING: Q7800A for panel mount or Q7800B for wall —part no. 203659 UV Flame Simulator.
or burner mount. —part no. 123514A Rectification Simulator.
REQUIRED COMPONENTS: Keyboard Display Module
Q7800 Subbase —part no. S7800A1001 (RM7840 only).
ST7800 Purge Timer Remote Display Mounting Bracket
RM7847/48/49/86 Flame Amplifier —part no. 203765.
ACCESSORIES: Remote Reset Module
5-Wire Connector —part no. S7820A1007.
—part no. 203541. Tester
Combustion Service Manager —part no. A7800A1002.
—part no. ZM7850A1001. Remote Display Power Supply
Communication Interface Base Unit —part no. 203968 Plug-in.
—part no. Q7700A1014.
Communication Interface ControlBus Module
—part no. QS7800A1001.

65-0100—2 2
ON - OFF BURNER CONTROL RECYCLE MODULATING BURNER CONTROL
RM7800M1011 WITH DISPLAY 60 HZ RM7800G1018 WITH DISPLAY 60 HZ
SELECT A RELAY RM7800M1003 WITH DISPLAY 50 HZ RM7800G1000 WITH DISPLAY 50 HZ
1.) 1 OR 1
MODULE RM7840M1017 WITHOUT DISPLAY 60 HZ RM7840G1014 WITHOUT DISPLAY 60 HZ
RM7840M1009 WITHOUT DISPLAY 50 HZ RM7840G1006 WITHOUT DISPLAY 50 HZ

Q7800A1005 PANEL MOUNT OR


SELECT A Q7800B1003 BURNER/WALL
2.)
SUBBASE MOUNT

ST7800A1005 2 SEC.
ST7800A1013 7 SEC.
SELECT A ST7800A1021 10 SEC.
3.)
PURGE CARD ST7800A1039 30 SEC.
ST7800A1047 40 SEC.
ST7800A1054 60 SEC.
ST7800A1062 90 SEC.
ST7800A1070 2.5 MIN.
ST7800A1088 4 MIN.
ST7800A1096 6 MIN.
ST7800A1104 9 MIN.
ST7800A1112 12 MIN.
ST7800A1120 15 MIN.
ST7800A1138 22 MIN.
ST7800A1146 30 MIN.

R7847A1025 0.8 SEC. FFRT (RECTIFICATION). USE


W/FLAME RODS OR PHOTOCELLS.
SELECT A FLAME R7847A1033 3.0 SEC. FFRT (RECTIFICATION). USE
4.) W/FLAME RODS, PHOTOCELLS OR
AMPLIFIER
C7012A,C.
R7847B1023 0.8 SEC. FFRT (RECTIFICATION). USE
W/FLAME RODS OR PHOTOCELLS.
R7847B1031 3.0 SEC. FFRT (RECTIFICATION). USE
W/FLAME RODS, PHOTOCELLS OR
C7012A,C.
R7847C1005 3.0 SEC. FFRT (C7012E,F)
R7848A1008 3.0 SEC. FFRT (C7015) 2
R7848B1006 3.0 SEC. FFRT (C7015)
R7849A1015 0.8 SEC. FFRT (C7027/C7035/C7044)
R7849A1023 3.0 SEC. FFRT (C7027/C7035/C7044)
R7849B1013 0.8 SEC. FFRT (C7027/C7035/C7044)
R7849B1021 3.0 SEC. FFRT (C7027/C7035/C7044)
R7886A1001 3.0 SEC. FFRT (C7076A,D)

COMMUNICATIONS
Q7700A1014 BASE UNIT 3
SELECT QS7800A1001 CONTROLBUS MODULE™
5.) ZM7850A1001 COMBUSTION SYSTEM MANAGER®
OPTIONS
S7810A1009 DATA CONTROLBUS MODULE™
(MUST USE IF KEYBOARD DISPLAY MODULE IS
NOT PRESENT ON RELAY MODULE)

EXPANDED ANNUNCIATION
S7830A1005 EXPANDED ANNUNCIATOR
S7810A1009 DATA CONTROLBUS MODULE™
(MUST USE IF KEYBOARD DISPLAY MODULE IS
NOT PRESENT ON RELAY MODULE)

REMOTE DISPLAY MOUNTING


203765 REMOTE MOUNTING BRACKET
13 VDC POWER SUPPLY
• 203968A PLUG-IN
S7810A1009 DATA CONTROLBUS MODULE™
(MUST USE IF KEYBOARD DISPLAY MODULE IS
NOT PRESENT ON RELAY MODULE)

REMOTE RESET
S7820A1007 REMOTE RESET MODULE

1 120 VAC. DISPLAY MODULE


S7800A1001 DISPLAY MODULE
2 FFRT = FLAME FAILURE RESPONSE TIME. (RM7840G OR RM7840M ONLY)

3 ONE Q7700 WILL SUPPORT ANY COMBINATION OF UP TO SIX (6) QS7700s/QS7800s. M1940C

3 65-0100—2
LOCKOUT MODULATION BURNER CONTROL
RM7800E1010 OR RM7800L1012 WITH DISPLAY 60 HZ
SELECT A RELAY RM7800E1002 OR RM7800L1004 WITH DISPLAY 50 HZ 1
1.)
MODULE RM7840E1016 OR RM7840L1018 WITHOUT DISPLAY 60 HZ
RM7840E1008 OR RM7840L1000 WITHOUT DISPLAY 50 HZ 2

Q7800A1005 PANEL MOUNT OR


SELECT A Q7800B1003 BURNER/WALL
2.)
SUBBASE MOUNT

ST7800A1005 2 SEC.
ST7800A1013 7 SEC.
SELECT A ST7800A1021 10 SEC.
3.)
PURGE CARD ST7800A1039 30 SEC.
ST7800A1047 40 SEC.
ST7800A1054 60 SEC.
ST7800A1062 90 SEC.
ST7800A1070 2.5 MIN.
ST7800A1088 4 MIN.
ST7800A1096 6 MIN.
ST7800A1104 9 MIN.
ST7800A1112 12 MIN.
ST7800A1120 15 MIN.
ST7800A1138 22 MIN.
ST7800A1146 30 MIN.

R7847A1025 0.8 SEC. FFRT (RECTIFICATION). USE


W/FLAME RODS OR PHOTOCELLS.
SELECT A FLAME R7847A1033 3.0 SEC. FFRT (RECTIFICATION). USE
4.) W/FLAME RODS, PHOTOCELLS OR
AMPLIFIER
C7012A,C.
R7847B1023 0.8 SEC. FFRT (RECTIFICATION). USE
W/FLAME RODS OR PHOTOCELLS.
R7847B1031 3.0 SEC. FFRT (RECTIFICATION). USE
W/FLAME RODS, PHOTOCELLS OR
C7012A,C.
R7847C1005 3.0 SEC. FFRT (C7012E,F) 3
R7848A1008 3.0 SEC. FFRT (C7015)
R7848B1006 3.0 SEC. FFRT (C7015)
R7849A1015 0.8 SEC. FFRT (C7027/C7035/C7044)
R7849A1023 3.0 SEC. FFRT (C7027/C7035/C7044)
R7849B1013 0.8 SEC. FFRT (C7027/C7035/C7044)
R7849B1021 3.0 SEC. FFRT (C7027/C7035/C7044)
R7886A1001 3.0 SEC. FFRT (C7076A,D)

COMMUNICATIONS
Q7700A1014 BASE UNIT 4
SELECT QS7800A1001 CONTROLBUS MODULE™
5.) ZM7850A1001 COMBUSTION SYSTEM MANAGER®
OPTIONS
S7810A1009 DATA CONTROLBUS MODULE™
(MUST USE IF KEYBOARD DISPLAY MODULE IS
NOT PRESENT ON RELAY MODULE)

EXPANDED ANNUNCIATION
S7830A1005 EXPANDED ANNUNCIATOR
S7810A1009 DATA CONTROLBUS MODULE™
(MUST USE IF KEYBOARD DISPLAY MODULE IS
NOT PRESENT ON RELAY MODULE)

REMOTE DISPLAY MOUNTING


203765 REMOTE MOUNTING BRACKET
13 VDC POWER SUPPLY
• 203968A PLUG-IN
S7810A1009 DATA CONTROLBUS MODULE™
(MUST USE IF KEYBOARD DISPLAY MODULE IS
NOT PRESENT ON RELAY MODULE)

REMOTE RESET
1 RM7800E1010 AND RM7840E1016 WITH S7820A1007 REMOTE RESET MODULE
ENERGY SAVINGS PREPURGE.

2 120 VAC. DISPLAY MODULE


S7800A1001 DISPLAY MODULE
3 FFRT = FLAME FAILURE RESPONSE TIME. (RM7840G OR RM7840M ONLY)
M1941C
4 ONE Q7700 WILL SUPPORT ANY COMBINATION OF UP TO SIX (6) QS7700s/QS7800s.

65-0100—2 4
DIRECTIONS:
1. Disconnect all power to control being replaced. Note 7 Select proper site configurable jumpers specified in
that more than one power supply disconnect may be the cross reference and shown in the Specifications,
involved. 65-0087 for RM7840 or 65-0117 for RM7800.
2. Remove old control from subbase.
3. Mark all wires on subbase; i.e., wires connected to 8 Select proper site configurable PFEP/MFEP speci-
terminal 1 should be marked 1. fied in the cross reference and shown in the Specifica-
4. Disconnect wires from subbase. tions, 65-0087 for RM7840 or 65-0117 for RM7800.
5. Remove old subbase.
6. Mount Q7800 Subbase. 9 If low fire switch is not used, a jumper is required
7. Connect wires to subbase according to wiring conver- between Q7800 Subbase terminals 5 and 18. NOTE:
sion for control being replaced. Pay close attention to This jumper will add 30 seconds to prepurge timing.
footnotes. The triangle symbol 1 with a number or
letter inside designates a footnote. 10 If replaced device had interrupted pilot on terminal 6,
8. Install the RM7800/RM7840 control. Make sure the connect to Q7800 Subbase terminal 8.
proper ST7800 purge card and flame detector were
selected for the application. 11 Locate the start interlock on the Q520 Subbase termi-
9. The RM7800/RM7840 have two or three site con- nal 16 and connect between Q7800 terminals 4 and
figurable jumper options. (depends on model number). 20. The start interlocks now become preignition
JUMPERS: interlocks. If start interlocks are not used, jumper the
• JR1 selects Pilot Flame Establishing Period. Q7800 Subbase terminal 4 to terminal 20.
• JR2 (RM7800G/RM7840G only) selects intermit-
tent or interrupted pilot. 12 Locate the preignition interlocks on the Q520 Sub-
• JR3 selects lockout/running interlock input base terminals 4 and 16. Connect the preignition
check. Refer to RM7800 instructions, 60-0117 or interlock between the Q7800 Subbase terminals 4
RM7840 instructions, 60-0087, for assistance and and 20. If preignition interlocks are not used, jumper
proper selection. the Q7800 Subbase terminal 4 to terminal 20.
10. Refer to instructions, 60-0087 or 60-0117, for check-
out and start-up. 13 Jumper Q7800 subbase terminal 8 to terminal 19 for
30 second MFEP.

GENERAL FOOTNOTES: 14 Locate the preignition interlock connection on the


Q520 Subbase terminal 16 and connect to the Q7800
1 RM7840 operates the same as the RM7800 but does subbase terminal 20.
not have the Display Module. (Display Module
S7800A1001 can be added later.) The RM7800 must 15 For direct spark ignition, discard any jumpers be-
have Display Module installed to operate. tween Q520 Subbase terminals 5, 6, and 7 and con-
nect according to the diagram shown.
2 Select proper prepurge timer according to the Firing
Line cross reference, 70-8313. 16 Many R4181 devices were used on North American
Company Burners. Because North American uses
3 Select proper flame amplifier according to the Firing many unique external circuits, such as Automatic
Line amplifier cross reference. Fuel Changeover, Valve Leak Checker, etc., it is
recommended that you contact Honeywell through
4 Proper grounding of the green subbase terminal screw your local distributor or sales representative before
to an electrical earth ground is a MUST for proper attempting conversions of North American Burners.
operation of the 7800 SERIES device.
17 For models without damper motors, jumper Q7800
5 NOTE: UL allows only two electrical wires to each Subbase terminal 14 to terminal 18, and terminal 4 to
subbase terminal. Wiring information may show more terminal 13.
than two wires to a particular terminal, which may
require an external connection to accomplish the 18 Be sure system is modernized to 120 Vac. The
connection. replacement 7800 SERIES control is 120 volts.
6 Q520 Subbase terminal 16 connection may have been 19 Select proper flame detector when converting from a
a wire nut connection. Remove wire nut and connect non-Honeywell control or when a different flame
to the Q7800 Subbase terminal 6. detection system is desired; i.e., the old flame ampli-
fier was flame rectification and the new flame ampli-
fier is to be ultraviolet. Refer to product selection
matrixes on pages 3 and 4.

5 65-0100—2
Section I
BC7000

65-0100—2 6
7800 SERIES CONVERSION WIRING DIAGRAM
BC700L1000 WITH
PM720G2005 OR G2103
FROM________________________________ RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 10
(OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 11

21 1ST STAGE
L2
FUEL VALVE
9 3 14 14
2ND STAGE
9
FUEL VALVE
L1 4 15 12 (OPTIONAL)

8 5 16

16 14 6 17

3 7 18 13 9

5 8 19 15

7 9 20 14

18 10 21 6 10

F 22 17
F

2 3 4 5 7 8 9 10 14 15 M2530B

GENERAL FOOTNOTES, SEE PAGE 5.

7 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
BC7000L1000 WITH
PM720L1030, 1139, L2020
FROM________________________________ RM7800L1012 OR RM7800E1010
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 10 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 11

8 L2
9 3 14 14

9 MAIN VALVE

L1&4 A 4 15 12

8 A 5 16

16 6 17

3 7 18 13

5 8 19 15

7 9 20 14

18 10 21 6

F F 22 17 A RM7800E ONLY – LOCATE HIGH FIRE


SWITCH ON THE Q520 SUBBASE
TERMINAL 8 AND CONNECT TO
THE Q7800 SUBBASE TERMINAL 4.
2 3 4 5 7 8 14 15
GENERAL FOOTNOTES, SEE PAGE 5. M2531B

65-0100—2 8
7800 SERIES CONVERSION WIRING DIAGRAM
BC7000L1000 WITH
PM720L2004
FROM________________________________ RM7800E1010
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
10 FOR DIRECT SPARK IGNITION
G G 12 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 11

8 L2
9 3 14 14

9 MAIN VALVE

L1&4 4 15 12

8 5 16

16 6 17

3 7 18 13

5 8 19 15

7 9 20 14

18 10 21 6

F F 22 17

2 3 4 5 7 8 14 15
GENERAL FOOTNOTES, SEE PAGE 5. M2532B

9 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
BC700L1000 WITH
PM720M2002
FROM________________________________ RM7800M1011
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 12

21 1ST STAGE L2
FUEL VALVE
9 3 14
2ND STAGE
9
FUEL VALVE
L1&4 4 15 11 (OPTIONAL)

8 5 16

16 14 6 17

3 7 18 13

5 8 19

7 9 20 14

18 10 21 6

F F 22 17

2 3 4 5 7 8 14 15 M2533B

GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 10
7800 SERIES CONVERSION WIRING DIAGRAM
BC7000L1000 WITH
PM720M2036
FROM________________________________ RM7800M1011
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 (OIL OR GAS)

10 IGNITION
A TRANSFORMER
L2 L2 13

21 1ST STAGE L2
A FUEL VALVE
9 3 14
2ND STAGE
9
FUEL VALVE
L1&4 4 15 (OPTIONAL)

8 5 16

16 6 17
14

3 7 18

5 8 19

7 9 20 14

18 10 21 6

F F 22 17

A JUMPER Q7800 SUBBASE TERMINAL


14 TO 18 AND 4 TO 13.
2 3 4 5 7 8 14 15
GENERAL FOOTNOTES, SEE PAGE 5. M2534B

11 65-0100—2
Section II
Honeywell R4140, R4150

65-0100—2 12
7800 SERIES CONVERSION WIRING DIAGRAM
R4140G WITH
FROM________________________________
START INTERLOCKS TO RM7840G1014 OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


10 (OIL OR GAS)
G G 12

10 IGNITION
TRANSFORMER
L2 L2 13 11
21 1ST STAGE
L2
FUEL VALVE

9 3 14 14
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
L1&4 4 15 12

8 5 16

16 6 6 17

3 7 18 13

5 8 19 13

7 9 20 11

18 10 21 6 10 A

F F 22 17

A R4140G1171 0NLY–REPLACEMENT
CONTROL CANNOT PROVIDE
60 SECOND MFEP.
1 2 3 4 5 6 7 8 11 13 15 M2536B

GENERAL FOOTNOTES, SEE PAGE 5.

13 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4140G WITH
PREIGNITION INTERLOCK
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 10 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 11

21 1ST STAGE L2
FUEL VALVE
9 3 14 14

9 2ND STAGE
FUEL VALVE
L1 4 15 12 (OPTIONAL)

8 5 16

16&4 6 17
12 6

3 7 18 13 9

5 8 19
13

7 9 20 12

18 10 21 6
10

F F 22 17

1 2 3 4 5 6
M2535B
7 8 9 10 12 13 14 15
GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 14
7800 SERIES CONVERSION WIRING DIAGRAM
RM7840E1016 OR RM7800E1010
R4140L/R4150L RM7840L1018 OR RM7800L1012
FROM________________________________ TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


10 (OIL OR GAS)
G G 12

10 IGNITION
TRANSFORMER
L2 L2 13 11
8 L2

9 3 14 14
9 MAIN VALVE

L1 B 4 15 12

8 B 5 16

16&4 12 6 17

3 7 18 13

5 8 19 15

7 9 20 12

A NO INTERMITTENT RM7840L/RM7800L
18 10 21 6 A MODELS AVAILABLE.

B RM7840E OR RM7800E ONLY–LOCATE


HIGH FIRE SWITCH CONNECTION ON
F F 22 17
Q520 SUBBASE TERMINAL 8. CONNECT
TO Q7800 SUBBASE TERMINAL 4.

1 2 3 4 5 7 8 12 15 M2537B

GENERAL FOOTNOTES, SEE PAGE 5.

15 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4140M/R4150M WITH
FROM________________________________
START INTERLOCKS TO RM7840M1017 OR RM7800M1011
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


G 12 (OIL OR GAS)
G
10 IGNITION
TRANSFORMER
17
L2 L2 13 12
21 1ST STAGE L2
FUEL VALVE
17
9 3 14
9 2ND STAGE
FUEL VALVE
(OPTIONAL)
L1&4&11 4 15 10

8 5 16

16 6 6 17

3 7 18 13

5 A 8 19

7 9 20 11

18 10 21 6 10

F F 22 17

A R4140M1103 AND M1111 HAVE 10 OR 30


SECOND MFEP OPTION.
REPLACEMENT RELAY MODULE HAS 10
1 2 3 4 5 6 SECOND MFEP OR INTERMITTENT PILOT.

7 8 9 10 11 15 17
M2538B
GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 16
7800 SERIES CONVERSION WIRING DIAGRAM
R4140M/R4150M WITH
PREIGNITION INTERLOCK
FROM________________________________ RM7840M1017 OR RM7800M1011
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 (OIL OR GAS)

10 IGNITION
17 TRANSFORMER
L2 L2 13 12

21 1ST STAGE L2
17 FUEL VALVE
9 3 14
2ND STAGE
9
FUEL VALVE
L1&11 4 15 10 (OPTIONAL)

8 5 16

16 4 6 17
6 12

3 7 18 13

5 8 19

7 9 20 12

18 10 21 6
10

F F 22 17

1 2 3 4 5 6 M2539B

7 8 9 10 11 15 17
GENERAL FOOTNOTES, SEE PAGE 5.

17 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4150A1007, A1023, A1122, A1247,
FROM________________________________
A1254, A1288, B1005, C1003, C1029 TO RM7840M1017 OR RM7800M1011
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
G G 12

10 IGNITION
TRANSFORMER
D
L2 L2 13
21 1ST STAGE
L2
FUEL VALVE
D
9 3 14
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
L1&4 4 15

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 C 7 18

5 8 19

7 9 20 B

10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START C AIR FLOW SWITCH MAY HAVE BEEN
INTERLOCKS CONNECTED BETWEEN Q520
TERMINALS 10 AND 11. CONNECT
A LOCATE THIS JUNCTION 3 BETWEEN Q7800 SUBBASE TERMINALS
OR TERMINAL 16
AIRFLOW 6 AND 7. BE SURE AIR FLOW SWITCH
AND CONNECT IT TO
SWITCH C IS RATED TO HANDLE LOADS ON Q7800
Q7800 SUBBASE
SUBBASE TERMINALS 8, 9, 10 AND 21.
TERMINAL 6
D JUMPER Q7800 SUBBASE TERMINAL
B LOCATE THE START INTERLOCKS AT THIS POINT AND
4 TO 13 AND TERMINAL 14 TO 18.
CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
M2540B
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 18
7800 SERIES CONVERSION WIRING DIAGRAM

R4150A1056, A1163, A1189, A1239


FROM________________________________ TO RM7840M1017 OR RM7800M1011
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
G G 12

10 IGNITION
TRANSFORMER
E
L2 L2 13
21 1ST STAGE
L2
FUEL VALVE
E
9 3 14
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
L1&4 4 15

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 C 7 18

6 8 19

7 9 20 B

5 D 10 21

F F 22

C AIR FLOW SWITCH MAY HAVE BEEN


CONTROLLER
CONNECTED BETWEEN Q520
L1 4
TERMINALS 10 AND 11. CONNECT
LIMITS START BETWEEN Q7800 SUBBASE TERMINALS
INTERLOCKS 6 AND 7. BE SURE AIR FLOW SWITCH
A LOCATE THIS JUNCTION 3 IS RATED TO HANDLE LOADS ON Q7800
OR TERMINAL 16 SUBBASE TERMINALS 8, 9, 10 AND 21.
AND CONNECT IT TO AIRFLOW
Q7800 SUBBASE SWITCH C D REPLACEMENT RM7840/RM7800
TERMINAL 6 PROVIDE 5 SECOND IGNITION VS. 10.

B LOCATE THE START INTERLOCKS AT THIS POINT AND E JUMPER Q7800 SUBBASE TERMINAL
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. 4 TO 13 AND TERMINAL 14 TO 18.
START INTERLOCKS NOW BECOME PREIGNITION
M2544B
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.

19 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM

R4150A1064, A1130, A1148


FROM________________________________ TO RM7840G1014 OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


G 12 (OIL OR GAS)
G
10 IGNITION
TRANSFORMER
D
L2 L2 13
21 1ST STAGE L2
FUEL VALVE
D
9 3 14
9 2ND STAGE
FUEL VALVE
(OPTIONAL)
L1&4 4 15

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 C 7 18

5 8 19

7 9 20 B

10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START C AIR FLOW SWITCH MAY HAVE BEEN
INTERLOCKS CONNECTED BETWEEN Q520
TERMINALS 10 AND 11. CONNECT
A LOCATE THIS JUNCTION 3 BETWEEN Q7800 SUBBASE TERMINALS
OR TERMINAL 16
AIRFLOW 6 AND 7. BE SURE AIR FLOW SWITCH
AND CONNECT IT TO
SWITCH C IS RATED TO HANDLE LOADS ON Q7800
Q7800 SUBBASE
SUBBASE TERMINALS 8, 9, 10 AND 21.
TERMINAL 6
D JUMPER Q7800 SUBBASE TERMINAL
B LOCATE THE START INTERLOCKS AT THIS POINT AND
4 TO 13 AND TERMINAL 14 TO 18.
CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
M2541B
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 20
7800 SERIES CONVERSION WIRING DIAGRAM
R4150A1080, A1155
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 (OIL OR GAS)

10 IGNITION
17 TRANSFORMER
L2 L2 13

21 1ST STAGE L2
17 FUEL VALVE
9 3 14
2ND STAGE
9
FUEL VALVE
L1&4 4 15 (OPTIONAL)

8 5 16

10 A 6 17

7 18 A LOCATE START INTERLOCK


CONNECTION ON Q520 SUBBASE
TERMINAL 10 AND CONNECT TO Q7800
SUBBASE TERMINAL 20. IF START
C 5 8 19 INTERLOCK WAS NOT USED, JUMPER
Q7800 SUBBASE TERMINAL 4 TO 20
START INTERLOCKS WILL NOW
BECOME PREIGNITION INTRLOCKS.
7 9 20 A
B R4150 TERMINAL 6 PROVIDES
30 SECOND MFEP. JUMPER Q7800
SUBBASE TERMINAL 5 TO 19 AND
11 10 21 6 B CLIP JUMPER JR2 TO ACHIEVE 30
SECOND MFEP.

C R4150 TERMINAL 5 PROVIDES A 15


F F 22
SECOND MFEP. TERMINAL 8 OF THE
7800 SERIES CONTROL PROVIDES A
10 SECOND MFEP.

1 2 3 4 5 7 8 15 17 M2545B

GENERAL FOOTNOTES, SEE PAGE 5.

21 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM

R4150A1106, A1171
FROM________________________________ TO RM7840M1017 OR RM7800M1011
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
G G 12

10 IGNITION
TRANSFORMER
D
L2 L2 13
21 1ST STAGE
L2
FUEL VALVE
D
9 3 14
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
L1&4 B 4 15

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 C 7 18

5 8 19

7 9 20 B

10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START C AIR FLOW SWITCH MAY HAVE BEEN
INTERLOCKS CONNECTED BETWEEN Q520
TERMINALS 10 AND 11. CONNECT
A LOCATE THIS JUNCTION 3 BETWEEN Q7800 SUBBASE TERMINALS
OR TERMINAL 16
AIRFLOW 6 AND 7. BE SURE AIR FLOW SWITCH
AND CONNECT IT TO
SWITCH C IS RATED TO HANDLE LOADS ON Q7800
Q7800 SUBBASE
SUBBASE TERMINALS 8, 9, 10 AND 21.
TERMINAL 6
D JUMPER Q7800 SUBBASE TERMINAL
B LOCATE THE START INTERLOCKS AT THIS POINT AND
4 TO 13 AND TERMINAL 14 TO 18.
CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
M2543B
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 22
7800 SERIES CONVERSION WIRING DIAGRAM

R4150A1197
FROM________________________________ TO RM7840M1009, OR RM7800M1003
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


G 12 (OIL OR GAS)
G
10 IGNITION
TRANSFORMER
D
L2 L2 13
21 1ST STAGE L2
FUEL VALVE
D
9 3 14
9 2ND STAGE
FUEL VALVE
(OPTIONAL)
L1&4 4 15

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 C 7 18

5 8 19

7 9 20 B

10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START C AIR FLOW SWITCH MAY HAVE BEEN
INTERLOCKS CONNECTED BETWEEN Q520
TERMINALS 10 AND 11. CONNECT
A LOCATE THIS JUNCTION 3 BETWEEN Q7800 SUBBASE TERMINALS
OR TERMINAL 16
AIRFLOW 6 AND 7. BE SURE AIR FLOW SWITCH
AND CONNECT IT TO
SWITCH C IS RATED TO HANDLE LOADS ON Q7800
Q7800 SUBBASE
SUBBASE TERMINALS 8, 9, 10 AND 21.
TERMINAL 6
D JUMPER Q7800 SUBBASE TERMINAL
B LOCATE THE START INTERLOCKS AT THIS POINT AND
4 TO 13 AND TERMINAL 14 TO 18.
CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
M2542B
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.

23 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM

R4150G1004, 1046, 1111, 1145, 1178


FROM________________________________ TO RM7840G1014, OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
G G 12 10
10 IGNITION
TRANSFORMER
L2 L2 13 11
21 1ST STAGE
L2
FUEL VALVE

9 3 14 14 C
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
L1&4 4 15 12

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 7 18 13

5 8 19

7 9 20 B

10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START C R4150G1004, 1046 ARE 3 WIRE
INTERLOCKS MODULATION DEVICES THAT WILL NOT
HAVE Q520 SUBBASE TERMINAL 14
A LOCATE THIS JUNCTION 3 CONNECTION.
OR TERMINAL 16
AND CONNECT IT TO AIRFLOW
Q7800 SUBBASE SWITCH
TERMINAL 6

B LOCATE THE START INTERLOCKS AT THIS POINT AND


CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
M2526B
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 24
7800 SERIES CONVERSION WIRING DIAGRAM

R4150G1012, G1079
FROM________________________________ TO RM7840M1017, OR RM7800M1011
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


G 12 (OIL OR GAS)
G
10 IGNITION
TRANSFORMER
L2 L2 13 C
21 1ST STAGE L2
FUEL VALVE

9 3 14
9 2ND STAGE
FUEL VALVE
(OPTIONAL)
L1&4 4 15 10

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 7 18 13 D

5 8 19

7 9 20 B

11 10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START C INSTALL JUMPER BETWEEN Q7800
INTERLOCKS SUBBASE TERMINALS 4 AND 13.
A LOCATE THIS JUNCTION 3 D IF LOW FIRE SWITCH IS NOT USED,
OR TERMINAL 16
AIRFLOW JUMPER Q7800 SUBBASE TERMINAL 5 TO
AND CONNECT IT TO
SWITCH 18. NOTE: THIS WILL EXTEND PREPURGE
Q7800 SUBBASE
30 SECONDS.
TERMINAL 6

B LOCATE THE START INTERLOCKS AT THIS POINT AND


CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
START INTERLOCKS NOW BECOME PREIGNITION
M2527B
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
JUMPER Q7800 TERMINALS 4 TO 20.

25 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM

R4150G1103, G1137
FROM________________________________ TO RM7840G1014, OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
G G 12 10
10 IGNITION
TRANSFORMER
L2 L2 13 11
21 1ST STAGE
L2
FUEL VALVE

9 3 14 14 D
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
L1&4 4 15 12

5 1 2 3 4
8 16
5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17

3 7 18 13

5 8 19 C

7 9 20 B

10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START
INTERLOCKS
A LOCATE THIS JUNCTION 3 C Q520 SUBBASE TERMINAL 6 PROVIDED 30
AND CONNECT IT TO
AIRFLOW SECOND MFEP. JUMPER Q7800 SUBBASE
Q7800 SUBBASE
SWITCH TERMINAL 19 TO 5 AND CLIP JUMPER JR2.
TERMINAL 6
D R4150G1103 HAD 3 WIRE MODULATION AND
B LOCATE THE START INTERLOCKS AT THIS POINT AND
DID NOT HAVE Q520 SUBBASE TERMINAL
CONNECT IT TO Q7800 SUBBASE TERMINAL 20.
14 CONNECTION.
START INTERLOCKS NOW BECOME PREIGNITION
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
M2528B
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 26
7800 SERIES CONVERSION WIRING DIAGRAM
R4150G1129(GP200) R4140G1189(GP201) RM7840E1016 OR RM7800E1010
R4150L1078(GP300) R4140L1089(GP301)
FROM________________________________ TO RM7840L1018
______________________
OR RM7800L1012
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12 X (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 10

8 L2
A 3 14 12

9 MAIN VALVE

L1 4 15 11

M&D B D 5 16

3&13 C 6 17

P 7 18 B
A IF Q520 SUBBASE TERMINAL 6 IS USED,
CONNECT RM7840, RM7800 FOR DIRECT
SPARK IGNITION. NOTE: GP TERMINAL 6
5 8 19 8 PROVIDED INTERMITTENT PILOT;
RM7840L/RM7800L DOES NOT.

B LOCATE LOW FIRE SWITCH CONNECTION


6&7 A 9 20 C TO Q520 SUBBASE TERMINAL D AND
CONNECT TO Q7800 SUBBASE
TERMINAL 18.

18 10 21 C LOCATE PREIGNITION INTERLOCK ON Q520


SUBBASE TERMINALS 3 AND 13. CONNECT
ONE LEAD TO Q7800 SUBBASE TERMINAL
20 AND THE OTHER LEAD TO Q7800
S1 F 22 17 SUBBASE TERMINAL 4.

D RM7840E/RM7800E CONNECT D TO Q7800


SUBBASE TERMINAL 4.
M2523B
1 2 3 4 5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.

27 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4150G1186
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 10 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 11

21 1ST STAGE L2
FUEL VALVE
9 3 14 14
2ND STAGE
9
FUEL VALVE
L1 4 15 12 (OPTIONAL)

8 5 16

4,16 12 6 17

3 7 18 13

5 8 19

7 9 20 12

10 21 6

F F 22

1 2 3 4 5 7 8 12 15 M2529B

GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 28
7800 SERIES CONVERSION WIRING DIAGRAM

R4150H1002
FROM________________________________ TO RM7840G1014, OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


G 12 (OIL OR GAS)
G
10 IGNITION
TRANSFORMER
L2 L2 13 10
21 1ST STAGE
L2
FUEL VALVE

9 3 14 12
9 2ND STAGE
FUEL VALVE
(OPTIONAL)
L1&4 4 15 11

D
8 5 16 1 2 3 4 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5.

A 6 17

3 7 18

5 8 19 C

7 9 20 B

10 21 6

F F 22

CONTROLLER
L1 4
LIMITS START
INTERLOCKS C Q520 SUBBASE TERMINAL 6 PROVIDED 60
SECOND MFEP. RM7840/RM7800
A LOCATE THIS JUNCTION 3 PROVIDE 30 SECONDS WITH Q7800
AND CONNECT IT TO SUBBASE TERMINALS 19 TO 5 JUMPED
Q7800 SUBBASE AIRFLOW
AND JUMPER JR2 CLIPPED.
TERMINAL 6 SWITCH
D JUMPER Q7800 TERMINAL 5 TO 18.
LOCATE THE START INTERLOCKS AT THIS POINT AND NOTE: 30 SECONDS WILL BE ADDED TO
B CONNECT IT TO Q7800 SUBBASE TERMINAL 20. PREPURGE TIMING.
START INTERLOCKS NOW BECOME PREIGNITION
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, M2525B

JUMPER Q7800 TERMINALS 4 TO 20.

29 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4150M1175(GP100)
R4140M1079(GP101)
FROM________________________________ RM7840M1017 OR RM7800M1011
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12 (OIL OR GAS)

10 IGNITION
B TRANSFORMER
L2 L2 13

21 1ST STAGE
L2
B FUEL VALVE
A 3 14
2ND STAGE
9
FUEL VALVE
L1 4 15 (OPTIONAL)

5 16

13,3 6 17
A

7 18

5 8 19

7 9 20

18 10 21 6 A LOCATE PREIGNITION INTERLOCK


CONNECTION ON Q520 SUBBASE
TERMINALS 13 AND 3. CONNECT
PREIGNITION INTERLOCK BETWEEN
S1 F 22 17 Q7800 SUBBASE TERMINALS 4 AND 20.

B JUMPER Q7800 SUBBASE TERMINALS


14 TO 18 AND TERMINAL 4 TO 13.
1 2 3 4 5 7 8 15
GENERAL FOOTNOTES, SEE PAGE 5. M2524B

65-0100—2 30
Section III
Honeywell R4126, R4127, R4181

31 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4126A1008, 1016, A1024, A1032, A1040,
A1057,A1081, A1149
FROM________________________________
R4126B1066,B1014,B1022 TO RM7840G1014, OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


G 12 (OIL OR GAS)
G 11
10 IGNITION
TRANSFORMER
L2 L2 13 14
21 1ST STAGE
L2
FUEL VALVE

9 3 14 13
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
L1&3 B 4 15 12

13
8&15 5 16 1 2 3 4 5

7 8 13 15 18
A 6 17 GENERAL FOOTNOTES, SEE PAGE 5.

4 7 18 16

5 8 19

7 9 20 B

10 21 6 13

F F 22 C

CONTROLLER
L1 3 C Q535 OR Q536 SUBBASE HAD U1 AND U2
LIMITS START TERMINALS THAT WERE USED FOR
INTERLOCKS C7020 AND C7012E,F FLAME DETECTORS.
A. TO MODERNIZE C7020 APPLICATIONS,
A LOCATE THIS JUNCTION 4 CHOOSE A NEW DECTOR AND
AND CONNECT IT TO REWIRE PER RM7840/RM7800
Q7800 SUBBASE AIRFLOW
SPECIFICATIONS.
TERMINAL 6 SWITCH
B. TO MODERNIZE A C7012E,F
APPLICATION, USE THE EXISTING
B LOCATE THE START INTERLOCKS AT THIS POINT AND SENSOR AND REWIRE PER
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. RM7840/RM7800 SPECIFICATIONS.
START INTERLOCKS NOW BECOME PREIGNITION
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
M2513B
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 32
7800 SERIES CONVERSION WIRING DIAGRAM
For Insurance Requirements
R4126A1008, A1016, A1024, A1032 A1040,
A1057, A1081, A1149 RM7840E1016, RM7800E1010
R4126B1006, B1014, B1022
FROM________________________________ TO RM7840L1018, RM7800L1012
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 11 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 14

8 L2
9 3 14 13

9 MAIN VALVE

L1&3 B 4 15 12

8 5 16 1 2 3 4 5 7 8 15 18
GENERAL FOOTNOTES, SEE PAGE 5.

A 6 17
C TO MODERNIZE TO AN RM7840L,E OR
RM7800L,E TO MEET INSURANCE
REQUIREMENTS, THE FOLLOWING
4 7 18 INTERLOCKS ARE NORMALLY REQUIRED.
C
(CONNECT OR JUMPER INTERLOCKS AS
SHOWN TO THE Q7800 SUBBASE TERMINALS).

5 8 19 C RM7840E/ RM7840L/
INTERLOCKS RM7800E RM7800L

RUNNING INTERLOCKS 6–7 6–7


7 9 20 3 C
PREIGNITION INTERLOCKS 4–20 4–20
HIGHFIRE SWITCH* 5–19 4–19
10 21 6 D LOWFIRE SWITCH* 5–18 5–18
* JUMPER WILL ADD ADDITIONAL 30 SECONDS
TO THE PREPURGE TIMING
F1 F 22 E
D TERMINAL 6 PROVIDED 30 SECOND MFEP.
THE REPLACEMENT CONTROL WILL
CONTROLLER PROVIDE 15 SECOND MFEP.
L1 3
E Q535 OR Q536 SUBBASE HAD U1 AND U2
LIMITS START TERMINALS THAT WERE USED FOR
INTERLOCKS C7020 AND C7012E,F FLAME DETECTORS.
A LOCATE THIS JUNCTION A. TO MODERNIZE C7020 APPLICATIONS,
4
AND CONNECT IT TO CHOOSE A NEW DETECTION AND
Q7800 SUBBASE AIRFLOW REWIRE PER RM7840/RM7800
TERMINAL 6 SWITCH SPECIFICATIONS.
B. TO MODERNIZE A C7012E,F
B LOCATE THE START INTERLOCKS AT THIS POINT AND APPLICATION, USE THE EXISTING
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. SENSOR AND REWIRE PER
START INTERLOCKS NOW BECOME PREIGNITION RM7840/RM7800 SPECIFICATIONS.
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, M2514B
JUMPER Q7800 TERMINALS 4 TO 20.

33 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
RM7840E1016 OR RM7800E1010
R4126A1073, A1164
FROM________________________________ TO RM7840L1018 0R RM7800L1012
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
G G 12 11
10 IGNITION
TRANSFORMER
L2 L2 13 14
8 L2

9 3 14 13
9 MAIN VALVE

L1&3 B 4 15 12

8 5 16 1 2 3 4

5 7 8 15 18
A 6 17 GENERAL FOOTNOTES, SEE PAGE 5.

4 7 18 16 C

5 8 19 15 D
C LOCATE LOW FIRE SWITCH WIRE ON Q535
OR Q536 SUBBASE TERMINAL 15 AND
CONNECT TO Q7800 SUBBASE TERMINAL 5.
7 9 20 B IF LOWFIRE SWITCH IS NOT USED, INSTALL
A JUMPER. NOTE: JUMPER WILL ADD 30
SECONDS TO PREPURGE TIMING.
10 21 6
D RN7840L/RM7800L–LOCATE Q535 OR Q536
SUBBASE L1 SIDE OF HIGH FIRE SWITCH
AND CONNECT TO Q7800 SUBBASE
F1 F 22 E TERMINAL 5. IF HIGH FIRE SWITCH IS NOT
USED, INSTALL A JUMPER. NOTE: JUMPER
WILL ADD 30 SECONDS TO PREPURGE
CONTROLLER TIMING.
L1 3
E Q535 OR Q536 SUBBASE HAD U1 AND U2
LIMITS START
TERMINALS THAT WERE USED FOR
INTERLOCKS
C7020 AND C7012E,F FLAME DETECTORS.
A LOCATE THIS JUNCTION 4 A. TO MODERNIZE C7020 APPLICATIONS,
AND CONNECT IT TO CHOOSE A NEW DECTOR AND
Q7800 SUBBASE AIRFLOW REWIRE PER RM7840/RM7800
TERMINAL 6 SWITCH SPECIFICATIONS.
B. TO MODERNIZE A C7012E,F
B LOCATE THE START INTERLOCKS AT THIS POINT AND APPLICATION, USE THE EXISTING
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. SENSOR AND REWIRE PER
START INTERLOCKS NOW BECOME PREIGNITION RM7840/RM7800 SPECIFICATIONS.
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
M2511B
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 34
7800 SERIES CONVERSION WIRING DIAGRAM
RM7840E1016 OR RM7800E1010
R4126A1172, A1180, A1198
FROM________________________________ TO RM7840L1018 OR RM7800L1012
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 11 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13
C

8 L2
9 3 14 13

9 MAIN VALVE

L1 4 15 12

8 5 16
C A. TO USE EXISTING GROUNDED MODULATING
CIRCUIT, JUMPER Q7800 TERMINALS
13 AND G.
3&4 F 6 17 B. IF A NONGROUNDED MODULATING CIRCUIT
IS DESIRED, IDENTIFY WIRE FROM MOD
MOTOR TERMINAL R AND Q535 OR Q536
TERMINAL G. DISCONNECT WIRE AND
F2 7 18 16 D CONNECT TO Q7800 SUBBASE TERMINAL 13.

D LOCATE LOW FIRE SWITCH WIRE ON Q535


OR Q536 SUBBASE TERMINAL 15 AND
5 8 19 15 E
CONNECT TO Q7800 SUBBASE TERMINAL 5.

E FOR RM7840E/RM7800E APPLICATION


ONLY. LOCATE HIGH FIRE SWITCH WIRE
7 9 20 F ON Q535 OR Q536 SUBBASE TERMINAL 8
AND CONNECT TO Q7800 SUBBASE
TERMINAL 4.
14 B 10 21 6 A
F LOCATE PREIGNITION INTERLOCK WIRE
ON Q535 OR Q536 TERMINALS 3 AND 4.
CONNECT PREIGNITION INTERLOCK
F 22 BETWEEN Q7800 SUBBASE TERMINALS 4
G
AND 20. IF PREIGNITION INTERLOCK WAS
NOT USED, INSTALL JUMPER.

G Q535 OR Q536 SUBBASE HAD U1 AND U2


1 2 3 4 5 7 8 15 18 TERMINALS THAT WERE USED FOR
GENERAL FOOTNOTES, SEE PAGE 5. C7020 AND C7012E,F FLAME DETECTORS.
A. TO MODERNIZE C7020 APPLICATIONS,
A R4126A1172,A1180, A1198 HAD 30 SECOND MFEP CHOOSE A NEW DETECTION AND
ON TERMINAL 6. REPLACEMENT RM7840/RM7800 REWIRE PER RM7840/RM7800
PROVIDE 15 SECOND MFEP ONLY. SPECIFICATIONS.
B. TO MODERNIZE A C7012E,F
B R4126 PROVIDED 10 SECOND IGNITION TIMING. APPLICATION, USE THE EXISTING
REPLACEMENT RM7840/RM7800 PROVIDES SENSOR AND REWIRE PER
5 SECONDS. RM7840/RM7800 SPECIFICATIONS.
M2515B

35 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4127A1007, A1015,1023, A1031, A1049
A1064, A1089, A1130, A1189, B1005,
B1013, B1021, B1047, C1003
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 11 IF USED (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 14

21 1ST STAGE L2
FUEL VALVE
9 3 14 13

9 2ND STAGE
FUEL VALVE
L1&3 B 4 15 12 (OPTIONAL)

8&15 D 5 16 1 2 3 4

5 7 8 15 18
A 6 17 GENERAL FOOTNOTES, SEE PAGE 5.

4 7 18 16 D

5 8 19

7 9 20 B

C R4127 PROVIDED 10 SECOND IGNITION-


REPLACEMENT. RM7840/RM7800
15 C 10 21 6 PROVIDES 5 SECONDS

D IF LOW FIRE SWITCH IS NOT USED,


F1 F 22 E JUMPER Q7800 SUBBASE TERMINALS 5
AND 18. NOTE: THIS WILL ADD 30 SECONDS
TO THE PREPURGE TIMING.
CONTROLLER
L1 3 E Q535 OR Q536 SUBBASE HAD U1 AND U2
TERMINALS THAT WERE USED FOR
LIMITS START C7020 AND C7012E,F FLAME DETECTORS.
INTERLOCKS A. TO MODERNIZE C7020 APPLICATIONS,
A LOCATE THIS JUNCTION 4 CHOOSE A NEW DECTOR AND
AND CONNECT IT TO REWIRE PER RM7840/RM7800
Q7800 SUBBASE AIRFLOW SPECIFICATIONS.
TERMINAL 6 SWITCH B. TO MODERNIZE A C7012E,F
APPLICATION, USE THE EXISTING
B LOCATE THE START INTERLOCKS AT THIS POINT AND SENSOR AND REWIRE PER
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. RM7840/RM7800 SPECIFICATIONS.
START INTERLOCKS NOW BECOME PREIGNITION
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, M2517B
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 36
7800 SERIES CONVERSION WIRING DIAGRAM
R4127A1056, A1080, A1122, A1148
A1155, A1171, A1197, B1039, B1054
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 11 IF USED (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 14

21 1ST STAGE L2
FUEL VALVE
9 3 14 13

9 2ND STAGE
FUEL VALVE
L1&3 B 4 15 12 (OPTIONAL)

8&15 D 5 16 1 2 3 4

5 7 8 15 18
A 6 17 GENERAL FOOTNOTES, SEE PAGE 5.

4 7 18 16 D

C R4127 PROVIDED 10 SECOND IGNITION-


REPLACEMENT. RM7840/RM7800
8 19 PROVIDES 5 SECONDS

D IF LOW FIRE SWITCH IS NOT USED,


7 9 20 JUMPER Q7800 SUBBASE TERMINALS 5
B
AND 18. NOTE: THIS WILL ADD 30 SECONDS
TO THE PREPURGE TIMING.

15 C 10 21 5 0R 6 E E Q535 OR Q536 TERMINAL 5 PROVIDED 15


SECOND MFEP. Q535 OR Q536 TERMINAL 6
PROVIDED EITHER 30, 55, OR 60 SECOND
22 MFEP (DEPENDS ON R4127 MODEL). JUMPER
F1 F F
RM7840G/RM7800G TERMINAL 19 TO 5 TO
GET 30 SECOND MFEP. 55 AND 60 SECOND
MFEP IS NOT ATTAINABLE.
CONTROLLER
L1 3 F Q535 OR Q536 SUBBASE HAD U1 AND U2
LIMITS START TERMINALS THAT WERE USED FOR
INTERLOCKS C7020 AND C7012E,F FLAME DETECTORS.
A LOCATE THIS JUNCTION A. TO MODERNIZE C7020 APPLICATIONS,
4
AND CONNECT IT TO CHOOSE A NEW DECTOR AND
Q7800 SUBBASE AIRFLOW REWIRE PER RM7840/RM7800
TERMINAL 6 SWITCH SPECIFICATIONS.
B. TO MODERNIZE A C7012E,F
B LOCATE THE START INTERLOCKS AT THIS POINT AND APPLICATION, USE THE EXISTING
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. SENSOR AND REWIRE PER
START INTERLOCKS NOW BECOME PREIGNITION RM7840/RM7800 SPECIFICATIONS.
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, M2516B
JUMPER Q7800 TERMINALS 4 TO 20.

37 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4127A1171, B1039, B1047, B1054
(RAY BURNER)
FROM________________________________ RM7800G1018 OR RM7840G1014
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 11 IF USED (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 14

21 1ST STAGE L2
FUEL VALVE
9 3 14 13

9 2ND STAGE
FUEL VALVE
B L1&15 4 15 12 (OPTIONAL)

8 5 16 1 2 3 4

5 7 8 15 18
A 6 17 GENERAL FOOTNOTES, SEE PAGE 5.

16 7 18 4 C

5 8 19 D

7 9 20 B

10 21 6 D

C IF NO LOW FIRE SWITCH, JUMPER Q7800


F1 F 22 SUBBASE TERMINALS 5 TO 18.
NOTE: ADDING THE JUMPER ADDS 30
SECONDS TO THE PURGE TIMING.
CONTROLLER
L1 15 D Q535 OR Q536 TERMINAL 5 PROVIDED
LIMITS START A 15 SECOND MFEP. Q7800 TERMINAL
INTERLOCKS 8 PROVIDES A 10 SECOND MFEP.
Q535 OR Q536 TERMINAL 6 PROVIDED
A LOCATE THIS JUNCTION 16 A 30, 55 OR 60 SECOND MFEP
AND CONNECT IT TO (SELECTED BY MODEL NUMBER).
Q7800 SUBBASE AIRFLOW
JUMPER Q7800 SUBBASE TERMINAL 4
TERMINAL 6 SWITCH
TO TERMINAL 19 AND CLIP JUMPER JR2
OF THE RM7800G/7840G RELAY MODEL
B LOCATE THE START INTERLOCKS AT THIS POINT AND TO GET A 30 SECOND MFEP. 55 AND 60
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. SECOND MFEP ARE NOT AVAILABLE.
START INTERLOCKS NOW BECOME PREIGNITION
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, M7447
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 38
7800 SERIES CONVERSION WIRING DIAGRAM
For Insurance Requirements
RM7840E1016 OR RM7800E1010
R4127 (ALL MODELS)
FROM________________________________ TO RM7840L1018 OR RM7800L1012
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 11 IF USED (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 14

8 L2
9 3 14 13

9 MAIN VALVE

L1&3 B 4 15 12

8&15 C 5 16 1 2 3 4 5 7 8 15 18
GENERAL FOOTNOTES, SEE PAGE 5.

A 6 17 IF LOW FIRE SWITCH IS NOT USED,


C
JUMPER Q7800 SUBBASE TERMINALS 5
AND 18. NOTE: THIS WILL ADD 30 SECONDS
4 7 18 16 C TO THE PREPURGE TIMING.

D R4127DEVICE MAY HAVE 15, 30, 55, OR 60


SECOND MFEP. REPLACEMENT DEVICE
5 D 8 19 PROVIDES 10 OR 15 SECONDS ONLY.
F
INSURANCE CODES REQUIRE 10 SECOND
MFEP. FOR GAS, NO.2 OIL AND NO.4 OIL
APPLICATIONS.
7 9 20 B
E R4127 PROVIDES 10 SECONDS IGNITION-
REPLACEMENT RM7840/RM7800 PROVIDE
15 10 21 5, 6 D 5 SECONDS.

F FOR RM7840L/RM7800L, JUMPER Q7800


SUBBASE TERMINAL 19 TO 5. NOTE: THIS
F1 F 22 G WILL EXTEND PREPURGE TIME 30 SECONDS.
FOR RM7840E/RM7800E,J JUMPER Q7800
SUBBASE TERMINAL 19 TO 4. NOTE: THIS
CONTROLLER WILL EXTEND PREPURGE TIME 30 SECONDS.
L1 3
LIMITS START G Q535 OR Q536 SUBBASE HAD U1 AND U2
INTERLOCKS TERMINALS THAT WERE USED FOR
A LOCATE THIS JUNCTION C7020 AND C7012E,F FLAME DETECTORS.
4 A. TO MODERNIZE C7020 APPLICATIONS,
AND CONNECT IT TO
Q7800 SUBBASE AIRFLOW CHOOSE A NEW DECTOR AND
TERMINAL 6 SWITCH REWIRE PER RM7840/RM7800
SPECIFICATIONS.
LOCATE THE START INTERLOCKS AT THIS POINT AND B. TO MODERNIZE A C7012E,F
B
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. APPLICATION, USE THE EXISTING
START INTERLOCKS NOW BECOME PREIGNITION SENSOR AND REWIRE PER
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, RM7840/RM7800 SPECIFICATIONS.
M2518B
JUMPER Q7800 TERMINALS 4 TO 20.

39 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
R4181A1000, A1026
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 13 (OIL OR GAS)

10 IGNITION
TRANSFORMER
2 (L2) + 15 L2 13 12

21 1ST STAGE L2
FUEL VALVE
9 3 14 10

9 2ND STAGE
FUEL VALVE
1 (L1) + 3 4 15 11 (OPTIONAL)

8 5 16 1 2 3 4 5

7 8 15 16 18
A 6 17 GENERAL FOOTNOTES, SEE PAGE 5.

4 7 18 18 E

8 19 C

7 9 20 B

C CONNECT JUMPER BETWEEN Q7800


SUBBASE TERMINAL 5 AND 19 FOR 30
10 21 5,6 C SECOND MFEP REQUIRED FOR TERMINAL
6 APPLICATION.

F D F 22 D DISCARD JUMPER WIRES FROM Q477 OR


Q514 SUBBASE TERMINALS F TO 14 OR
F TO 16.
CONTROLLER
L1 OR 1 3 E THE LOW FIRE SWITCH, IF REQUIRED,
WAS CONNECTED BETWEEN Q477 OR Q514
LIMITS START SUBBASE TERMINALS 1 AND 18. THE WIRE
INTERLOCKS FROM THE LOW FIRE SWITCH AND 1 MUST
A LOCATE THIS JUNCTION 4 BE IDENTIFIED AND CONNECTED TO Q7800
AND CONNECT IT TO SUBBASE TERMINAL 8.
Q7800 SUBBASE AIRFLOW IF NO LOW FIRE SWITCH WAS USED,
TERMINAL 6 SWITCH Q477,Q514 TERMINALS 1 AND 18 WERE
JUMPED. REMOVE TERMINAL 1 AND
B LOCATE THE START INTERLOCKS AT THIS POINT AND CONNECT TO Q7800 SUBBASE TERMINAL 8.
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. NOTE: THIS JUMPER ADDS 30 SECONDS
START INTERLOCKS NOW BECOME PREIGNITION TO THE PURGE TIMING.
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, M2522B
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 40
7800 SERIES CONVERSION WIRING DIAGRAM
For Insurance Requirements
RM7840E1016 OR RM7800E1010
R4181A1000, A1026
FROM________________________________ TO RM7840L1018 OR RM7800L1012
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
G G 12 13
10 IGNITION
TRANSFORMER
2 (L2) + 15 L2 13 12
8 L2

9 3 14 10
9 MAIN VALVE

1 (L1) + 3 4 15 11

1 2 3 4 5
8 5 16
7 8 15 16 18
GENERAL FOOTNOTES, SEE PAGE 5.
A 6 17
C R4181A, TERMINAL 6, PROVIDES 30
SECOND MFEP. REPLACEMENT
RM7840/RM7800 PROVIDES 15
4 7 18 18 E SECONDS ONLY.

D REMOVE AND DISCARD ANY JUMPERS


8 19 17 F BETWEEM Q477 OR Q514 SUBBASE
TERMINALS F TO 14 OR F TO 16.

E RM7840L/RM7800L ONLY – LOCATE LOW


7 9 20 B FIRE SWITCH CONNECTED TO Q477 OR
Q514 SUBBASE TERMINAL 1(L1) AND
CONNECT TO Q7800 SUBBASE TERMINAL 5.
10 21 5,6 C IF LOWFIRE SWITCH IS NOT USED,
CONNECT A JUMPER FROM TERMINAL 18
TO 5. NOTE: THIS JUMPER WILL EXTEND
PREPURGE TIME BY 30 SECONDS.
F D F 22 16 G
F RM7840L/RM7800L – CONNECT JUMPER
BETWEEN Q7800 SUBBASE TERMINALS 5
CONTROLLER AND 19. NOTE: THIS WILL EXTEND
L1 3 PREPURGE TIME BY 30 SECONDS.
LIMITS START RM7840E/RM7800E – CONNECT JUMPER
INTERLOCKS BETWEEN Q7800 SUBBASE TERMINALS 4
AND 19. NOTE: THIS JUMPER WILL
A LOCATE THIS JUNCTION 4 EXTEND PREPURGE TIME BY 30
AND CONNECT IT TO SECONDS.
Q7800 SUBBASE AIRFLOW
TERMINAL 6 SWITCH
G NOTE: R4181 TERMINAL 16 MAY HAVE
BEEN USED FOR THE FLAME DETECTOR.
B LOCATE THE START INTERLOCKS AT THIS POINT AND IF R4181 TERMINAL 16 IS NOT CONNECTED
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. TO R4181 TERMINAL F, CONNECT R4181
START INTERLOCKS NOW BECOME PREIGNITION TERMINAL 16 TO Q7800 TERMINAL 22.
INTERLOCKS. IF START INTERLOCKS ARE NOT USED,
M2521B
JUMPER Q7800 TERMINALS 4 TO 20.

41 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
RM7840E1016 OR RM7800E1010
R4181A1018, A1034
FROM________________________________ RM7840L1018 OR RM7800L1012
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 13 (OIL OR GAS)

10 IGNITION
TRANSFORMER
2 (L2) + 15 L2 13 12

8 L2
9 3 14 10

9 MAIN VALVE

1 (L1) + 3 4 15 11

8 5 16 C A. R4181A1018 ONLY - IF Q477 OR Q514


SUBBASE TERMINAL 5 WAS USED, 15
SECOND MFEP WAS PROVIDED, AND
TERMINAL 6 PROVIDED 30 SECOND
A 6 17 MFEP. REPLACEMENT RM7840/RM7800
PROVIDE ONLY 10 OR 15 SECOND MFEP
. SELECT 15 SECOND PER SPECIFICATION
65-0087 FOR 7840 OR 65-0088
4 7 18 18 F FOR RM7800.
B. R4181A1034 ONLY - IF Q477 OR Q514
SUBBASE TERMINAL 5 WAS USED, 10
SECOND MFEP WAS PROVIDED.
5 C 8 19 17 E TERMINAL 6 WAS USED FOR 15
SECONDS. SELECT PROPER
CONFIGURATION JUMPER PER
SPECIFICATION 65-0087 FOR
7 9 20 B RM7840 OR 65-0088 FOR RM7800.

D REMOVE AND DISCARD ANY JUMPERS


BETWEEN Q477 OR Q514 SUBBASE
10 21 6, 5 C TERMINAL F TO 14 OR F TO 16.

E RM7840L/RM7800L APPLICATIONS ONLY-


LOCATE Q477 OR Q514 SUBBASE
F D F 22 16 G TERMINAL (L1) SIDE OF THE HIGH FIRE
SWITCH AND CONNECT TO Q7800
SUBBASE TERMINAL 5. NOTE: IF HIGH
FIRESWITCH IS NOT USED, INSTALL A
1 2 3 4 5 7 8 15 16 18 JUMPER. PREPURGE TIMING IS EXTENDED
30 SECONDS.
GENERAL FOOTNOTES, SEE PAGE 5.
CONTROLLER F LOCATE LOW FIRE SWITCH WIRE
L1 3 CONNECTED TO Q477 OR Q514 SUBBASE
LIMITS TERMINAL 17 AND CONNECT TO Q7800
START
SUBBASE TERMINAL 5. IF LOWFIRE
INTERLOCKS SWITCH IS NOT USED, INSTALL A JUMPER.
A LOCATE THIS JUNCTION 4 NOTE: PREPURGE TIMING IS EXTENDED 30
AND CONNECT IT TO SECONDS.
Q7800 SUBBASE AIRFLOW
TERMINAL 6 SWITCH G NOTE: R4181 TERMINAL 16 MAY HAVE
BEEN USED FOR THE FLAME DETECTOR.
B LOCATE THE START INTERLOCKS AT THIS POINT AND IF R4181 TERMINAL 16 IS NOT CONNECTED
CONNECT IT TO Q7800 SUBBASE TERMINAL 20. TO R4181 TERMINAL F, CONNECT R4181
START INTERLOCKS NOW BECOME PREIGNITION TERMINAL 16 TO Q7800 TERMINAL 22.
INTERLOCKS. IF START INTERLOCKS ARE NOT USED, M2520B
JUMPER Q7800 TERMINALS 4 TO 20.

65-0100—2 42
7800 SERIES CONVERSION WIRING DIAGRAM
RM7840E1016 OR RM7800E1010
R4181A1042, A1059
FROM________________________________ TO RM7840L1018 OR RM7800L1012
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
G G 12 13 (OIL OR GAS)

10 IGNITION
TRANSFORMER
2, L2 L2 13
C

8 L2
9 3 14 10

9 MAIN VALVE

1, L1 4 15 11

8 5 16 1 2 3 4 5

7 8 15 16 18
3,4 B 6 17 GENERAL FOOTNOTES, SEE PAGE 5.

C A. TO USE EXISTING GROUNDED MODULATING


CIRCUIT, JUMPER Q7800 TERMINALS
15 7 18 18 E 13 AND G.
B. IF AN ISOLATED MODULATING CIRCUIT IS
DESIRED, IDENTIFY THE WIRE CONNECTED
BETWEEN THE MODULATING MOTOR
5 8 19 17 D TERMINAL R AND Q477 OR Q514 TERMINAL G.
DISCONNECT THE WIRE AND CONNECT TO
Q7800 SUBBASE TERMINAL 13.

7 9 20 B D RM7840E, RM7800E ONLY: LOCATE HIGH FIRE


SWITCH CONNECTED TO Q477 OR Q514
TERMINAL 8 AND CONNECT TO Q7800 SUBBASE
TERMINAL 4. IF HIGH FIRE SWITCH IS NOT USED,
12 A 10 21 6 A JUMPER IS REQUIRED BETWEEN Q7800
SUBBASE TERMINAL 4 AND 19. NOTE: THIS
ADDS 30 SECONDS TO THE PREPURGE
TIMING.
F F F 22 16
E LOCATE THE LOW FIRE SWITCH CONNECTION
ON Q477 OR Q514 SUBBASE TERMINAL 17 AND
CONNECT TO THE Q7800 SUBBASE TERMINAL 5.
A R4181 HAD 10 SECOND EARLY SPARK TERMINATION; NOTE: IF LOW FIRE SWITCH IS NOT USED,
REPLACEMENT RM7840/RM7800 HAS 5 SECONDS. JUMPER Q7800 SUBBASE TERMINAL 5 TO 18.
30 SECONDS WILL BE ADDED TO THE PREPURGE
B LOCATE PREIGNITION INTERLOCKS ON Q514 OR Q477 TIMING.
SUBBASE TERMINALS 3 AND 4. CONNECT ONE
LEADWIRE TO Q7800 SUBBASE TERMINAL 4 AND THE F REMOVE AND DISCARD JUMPER FROM Q477 OR
OTHER TO Q7800 SUBBASE TERMINAL 20. IF Q514 SUBBASE TERMINAL F TO 14 OR F TO 16.
PREIGNITION INTERLOCK IS NOT USED, JUMPER Q7800
M2519B
TERMINALS 4 TO 20.

43 65-0100—2
Section IV
Fireye C, D, and E Series

65-0100—2 44
7800 SERIES CONVERSION WIRING DIAGRAM
FIREYE 70D10, 26CF6 5022, 26CU6 5065 RM7840E1016 OR RM7800E1010
EP160/EP161/EP170
FROM________________________________ RM7840L1018 OR RM7800L1012
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12 X (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 10

8 L2
A 3 14 12

9 MAIN VALVE

L1 4 15 11

M&D B 5 16

3&13 A 6 17

P 7 18 C

5 8 19 8

A LOCATE PREIGNITION INTERLOCK


LEADWIRES AND CONNECT IT BETWEEN
7 9 20 A THE Q7800 SUBBASE TERMINALS 4 AND 20.

B FOR RM7840E/RM7800E ONLY - CONNECT


FIREYE TERMINAL D TO Q7800 SUBBASE
10 21 6 TERMINAL 4.

C LOCATE LOW FIRE SWITCH LEADWIRE OFF


FIREYE TERMINAL M AND CONNECT IT TO
S1 F 22 Q7800 SUBBASE TERMINAL 18.

M2549B
1 2 3 4 5 7 8 19
GENERAL FOOTNOTES, SEE PAGE 5.

45 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
For Replacement
FIREYE 24CJ5 5010/5011/3010/3011
25CU6 5062/5063/RS2E
26CF6 5020/5021/1010/1011
70D30
EP380/EP381/EP390
FROM________________________________ RM7840M1017 OR RM7800M1011
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12 (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13

21 1ST STAGE L2
FUEL VALVE
A 3 14
2ND STAGE
9
FUEL VALVE
L1 4 15 10 (OPTIONAL)

M 5 16

3 A 6 17

P 7 18 D

5 8 19

7 9 20 A A LOCATE JUNCTION OF CONTROLLER,


PREIGNITION INTERLOCK AND RUNNING
INTERLOCKS AND CONNECT TO Q7800
21 SUBBASE TERMINAL 6. LOCATE AND
X 10 6
IDENTIFY PREIGNITION INTERLOCK, AND
CONNECT ONE LEAD TO Q7800 SUBBASE
TERMINAL 4 AND THE OTHER LEAD TO
22 TERMINAL 20. IF NO PREIGNITION
S1 F
INTERLOCK IS USED, JUMPER Q7800
SUBBASE TERMINALS 4 TO 20.

1 2 3 4 5 7 8 19 M2551B

GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 46
7800 SERIES CONVERSION WIRING DIAGRAM
For Insurance Requirements
FIREYE 24CJ5 5010/5011/3010/3011
25CU6 5062/5063/RS2E
26CF6 5020/5021/1010/1011
70D30 RM7840E1016 OR RM7800E1010
FROM________________________________
EP380/EP381/EP390 TO RM7840L1018
______________________
OR RM7800L1012
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12
B (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 10

8 L2
A 3 14

9 MAIN VALVE

L1 B 4 15 B

M A 5 16

A TO MODERNIZE TO MEET INSURANCE


REQUIREMENTS, THE FOLLOWING
3 A 6 17 INTERLOCKS ARE NORMALLY REQUIRED:
LOCKOUT INTERLOCK, PREIGNITION
INTERLOCK, HIGH FIRE SWITCH AND LOW
FIRE SWITCH (CONNECT OR JUMPER
P A 7 18 D INTERLOCK TERMINALS ON Q7800 SUBBASE
AS SHOWN).
RM7840L/ RM7840E/
5 8 19 INTERLOCKS RM7800L RM7800E

LOCKOUT INTERLOCKS 6–7 6–7


PREIGNITION INTERLOCKS 4–20 4–20
7 9 20 A
HIGH FIRE INTERLOCK* 5–19 4–19
LOW FIRE INTERLOCK* 5–18 5–18

X 10 21 6 C * JUMPER ADDS ADDITIONAL 30 SECONDS


TO THE PREPURGE TIMING.

B JUMPER Q7800 SUBBASE TERMINALS 12


S1 F 22 AND 15 TO TERMINAL 4.

C FIREYE TERMINAL 6 PROVIDED


INTERMITTENT PILOT. RM7840L,E/
RM7800L,E PROVIDE 15 SECOND
1 2 3 4 5 7 8 19 INTERRUPTED PILOT. M2550B
GENERAL FOOTNOTES, SEE PAGE 5.

47 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
For Replacement
FIREYE 24CJ5 5015
25CU6 5066
26CF6 5023
70D20
EP260&EP261/EP270
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12 X (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 10

21 1ST STAGE L2
FUEL VALVE
A 3 14 12

9 2ND STAGE
FUEL VALVE
L1 A 4 15 11 (OPTIONAL)

M 5 16

13 A 6 17

P 7 18 D

5 8 19 B

A LOCATE PREIGNITION INTERLOCK,


7 9 20 A FIREYE SUBBASE TERMINAL 3 AND
CONNECT BETWEEN Q7800 SUBBASE
TERMINAL 4 AND 20.
10 21 6 B B TRMINAL 6 PROVIDED 30 SECONDS MFEP.
SELECT PROPER CONFIGURATION JUMPER
AND JUMPER Q7800 TERMINAL 5 TO 19 IF
TERMINAL 6 WAS USED.
S1 F 22

1 2 3 4 5 7 8 19 M2552B

GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 48
7800 SERIES CONVERSION WIRING DIAGRAM
For Insurance Requirements
FIREYE 24CJ5 5015
25CU5 5066
26CF6 5023
70D20 RM7840E1016 OR RM7800E1010
EP260/EP261/EP270
FROM________________________________ RM7840L1018 OR RM7800L1012
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12 X (OIL OR GAS)

10 IGNITION
TRANSFORMER
L2 L2 13 10

8 L2
A 3 14 12

9 MAIN VALVE

L1 4 15 11

M 5 16

3&16 A 6 17
A TO MODERNIZE TO MEET INSURANCE
REQUIREMENTS THE FOLLOWING
INTERLOCKS ARE NORMALLY REQUIRED:
P 7 18 D LOCKOUT INTERLOCK, PREIGNITION
INTERLOCK, HIGH FIRE SWITCH AND LOW
FIRE SWITCH (CONNECT OR JUMPER
INTERLOCK TERMINALS ON Q7800 SUBBASE
5 8 19 AS SHOWN).
A
RM7840L/ RM7840E/
INTERLOCKS RM7800L RM7800E
7 9 20 A LOCKOUT INTERLOCKS 6–7 6–7
PREIGNITION INTERLOCKS 4–20 4–20
10 21 6 B HIGH FIRE INTERLOCK* 5–19 4–19
LOW FIRE INTERLOCK* 5–18 5–18
* JUMPER ADDS ADDITIONAL 30 SECONDS
S1 F 22 TO THE PREPURGE TIMING.

B FIREYE TERMINAL 6 PROVIDES 30 SECOND


MFEP. REPLACEMENT CONTROL
PROVIDES ONLY 15 SECONDS.
1 2 3 4 5 7 8 19
M2553B
GENERAL FOOTNOTES, SEE PAGE 5.

49 65-0100—2
Section V
Fireye P Series

65-0100—2 50
7800 SERIES CONVERSION WIRING DIAGRAM
25CU6 - 1050
FROM________________________________ RM7840M1017
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
4 S2 G 12 (OIL OR GAS)
C
10 IGNITION
17 TRANSFORMER
L2 L2 13

21 1ST STAGE L2
17 FUEL VALVE
A 3 14
2ND STAGE
9
FUEL VALVE
L1 4 15 (OPTIONAL)

M 5 16

3 A 6 17

P 7 18

5 8 19
A IDENTIFY THE STARTING INTERLOCK
CONNECTION (USUALLY PROOF OF CLOSURE
7 9 20 D A SWITCH ON GAS VALVE) TO FIREYE
CONNECTION 3. MOVE TO Q7800 TERMINAL 4.

B USE UV FLAME DETECTION:


X 10 21 6 • R7847A1033 OR R7847B1031 WITH
C7012A,C DETECTOR.
OR
• R7849A1023 OR R7849B1021 WITH
S1 F 22 C7027 OR C7035 DETECTOR.
B
C CLIP CONFIGURATION JUMPER JR1
(4 SECONDS PFEP).

2 4 5 7 8 17 18 19 M7446

GENERAL FOOTNOTES, SEE PAGE 5.

51 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
For Replacement
FIREYE 26RJ8 1016, 1016T
26RJ8 1012, 1012T, 6012, 6016
FROM________________________________ RM7840G1014 OR RM7800G1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
15 G 12 B (OIL OR GAS)

10 IGNITION
JUMPER TRANSFORMER
2 L2 13 R

21 1ST STAGE L2
FUEL VALVE
9 3 14 W
2ND STAGE
9
FUEL VALVE
B 4 4 15 10 (OPTIONAL)

A 8 5 16

3&11 6 17

12 7 18 A

5 8 19

7 9 20 B A CONNECT LOW FIRE INTERLOCK BETWEEN


Q7800 SUBBASE TERMINAL 5 AND 18. IF NO
LOW FIRE INTERLOCK, ADD JUMPER. NOTE:
21 JUMPER ADDS 30 SECONDS TO THE
10
PREPURGE TIMING.

B CONNECT PREIGNITION INTERLOCK


22 BETWEEN Q7800 SUBBASE TERMINALS 4 AND
13&14 F
20. IF PREIGNITION INTERLOCK, ADD A
JUMPER.

1 2 3 4 5 7 8 19 M2554B

GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 52
7800 SERIES CONVERSION WIRING DIAGRAM
FIREYE 26RJ8 1016, 1016T RM7840E1016 OR RM7800E1010
26RJ8 1012, 1012T, 6012, 6016
FROM________________________________ TO RM7840L1018
______________________
OR RM7800L1012
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
15 G 12 B (OIL OR GAS)

10 IGNITION
TRANSFORMER
2 L2 13 R

8 L2
9 3 14 W

9 MAIN VALVE

B 4 4 15 10

A 8 5 16

3&11 6 17
A CONNECT LOW FIRE INTERLOCK BETWEEN
Q7800 SUBBASE TERMINAL 5 AND 18. IF NO
7 18 LOW FIRE INTERLOCK, ADD JUMPER.
12 A NOTE: JUMPER ADDS 30 SECONDS TO THE
PREPURGE TIMING.

8 19 B CONNECT PREIGNITION INTERLOCK


5 C BETWEEN Q7800 SUBBASE TERMINALS
4 AND 20. IF NO PREIGNITION INTERLOCK,
ADD A JUMPER.
7 9 20 B C RM7840L/RM7800L CONNECT HIGH FIRE
SWITCH BETWEEN Q7800 SUBBASE
TERMINAL 5 TO 19.
10 21 RM7840E/RM7800E CONNECT HIGH FIRE
SWITCH BETWEEN Q7800 SUBBASE
TERMINAL 4 TO 19.
IF HIGH FIRE SWITCH IS NOT USED,
F 22 CONNECT A JUMPER BETWEEN THE
13&14
TERMINALS NOTED. NOTE: JUMPER ADDS
30 SECONDS TO THE PREPURGE TIMING.

M2555B
1 2 3 4 5 7 8 19
GENERAL FOOTNOTES, SEE PAGE 5.

53 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
RM7840E1016 OR RM7800E1010
FIREYE 25RU8 4580
FROM________________________________ TO RM7840L1018
______________________
OR RM7800L1012
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
15 G 12 10 (OIL OR GAS)

10 IGNITION
TRANSFORMER
2 L2 13 1

8 L2
9 3 14

9 MAIN VALVE

4 4 15 11

8 D 5 16

3&F, V A 6 17

R 7 18 B C
A LOCATE FUEL VALVE CLOSED INTERLOCK ON
FIREYE TERMINALS 3 AND FV. CONNECT TO
Q7800 SUBBASE TERMINALS 4 AND 20.
8 19 W C INSTALL JUMPER BETWEEN Q7800 TERMINAL
5
4 AND TERMINAL 20 IF VALVE CLOSED
INTERLOCK IS NOT USED.

7 9 20 B WIRE REPLACEMENT DETECTOR AS


A
SPECIFIED IN DETECTOR SPECIFICATIONS.

C LOCATE LOW FIRE IGNITION INTERLOCK


10 21 6 CONNECTION TO FIREYE W TERMINAL AND
CONNECT TO Q7800 SUBBASE TERMINAL 5.

D RM7840E/RM7800E ONLY – LOCATE PURGE


F 22 B AIRFLOW INTERLOCK CONNECTION ON
B FIREYE TERMINAL 8 AND CONNECT TO Q7800
SUBBASE TERMINAL 4.

M2556B
1 2 3 4 5 7 8 19
GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 54
7800 SERIES CONVERSION WIRING DIAGRAM
FIREYE 25RU8 6560, 6570, 6580 RM7840E1016 OR RM7800E1010
26RJ8 6060, 6070, 6080(D), 6160
FROM________________________________ TO RM7840L1018
______________________
OR RM7800L1012
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
15 G 12 13
10 IGNITION
TRANSFORMER
2 L2 13 10
8 L2

9 3 14 12
9 MAIN VALVE

4 A 4 15 11

8 D 5 16 A LOCATE FUEL VALVE CLOSED INTERLOCK,


IF USED ON FIREYE TERMINALS 3 AND FV.
CONNECT TO Q7800 SUBBASE TERMINALS
4 AND 20. INSTALL JUMPER BETWEEN
3&FV A 6 17 Q7800 TERMINAL 4 AND TERMINAL 20 IF
INTERLOCK NOT USED.

B REPLACEMENT RM7840/RM7800 PROVIDE 15


R 7 18 B C SECOND MFEP. FIREYE CONTROL PROVIDED
15, 30, OR 40 SECONDS.

C LOCATE LOW FIRE SWITCH OR IGNITION


5 8 19 W C INTERLOCK, IF USED CONNECTION TO FIREYE
E
TERMINAL W AND CONNECT TO Q7800
SUBBASE TERMINAL 5. IF LOW FIRE SWITCH
OR IGNITION INTERLOCK NOT USED, JUMPER
7 9 20 A Q7800 SUBBASE TERMINALS 5 AND 18.
NOTE: JUMPER ADDS 30 SECONDS TO
PURGE TIME.

1 10 21 6 B D RM7840E/RM7800E ONLY – LOCATE HIGH FIRE


SWITCH CONNECTION ON FIREYE SUBBASE
TERMINAL 8 AND CONNECT TO Q7800
SUBBASE TERMINAL 4.
14 F 22
E IF THERE IS NO CONNECTION ON FIREYE
SUBBASE TERMINAL W, INSTALL A JUMPER
BETWEEN Q7800 SUBBASE TERMINAL 5
1 2 3 4 5 7 8 19 AND TERMINAL19. NOTE: INSTALLING THE
JUMPER ADDS 30 SECONDS TO THE
GENERAL FOOTNOTES, SEE PAGE 5. PURGE TIME. M2557B

55 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
FIREYE 29RF5 1001, 1009, 6009
FROM_______________________ RM7840G1014 OR RM7800G1018
TO _______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


(OIL OR GAS)
15 G 12
10 IGNITION
TRANSFORMER
2 L2 13
21 1ST STAGE
L2
FUEL VALVE

10 3 14
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
C 4 4 15 9 E

1 2 3 4 5
8 5 16
7 8 9 18 19

GENERAL FOOTNOTES, SEE PAGE 5.


B 6 17

A WIRE NUT FIREYE TERMINAL 3 AND W


9 TOGETHER. NOTE: CHECK ELECTRICAL
R 7 18 RATINGS OF THE CONTROLLER, START
INTERLOCKS AND AIRFLOW SWITCH. THEY
MUST BE RATED 120 VAC AND THE
CONTROLLER ALSO MUST BE CAPABLE OF
5 8 19 HANDLING LOADS OF FIREYE TERMINALS
5,6,7 AND 9.

B CONNECT THIS JUNCTION TO Q7800


E 7 9 20 C B SUBBASE TERMINAL 6.

C IDENTIFY AND REMOVE START INTERLOCK


CONNECTION AT THIS POINT AND CONNECT
10 21 6 D TO Q7800 SUBBASE TERMINAL 4. START
INTERLOCK NOW BECOMES A PREIGNITION
INTERLOCK. JUMPER Q7800 SUBBASE
TERMINAL 4 TO 20 IF START INTERLOCK IS
14 F 22 NOT USED.

D IF TERMINAL 6 WAS USED, CONFIGURE


R7840/RM7800 FOR INTERMITTENT PILOT.
LIMITS CONTROLLER
4 3 W B E IF APPLICATION HAS A SECOND STAGE
BURNER A FUEL VALVE, INSTALL A JUMPER BETWEEN
START
SWITCH Q7800 TERMINALS 9 AND 13. CONNECT
INTERLOCKS
THE SECOND STAGE FUEL VALVE, FIREYE
B C SUBBASE TERMINAL 9 TO Q7800
R
TERMINAL 15.
AIRFLOW M2558B
SWITCH

65-0100—2 56
7800 SERIES CONVERSION WIRING DIAGRAM
FIREYE 26RJ8 6058, 6066, 6068
FROM________________________________
25RU8 6558, 6566 TO RM7840G1014 OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


G 12 13 (OIL OR GAS)
15
10 IGNITION
TRANSFORMER
2 L2 13 10
21 1ST STAGE
L2
FUEL VALVE

9 3 14 12
2ND STAGE
9
FUEL VALVE
(OPTIONAL)
A 4 4 15 11

8 5 16

3&W A 6 17

9
R 7 18

B 5 8 19 13
A LOCATE LOW FIRE START INTERLOCK
CONNECTION ON FIREYE TERMINAL W.
DISCONNECT AND RECONNECT TO Q7800
7 9 20 A B SUBBASE TERMINAL 4. START INTERLOCK
NOW BECOMES A PREIGNITION INTERLOCK.
IF NO START INTERLOCK, CONNECT JUMPER
1 10 21 6 B BETWEEN Q7800 SUBBASE TERMINALS 4
AND 20.

B FIREYE 26RJ8 6058 MFEP TIMINGS ARE 15


14 F 22 AND 55 SECONDS. RM7800G AND RM7840G
MFEP TIMINGS ARE 10,15 OR 30 SECONDS
AND INTERMITTENT PILOT.

1 2 3 4 5 7 8 9 13 19 M2560B

GENERAL FOOTNOTES, SEE PAGE 5.

57 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
FIREYE 26RJ8 1002, 1003, 1008, 1011, 1018, 6008, 6018
29RF5 1000, 1002, 1005, 1015, 1104
FROM________________________________
29RF5 6015 TO RM7840G1014 OR RM7800G1018
______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800 FOR DIRECT SPARK IGNITION


13 (OIL OR GAS)
15 G 12

10 IGNITION
TRANSFORMER
2 L2 13 10
21 1ST STAGE L2
FUEL VALVE

9 3 14 12
9 2ND STAGE
FUEL VALVE
(OPTIONAL)
C 4 4 15 11

5 1 2 3 4
8 16
5 7 8 9 19
GENERAL FOOTNOTES, SEE PAGE 5.
B 6 17

9
R 7 18
A WIRE NUT FIREYE TERMINAL 3 AND W
TOGETHER. NOTE: CHECK ELECTRICAL
RATINGS OF THE CONTROLLER, START
8 19 INTERLOCKS AND AIRFLOW SWITCH. THEY
MUST BE RATED 120 VAC AND THE
CONTROLLER ALSO MUST BE CAPABLE OF
HANDLING LOADS OF FIREYE TERMINALS 5,6
7 9 20 AND 7.
C B
B IDENTIFY THIS JUNCTION AND CONNECT TO
Q7800 SUBBASE TERMINAL 6.
10 21 5&6 D
C IDENTIFY AND REMOVE START INTERLOCK
CONNECTION AT THIS POINT AND CONNECT
TO Q7800 SUBBASE TERMINAL 4. START
14 22 INTERLOCK NOW BECOMES A PREIGNITION
F
INTERLOCK. JUMPER Q7800 SUBBASE
TERMINAL 4 TO 20 IF START INTERLOCK IS
NOT USED.

LIMITS CONTROLLER D FIREYE TERMINAL 5 PROVIDED 15 SECOND


4 3 W B MFEP. TERMINAL 6 PROVIDED 30 SECOND
BURNER A START MFEP. SELECT PROPER CONFIGURATION
SWITCH INTERLOCKS JUMPER FOR 15 SECONDS OR ADD JUMPER
FROM Q7800 SUBBASE TERMINAL 5 TO 19
B C FOR 30 SECOND MFEP TIMING.
R
AIRFLOW M2559B
SWITCH

65-0100—2 58
Section VI
Eclipse

59 65-0100—2
7800 SERIES CONVERSION WIRING DIAGRAM
Lockout Modulation
ECLIPSE 5602
FROM________________________________ RM7800L1012 OR RM7840L1018
TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)

Q7800
FOR DIRECT SPARK IGNITION
S2 G 12 13 (OIL OR GAS)

10 IGNITION
TRANSFORMER
2 L2 13 10

8 L2
A 3 14 12

9 MAIN VALVE
1,D A 4 15 11

8 5 16

7 6 17

A 5602 HAS PROOF OF CLOSURE AND HIGH


A 6 7 18 B PURGE DAMPER SWITCH LOCATED BETWEEN
6 AND D. LOCATE PROOF OF CLOSURE SWITCH
AND CONNECT BETWEEN Q7800 TERMINALS
4 AND 20. LOCATE HIGH PURGE DAMPER
B 3 8 19 A SWITCH AND CONNECT BETWEEN Q7800
TERMINALS 4 AND 19.

5 9 20 A B 5602 HAS LOW FIRE PROVING IN SERIES WITH


THE PILOT VALVE. LOCATE PILOT VALVE
CONNECTION AND CONNECT TO Q7800
TERMINAL 8. LOCATE WIRE TO LOW FIRE
4 10 21
PROVING SWITCH AND CONNECT SWITCH
BETWEEN Q7800 TERMINALS 5 AND 18. 5602
HAD PURGE TIME, INTERMITTENT/INTERRUPTED
S1 F 22 PILOT, AND RECYCLE/NONRECYCLE SELECTIONS
MADE BY A DIP SWITCH LOCATED ON THE
REAR PLATE OF THE CONTROL UNIT. THE
REPLACEMENT RM7800L/RM7840L IS A
1 2 3 4 LOCKOUT DEVICE WITH INTERRUPTED PILOT.
SELECT ST7800 TO MATCH 5602 TIMING.
5 7 8 18 19
M7448
GENERAL FOOTNOTES, SEE PAGE 5.

65-0100—2 Printed 60
in U.S.A.