UNIVERSITY OF JORDAN RC II STUDENT NAME:

SUMMER 2020-2021 EXAM STUDENT ID:

Question 1: Design the solid slab shown in figure below using ACI direct design method. All columns are 450 mm
X 450 mm. All beams are 450 mm wide and 550 mm deep. qu=20 kN/m2 (including own weight). f’c=28 MPa and
fy=420 MPa. Use 300 mm slab thickness.

a. Check if provided slab thickness satisfy the minimum thickness requirement of the code
b. Design the slab in the long direction (x-direction).
c. Check the slab for one-way shear
UNIVERSITY OF JORDAN RC II STUDENT NAME:
SUMMER 2020-2021 EXAM STUDENT ID:

Question2: Consider the concrete building frame shown. The relative lateral deflection for the
third storey under total wind shear Vwind= 300 kN is 25mm. The load combination: U = 1.2 D
+1.6 W + 1 L + 0.5 ( Lr or S or R) controls. All columns cross sections are 450 mm x 450 mm.
All beams cross sections are rectangular 250 mm x 450 mm. The column is subjected to double
curvature under dead load and single curvature under live load. Column 3 is to be designed using
fc= 28 MPa, fy=420MPa. Consider the floor thickness is 450 mm.
Cols A3 and F3 Cols B3 and E3 Cols C3 and D3
Pdead 500 kN 900kN 1000 kN
Plive 400 kN 600kN 900 kN
Pwind 140 kN 70kN 35 kN
Vwind 30 kN 60kN 60 kN
M2,dead 5 kN.m
M2,live 130 kN.m
M2,wind 120 kN.m
M1,dead -5 kN.m
M1,live 100 kN.m
M1,wind 110 kN.m
4 stories at 6 m = 24 m

5 bays at 7 m = 35 m

1- The stability index Q =


2- The required frame analysis is .
3- ψA and ψB for column 3 =
4- The slenderness ratio for column 3 =
5- The maximum factored end moments in kN.m resulting from sway and non-sway
loads for column 3 =
UNIVERSITY OF JORDAN RC II STUDENT NAME:
SUMMER 2020-2021 EXAM STUDENT ID:

Question3: A cantilever beam is subjected to uniformly distributed dead load of 10 kN/m (and concentrated live
load of 20 kN ). Of the total live load, 25% is considered sustained for 2 year. The beam has a rectangular cross-
section of 400 mm width and 700 mm depth. The beam will support nonstructural partitions that are likely to be
damaged by large deflection. Check if deflection of this beam satisfies ACI 318-11 limitation. f’c=28 MPa and
fy=420 MPa.