Professional Documents
Culture Documents
1. OPERATION
This program functionally controls different elements of the sheetline, which
require timing functions in their sequencing. By taking on the functions using
the mini-plc, we eliminate the discrete timers required as well as numerous
latch-in relays, which were also required. There is also the added benefit of
“consistency of operation” which comes with using a master program. The
following sections detail how the program sequence controls each element. I/O
will be referenced by terminal #, not address in order to make it more readable
when referencing the print (the wire#’s are still the address per our
standard). Inputs will be IN 0 through IN 23, while Outputs will be OUT 0
through OUT 15.
The circuit will then de-energize until a pump start is initiated again.
The pump will be shut-off with E-stop tripped after 20 seconds. This will
ensure adequate system pressure to open the rolls. The roll close circuit is
disabled instantly on E-stop obviously.
The following I/O are sequenced by the program for Roll Open/Close operation:
• IN 0 E-stop status
• IN 13 Hydraulic Pump stop request/pump running status
• IN 23 System up to pressure
• IN 14 Roll #1 Close request
• IN 15 Roll #1 Open request
• IN 16 Roll #2 Close request
• IN 17 Roll #2 Open request
These conditions will cause the circuit to de-energize which will open the
roll.
1.4.4 Opening
As soon as the circuit is de-energized, the “instant-ON” trial time of 12
seconds begins. If motion is re-initiated within this time frame, the close
solenoids will be actuated immediately. If the roll has been opened for longer,
the trial delay will be active again. As opposed to locomotion, the motion
warning horn only needs to sounded during the delay, not while closing or
closed.
1.5 LOCOMOTION
The following I/O are sequenced by the program for locomotion operation:
1.5.4 Stopping
As soon as the selector is released, The locomotion relay will de-activate to
stop the line. This will start the “instant-ON” trial time of 12 seconds. If
motion is re-initiated within this time frame, the run relays will be actuated
immediately. If the locomotion drive has been inactive for longer, the trial
delay will be active again.