Panel Name: SLP Voltage: 400/23

Enclosure Type: IP:52 Frequency: 60 Hz


(B04) SECURITY
Location: Mounting: Reces
BUILDING
Conduit Connected Load
2
Diame- Branch Ckt. Conductors (mm ) Load Description VA per Phase
ter (mm) R Y B

113
multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC + Site Lighting
113
1/C × 6mm² Cu/PVC Gnd (SLP-1,3,5 -1005VA)
113
175
multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC + Site Lighting
175
1/C × 6mm² Cu/PVC Gnd (SLP-7,9,11 -1500VA)
175
100
multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC + Site Lighting
100
Direct Buried

1/C × 6mm² Cu/PVC Gnd (SLP-13,15,17 -750VA)


100

Site Lighting 150


multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
(SLP-19,21,23 - 150
1/C × 6mm² Cu/PVC Gnd
1752VA)
150

Site Lighting 175


multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
(SLP-25,27,29 - 175
1/C × 6mm² Cu/PVC Gnd
1626VA)
175

Site Lighting 340


multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
(SLP-31,33,35 - 340
1/C × 6mm² Cu/PVC Gnd
1251VA)
340

Spare

Sub-Total Load Per Phase 1053 1053 1053

Sub-Total Load Phase-R = 2288 VA


Sub-Total Load Phase-Y = 1788 VA
Sub-Total Load Phase-B = 1788 VA
Total Connected Load = 5864 VA

Demand Load Current = 5864 / (400*1.732)


= 8.46 Amps
Load Current @ 120% = 10.16 Amps
Use Standard C.B. = 50 Amps
Demand Load Current = 5864 / (400*1.732)
= 8.46 Amps
Load Current @ 120% = 10.16 Amps
Use Standard C.B. = 50 Amps
Voltage: 400/230 VAC, 3-P, 4-W Main CB: 50 AT/ 100 AF, 3P, MCCB Feeder Size:

Frequency: 60 Hz K.A.I.C.: 14 Equipment Ground Size:

Mounting: Recess Wall-Mounted No. of Poles: 42 Feeder Conduit Size:

Connected Load CB CB Connected Load VA per


Ckt. Ckt.
VA per Phase Amps Amps Phase Load Description
No. No.
R Y B Rating R Y B Rating R Y B

113 1 2 170
Site Lighting
113 3 32 32 4 170
(SLP-2,4,6 -1125VA)
113 5 6 170
175 7 8 175
Site Lighting
175 9 32 32 10 175
(SLP-8,10,12 -1875VA)
175 11 12 175
100 13 14 270 Site Lighting
100 15 32 32 16 270 (SLP-14,16,18 -
1125VA)
100 17 18 270
150 19 20 100
Site Lighting
150 21 32 32 22 100
(SLP-20,22,24 -750VA)
150 23 24 100
175 25 26 20 Site Lighting
175 27 32 32 28 20 (SLP-26,28,30 -
1500VA)
175 29 30 20
340 31 32 32 500 Contactor
340 33 32 32 34 Spare
340 35 36 Space
37 38
39 32 32 40 Spare
41 42
1053 1053 1053 1235 735 735 Sub-Total Load Per Phase

Main CB
2288 VA Demand Load Calculations: (VA)
1788 VA N R Y B G D.L. Lighting @ 100% =
1788 VA
5864 VA

Total Demand Load =

5864 / (400*1.732)
8.46 Amps
10.16 Amps
50 Amps
Feeder Entry: Bottom
5864 / (400*1.732)
8.46 Amps
10.16 Amps
50 Amps
Feeder Entry: Bottom
2
4/Cx25 mm Cu/XLPE/PVC
Feeder Size: 2
+ 1/Cx 10mm Cu/PVC G
Equipment Ground Size: 1/C x 10mm² BCW

Feeder Conduit Size: 40 mm dia.PVC

Conduit
2
Load Description Branch Ckt. Conductors (mm ) Diame-
ter (mm)

ckt no kva
Site Lighting multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
SLP-2,4,6 -1125VA) 1/C × 6mm² Cu/PVC Gnd
1,3,5 0.3
2,4,6 0.5
Site Lighting multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
7,9,11 0.5
SLP-8,10,12 -1875VA) 1/C × 6mm² Cu/PVC Gnd
8,10,12 0.5

Direct Buried
Site Lighting 13,15,17 0.3
multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
(SLP-14,16,18 - 14,16,18 0.8
1/C × 6mm² Cu/PVC Gnd
1125VA)
19,21,23 0.4
20,22,24 0.3
Site Lighting multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
25,27,29 0.5
SLP-20,22,24 -750VA) 1/C × 6mm² Cu/PVC Gnd
26,28,30 0.0

Site Lighting 31,33,35 1.0


multi core cable 3/C × 6mm² Cu/XLPE/ SWA/PVC +
(SLP-26,28,30 -
1/C × 6mm² Cu/PVC Gnd
1500VA)

Contactor 2-1/Cx6mm² Cu/XLPE/PVC+ 1/Cx4mm² Cu/PVC Gnd 20


Spare
Space

Spare

ub-Total Load Per Phase

ad Calculations: (VA)
g @ 100% = 5864

and Load = 5864

Source : Panel B04-LP-GF


Source : Panel B04-LP-GF
ckt no kva

1,3,5 0.339
2,4,6 0.51
7,9,11 0.53
8,10,12 0.525
13,15,17 0.30
14,16,18 0.81
19,21,23 0.45
20,22,24 0.30
25,27,29 0.53
26,28,30 0.06
31,33,35 1.02

You might also like