Professional Documents
Culture Documents
Model ZW209FP ®
Fire Protection Pressure Reducing Valve Assembly ®
Globe Fire Protection
and Angle Pressure
Pattern Bodies Reducing Valve Assembly
1-1/4", 1-1/2", 2", 2-1/2", 3", 4", &3",
1-1/4", 1-1/2", 2", 2-1/2", 6" 4" & 6"
Installation Start-up
Installation Start-up Maintenance
Maintenance Instructions
Instructions
DESCRIPTION
DESCRIPTION
The Zurn The Zurn
Wilkins Wilkins
Model ZW209FP
ZW209FP pilotpilot operated
operated pressure
pressure reducing
reducing valve
valve
is designed is designed
specifically for fire suppression for systems
suppression
to reduce systems
high inlet
pressurestotoreduce
a safe high inlet pressures
and stable to a safe
outlet pressure. The and stable
pilot outletreacts
assembly
pressure. The pilot assembly reacts to changes
to changes in downstream pressure allowing the main valve to modulate in downstream
pressure allowing the main valve to modulate between the
between the closed and open position ensuring a constant downstream
closed and open position ensuring a constant downstream
set pressure. Once the downstream pressure reaches the pilot setting,
set pressure. Once the downstream pressure reaches the
the main valve will sealthe
pilot setting, shut
mainpreventing damage
valve will seal shutdownstream.
preventingPressure
damage
ZW209FP ZW209FPG ZW209FPX
regulationdownstream.
is not dependent upon flow rate, resulting
Pressure regulation is not dependent in minimal pressure
upon Class 300 Flanged Grooved Class150 Flanged
loss through the
rate, valve. Ininaddition
resulting minimalthe ZW209FP
pressure loss comes
throughstandard with
the valve. Max 300 psi Inlet Max 300 psi Inlet Max 250 psi Inlet
red epoxyIncoating
additioninternally and externally
the ZW209FP for corrosion
and ZW209FPG comeprotection,
standardas ZW209FPTH
well as pressure
with redgauges
epoxy for quickinternally
coating and easyand maintenance
externally or
forrepair. The
corrosion Threaded
ZW209FPprotection,
is availableasinwell
bothasglobe
isolation valvespattern
and angle and pressure
bodies. gauges for
Max 300 psi Inlet
quick and easy maintenance or repair
Installation / Start-up
Installation / Start-up
INSTALLATION 8. Bleed all trapped air from supply riser and sprinkler system.
NOTE: Prior INSTALLATION
to installation of the ZW209FP, ensure that all debris is 7.Trapped
It is suggested
air may cause that aoutlet
line size tee connection
pressure fluctuations beatinstalled
low flows.
flushed out NOTE: Prior to
the piping installation
system before of the ZW209FP, ensure that all downstream of sprinkler system valves to allow full
installed. testing
1. During the installation of a ZW209FP in a sprinkler system, Under- 9. asZurn
required
Wilkinsevery
valves are years per NFPA
designed 25.
to operate in both the vertical and
writer 1. During the
Laboratories (UL)installation of a ZW209FP
requires NFPA 13 “Standard in aforsprinkler system,
Installation of horizontal positions. However, it is recommended that ZW209FP's
Underwriter
Sprinkler Systems” Laboratories
be followed. (UL) requires NFPA 13 “Standard for 8.6" and Bleelarger,
d all trabeppinstallation
ed air frominsuthe pplyhorizontal
riser andposition.
sprinklerThe syshorizon-
tem.
Installation of Sprinkler Systems” be followed. Trapped air mayofcause
tal positioning outletvalves
the larger pressure avoids premature atwear
low due to
2. Upon installation UL also requires that the ZW209FP be tested in
mass of plunger assemblies as well as allows for greater accessi-
accordance
2. Upon with NFPA 13 or NFPA
installation UL also 14.requires
Thereafter thethe
that valve shall be be 9. Zurn Wilkins valves are designed to operate in both the verti-
ZW209FP bility during annual inspections, and maintenance.
inspected,
tested tested, and maintained
in accordance in accordance
with NFPA 13 or NFPA to NFPA 25 “Stan- the cal and horizontal positions. However, it is recommended that
14. Thereafter
dard for the shall
valve Inspection, Testing,tested,
be inspected, and Maintenance
and maintained of Water-Based
in accordance to START-UP
ZW209FP’s 6” and larger, be installation in the horizontal position.
Fire Protection “Standard NOTE:
NFPA 25 Systems”. Initial testing
for the Inspection, mustand
Testing, be done with
Maintenance The horizontal positioning of the larger valves avoids premature
the design inlet pressure so the proper outlet NOTE:
pressure can testing
be CAUTION: To prevent personnel injury and damage to equipment
of Water-Based Fire Protection Systems”. Initial wear due to mass of plunger assemblies as well as allows for
verified. check that downstream venting is adequate prior to start-up and
must be done with the design inlet pressure so the proper greater accessibility during annual inspections, and maintenance.
test procedures. All adjustments under pressure should be made
3. For making adjustments and servicing allow for adequate space
around the valve. slowly
START-UP while under flowing conditions. If the main valve closes too
3. For making adjustments and servicing allow for adequate fast it may
CAUTION: cause surging personnel
To prevent in upstream piping.
injury and damage to equip-
4. When installing a ZW209FP valve gate valves installed on both inlet
space around the valve. ment check that downstream venting is adequate prior to
and outlet are recommended for maintenance allowing for isolation 1. start-up
Slowly and opentesttheprocedures.
upstream shutoff valve only enough
All adjustments under to fill main
pressure
of valve. valve assembly and pilot system. Prior to pressurizing the valve as-
4. When installing a ZW209FP valve gate valves installed on If
5. Position theinlet
both ZW209FP in line
and outlet arematching
recommended the direction of flow as allowing the
for maintenance sembly
main itvalve
is also recommended
closes too fast it may that cause
a ZPI valve position
surging indicator be
in upstream
indicated on the valve
for isolation model tag with the proper direction of flow in
of valve. installed to aid in verifying proper valve movement.
piping.
the system. Once attached to line double check all fasteners/bolts in
the pilot
5. system
PositionandtheonZW209FP
main valve in are
line tight and there
matching is no damage
the direction of as 2. 1.As Slowly
the valve is filling
open with water,shutoff
the upstream it is necessary
valve only to enough
bleed the tomain
prior toindicated
pressurizingon thesystem.
valve model tag with the proper direction of valve
main and assembly
valve pilot system andof pilot
air. Tosystem.
vent air,Priorpartially open or loosen
to pressurizing the
NOTE:inPressure
the system. in some
Once applications
attached to line can be very
double checkhighallsofasteners/
be the highest
valve assembly plugs
it isoralso
fittings in the system.
recommended thatThe a ZPI valve position
position
thoroughboltsininchecking and inspecting
the pilot system and on main for proper
valve are installation and is indicator
tight and there indicatorbe is installed
a great location,
to aid inas it has a proper
verifying test cock at the
valve top to vent
movement.
makeup. no damage prior to pressurizing system. air pressure. It may be necessary to bleed system more than once.
6. ValvesNOTE:
installed Pressure in some
in sprinkler applications
or standpipe systemscan shallbehave
verythe
high
fol- so be 2.After Asremoval
the valve of is
air in thewith water,
system it is necessary
tighten to bleed
all loose fittings. NOTE: the If
lowing:thorough in checking and inspecting for proper installation main valve valve and pilotvertically,
is installed system ofitair. willTobevent air, partially
necessary open or
to loosen some
and makeup. loosen
upperthe highest
cover boltsplugs
untilor you haveinvented the system.all theThe ZPI valve
air from the cover
a. Union or rubber gasket fittings installed immediately up stream or position indicator is a great location, as it has a test cock at the
downstream chamber.
6. Valvestoinstalled
permit replacement.
in sprinkler or standpipe systems shall have top to vent air pressure. It may be necessary to bleed system
b. A the
relieffollowing:
valve (at least 1/2" size and 175 psi max.) installed on 3. more
At thisthan once.
point withAfter removal ofshutoff
the upstream air in the
valve system tighten
partially openall slowly
a)downstream
the Unions or siderubberandgasket
plumbed to ainstalled immediately up
safe drainage. loose
open the downstream shut off valve. Flow will begin to occur and
stream or downstream to permit replacement. pressure should build up in valve and eventually stabilize.
c. Pressure gauges installed on the inlet and outlet.
b) A relief valve (at least ½” size and 175 psi max.) installed 3. At this point with the upstream shutoff valve partially open,
d. Shall not on be
thesetdownstream
for less than side
50and
psi. plumbed to a safe drainage. slowly open the downstream shut off valve. Flow will begin to
c) Pressure gauges installed on the inlet and outlet. occur and pressure should build up in valve and eventually
7. It is suggested that a line size tee connection be installed down-
d) Shall not be set for less than 50 psi. stabilize.
stream of sprinkler system valves to alow flow testing as required
every five years per NFPA 25.
® ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766 1
! WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
www.zurn.com
! ADVERTENCIA: Cáncer y daño reproductivo - www.P65Warnings.ca.gov
! AVERTISSEMENT: Cancer et néfastes sur la reproduction - www.P65Warnings.ca.gov
ZURN WILKINS
®
MAX. FLOW RATE (GPM) 125 160 250 375 600 1000 2250
Operation
The Zurn Wilkins ZW209FP utilizes a pressure reducing pilot valve that installs on the discharge side of the control circuitry. The
pilot Model PV-PRD is a direct acting, normally open, spring loaded, diaphragm actuated valve. The operation of the ZW209FP
begins with accurately sizing the valve, then tuning the control circuitry by adjusting the PV-PRD to the desired downstream
pressure.
Inlet pressure is piped to the inlet of the PV-PRD. A sensing line runs internally from the discharge side of the pilot to its lower con-
trol chamber under the diaphragm. Thus, downstream pressure exceeding the preset of the pilot acts to close the pilot valve while
the adjustable spring in the pilot seeks to keep it open. The result is a modulating action in the pilot that is transmitted to the cover
of the main valve. This creates a mirror modulation of the diaphragm assembly in the main valve. Downstream pressure is main-
tained with narrow limits regardless of changing rates or varying inlet pressure.
ZURN WILKINS ®
2 1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
www.zurn.com
Flow Characteristics
PRESSURE REDUCTION LIMIT
BODY MINIMUM FRICTION LOSS UL Limit Damage Zone Noise Limit
300
be le le
100
lo g g
G An An
Cavitation damage
e
2" " &
gl
1/ /2 e
An
zone (intermittent
1- 1-1 lob
&
G
gl be
gl lob
250
e
operation allowed)
gl ob
be
be
e
gl ob
4"
An Glo
gl lob
ng Glo
An G
An Gl
lo
1/
An Gl
e
e
e
2" /2"
G
1-
An " G
3" 3"
6" 6"
e
8"
" A 0"
e
4"
1
Do not operate
le
2
1
PRESSURE DROP (PSI)
in this area
8"
1/
2"
Noise
2-
200
10
zone
10
150
Safe
operating zone
100
1
50
0
0
0 20 40 60 80 100 120
10 100 1000 10000
FLOW (GPM) OUTLET PRESSURE (PSI)
Maintenance Instructions
MAINTENANCE (Main Valve) assembly can be dismantled. When disassembling be sure to
In addition to complying with UL standard NFPA 25 every five clean, inspect, and save all components. Replace any damaged
years, scheduled preventative maintenance and inspection is components as necessary.
highly recommended. It is also recommended that a repair kit
with a new diaphragm, disc, and o-rings be on hand before 6. Next clean and inspect the seat inside the main valve body.
work begins If excessive water deposits are present fine grit sand paper can
DISASSEMBLY be used to clean. The seat is designed to be removed, but typi-
Warning: With the ability to perform inspections and cally does not require removal. If damage is noticeable or seat
maintenance without removal from the system. It is very is excessively worn, replace the seat before reassembly.
important that all shut off valves be closed and all pres-
sure relieved in the valve before beginning disassembly. 7. Refer to www.zurn.com to find ZW209 instruction sheet for
Failure to do so can result in personnel injury or equip- more detailed instructions for disassembly and reassembly of
ment damage. main valve.
1. With all isolation valves closed to the ZW209FP, begin REASSEMBLY
slowly removing flare fitting in the pilot system until residual Prior to reassembly clean, inspect, and replace any parts as
pressure is removed. After excess pressure has been relieved needed.
begin removal of pilot tubing to cover.
1. Using a vise, diaphragm assembly can be held and as-
2. Begin loosening cover bolts and remove cover lifting up sembled in the reverse order as disassembly section.
to slide cover bushing off plunger shaft. For valves larger than
6” it is recommended that lifting lugs and a hoist be used due 2. Clamp valve stem hex in a vise and reassemble diaphragm
excessive weight of the larger covers. assembly. Make sure to center diaphragm on plunger before
placing diaphragm disc. Refer to ZW209 instruction sheet at
3. Once the cover is removed the plunger spring and spring www.zurn.com or call product support 877-222-5356 for further
washer can be removed. Then remove the diaphragm assem- assistance.
bly by grabbing the stem or lifting from two sides of the dia-
phragm. Be sure to lift straight up to avoid binding the stem in 3. Once diaphragm assembly is assembled, gently lower
the seat bushing, as damage can occur. NOTE: Again with the stem into seat guide. Rotate diaphragm as needed until bolt
larger size valves 6” and up it is recommended that a lifting lug holes line up with body bolt holes.
and hoist be used to remove larger plunger assemblies.
4. Install spring then the cover. Tighten bolts in a cross pat-
4. Place diaphragm assembly in a vise with the bottom hex tern. Be careful not to pinch the diaphragm when inserting and
secured. Remove the stem nut and inspect threads for dam- tightening cover bolts.
age, corrosion, or pitting.
5. Reattach pilot assembly and tighten all bolts and fitting as
5. After inspecting the stem and removing the nut the diaphragm needed. Test system per UL standard NFPA 25.
® ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766 3
www.zurn.com
Maintenance Instructions
ITEM DESCRIPTION CENTER YOKE LEGS
17 1 BODY (GLOBE OR ANGLE) BETWEEN
20 2 SEAT DIAPHRAGM HOLES
16
3 O-RING
20 15
4 STEM
12 5 SEAL RETAINER
11
6 O-RING
13 14
7 SEAL RING
19 10
8 PLUNGER
18
9 9 DIAPHRAGM
6
6 10 DIAPHRAGM DISC
8
5 11 WASHER
7
3 12 3/4-16 UNF NUT
4 YOKE LEGS
13 LOWER SPRING WASHER
2
14 SPRING
1 15 UPPER SPRING BUSHING
16 COVER BUSHING NOTE: Line up diaphragm screw holes with holes in body.
17 COVER Move yoke up and down checking for yoke contacting or
18 WASHER dragging on valve body.
19 1/2-13X2" CAP SCREW
20 3/4" NPT PLUG
3. Then attach plunger to the bottom of the pilot yoke via the
MAINTENANCE (3/8" PV-PRD VALVE) main cap hole and tighten with a 13 mm socket.
The PV-PRD pressure reducing control may be installed in
any position. There is one inlet port and two outlets, for either 4. Install main cap in bottom of valve body with new o-ring.
straight or angle installation. A arrow is marked on the
body and should be oriented as needed. 5. Install spring, spring disc, and pilot bell on the valve body.
DISASSEMBLY 6. Insert socket head cap screws into pilot bell holes and
Prior to disassembly, relieve all pressure in pilot system and thread into valve body. Tighten all screws in a cross pattern.
then remove the PV-PRD.
7. Install adjusting screw by hand with jam nut. Set valve
1. Secure valve body and remove main cap on bottom of once reinstalled into main valve pilot system. For setting pilot
valve using an adjustable wrench. refer to “Start Up” section on page one. For further assistance
or ordering replacement parts go to www.zurn.com or call pro-
2. Use a 13 mm socket to remove the plunger. duct support 877-222-5356.
4 ITEM DESCRIPTION
3. Next remove adjustment cover (plastic cover), 3/8” adjust-
1 3/8" PRV-PILOT BODY, LEAD FREE BRASS
ment bolt with nut, 8 socket head screws around the pilot bell
5 2
using a 5/32 hex key, spring, and spring disc. 16
PLUNGER, SS W/BUNA NITRILE 90 SHORE
4. At this point the PRV stem yoke is free to move and can be 4 ADJUSTMENT COVER
9
slid out of the valve body. 5 3/8"-16 ADJUSTMENT BOLT, BRASS
17 9 SPRING DISC, SS
inspect all components before reassembly. Replace any parts 15 11 O-RING, BUNA NITRILE NSF LISTED