Professional Documents
Culture Documents
INCOMING
1 Nos 200 TPN MCCB (25 KA)
1 Sets of 400 Amps TPN , Al Bus bars with color coded heat shrinkable
PVC sleeve.
1 Set of RYB indicating lamps with 6A SP MCB.
1 No 96 Sq.mm 0.400 Amps, Ammeter with selector switch and suitable
rated current transformers
1 No 0-400 96 Sq.mm Voltmeter with selector switch
OUTGOINGS
SUPPLY ERECTION
SL NO DESCRIPTIONS UNIT QTY SUPPLY RATE ERECTION AMOUNT
AMOUNT RATE
Feeder for main pump - 2 No
1Nos 125 A TP MCCB
Star delta starter with over load relay, single phase preventor and
indicating lamps with ON/OFF push buttons
Feeder for Jockey Pump- 2 No
1 No. 25 A TP MCCB
DOL starter with over load relay, single phase preventor and indicating
lamps with ON/ OFF push buttons-
1 No Automanual selector switch
Feeder for Diesel Engine Autostart panel- 1 No
a) 20 Amps DPMCB - 1Nos
b) Battery charger with transformer with reclifier resistance DC ammeter,
DC voltmeter, Trickle / booster / off selector switch - 1 Nos
c) 1 Set of indicating lamps for the following :
1. phase indication
2. battery charger on
3. over load relay
4. DC supply on
5. control switch on
6. Engine fails to start
7. Pump on
8. Low oil pressure
9. High water temperature
10. Auto manual selector switch
d) 1 sets of push button stations for the following :
1. Engine Start
2. Engine Stop
3. Engine - hooter ACK
4. Engine - fault resete) Selector switches (Engine control, mode selector)-
1 No
f) Auxilary relays / contactors / timer for sequence operating for starting
and stopping of the engine - 1 set
g) Hooter for audio alarm (industrial type) - 1 No
Also panel shall have sufficient (min. 20 Nos) NO/NC contacts for
extending the status (annunciation) of fire pumps to the fire alarm panel.
Autostart panel for the Diesel engine complete auto / manual switch,
indication lamps protective fuses with battery charges, suitable of
6 working on 230 V, with one hour back up,AC, single phase, enclosure Nos 1
being vermin,dust proof and panel compatable to BMS. Location at
Ground floor lvl.
Supplying, laying, testing & commissioning of FRLS,PVC outer sheath,
steel armoured, aluminium conductor, 1100v grade power cables with
glands etc.The cables shall be laid in tray / Hume pipe / in trenches/on
walls/ floor etc. as required. For cables laid out door the rate shall
include earth excavation providing brick and sand protection, refilling and
7
compacting the earth.The rate shall exclude tray & Hume pipes but
includes for the required no of end terminations as mentioned below.The
minimum size of the cables shall as mentioned below, with all the end
terminations
SUPPLY ERECTION
SL NO DESCRIPTIONS UNIT QTY SUPPLY RATE ERECTION AMOUNT
AMOUNT RATE
1R X 3.5 C X 70 sq.mm Aluminium armoured cable for main pumps
a) Mtr 40
b) 1R X 4 C X 6 sq.mm. Copper armoured cable for Jockey pumps Mtr 40
c) 12 C x 2.5 sq.mm.Aluminum cable Diesel engines Mtr 30
d) 4 C x 1.5 sq.mm Copper armored for Instrumentation Mtr 30
Supplying and installing of perforated G.I.sheet cable tray with necessary
angle iron suspension supports, anchor fasteners etc. complete.
8 Maximum height of suspension shall Not exceed 500 mm.Size of the tray Mtr 30
shall be suitable for laying the above mentioned cables.
G.I. Earthing strips of sizes mentioned below, strip shall be run on floor /
ceiling / walls, from the equipment to the nearest Earth pit with
9 neccessory accessories as required. (Earth pit shall be executed by other
agencies).
a) 25 x 3 mm GI strip Mtr 25
b) 50 x 6 mm GI strip Mtr 15
Supplying, installing, testing and commissioning of MS 'C' class pipes ( It
should confirm to IS 1239 Pt-1 Heavy grade for pipe dia upto 150 mm and
IS 3589 for pipe dia above 200 mm)for underground yard hydrant piping
with painting(color shade should be 536 as per IS 5), suitable type of
supports, anchor fasteners, bolts nuts ( Galvanised), clamps, "U" bolte,
malleable specials such as couplers, flanged joints, reducers, bends, tees
10 ,orifice plates, MS tapers special bolts, nuts gaskets. Including cutting,
Welding, fixing in / on walls, ceiling by using suitable supports etc, as per
drawings. The quoted rate shall also include for chasing / chipping walls,
making bore holes in walls / floor and making them good with filler
material and finished in cement morter etc. complete.
150 mm dia M.S. Medium grade with mineral wool insulation with
a) Mtr 15
aluminum sheeting & Structural Steel Supports
Supply & installation of 20 NB Automatic Air Release Valve along with
21 Nos. 10
ball valve all complete as per specifications.
TOTAL - A - -
Providing & fixing indoor type hose lockable cabinet frames fabricated
from 40 x 40 x 5 angle iron sections and 16 gauge MS sheet with full front
glass door and locking arrangement, suitable to accommodate landing
valves, 15 m long hoses, first-aid hose reel and branch pipe nozzle & fire
f) mans’ axe. The cabinet frame shall be painted with one coat of primer Nos 18
and two or more coats of synthetic enamel paint of approved make and
shade of as required (Approx 2.1 m (high) x 0.9 m (wide) x 0.6 m (deep) ).
The item shall be complete of MS housing with front door.
(Cost shall be inclusive of providing break glass box containing key for the
cabinet along with hammer).
Providing and fixing standard fireman's axe with heavy rubber handle.
g) Nos 18
25mm dia MS conduit with 2mm thick for laying of fire cable including
7 Rmt 650
necessary accessories like bend, junction box fixing of clamps etc.,
TOTAL - C - -
i) 6 kg Nos 40
Fire bucket of 24 gauge galvanised steel sheet, standard 9 litre capacity
& of round bottom shape painted white inside & red outside & black on
c) the bottom done with letters " FIRE" in black & gold with wall mounting Nos 16
bracket, Fire bucket stands & screws. ( Each 4 no.s )
TOTAL - D - -
PART E- SIGNAGES:
1 EMERGENCY EXIT (400mmx150mm double side) Nos 27
2 FIRE EXTINGUISHER (100mmx150mm single side) Nos 80
3 FIRE EXIT (400mmx150mm double side) Nos 50
4 EXIT (400mmx150mm double side) Nos 50
5 MANUAL CALL POINT (100mmx150mm single side) Nos 36
6 HOOTER (100mmx150mm single side) Nos 36
7 EVACUATION PLAN with AUTO GLOW in A2 Nos 18
TOTAL - E - -
2 REPEATER PANEL - -
Supply, Installation, Testing & Commissioning of remote annunciators
with 4 line 80 character LCD display. The annunciator shall have built in
memory to record the alarm events and shall have standard buttons for Nos 0
alarm ack, reset etc. Max of 32 remote annunciators shall be loopable to
one FACP.
Hooters with Strobes: Supply, Installation, testing and commissioning
2 of Hooters with Strobes with all mounting accessories complete as Nos 36
required.
Supply, Installation & Testing of of Addressable type Manual Call Point
3 Nos 36
with a glass cover marked " IN CASE OF FIRE PRESS"
SUPPLY ERECTION
SL NO DESCRIPTIONS UNIT QTY SUPPLY RATE ERECTION AMOUNT
AMOUNT RATE
Supply, Installation, Testing and Commissioning of UL listed and
FM approved Intelligent Addressable Smoke detector above
false ceiling with photoelectric and false alarm resistance along
with standard base. Detector should be electronically addressed,
rotary/DIP switches for addressing are not acceptable. Smoke
detector shall be an intelligent digital photoelectric detector.
4 The detector shall have tri color LED, Green for Normal, Amber Nos 380
/yellow for trouble and Red for alarm. Shall be Polarity
Insensitive and facility to mount in different comprehensive
environment like Hostile environment, Parking Garage,HVAC Ducts,
Precious storage,Transformer rooms, Ware house, Dormitory and
normal working environments and as per the specification.
-
TOTAL - F - -
PART G - PA SYSTEM
PA Rack
Supply, Installation, Testing & Commissioning of sheet metal 17U
rack (or vendor shall calculate and propose suitable rack) for
1 Nos 1
mounting of Access Conrtoller & DVR's as per the technical
specification with all mounting accessories etc
System Controller
SUPPLY ERECTION
SL NO DESCRIPTIONS UNIT QTY SUPPLY RATE ERECTION AMOUNT
AMOUNT RATE
Supply, Installation, Testing & Commissioning of Programmable
System Controller with built in DVR, Amplifier, zone selection for 11
zones, and All Call having 1st level priority for DVR (Fire message),
2 2nd level for Announcement, least level for Music. And also built in Nos 1
monitoring facility as per the technical specification with all
mounting accessories etc
Supply & Laying of FRLS Conduit of 3/4” dia & 2mm thickness with
accessories like saddles, saddle base etc complete as required as
9 Rmt 1400
per the technical specification with all mounting accessories etc
TOTAL - G - -
TOTAL - H - -