VISY-X
Tank Level Gauging and Environmental Sensors
Application
VISY-X, the high-precision tank for any area of industry in which
gauging system, is specially de- mineral oil products are stored.
signed for use in petrol stations. VISY-X is suitable for both under
Its modular architecture, how- ground tanks and above-ground
ever, also makes it ideal for use storage tanks.
as a tank management system
VISY-X system
Printer Truck-Diver Point of Sale SECON-Lev
Display (PoS)
VISY-View
Touch
VISY-Command
(control unit) VISY-Stick Flex
(filling level and
environmental sensors)
VISY-Input
System Design
Level / environmental sensor Control unit Display Software
Magnetostrictive Sensors VISY-Command 2/4/8/16 VISY-View Touch VISY-Monitor
Reed sensors VISY-Command GUI
VISY-Command RF
Function Design
The VISY-Stick sensor operates lar magnetic field. A torsional A VISY-Stick comprises:
in accordance with the mag wave develops at the point »» Stainless steel sensor housing
netostrictive measuring prin- where the two magnetic fields »» Stainless steel probe tube
ciple. The probe tube contains overlap and it propagates to- »» Brass screw-in unit
a wire made of magnetostric- wards the probe head. In the (height adjustable)*
tive material. Magnets inte- probe head, these waves are »» Stainless steel product float
grated in the floats magnetise converted into an electrical »» Stainless steel water float
the wire at the float position. signal. The float positions and
The sensor electronics trans- the temperature are calculated
mit current pulses through the from the different propagation
Edition 05.2016 Technical changes reserved
6 | VISY-Stick www.fafnir.com
Technical data
VISY-Stick
Standard version »» Temperature: Options
»» Product: Measuring range »» Riser installation
Accuracy ± 0.5 mm; - 40 °C to + 85 °C; »» Battery-powered transmitter
Repeatability ± 0.1 mm; Accuracy ± 1 °C (20 °C); VISY-RFT for wireless link to
Resolution 0.001 mm; Repeatability ± 0.5 °C; the VISY-Command RF control
Response threshold 75 mm*; Resolution 0.001 °C unit
Float Ø 43 mm, 1½“; »» Process connection: »» 1” installation kit
»» Water: R 1½ screw-in unit, »» Screw-in unit made of
Accuracy ± 2 mm; brass, height adjustable stainless steel
Repeatability ± 0.5 mm; »» Electrical connection:
Resolution 0.001 mm; M12 Plug connector
Response threshold 23 mm*; »» Casing protection: IP68
Float Ø 43 mm, 1½“; »» Sensor material:
*P
roduct density and the position of the
Stainless steel
other float may result in variations »» Approvals:
ATEX, NEPSI, IECEx, UL-Brazil
»» Certificates: CPA, OIML
VISY-Stick
VISY-Stick VISY-Stick
(riser installation) (screw-in unit installation)
Ø 47,2 Ø 47,2
M12 Connector
brown +
white A
black B
blue -
Equipotential bonding
123
123
Sensor head
stainless steel
Screw-in unit
R 11/2 WAF 55
brass
Sensor length
Sensor length
Sensor tube Ø 12
stainless steel
Edition 05.2016 Technical changes reserved
Product float Ø 43 x 43
stainless steel
Water float Ø 43
stainless steel
Guard ring
Dimensions in mm
VISY-Stick Advanced
magnetostrictive sensors
with screw-in unit (left) and
for riser installation (right)
Function description
The VISY-Stick Advanced sen- current pulses through the wire, sitions are calculated from the
sor operates in accordance with which generate a circular mag- different propagation times. For
the magnetostrictive measuring netic field. A torsional wave de- precision temperature measure-
principle. The probe tube con- velops at the point where the ments, the sensor tube of the
tains a wire made of magneto- two magnetic fields overlap VISY-Stick Advanced contains
strictive material. Magnets inte- and it propagates towards the temperature sensors.
grated in the floats magnetise probe head. In the probe head,
Edition 05.2016 Technical changes reserved
the wire at the float position. these waves are converted into
The sensor electronics transmit an electrical signal. The float po-
VISY-Stick Advanced
Ø 47,2 Ø 47,2
M12 Connector
brown +
white A
black B
blue -
Equipotential bonding
123
123
Centring aid 3” / 4”
Sensor head
stainless steel
Screw-in unit
R 1½ WAF 55
brass
Sensor length
Sensor length
Sensor tube Ø 12
stainless steel
Edition 05.2016 Technical changes reserved
Product float Ø 54
stainless steel
Water float Ø 43
stainless steel
Guard ring
Dimensions in mm
Function description
Inside the VISY-Density module* legal and in-house standards. VISY-Density combination will
the buoyancy of a displacer is Any changes and deteriora- enable you to control and man-
measured (Archimedean prin- tions of the product quality can age your valuable wet stocks in
ciple). It provides precise infor be measured and alarms can be every respect.
Edition 05.2016 Technical changes reserved
10 | VISY-Density www.fafnir.com
VISY-Density Technical data
VISY-Density
»» Product:
Accuracy ± 2 g/l,
Ø 47,2 M12 Connector
brown + Resolution 0.1 g/l
white A »» Temperature range:
black B
blue - - 40 °C to + 85 °C
»» Dimensions:
Equipotential bonding
Diameter 50 mm;
Length 129 mm
123
Screw-in unit
R 1½, WAF 55
brass
Sensor tube Ø 12
stainless steel
Product float Ø 54 x 31
stainless steel
Spacer
Sensor length
VISY-Density Ø 50 x 129
stainless steel
Water float Ø 43 x 40
stainless steel
Guard ring
Dimensions in mm
Example
VISY-Stick 5
Edition 05.2016 Technical changes reserved
mit Density
Function description
The VISY-Stick Flex sensor oper- shipped at low cost. Another movement of the VISY-Stick Flex
ates according to the magneto- advantage is the easy installa- is avoided. When the installa-
strictive measuring principle. A tion. A weight at the lower end tion of the VISY-Stick Flex level
wire made of magnetostrictive of the sensor stretches it out sensor has been completed, the
material has been integrated to its full length, and a magnet corrugated hose is positioned
into the flexible corrugated placed below the weight secures vertically and both the product
hose. The special design of the the sensor to be in place. When and the water float can freely
sensor allows the sensor body to the magnet is in contact with move up and down.
be bent. So the VISY-Stick Flex the bottom of the tank (after
can be packed compactly and installation) any unintentional
Edition 05.2016 Technical changes reserved
Options
Magnetic base
plastic encapsulated
»» Battery-powered transmitter
Edition 05.2016 Technical changes reserved
Function
The VISY-Stick LPG sensor oper- float position. The sensor elec- towards the probe head. In the
ates in accordance with the mag- tronics transmit current pulses probe head, these mechanical
netostrictive measuring principle. through the wire, which gener- waves are converted into an
The probe tube contains a wire ate a circular magnetic field. electrical signal. The float posi-
Edition 05.2016 Technical changes reserved
made of magnetostrictive mate A torsional wave develops at the tions and the temperature are
rial. A magnet integrated in the point where the two magnetic calculated from the propagation
float magnetises the wire at the fields overlap and it propagates time.
VISY-Stick LPG
Ø 47,2
M12 Connector
brown +
white A
black B
blue -
Equipotential bonding
123
Sensor head
stainless steel
Sensor tube Ø 12 x 1
stainless steel
Edition 05.2016 Technical changes reserved
Product float
Ø 40 x 120
buna
Guard ring
Dimensions in mm
the tank.
Adjusting ring
Dimensions in mm
VISY-Stick Interstitial
with screw-in unit (left)
and for riser installation (right)
Function
The VISY-Stick Interstitial sensor at the float position. The sensor towards the probe head. In the
operates in accordance with the electronics transmit current puls- probe head, these waves are con-
Edition 05.2016 Technical changes reserved
magnetostrictive measuring prin- es through the wire, which gen- verted into an electrical signal.
ciple. The probe tube contains a erate a circular magnetic field. A The float position is calculated
wire made of magnetostrictive torsional wave develops at the
from the propagation time.
material. A magnet integrated point where the two magnetic
in the float magnetises the wire fields overlap and it propagates
VISY-Stick Interstitial
Ø 47,2
M12 Connector
brown +
white A
black B
blue -
Equipotential bonding
123
Riser installation
centring aid 3” / 4”
Sensor head
stainless steel
Sensor tube Ø 12
stainless steel
Sensor length
Product float Ø 43 x 43
stainless steel
Guard ring
Dimensions in mm
VISY-Stick Sump
(blue for manhole sump,
red for dispenser sump)
and the VISY-Stick Sump
installation kit
Function description
The VISY-Stick Sump sensor The sensor electronics trans- probe head, these waves are
operates in accordance with
mit current pulses through the converted into an electrical
the magnetostrictive measuring wire, which generate a circu- signal. The float positions are
principle. The probe tube con- lar magnetic field. A torsional calculated from the differ-
Edition 05.2016 Technical changes reserved
tains a wire made of magneto- wave develops at the point ent propagation times. When
strictive material. Magnets inte- where the two magnetic fields necessary the water level, fuel
grated in the floats magnetise overlap and it propagates to- alarm or tamper alarm are re-
the wire at the float position. wards the probe head. In the ported.
VISY-Stick Sump
VISY-Stick Sump
Ø 47,2 M12 Connector
brown +
white A
black B
blue -
approx. 102
Equipotential bonding
approx. 60
VISY-Stick Sump
installation kit
Protective tube
blue for manhole sump,
red for dispenser sump
Mounting tube
(customer site)
Ø 65
Dimensions in mm
Function description
VISY-Reed Interstitial sensors The float follows the level of to VISY-Command. Thanks to
combine simple float switches the liquid as it rises, and a mag- the low power input, VISY-Reed
Edition 05.2016 Technical changes reserved
based on reed contacts with the net opens a reed switch inside sensors of different types can be
VISY-Sensor interface for con- the sensor tube. This alarm operated parallel to a VISY-Stick.
nection to the VISY-Command. message is transmitted directly
Label: White
Assignment
brown +
white A
black B
blue –
Cable connection
brass nickel-plated
Ø 46
Housing
brass nickel-plated
125
approx. 48
Sensor pipe
stainless steel
Edition 05.2016 Technical changes reserved
Float
stainless steel
Dimensions in mm
VISY-Reed Sump
blue for the manhole sump
red for the dispenser sump
Function description
VISY-Reed Interstitial sensors The float follows the level of the Command. Thanks to the low
combine simple float switches liquid as it rises, and a magnet power input, VISY-Reed sensors
Edition 05.2016 Technical changes reserved
based on reed contacts with the opens a reed switch inside the of different types can be oper
VISY-Sensor interface for con- sensor tube. This alarm message ated parallel to a VISY-Stick.
nection to the VISY-Command. is transmitted directly to VISY-
VISY-Reed Sump
Label:
Blue for VISY-Reed Sump Manhole
Red for VISY-Reed Sump Dispenser
Assignment
brown +
white A
black B
blue –
Cable connection
brass nickel-plated
Housing
brass nickel-plated
125
Sensor pipe
Edition 05.2016 Technical changes reserved
stainless steel
Float
stainless steel
Ø 60
Dimensions in mm
www.fafnir.com VISY-Command | 25
Function description
The VISY-Command control unit VISY-Command provides an in- The optional VISY-ICI 485 in-
has a modular architecture. The trinsically safe power supply terface makes it possible to
internal components are mod- for the VISY-Stick sensors. The connect multiple VISY-Input/-
ules for DIN rail installation that measured values supplied are Output units. These enable the
can be retrofitted or converted prepared in such a way that all inputting (VISY-Input) of addi-
at any time. VISY-Command is of the latest measurement data tional external alarms (e.g. oil
available in the form of basic can be viewed at any time on separators) and/or the output-
versions VISY-Command 8 and a superordinate system (e. g. ting (VISY-Output) of alarms by
16, i. e. with either 2 / 4 / 8 or 16 cash system, petrol station con- way of relay contacts.
sensor connections. Up to 3 dif- troller, VISY-Monitor PC soft-
ferent sensors (e. g. VISY-Stick, ware ...) connected to a serial VISY-Command is configured
VISY-Stick Interstitial and VISY- port. Data transmission is sup- using the VISY-Setup software
Stick Sump) can be connected ported by various, common application through the sepa-
to one terminal by a common data protocols, e. g. Ethernet and rate serial service port. As a
cable. IFSF-LON. result, practically all mainte-
The control unit is also available nance and diagnostics tasks can
in the form of VISY-Command The extension interface of VISY- be carried out while the entire
RF; this supports the wireless Command enables multiple system is still in operation. It is
operation of up to 16 VISY-Stick external VISY-View Touch dis-
not necessary to switch off indi-
sensors. plays (e.g. fuel tanker display vidual components: petrol sta-
and local display in the office) tion operations are not affect-
to be connected and positioned ed. VISY-Setup is free of charge
where they can be seen and op- and, in addition to offering us-
erated by personnel at all times. er-friendly and efficient direct
VISY-Command itself can be fit- configuration by notebook, it
ted in a location that achieves also supports remote servicing
the most cost-effective cabling via a modem or serial-to-Ether-
arrangement (e.g. power dis- net converter.
tribution unit or basement). By
contrast with systems having
an integrated display, the ma-
jor advantage of our system is
that it is not necessary to have
all of the sensor cabling routed
though the building to the view-
ing point (e.g. the office).
Functions
VISY-Command
Communication with the PoS / BOS system or standard
petrol station controller
Automatic filler recognition standard
Automatic tank calibration optional (4)
Loss / leak monitoring standard (5)
Stock, filling and alarm histories standard (5)
Edition 05.2016 Technical changes reserved
(1) Alternatively, one of the available options (2) Multiple available options can be used (4) In conjunction with VISY-Monitor
can be used at the interface concerned. simultaneously at the interface concerned. and a compatible cash system/
(3) In conjunction with VISY-View Touch. automatic fuel dispenser.
(5) In conjunction with VISY-Monitor.
ssage
In s ta n t alarm me
VISY-Command GUI •
il
with printer via e-ma ail
r e p ort via e-m
• Daily tion
ak detec
• Static le
VISY-Command GUI contains the plays the current measurement are displayed directly and up-
intrinsically safe power supply for values and the reporting functions to-date on the screen. Using the
the VISY-Stick sensors and their (log file) in a user-friendly form. touch screen, operators can call
control unit. Various interfaces The VISY-Command GUI has a up detailed information simply
ensure that it always has access display with a clearly structured by touching the tank graphics or
to the latest data. The integrated and easy to operate interface. the function keys.
display unit with the 5.7“ colour The most important informa-
touch screen provides and dis- tion, e.g. tank level and alarms
Design
VISY-Command GUI
Housing Up to 8 sensor terminals: 16 sensor terminals:
H 300 x W 300 x D 175 H 300 x W 400 x D 175
[mm] [mm]
Casing protection IP20
Weight 6.7 kg 10.7 kg
Ambient temperature 0 °C to +40 °C
Supply 230 VAC ± 10 %, approx. 50 VA
Internal display 5.7“ TFT touch screen
Number of sensor terminals 2, 4 or 8 16
Host interface (RS232 / RS485) standard
– Ethernet module (MoxaNPort5110) optional
for long distance scanning
– Modem for long distance scanning optional
Service interface (RS232) standard
– Modem for long distance scanning optional
Extension interface (RS485) standard
– VISY-View Touch display optional
VISY-ICI 485 module optional
– VISY-Output (relay outputs) optional
– VISY-Input (digital switch inputs) optional
Edition 05.2016 Technical changes reserved
Printer optional
Functions
VISY-Command GUI
Communication with the PoS / BOS system or standard
petrol station controller
Automatic filler recognition standard
Static leak detection standard
VISY-Command RF
VISY-Command GUI RF
External antenna
VISY-RFT module
The VISY-X tank gauging system data recorded by the VISY-Stick the VISY-RFR module (radio fre-
can also be operated wirelessly. sensors and the data of the envi- quency receiver) to which 2 op-
The VISY-RFT module (radio fre- ronmental sensors wirelessly to tional available antennas can be
quency transmitter) mounted in the VISY-Command RF control connected.
the manhole, transmits the tank unit. The control unit includes
30 | VISY-RF www.fafnir.com
Application
VISY-RF is used wherever the The wireless system proves ben- The wireless system is suitable
routing of cables is unfeasible, eficial in this scenario because for all above-ground and under-
or would be too cost-intensive. no excavation work is required. ground storage tanks.
Design
VISY-Command RF / VISY-Command GUI RF
Housing up to 16 measuring sensors
H 300 x W 300 x D 125 / 175 [mm]
Casing protection IP20
Weight 6.7 kg
Ambient temperature 0 °C to + 40 °C
Supply 230 VAC ± 10 %, approx. 50 VA
Internal display 5.7“ TFT touch screen
Number of measuring sensors 16 per sensor type
Host interface (RS232 / RS485) standard
– Ethernet module (MoxaNPort5110) optional
for long distance scanning
– Modem for long distance scanning optional
Service interface (RS232) standard
– Modem for long distance scanning optional
Extension interface (RS485) standard
– VISY-View Touch display optional
VISY-ICI 485 module optional
– VISY-Output (relay outputs) optional
– VISY-Input (digital switch inputs) optional
Printer optional
VISY-RFT module
Housing H 82* x W 80 x D 55 [mm]
Casing protection IP67
Ambient temperature - 20 °C to + 60 °C
Transmission frequency: 433 MHz
Transmission range (line of sight) max. 250 m
Battery operating time: 8 years at 5-minute transmission intervals;
4 years at 1-minute transmission intervals
Edition 05.2016 Technical changes reserved
Functions
VISY-Command GUI RF
Communication with the PoS / BOS system or standard
petrol station controller
Automatic filler recognition standard
Static leak detection standard
VPI
VPI-Supply
The VPI (VISY-Power Interface) Up to 1,024 sensors can be con- Up to 32 VPIs can be circuited
provides a communications in- nected to 32 VPIs. The sensors in parallel, depending on the
terface between the sensors and require a connection to the VPI. quantity of sensors to be con-
a higher-level system (master). The installation location for the nected.
For the sending of commands VPI must be outside the poten-
to the sensors, the VPI supports tially explosive atmosphere.
two protocols*. The response is The VPI is designed for DIN car-
* The following protocols are supported:
assigned and forwarded to the rier rail installation and has eight 1. FAFNIR Universal Device Protocol (UDP)
individual sensor terminals. intrinsically safe sensor terminals. 2. H-Protocol
Edition 05.2016 Technical changes reserved
ssage
In s ta n t alarm me
VISY-View Touch •
il
via e-ma ail
r e p ort via e-m
• Daily tion
ak detec
• Static le
Application
VISY-View Touch is a display for of the installed level and envi- ing tank content data. In addi-
use with the tank gauging sys- ronmental sensors. The VISY- tion, it is particularly useful to
tem VISY-X. It is a visualisation View Touch display module is the fuel tanker driver, who will
and working platform for tank used wherever no petrol station be able to read tank levels
contents at petrol stations and cash system is available, cannot before refuelling the petrol
provides a convenient overview or should not be used for view- station.
Edition 05.2016 Technical changes reserved
VISY-View
table stand
www.fafnir.com Printer | 35
VISY-Input
Input module for external alarms
Input module
VISY-Input
Application
VISY-Input is an octal input mod- For a central logging alarms systems at one central point.
ule installed in a splash proofed detected by external systems To connect to the VISY-X tank
case with protection class IP66. It can be forwarded to the VISY-X gauging system only a low-cost
Edition 05.2016 Technical changes reserved
connects external alarm outputs tank gauging system via VISY- communication cable has to be
to the VISY-X high-precision tank Input. This allows the indica- laid.
gauging system. tion of alarms from different
36 | VISY-Input www.fafnir.com
Technical data
VISY-Input
»» Housing dimensions: »» LEDs: »» Voltage inputs:
H 130 x W 180 x D 60 [mm] 2 x power LED, input voltage range
(excluding cable connections) 1 x status LED, 5 VDC (appr. 1 mA) to 24 VDC
»» Ambient temperature: 2 x communication LED, (appr. 7 mA), potential-free,
0 °C to + 40 °C 8 x input LED protected against polarity
»» Casing protection: IP66 »» Inputs: reversal
»» Communication: 8 inputs, which can be »» Relay inputs: internal
1 x RS485 (connection configured either as potential- power supply 12VDC,
to VISY-Command free voltage inputs or as relay contact current
via VISY-ICI 485 module) inputs for relay contacts appr. 10 mA
»» Power supply:
230 VAC ± 10 %, 50 to 60 Hz,
≤ 4 VA
Edition 05.2016 Technical changes reserved
ICI-485 module
required to connect
VISY-Input / VISY-Output
VISY-Output module
Application
VISY-Output is an eight relays indicators to the VISY-X high- To connect to the VISY-X tank
output module installed in a precision tank gauging system. gauging system only a low-cost
splash proofed case with pro- Alarms, by the tank gauging sys- communication cable has to be
tection class IP66. It connects tem VISY-X detected, can freely laid.
Edition 05.2016 Technical changes reserved
38 | VISY-Output www.fafnir.com
Technical data
VISY-Output
»» Housing dimensions: »» LEDs: »» Outputs:
H 130 x W 180 x D 60 [mm] 1 x power LED, 8 x relays each with one
(excluding cable connections) 1 x status LED, potential-free changeover
»» Ambient temperature: 8 x alarm LED, contact;
0 °C to + 40 °C 8 x relay LED load rating of the contacts:
»» Casing protection: IP66 »» Power supply: AC voltage:
»» Communication: 230 VAC ± 10 %, Ueff ≤ 250 V, cos ϕ ≥ 0,7,
1 x RS485 (connection 50 Hz to 60 Hz, ≤ 4 VA Ieff ≤ 3 A, Peff ≤ 300 VA;
to VISY-Command DC voltage:
via VISY-ICI 485 module) U ≤ 24 V, I ≤ 2 A, P ≤ 50 W
Edition 05.2016 Technical changes reserved
ICI-485 module
required to connect
VISY-Input / VISY-Output
The VISY-Monitor
software application
40 | VISY-Monitor www.fafnir.com
Function Data Management
VISY-Monitor displays a fully It is also possible to connect »» Volumetric representation of
comprehensive range of tank an external journal printer for tank contents
data. The filling level data from documenting current tank lev- »» Temperature-compensated
the VISY-X system (VISY-Stick els and enabling mandatory volume
and VISY-Command) are for- printouts of all alarm messages. »» Product temperature
warded to the PC and displayed For audible alarms, it is a sim- »» Ullage
by the VISY-Monitor software ple matter of connecting up to a »» Tank and product name
application. VISY-Monitor sup- standard audio system. »» Water level
ports different types of tank »» Variable number of displayed
data, including all relevant data In addition to FAFNIR sensors, tanks
about the tank (tank number two further tank gauging sys- »» Alarm messages
and content) and the product tems from the most common and logging
(filling level, water level and manufacturers can be connect- »» Automatic tank calibration
product temperature) as well ed in parallel, which means that »» Reconciliation
as additional information (e.g. existing sensors can be replaced »» Automatic loss and leakage
ullage). The tank
information in stages. monitoring
displayed is continuously re- »» History logging
freshed and viewable at all »» All data stored in a database
times. In addition, VISY-Moni-
tor offers a wide range of other
features, such as automatic tank System requirements
calibration, optimum leakage »» CPU 700 MHz
monitoring and the ability to »» RAM 512 MB
display historical data. Historical »» Spare hard drive capacity
data are displayed in tabular and for VISY-Monitor software
graphical form and can be print- application: 30 MB
ed out. All inventory and event »» Windows 2000 Professional
data are stored indefinitely in a with SP4, Windows XP
database for further processing. Professional with SP2 or
Windows Vista with SP1,
Win 7 (32 bit)
»» Microsoft.NET 2.0 Framework
»» 2 x RS 232 ComPort
– to connect VISY-Command
– to connect to PoS
(no USB-To-Serial Adapter)
Edition 05.2016 Technical changes reserved
1“ Installation Kit
The optional installation kit
comprises a product float, a wa-
ter float and a screw-in unit.
It makes it possible to install a
VISY-Stick using an G 1 threaded
coupler. The screw-in unit is also
available in stainless steel.
1“ Installation Kit
1“ Installation Kit
Ø 29,5
WAF 41
55
Product and
water float
40
G1
42 | Accessories www.fafnir.com
VISY-RFT installation kit RFT-Battery
Installation kit Battery for the
for mounting VISY-RFT module
a VISY-RFT module.
Junction Tube
1“ LPG float
The 5-pin cable coupler makes
Optional available
it quick and easy to establish
instead of the
the connection between the
standard LPG float
VISY-Stick and the cable to
the VISY-Command.