Professional Documents
Culture Documents
354
Publicalion
EPUV- / f r r |/ t :
354
Publication
Premidre - Firstedition
6dition
1 9 72
pourlransformateurs
decharge
Guide immergfs fhuile
dans
1
l
I
t
a'
t7'
I
I Loading tianslormers
guideforoil-immersed
t,
l .
t ,
l
l
t
I
I
I
7
l/ i \
I'
rdservds
dereproduction
Droits - all rightsreserved
- Copyright
Bureau delaCommission
Central lnternationale
Electrotechnique
1, ruedeVaremb6
Suisse
Gendve,
{r
t\ + -"- - ''"/i
L\.*
C.D.U./U.D.G. : 621.314.212.016.3
I N T E R N A T I t l NE AL LE C T N ( } T E C H NCI C
( )AMLM I S S I ( l N
(affiliated
to the lnternational
0rganization - lS0)
for Standardization
IEC REC()MMENIlATI(lN
Publication
354
r ed i t i o-n F i r s e
Premid6 t dition
1 9 72
EPLIY- iTA
Guide pourtransformaleurs
decharge immergfs
dans
I'huile
guidefor oil-immersed
Loading transformers
.%-
{ ' i ,t t P { , : i T 1 ftiy, 1
irrltr(Atrtr4rsAlrs !ft t_i$rBrh,
iYjiyr r.r
I J ']77
Bureau
Central
delaCommission
Electrotechnique
lnternationale
1 , r u ed e V a r e m b 6
Geneve,
Suisse
?,6s.-
Biil,'r
- 3 -
CONTENTS
Page
ForrrvoRo 5
Pr.rracr . 5
Clause
1. Scope 7
2 . O bjec t 7
3. Limitations adopted in the guide 9
-1. Sy'mbols used in the tables . 9
5. Basesof guide 11
6. Selection of appropriate table, with examples 15
FOREWORD
l) The formal decisions or agreements of the IEC on technical matters, prepared by Technical Committees on which all the
National Committees having a special interest therein are represented, express, as nearly as possible, an international
c o n s e n s l l so f o p i n i o n o n t h e s u b j e c t s d e a l t w i t h .
2) They have the form of recommendations for international use and they are accepted by the National Committees in that
sense.
3) ln order to promote this international unification, the IEC expressesthe wish that all National Committees having as
yet no national rules, when preparing such rules, should use the I E C recommendations as the fundamental basis for these
rules in so far as national conditions will permit.
4) The desirability is recognized of extending international agreement on these matters through an endeavour to harmonize
national standardization rules with these recommendations in so far as national conditions will permit. The National
Committees pledge their influence towards that end.
PREFACE
This Recommendationhas been preparedby IEC TechnicalCommittee No. 14, Power Transformers.
A draft was discussedat the meeting held in Zagreb 1n 1967.As a resr-rltof this meeting a final draft
of tlie main part of the publication and Appendix A was submitted to the National Committees for
approval under the Six Months' Rule in April 1969.A final draft of Appendix B was submitted to the
National Committeesfor approval under the Six Months'Rule in January 1970.
The following countriesvoted explicitly in favour of publication :
Australia Netherlands
Austria Norway
Belgium Poland
Czechoslovakia Romania *
Denmark South Africa
Finland Sweden
France Switzerland
Germany Turkey
Hungary Union of Soviet
lran t"t Socialist Republics x
Israel United Kingdom
Italy United States of America
Japan * Yugoslavia
* Voted in favour of the main part of the publication and Appendix A only.
** Voted in favour of Appendix B only.
-.-- 7 -"
t. Scope
This guide is applicable to oil-immersedtransformers complying with IEC Publication 76 (second
edition - 1967),Power Transformers, and operated within the limitations referred to in Clause 3.
For very large transformers, e.g. 100 MVA and above, the advice of the manufacturer should
be followed.
IEC Publication 76 does not take into consideration either temperaturesdifferent from normal or
variations in the load (which only exceptionally correspond to uninterrupted continuous operation
at rated power).
This guide indicates how oil-immersed transformers may be operated in different conditions of
ambient temperatureand service,without exceedingthe acceptablelimit of deterioration of insulation
through thermal effects.
For transformerswith forced oil circulation, the guide is rather conservativeand the loads indicated
may probably be exceeded, but again the manufacturer should be consulted.
2 . Object
The object of this guide is to give the permissible loading, under certain defined conditions, in
terms of the IEC rated power of the transformer, for the guidance of users and to help planners
in choosing the rated power required for new installations.
The rated power defined in IEC Publication 76 is a conventional referencebasis for uninterrupted
continuous operation (with definedlimits of cooling-medium temperature)with a normal expectation
of life.
oC, but deviations from this are provided for,
Basically, the cooling-medium temperature is 20
in such a way that the increased use of life when operating with a cooling-medium temperature
above 20 "C (as in summer) is balanced by the reduced use of life when it is below 20'C in winter.
Experienceindicates that normal life is some tens of years. It cannot be stated more precisely,
becauseit may vary even between identical units, owing in particular to operating factors which
may differ from one transformer to another.
In practice, uninterrupted continuous operation at full rated power is unusual, and this guide
gives recommendations for cyclic daily loads, taking into account seasonalvariations of ambient
o'normal"
temperature. The daily use of life due to thermal effectsis indicated by comparison with the
use of life corresponding to operation at rated power in an ambient temperature of 20"C.
Tables I to X, pages 18 to 27, show the permissible load, for a normal daily use of life, in the
following two sets of conditions :
a) continuous duty, with different cooling-medium temperatures ;
b) cyclic duty, with different cooling-medium temperatures.
In addition, Appendix B gives guidance in the following case, in which allowance is made for a
more rapid use of life than normal:
c) emergencyloading, as may be required when one transformer of a group is temporarily out of
service or when an exceptional load has to be carried.
--9
The general method described in Appendix A is also applicable to duties with any sort of load
diagram as a function of time.
Notes 1. - This guide is restricted to thermal considerations. Other considerations, notably economic (capitalisation
of losses, etc.), may determine the choice of rated power.
2. - Attention is drawn to the fact that a transformer that has been operating at load powers greater ihan the
rated power may not comply with the thermal requirements on short-circuit specified in IEC Publication 76
(1967).
ln preparing this guide, the following limitations on the operation of the transformer have been
assumed:
a) For normal cyclic duty (seeClause2b) ), the current does not exceed1.5 times rated value.
Note. - If currents up to this limit, andfor the durations permitted by this guide, are to be carried with safety, it is
necessary for the terminal outlets, the tap-change device and similar attachments also to be suitable for the
duty. Because IEC Publication 76 does not deflne the loading possibility of these fittings, their suitability
should be determined by reference to the manufacturer and, if they are found not to be suitable, lower limits
of loading and duration will need to be accepted. The user should ascertain the thermal capability of associated
equipment, e.g. cables, circuit-breakers and current transformers.
c) For emergencyduty, currents in excessof 1.5 times rated value and load cycles which give
greater than normal rate of insulation deterioration are permissible, provided that the hot-spot
'C is not exceeded,that the fittings and associatedequiprnent are capable
. temperature of 140
of carrying the overload, and that the oil temperature does not exceed l15'C. Currents in
excessof 1.5 times rated value in load cycleswhich produce a rale of insulation deterioration not
greater than normal are included, in italics, in Tables I to X, pages 18 to 27.
Notes 1. - Appendix B indicates the daily use of life for various load diagrams which do not result in a hot-spot
temperature exceeding 140'C. Life usage related to load diagrams is considered in Appendix A, Sub-
c l a u s e ? . 3.
2. - T h e limit of ll5'C for the oil temperature has been set bearing in mind that the oil may overflow at oil
temperatures above normal. Depending on the provision made for oil expansion on a particular transformer,
the oil may overflow at temperatures lower than 115'C.
5 . Bases of guide
The bases for establishing the tablesin this guide are as follows:
a) Thermal deterioration of the insulation (detailed in Appendix A, Clause 2)
In a temperaturezone extendingup to 140 "C, the rate at which transformer insulation deteriorates
increasesexponentially with temperature; it doubles for every temperature increaseof 6 deg C.
€ ;
O O
L
( o ( D
a ( o
;
L
o)
o-
E (winding
c)
F
0 n ( t o po i l )
0a (ambient)
Tables VI to X, pages23 to 27, (each for a specificvalue of 9") are for OFAF and OFWF cooling.
For transformers rated for both ONAN and ONAF cooling, use Tables I to V in terms of the
rated power for ONAN cooling if the fans are not brought into operation and in terms of the rated
power for ONAF cooling if the fans are brought into operation.
For transformers rated for both ONAN and OFAF cooling, use Tables I to V if the oil pumps
are not brought into operation, but Tables VI to X in terms of the rated power for OFAF cooling
if the oil pumps and fans are brought into operation.
The fans and oil pumps are normally put into service by a temperature sensitive device (thermal
image corresponding to winding hot-spot temperature or thermometer corresponding to top oil
temperature). It is recommended that pumps and fans (where their use is not restricted by other
considerationssuch as noise) are put into service before the high loading occurs, in order to have
the winding hot-spot temperature low enough to slow down the ageing process. The power taken
by these auxiliaries is at least partially compensatedfor by the decreasein load loss resulting from
a lower temperature.
Example I : 1000 kVA ONAN transformer, initial load power 500 kVA. Required to find permis-
sible load power for 2 h at an ambient temperature of 20'C.
Example 2 ; With 0u : 20'C, an ONAN transformer is required for I 400 kVA for 6 h and 800 kVA
for the remainins 18 h each dav:
-1 400
: ,s, :
1,75
800 sl
K2
From the curve of Table III, on the t : 6 line, the values of Kz and Kl giving 1.75 are
Kr
Kz:1.18 and Kt :0.68. ( S e eF i g u r e 2 . ) T h e r e f o r et h e r a t e d p o w e r i s :
s:r:|-.1|f,:#0,-rr8okvA
1 7 -
Lineof
ft:,.ru
TlsrBnu I Tlprn I
Transformateurs OIr{AN et ONAF : 0o : g "g ONAN and ONAF transfortners: 0o : g og
Valeurs de K2 pour des valeurs donndescle K1 et t Values of K, for given values of K, and t
Note. - En service cyclique normal, la valeur de K2 ne Note. -- In normal cyclic duty the value of K2 should not
doit pas Otre sup6rieure d 1,5. Les valeurs d,e K2 be greater than 1.5. The values of K2 greater
sup6rieures e 1,5, imprimdes en italique, s'ilp_ than 1.5, printed in italics, apply to emergency
pliquent aux services de secours. (Voir article 3.) duties. (See Clause 3.)
Le signe f indique que K2 est supdrieur d 2,0. The * sign indicates that K2 is higher than 2.0.
l
,
I.l
K2
2 .0
t \ : 0.5
1.8 z --r-
\
\
\r\
\,\
4 i\
1.4 6
8
t\
12
24
--+
l
0.6 1.2 K1
- 1 9-
T,q.nr,BA,u
II TnsrB II
TransformateursOI{AN et ONAF : 0o : I0'C OI,{AI{ and OI{AF transformers r 0a : l0 "C
I'uleurs de Kz pour des valeurs donndesde Kt et t Volues of Kt for given values of Kt and t
\',71s.- En service cyclique normal, la valeur de K2 ne Note, - In normal cyclic duty the value of K2 should not
doit pas €tre supdrieure 2r 1,5. Les valeurs de K2 be greater than 1.5. The values of K2 greater
sup6rieures a 1,5, imprim6es en italique, s'&p- than 1.5, printed in italics, apply to emergency
pliquent aux services de secours. (Voir article 3.) duties. (See Clause 3.)
'
Le signe f indique que K2 est supdrieur d 2,0. The * sign indicates that K2 is higher than 2.0
K2
2.0
-20-
Kz
2.0
I
t\
t:0.1
L
1 I \
\
1.6 \
2 \
\
1,2
12
1.0
24
1.2 Kt
-21 -
Tlsr,rA.u IV Tasrn IV
Kr : 0.80
Kz
2 .0
t:0.5
--''j
1.8
1
1.4 \ \
\\
4
\ \
6
\
6
12
1.0
24 \
'-T-..
0.4 1 . 2K t
-22_
TAsrBA.u V Tmr,B V
TransformateursONAI{ et ONAF.. 0o : 40"C OI{AI{ and OIr'lAF transformers.. 0o : 40 "C
Valeurs de Kz pour des valeurs donn1esde K1 et t Values of K, for given values of K, and t
Note. - En service cyclique normal, la valeur de K2 ne Note. - In normal cyclic duty the value of K2 should not
doit pas €tre sup6rieure d 1,5. Les valeurs de K2 be greater than 1.5. The values of K2 greater
supdrieures ir 1,5, imprim6es en italique, S'ilp- than l 5, printed in italics, apply to emergency
pliquent aux services de secours. (Voir article 3.) duties. (See Clause 3.)
Kz
2.0
' ,,2
Kr
-23-
Tanrnlu VI Tmr-p VI
-- 0'C
TransformateursOFAF et OFWF : 0o : 6 "g OFAF and OFWF transfornters: 0a
Valeurs de Kz pour des valeurs donndesde K1 et t Values of K, for given values of Kt and t
Note. - En service cyclique normal, la valeur de K2 ne Note. - In normal cyclic duty the ralue of K2 should not
doit pas 6tre supdrieure ir 1,5. Les valeurs de K2 be greater than 1.5. The values of K2 greater
sup6rieures a 1,5, imprimdes en italique, s'aP- than 1.5, printed in italics, apply to emergency
pliquent aux services de secours. (Voir article 3') duties. (See Clause 3.)
Kz
2.0
-24-
K2
2.0
- f : 0 ,5 _
1.4 2 \
J
il
4
6
1.2 8
12
24
= N
-\N
1.0
0,2 1.0 1 , 2K 1
-25-
Kr:0.90 | Kt:1.00
K2
1.8
f:0.1
1.2 -4 \\
6
8 \\
12
24 S
Tanlrnu X Tanre X
TransformateursOFAF et OFWF : 0o : 40 "C OFAF and OFWF transformers : 0o -- 40 "C
Valeursde Kz pour desvaleursdonndes
de Kt et t Values of Kt for given values of Kt and t
Kz
1.4
1+
1
1.2
2
\
4
\
1.0 o
8
0.8
12
24
\
$
0,6
0.2 0.4 0.6 0.8 1.0 1 . 2K r
-29-
APPENDIX A
Symbols used
Examples
"f) The hot-spot temperature rise is higher than the averagetemperature rise of the top coil. To
take account of the difference between these two temperature rises, a value of 0.1 Ag*o is
assumed for natural oil circulation. (Forced oil circulation is considered in Appendix A,
Sub-clause1.2.2.) Thus, the temperaturerise of the hot spot is equal to the top oil temperature
rise plus 1.1 A0*o.
, Hotspot
Top of winding Top oil J
\
Au.rug.top coil
Averagewinding
Averageoil (65deg C at rated power)
I
Bottom of winding Bottom oil I
T e m p e r a t u r rei s e
Hot-spot temperature rise - top oil temperature rise plus I .1 A0*o" : 55 + 23 : 78 deg C
-
No'|e
*-$;',:'ffJ,TJ"fi3ff:"l"#:::,il::n":ll,:T,:H:'rTitffl,':ff::'fi'J.::,'"t,
in the assumed values only slightly influence the permissible loading given in the tables. Greater accuracy
is not required, because there is in practice inevitable inaccuracy in the estimation of the ambient tempera-
ture and from the variability of the load (current and voltage), etc.
Also, in general, higher working current densities are used than with natural oil circulation
and it is generally more economic to have a lower averageoil temperaturerise and a higher value
for A0*o.. Therefore, for the guide, a top oil temperaturerise of 40 deg C and a hot-spot tempera-
ture rise of 78 deg C at rated power have been assumed, as the most severecondition.
aob:
^0,,(+#).
For this guide :
d is assumed equal to 5 ;
x is assumedequal to 0.9 for ONAN and ONAF *
1 .0 fo r OFA F and OFW F ;
A96" is assumedequal to 55 deg C for ON, and 40 deg C for OF, as given in Appendix A,
S u b -c l a u s e1 .2 .
The value of dis relatively unimportantat high loading, giving only marginally higher or lower
oil temperature rises in practice. Moreover this is compensatedfor to some extent by the cor-
respondingly lower or higher oil temperature rises at low loads.
* This value of 0.9 has been taken instead of the values of 0.8 (for ONAN) and 1.0 (for ONAF) specified in Sub-clause 41.7.l
of IEC Publication 76 (1967), because it allows a single set of tables to be used for both kinds of cooling, with errors
only of the order of t2o/o.
35 --
p is a constant
0 is the temperature, in Celsius degrees.
Various investigators have not always agreed on the length of life at any given temperature.
They do agree reasonably well, however, that over the range 80 "C to 140 "C the rate of using
life in transformers is doubled for every temperature increaseof approximately 6 deg C, and this
value is used as the basis value for the suide.
-31 -
Relative rate
of using life
80 o.t25
86 0.25
92 0.5
98 1.0
104 2.O
110 4.0
l16 8.0
122 16.0
t28 32.0
r34 64.0
140 128.0
E.xample; 10 h at 104 'C and 14 h at 86 "C would use (10x2) plus (14X0.25) :23.5 h life in 24 h operation.
From formula 2 :
0" : 98 + 19.93logtoV (3)
-39__
2 4 t 9 8
16 | 101.s
t2 | r04
8 | 107.5
6 | 110
4 | 113.5
3 | 116
2 | 119.5
1.5 | r22
I .0 | 125.5
o , 7s | 128
0.5 I 131.5
Consider operation at constant load with a varying ambient temperature 0ufor a given period r.
The weighted ambient temperature 0'u during that period is given by the formula:
t
| ,'
20'"16:L l20^16dt
rJ
o
if the time / is divided into N equal intervals, the preceding formula becomes:
N
I
2 o'"16: : - ! l r"/u
1/ I
-41 -
2otog,o t lsr',,01
-'" t* 4J
L./V J
For a transformer operating on constant load throughout the year, a weighted ambient tempera-
ture can be fixed once and for all in a given climate. This must be suchthat the fastersummerdeterio-
ration is exactly balanced by the slower winter deterioration. In a temperate climate, it is found
that the annual weighted mean is generally 5 deg C higher than the arithmetic mean.
:20
Annual weightedambienttemperature logr^
o [,t"
l t 2i + lgu,nof
"
l
0u : 30 'C for
2 months
20 'C for 4 months
average 15 "C
'C for 4
10 months weighted average 19.8 'C
0 "C for 2 months
-42-
o 0 )
> =
O ( ' ,
I
e c
c ' 6
. 9 f
! o
C i \
E * 100
o i :
a n ,
= >
O E
-o.:
a E5
c)
.z
(g
c)
L
0)
a
a
q)
.=
T e m p 6 r a t u r e9 c d e p o i n t c h a u d
Hot spot temperature0s
Frc. 4. - Droite de
Life line.
--45-
APPENDIX B
EMERGENCY DUTY
l. Object
Tables I to X of the loading guide correspond to duties which result in the same use of life in one
oC, i.e. at rated power and at an ambient temperatureof 20 'C.
day as in a day's operation at 98
The daily use of life for these "normal" duties will be called a "normal day"
In this Appendix, as for normal duties, two kinds of transformer and five values of ambient tem-
peratureare considered.
Clauses3a) and3c) of the loading guide draw attention to limitations to the permissibleloading
u,hich may be imposed by fittings and associatedequipment.
2.1 General
As for normal duties, a daily load diagram consistingof rh at a load powerof Kr.S"and (24-t)h
at a load power of Kl,S'"has been considered.
2.2 Valuesof t
T h e v a l u e s or fa r e t h e e i g h t v a l u e s a l r e a d y u s e d f o r n o r m a l d u t i e s , i . e . 0 . 5 h ; 1 h ; 2 h ; 4 h ; 6 h ;
8 h : 1 2 h a n d2 4 h .
a ) Minimum value
There is no need to include in the table values which always lead to a daily use of life much less
'onormalday", even in an ambient temperatureof 40 'C.
than unity, i.e. lessthan a
However, Tables V and X (for normal duties) show that a use of life of unity is reachedfor an
ambient temperature of 40 "C on continuous duty (r : 24) :
- for natural oil circulation, at a load power of 0.825. ;
- for forced oil circulation, at a load power of 0.845".
Any lower load must result in use of life lessthan unity, whatever the value of r.
This has led to the adoption of 0.7 as the lower limit of Kz to appear in the tables.
b) Maximum value
For a given type of transformer, an overriding limit for the value of Kz is fixed by the fact that,
even for the lowest ambient temperature (0'C) and starting from the coldest condition
(Kt -- 0.25i),a hot-spot temperature of 140 "C must not be exceeded.
With forced oil circulation the value of Kz is thus limited to 1.7 for the shortest overloads and to
values between 1.3 and 1.6 for other durations of overload. With natural oil circulation the
limiting value rangesfrom 1.4 for t :24 to greater than 2 for t: 0.5 and 1, but it has been
decided not to take into considerationvalues of Kz greater than 2.
3.1 Introduction
It would be possible to have one table for each of the five values of ambient temperature, as for
normal duties, but the number of tables would be inconveniently large.
The total number of caseswould be about 15 times greater than for normal duties, becauseabout
ten values of Kz would have to be consideredfor each given value of r and K1, instead of one, and
becausethe number of values of Kl is greater than for normal duties.
In practice, it is not necessaryto have a series of tables for each of the five values of ambient
temperatureand the arrangementadopted has reducedthe number of tables to about a fifth of what
would otherwisehave been required.
With the aid of these tables it can be ascertainedwhether a load diagram charactetizedby par-
ticular values of Kl and Kz is permissible for a given ambient temperature and, if so, what daily
use of life it will entail. This use of life is expressedin "normal days", i.e. equivalent days of opera-
'C.
tion at rated power in an ambient temperatureof 20
a1 For Kz:1.6, the letter B appearsin the table, which indicatesthat this load diagram is not
permissiblein an ambient temperatureof 30'C.
b I For Kz : 1.5, the letter A appearsin the table. This indicatesthat the load diagram is permissible
'C. The daily use of life would be :
in an ambient temperatureof 30
0.416x3.2: 1 . 3 3" n o r m a l d a y s "
which would be rounded off to 1.3 "normal days".
Winding hot-spottemperaturerise
Sign
or
letter Up to and including
(des C)
+ l 4 0 l -
D 130 | 140
C 12O I 130
B ll0 | r20
A 100 | ll0
Where neither the sign nor a letter appearsin the table, the hot-spot temperature rise would not
exceed100deg C.
oC, 10'C,
This immediately indicateswhat duties are permissiblein ambient temperaturesof 0
20 "C, 30'C and 40 "C without exceedinga winding hot-spot temperatureof 140'C.
The values given in the body of the table represent "relative use of life" when the daily use of
life corresponding to the load diagram under consideration is compared with the daily use of life
in the same ambient temperature due to continuous operation at rated power. Such operation is
representedby the case in which Kr : Kz : 1. As this referenceload diagram gives a daily use
o' normaldays"
of one " no rma l d u y " i n a n a m b i e n tte m p eratureof 20' C , and 10 ;3.2;0.32and 0.1
in ambient temperaturesof 40 "C, 30'C, 10'C and 0'C respectively,it follows that the method
already describedmay be used.
The relative use of life is given in the tables to an accuracy of three significant figures. Such pre-
cision may appear unjustifiable, but it makes it easy to draw curves and make interpolations, on the
understandingthat the values obtained will be rounded off at the end of the calculations.
5l
Strictly, it is not the 16 "normal days" but the differencebetween 16 and 3.2 (i.e. 12.8) "normal
days" that should be attributed to the overload.
In general, to obtain the 'oover-consumptionof life" due to the overload, for the duties covered
by the tables, it is necessaryto deduct from the use of life shown in the tablesthe "base consumption"
or use of life which would have occurred on the particular day if the normal load cycle, correspond-
ing to a use of life of 365 "normal days" in the courseof a year, had been applied.
The "base consumption" for a given day is equal to a "normal day" when the daily ambient
oC, used in defining the
temperature is equal to the weighted annual ambient temperature of 20
normal annual load cycle.
'C and 40 'C the use of life is ei venbel ow :
For daily ambient temperaturesbetween0
Ambient
Use of life
temperature
o I o.r\
l0 | 0.32
20 | 1.0
30 | 3.2
4 0 t 1 0
-- 53 --
fasrE XI
OI,{AN and ONAF transformers.' t - 0.5 h
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0'C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40 "C.
No value is given where K2 would be less than K1.
0.25 0.5
0.7
1.5 0.006 5 . 5 0B 2 3 . 0C 1 0 9D 5 8 3D
0.023 0.059 8 . 6 8C 3 2 . 0D
1.9 0.101 0 . 2 5 2A
0 . 5 6 0B
-55--
Tlprr XII
ONAN and ONAF transforn'ters: t: I h
5 . 0 _ t A l 2 0 . 9 IB s q . o s
r . 7 s A l 5 . e 7 B l2 3 . 6 8l r O s C
0 . 9 5 3A
0 . 8 1 5B
0 . 3 5 3A 0 . 9 5 8B 8 . 1 5C
0 . 3 9 7A 0 . 8 7 6B 1 8 . 0D
2 . 2 9C
6 . 2 7D
-57--
Tasrr XIII
OI{AIV and ONAF transformers
: t: 2h
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 'C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40 'C.
No value is given where K2 would be less than K1.
1.4 0 . 1l 6 0.221 0 . 5 0 6A 0 . 8 6 8A 3 . 6 3B 1 1 9C
1.7 3 . 1 8C 5 . 7 5C 1 2 . 0D 1 8 . 8D | +-
1 0 . 9D 1 9 . 5D
- 59 -,-
Taslt XIV
: t :
OM^ t a n d O N A F transformers 4h
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 'C. Where neither the -1- sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40 'C.
No value is given where l(2 would be less than K1.
1 . 3 24
T.tsrn XV
: t:
OI{AIVand ONAF transformers 6h
o'normal days")
Permissibleduties and correspondingdaily use of life (in
Where the * sign appears, the duty is not permissible even in an ambient temperatureof
0 "C. Where neither the f sign nor a letter appears in the table the hot-spot temperaturerise
will not exceed 100 deg C and operation is permissible at ambienttemperatures up to 40'C.
No value is given where K2 would be less than K1.
0.004 | 0.008
0.008 | 0.014
0.0s5 | 0.07'1
0.618 t0.798 6 . 9 0A
10.5
c [3.1 c t 7 . 4C 2 0 . 9C l26.t C 49.1C l78D I s58D
49.sD l6r.2D 8 0 . 0D
- 63 ---
Tesre XVI
: t:
ONAN andONAF transformers Bh
Where the * sign appears, the duty is not permissible even in an ambient temperature cf
0 "C. Where neither the * sign nor a letter appears in the t a b l e t h e h o t - s p o t t e m p e r a t u r e r i s e
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40 "C.
No value is given where K2 would be less than K1'
8 . 0 7 A| 1 9 . 3 A
1 5 . 6B 39.4B
6 5 . 1D 1 1 8D 5 5 8D
+
- 6 5 -
Tesrn XVII
: t:
ONAN and ONAF transformers 12lt
Where the * sign appears, the duty is not permissible even in an ambient temPerature of
0'C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures uP to 40'C.
No value is given where K2 would be less than K1.
6 . 1 7A 1 9 . 3A
2 6 . 7B 52.3B
-67
Tesn XVIII
: t:
OI{AIr{and ONAF transformers 24 h
I
that duty is not permissible at ambient
below
temperatures above the value indicated
II Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 "C. Where neither ttre + sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40
No value is given where K2 would be less than K1.
'C.
l K2
o.7
0 .8
0.9
1.0
|
|
|
|
0.026
o.o7e
0.266
1.00
1.1 | 4.18
r.2 I 19.3 A
1.3 | 99.0 B
1.4 | 558 D
1.5 | +
Note. - The values given in this table have already appeared in the seven preceding tables in
the cases where Kt : Kz.
-69--
Tasrs XIX
OFAF and OFWF transformers: t:0.5 h
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 "C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
'C.
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40
No value is given where K2 would be less than K1.
1.6 | 0 . 7 0 2B 1 . 3 0C 2 . 8 7C 4 . 7 4D 8 . 4 6D + + + + +
r.7 | 2 . 7 7C 5 . 1 1D II.2D + + + + + + +
1.8 + + + + + + + + + +
- 7l
Tasm XX
OFAF and OFWF tronsformers
: t: I h
Where the -l-- sign appears, the duty is not permissible even in an ambient temperature of
0'C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at a m b i e n t t e m p e r a t u r e s u p t o 4 0 ' C .
No value is given where K2 would be less than 1(1.
0.001 | 0.003
0.019
0.021 0.225
0.027 0.246
0.044 0.294
0.096 0.431
0.274 0 . 8 8 0A
0.282A 0.474A 0 . 9 3 7B 2 . 5 1B
l.r3B | 1.89C 3 . 6 5C 9 . 0 9D
5 . 0 1D | 8.27D
Tanrp XXI
OFAF and OFWF transformers
: t: 2h
Where the * sign appears, the duty is not permissible even in an ambient ternperature of
0 "C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40 "C.
No value is given where K2 would be less than K1.
0.003 | 0.018
0.020 | 0.059
0.026 | 0.068
0.011
0.035
0 . 5 3 9A 1 . 2 5 2 4| t . 7 4 B 2.628 | 4.648
18.5D t28.8D
-- 75 --
TnnrB XXII
OFAF and OFWF transformers : t -- 4lt
Where the * sign appears, the duty is not perrnissible even in an ambient temperature of
0'C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
'C.
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40
No value is given where K2 would be less than K1.
K2
0.7 0.018
|
r"" l;
0.014 0.019
0.048 o.062
29.OD 34.3D 4 3 . 0D 1 4 9 . 7D 9 7 . 9D
+ +
Tasrr XXIII
OFAF and OFWF transformers
: t: 6h
To determine whether a daily load diagram characterized by particular values of K1 and rK2 is
permissible and to evaluate the daily use of life entailed, proceed as follows :
Amb i e nte
t m p e ra tu r" 40' c ,o " . ,o' . ,o " . o' .
| | | | I
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 "C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40 "C.
No value is given where K2 would be less than K1.
x_
TasrE XXIV
OFAF and OFWF transformers: t: 8h
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 'C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
'C.
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40
No value is given where K2 would be less than K1.
0.203
0.930
4 . 9 5A
3 0 . 4C
-_ 81
Taurr XXV
OFAF and OFWF transforrners:t : l2 h
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 "C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at a m b i e n t t e m p e r a t u r e s u p t o 4 0 ' C .
No value is given where K2 would be less than K1.
0.009 I 0.018
0.026 I 0.037
0.455
2.01
1 0 . 8A 11.5A | 12.8A
I
-83-
Tasre XXVI
OFAF and OFWF transformers
: t: 24 h
:II
I Daily use of liJb :
Multiply the value given in the table below
{ by the factor given here, then round off o.32 0.1
the result
Where the * sign appears, the duty is not permissible even in an ambient temperature of
0 'C. Where neither the * sign nor a letter appears in the table the hot-spot temperature rise
will not exceed 100 deg C and operation is permissible at ambient temperatures up to 40 'C.
No value is given where K2 would be less than K1.
K2
0.7 0.018
0.8 0.059
0.9 o.225
1.0 l.00
1.1 5 . 1I
1.2 3 0 A
1.3 202 C
1.4 +
Note. - The values given in this table have already appeared in the seven preceding tables in
the cases where Kt : Kz.